AC INDUCTION MOTOR DATA SHEET
Model No. or RFQ No. HT400-18-5008RB Item No. Rev. No.
Project Name Project No. Quantity
GENERAL SPECIFICATION PERFORMANCE DATA
Frame Size 5008 Rated Output 400 HP
Type HLE5 5008 Number of Poles 4
Enclosure (Protection) TEFC (IP54) Rotor Type SQUIRREL CAGE
Method Of Cooling IC411 Starting Method * D.O.L.
Rated Frequency 60 Hz Rated Voltage 4160 V 2300 V
Number Of Phases 3 Full Load 50.6 A 91.6 A
Insulation Class F
Temp. Rise At Full Load (By Resistance Method) Efficiency
At 1.0 S.F. 80°C 50% Load 93.2 %
Motor Location Indoor 75% Load 93.9 %
Altitude Less Than 1000 Meters 100% Load 94.0 %
Relative Humidity Less Than 90% Power Factor (p.u.)
Ambient Temp. 40°C (Max.) 50% Load 0.77
Duty Type Continuous (S1) 75% Load 0.84
Service Factor 1.15 100% Load 0.87
Mounting B3, Horizontal Speed at Full Load 1784 RPM
Type Anti-Friction Torque
Bearing
DE/N-DE NU322M / 6219C3 Full Load 1178 LB-FT
Lubricant Grease (Multemp SRL)
External Thrust Not Applicable
Coupling Method V Belt GD
Shaft Extension Single Load
Terminal
Box
Main Steel Motor
Aux. Yes Sound Pressure Level (No-load & Mean Value At 1m From Motor)
Location Refer To Outline Drawing 85 dB(A)
Application --- Vibration 3.8 mm/sec (peak)
Area Classification Non-Hazardous, Non-Seismic Cold 2 times
Type Of Ex-Protection Not Applicable
Applicable Standard IEEE, NEMA Paint Munsell No. 7.5BG6/1.5
ACCESSORIES
1. Winding Temp. Detector (Pt 100 Ω) : 2 EA / Phase Outline Dimension Drawing / Motor Weight (Approx.)
2. Space Heater : 120V, 180W, 1 Phase HT400-18-5008RB 4240 lbs.
SPARE PARTS REMARK
Date DSND CHKD CHKD APPD
Note: Others not mentioned in this data sheet shall be in accordance with maker standard.
Above technical data are only design values and shall be guaranteed with tolerance of applicable standard.
Inspection and performance test shall be maker standard, if not mentioned.
* In case of Inverter-Fed Motor, performance data is based on sine wave tests.
** The data are bas ed on rated voltage & frequency, and data are expressed as a percentage of full load value.
HHI W230-131-1 A4(210MM x 297MM)
Current
2
Permissible Number Of
Consecutive Starts
11-19-09 M.H.KIM S.C.HWANG
Locked-Rotor**
Locked-Rotor**
Breakdown**
Hot 1 time
SUBMITTAL DRAWING
600% 600%
90 % 80 %
220 % 200 %
J.W.LIM
NOTE
Motor can be operated in the other direction
THREE PHASE INDUCTION CAGE ROTOR MOTOR (TEFC)
TYPE FRAME NO. OUTPUT POLES VOLTAGE FREQUENCY MOUNTING WEIGHT
by reversing the L1 and L3 leads.
BEARING NO.
D.E. N-D.E.
HLE5 5008 5008 400 HP 4 P 4160 V / 2300 V 60 Hz B3 4240 lbs. NU322M 6219C3
NOTE
Permissible Cantilever Force : 18025N (4052 lbs.)
(The center of belt pulley is on the end of shaft extension part.)
DISTRIBUTED IN THE UNITED STATES BY:
WORLDWIDE ELECTRIC CORPORATION
ROCHESTER, NEW YORK
HT400-18-5008RB