Worldwide Electric Corporation EP125-18-444T Data Sheet

HORSEPOWER RPM / POLES VOLTAGE / PHASE FRAME ENCLOSURE / DEGREE OF PROTECTION FREQUENCY FULL LOAD SPEED SERVICE FACTOR INSULATION CLASS FULL LOAD AMPS; 230 / 460 LOCKED ROTOR AMPS (STARTING); 230 / 460 NO LOAD CURRENT NEMA CODE LETTER
LOAD EFF. P.F.
100% 95.4% 0.86
75% 95.2% 0.85
50% 93.8% 0.80
DUTY CYCLE
FULL LOAD LRT BDT
367.0 lb.ft. 170% 250%
SLIP NEMA DESIGN MOMENT OF INERTIA NUMBER OF STARTS (Hot / Cold) MAX. AMBIENT TEMPERATURE MAX. ELEVATION TEMPERATURE RISE (At Full Load) DE BEARING ODE BEARING GREASE TYPE MOUNTING ROTATION APPROXIMATE WEIGHT AREA CLASSIFICATION TEMPERATURE CODE AT 40°C AMBIENT TEMPERATURE CODE AT 55°C AMBIENT INVERTER RATING SPECIFICATION - In Accordance With
WORLDWIDE ELECTRIC MOTOR DATA SHEET
EP125-18-444T
125
1800 / 4
230 / 460 V / 3
444T
TEFC / IP55
60 HZ Suitable For 50 HZ Operation With 1.0 SF
1790 RPM
1.25 SF at 40° C / 1.0 SF at 55° C
F
285.2 / 142.6 A
1816 / 908 A
94.54 / 47.27 A
G
EFFICIENCY / POWER FACTOR
S1 / Continuous
TORQUE
0.56%
B
65.1 lb.ft.
2
2 Hot / 3 Cold
40° C at 1.25 SF / 55° C at 1.0 SF
3300 Ft. Above Sea Level
80° C
NU318
6314
Mobil Polyrex EM
F1 (F2 Suitable)
Bi-Directional
T3A
T3
Class I, Division 2, Groups A, B, C, D
10:1 CT / 20:1 VT PWM Type
NEMA, CSA
JUNE 23, 2016
1609 lbs.
E 2F1 2F2 H BA A B C D G J P L AB
9 14.5 --- 0.81 7.5 22 18.5 43.7 11 1.38 3.35 23.58 26.43 18.93
AA XB XC XD XE
2 x 3 5.67 11.73 11.34 13.39
U
WORLDWIDE ELECTRIC MOTOR DRAWING
EP-444T
DIMENSIONS - INCHES
MOUNTING
KEYSET
SHAFT
TERMINAL BOX
2.88
8.5
3.375
KEY
S
0.875
ES
6.91
R
N-W
REVISED - 03/17/15
Loading...
+ 1 hidden pages