Worldwide Electric Corporation EP20-18-256T Data Sheet

HORSEPOWER RPM / POLES VOLTAGE / PHASE FRAME ENCLOSURE / DEGREE OF PROTECTION FREQUENCY FULL LOAD SPEED SERVICE FACTOR INSULATION CLASS FULL LOAD AMPS; 230 / 460 LOCKED ROTOR AMPS (STARTING); 230 / 460 NO LOAD CURRENT NEMA CODE LETTER
LOAD EFF. P.F.
100% 93.8% 0.85 75% 93.0% 0.84 50% 91.1% 0.81
DUTY CYCLE
FULL LOAD LRT BDT
60.0 lb.ft. 200% 250%
SLIP NEMA DESIGN MOMENT OF INERTIA NUMBER OF STARTS (Hot / Cold) MAX. AMBIENT TEMPERATURE MAX. ELEVATION TEMPERATURE RISE (At Full Load) DE BEARING ODE BEARING GREASE TYPE MOUNTING ROTATION APPROXIMATE WEIGHT AREA CLASSIFICATION TEMPERATURE CODE AT 40°C AMBIENT TEMPERATURE CODE AT 55°C AMBIENT INVERTER RATING SPECIFICATION - In Accordance With
NEMA, CSA
F1 (F2 Suitable)
Bi-Directional
Class I, Division 2, Groups A, B, C, D
10:1 CT / 20:1 VT PWM Type
TORQUE
436 lbs.
6308
Mobil Polyrex EM
2 Hot / 3 Cold
EFFICIENCY / POWER FACTOR
290 / 145 A
G
4.09 lb.ft.
2
B
S1 / Continuous
80° C
6309
3300 Ft. Above Sea Level
60 HZ Suitable For 50 HZ Operation With 1.0 SF
EP20-18-256T
1.25 SF at 40° C / 1.0 SF at 55° C
F
17.14 / 8.57 A
1.70%
40° C at 1.25 SF / 55° C at 1.0 SF
T3C
T3A
WORLDWIDE ELECTRIC MOTOR DATA SHEET
256T
1750 RPM
47.94 / 23.97 A
20
1800 / 4
230 / 460 V / 3
TEFC / IP55
JUNE 23, 2016
E 2F1 2F2 H BA A B C D G J P L AB
5 8.25 10 0.53 4.25 12.25 12.36 25.196 6.25 0.866 2.4 14.64 15.62 10.9
AA XB XC XD XE
1.5 3 7.2 6.3 8.66
U
WORLDWIDE ELECTRIC MOTOR DRAWING
EP-256T
DIMENSIONS - INCHES
MOUNTING
KEYSET
SHAFT
TERMINAL BOX
1.416
4
1.625
KEY
S
0.375
ES
2.91
R
N-W
REVISED - 03/17/15
Loading...