Worcester RT 10 Installation, User Instructions & Customer Care Manual

Page 1
Installation and Operating Instructions
7719 002 505
RT 10
Room temperature controller for heating appliances with
ROOM TEMPERATURE CONTROLLER
bus-enabled Heatronic 3 and
FOR WORCESTER HEATING APPLIANCES WITH BUS-ENABLED HEATRONIC 3 AND TD 200
RT 10
TD 200
1R
0. 0
18­2
12 6
20 7
6
6 720 612 218 GB (05.09) OSW
Order no. 7 719 002 505
INSTALLATION, USER INSTRUCTIONS & CUSTOMER CARE GUIDE
Page 2
Dear customer,
Congratulations on having decided in favour of a top-quality product from our company.
The
RT 10
offers everything you can expect from a modern heating control: It is both reliable and energy saving.
Like all Bosch Group products, the
RT 10
has been produced and tested according to the most stringent quality standards so that you can enjoy the
WORCESTER
warmth for a long time
to come.
2
6 720 612 218 GB (05.09)
Page 3
Contents
Contents
Safety precautions 4
Symbols 4
1 Technical data for
the accessory item 5
1.1 Standard package 5
1.2 Technical data 5
1.3 Accessories 5
1.4 Description of function 6
2 Installation 7
2.1 Assembly 7
4 General information 13
5 Troubleshooting 14
2.2 Electrical connections 9
3 Operation 10
3.1 Change required room
temperature, time limited (a) 11
3.2 Advance the next
switching time and the associated operating mode to the current time (b) (Advance Heating) 11
3.3 Frost protection 12
3.3.1 Room frost protection 12
3.3.2 Frost operating mode 12
3.4 Further operation and
features 12
6 720 612 218 GB (05.09)
3
Page 4
Safety precautions
Safety precautions
B
These instructions must be observed to ensure correct opera­tion.
B
The accessories should be installed by an authorised heating installer only.
B
Only use these accessories in con­junction with the heating appliances listed. Observe connection dia­gram!
B
Never connect this accessory item to the 230 V mains electricity sup­ply.
Symbols
Safety instructions
this document are identi­fied by a warning-trian­gle symbol and are printed on a grey back­ground.
Signal words indicate the seriousness of the hazard in terms of the conse­quences of not following the safety instructions.
Caution
age to property could result.
indicates that minor dam-
in
B
Before assembling these accesso­ries: Interrupt voltage supply (230 V AC) to the heating appliance and all additional devices using the bus.
B
Do not install this accessory in damp areas.
Warning
sonal injury or serious damage to property could result.
Danger
sonal injury could result. In particu­larly serious cases, lives could be at risk
indicates that minor per-
indicates that serious per-
Notes
by the symbol shown
are identified
i
on the left. They are bordered by horizon­tal lines above and be­low the text.
4
Notes contain important information in cases where there is no risk of personal injury or damage to property.
6 720 612 218 GB (05.09)
Page 5
Technical data for the accessory item
1 Technical data
for the accessory item
Only use the RT 10 in heating systems with
i
bus-enabled Heatronic 3 in the heat­ing appliance and TD 200.
The RT 10 allows the control of the room temperature of an unmixed heat­ing circuit.
1.2 Technical data
Dimensions Nominal voltage
bus supply Mains supply Controller output Control range
permissible ambi­ent temperature
Class of protection
Type of protection
Figure 1, page 7
10...24 V DC 15 V DC
3.5 mA Bus approx. 5...30˚C
in 0.5 K increments
0... +50 °C
III
IP20
1.1 Standard package
Room temperature controller RT 10
1.3 Accessories
Text display TD 200
6 720 612 218 GB (05.09)
5
Page 6
Technical data for the accessory item
1.4 Description of function
The integrated temperature sensor indicates the
perature
current room tem-
to the TD 200. The cur­rent room temperature is shown on the display.
If Automatic mode is active on the TD 200, it is possible via the RT 10 to set the
ature
required room temper-
restricted to a certain time
(see Chapter 3.1 on page 11)
If Automatic mode is active on the TD 200, the next switching time and associated operating mode can be advanced to the current time
(
Advance Heating
) (see
Example:
desired room temperature: 21 ˚C
current room temperature: 16 ˚C
Factor for room heating: 1 K in 10 minutes
To reach the desired room tempera­ture, the heating requires 50 minutes on account of the 5 K difference. Therefore, the heating starts only 10 minutes after
High
the pro-
grammed switching time.
Chapter 3.2 on page 11).
Optimum Start
This function on the TD 200 can be switched on and off and is only acti­vated when in Automatic mode. The RT 10 must display
auto
.
Optimum Start delays the heating start after an economy phase. To ensure that the required room tem­perature is reached approx. 1 hour after the programmed switching time
High
, the TD 200 calculates the optimum time point for the heating start.
6
6 720 612 218 GB (05.09)
Page 7
2 Installation
Danger:
risk of electric shock!
Installation
B
Before installing these accessories: Interrupt voltage supply (230 V AC) to the heating appli­ance and all addi­tional devices using the bus.
2.1 Assembly
The control quality of the RT 10 depends on the installation location.
The installation location must be suita­ble for controlling the entire heating
3.
1.
2.
6 720 612 218-04.1R
Fig. 2 Remove front casing
system.
100 mm
85 mm
25 mm
35 mm
0,6 m
1,2 m
1,0 m
0,75 m
6 720 612 218-02.1J
Fig. 1 Select installation location
6 720 612 218 GB (05.09)
7
Page 8
Installation
6 720 612 218-05.1R
3,5 mm
Fig. 3 Fasten base plate to the wall
B
Make all electrical connections (see Fig. 4).
B
Replace front cover.
6 mm 3,5 mm6 mm
8
6 720 612 218 GB (05.09)
Page 9
2.2 Electrical connections
B
Bus connection from the RT 10 to
Installation
B
To avoid inductive influences, sepa­additional devices using the bus (e. g. TD 200): Use electrical cables correspond­ing to type H05 VV-... (NYM-I...) minimum.
Permissible cable lengths from the bus-enabled Heatronic 3 circuit board to RT 10:
Cable length
80 m
100 m
150 m
200 m
300 m
Cross section
0.40 mm
0.50 mm
0.75 mm
1.00 mm
1.50 mm
2
2
2
2
2
rate all leads carrying low voltage
from lines of 230 V or 400 V (mini-
mum spacing 100 mm).
B
Shield the cables in the case of
external inductive influences.
This ensures that the leads are
shielded against external influences
(e.g. heavy current cables, over-
head contact wires, transformer
stations, radio and television appli-
ances, amateur radio stations,
microwave appliances etc).
Heatronic 3
TD 200
RT 10
B
B
ST 19
AF
Fig. 4 Connect RT 10 to the bus-enabled Heatronic 3.
124BB
6 720 612 218-03.1J
6 720 612 218 GB (05.09)
9
Page 10
Operation
3 Operation
Operating elements
Symbols
auto
a
Fig. 5
Operating elements
a
Selection knob : Change the required room temperature until the next
b
6 720 612 218-01.1J
auto
Current room temperature
High
Low
Frost
Automatic mode
Next switching time and associated operating mode
=
High
=
Low
=
Frost
advanced to the current time
b
10
switching time of the heating program
Button : Advances the next switching time and the associated operating mode
=
High
=
Low
=
Frost
to the current time
Burner on symbol
Set the flow tempera­ture controller on the
i
heating appliance to the maximum inlet temperature required.
6 720 612 218 GB (05.09)
Page 11
Operation
3.1 Change required room temperature, time limited (a)
If the RT 10 displays
B
Use the selection button to change the
perature
mode / / between 5.0˚C ... 30˚C. The required room temperature is briefly displayed flashing in the dis­play instead of the current room temperature. The change to the required room temperature remains
required room tem-
for the current operating
auto
:
3.2 Advance the next switching time and the associated oper­ating mode to the current time (b)
(Advance Heat-
ing)
This function is for use in case of unexpected
i
heating demands.
If the RT 10 displays Automatic mode
auto
:
active until the next switching time of the heating program. After this the room temperature for the corre­sponding operating mode pro­grammed on the TD 200 applies again. If the RT 10 calls for heat, the boiler operates until the set room temper­ature is reached.
If instead of the re­quired room tempera-
i
ture -- is displayed, the room temperature cannot be changed.
B
Press the button to advance the next switching time and the associ­ated operating mode
=
High
=
Low
=
Frost
to the current time.
is shown on the display and the corresponding symbol also appears to indicate the change of operating mode / / .
If two lines -- are dis­played instead of ,
i
the function is not available.
6 720 612 218 GB (05.09)
11
Page 12
Operation
3.3 Frost protection
3.3.1 Room frost protection
If the temperature in the room drops below 5˚C, the heating is switched on. To maintain a minimum 5˚C room tem­perature, the heating is switched on and off as appropiate.
3.3.2 Frost operating mode
The TD 200 enables the room temper­ature for the to be set from 5˚C to 30˚C. With the default setting the room temperature for the room in which the RT 10 is mounted is 7 °C.
Frost
operating mode
3.4 Further operation and features
Additional operating options and func­tions are described in the TD 200 and the boiler literature. Please refer to the corresponding operating instructions.
12
6 720 612 218 GB (05.09)
Page 13
4 General information
... Notes on saving energy:
General information
Ventilate fully for a short time (com-
The temperature in the room where the RT 10 is installed acts as a guide parameter for the entire heat­ing network. As a result, the power of the radiators must be set as low as possible, using thermostatic radiator valves.
Control the temperature in the adjoining rooms via thermostatic radiator valves.
Heat from other sources in the room (e.g. sunshine etc.) can lead to the heating in the adjoining rooms remaining too low.
pletely open windows).
Turn the thermostatic valve during ventilation or switch to low setting.
A significant amount of energy can be saved by lowering the room tem­perature. A reduction in tempera­ture by 1 K (˚C) can result in up to 5 % energy saving.
Good thermal insulation of the building: The set low temperature level is not reached. Energy is therefore saved, as the heating remains switched off.
Do not keep windows open on vent setting to ventilate. This would con­tinuously cool down the room with­out significantly improving the air in the room.
6 720 612 218 GB (05.09)
13
Page 14
Troubleshooting
5 Troubleshooting
In the event of a fault in the heating appliance, the display will show e.g.
A7 E
. In the event of a fault in the RT 10, the display will show e.g.
1A4 E
. Here the figure 1 stands for a fault in the RT 10 and the letter E for Error (= fault):
B
Contact a heating expert.
Display
1A4 E
Cause Remedy by an expert
Temperature sensor in the RT 10 defective.
1A8 E
TD 200 using the bus no longer responds.
Replace RT 10.
Check bus connection and, if necessary, rectify interruption.
e.g.:
A7 E ...
Heating appliance using the bus no longer responds.
Error display for the heating appliance.
Check bus connection and, if necessary, rectify interruption.
Rectify the fault in accordance with the heating appliance docu­mentation.
14
6 720 612 218 GB (05.09)
Page 15
Troubleshooting
Complaint
Required tem­perature not reached
Required room temperature is greatly exceeded
Excessive room temperature
Cause Remedy
Thermostatic valve(s) in the room set to low
Flow temperature control­ler on the heating appli-
Open the thermostatic valve(s).
Set flow temperature controller higher.
ance set too low Air lock in the heating sys-
tem Installation location of the
RT 10 not suitable, e.g. outer wall, proximity to win­dow, draught, ...
Temporary effect of heat from other sources on the
Vent radiator and heating sys­tem.
Choose a better installation location (see Chapter 2.1) and have the RT 10 moved by a professional.
Choose a better installation location (see Chapter 2.1) and
fluctuations
Temperature rise instead of fall
Room tempera­ture too high in low mode
Incorrect or no control
room, e.g. from sunshine, room lighting, TV, fire­place etc.
Time of day set incorrectly on the TD 200
Building has high degree of heat storage
Bus connection defective for the devices using the bus
have the RT 10 moved by a professional.
Check setting.
Select low mode earlier.
Have the bus connection checked and, if necessary, rec­tified by a professional accord­ing to the connection diagram.
6 720 612 218 GB (05.09)
15
Page 16
INSTALLATION, USER INSTRUCTIONS & CUSTOMER CARE GUIDE
Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 01905 754624 Fax. 01905 754619
www.worcester-bosch.co.uk
Worcester Bosch Group is a trading name of BBT Thermotechnology UK Ltd.
6 720 612 218 (05/09) OSW
Loading...