worcester Greenstar Heatslave Internal 12/18 User guide

INSTRUCTION MANUAL
INSTALLATION, COMMISSIONING & SERVICING
FLOOR STANDING OIL FIRED CONDENSING COMBINATION BOILER CONVENTIONAL FLUE & ROOM SEALED FLUE
GREENSTAR HEATSLAVE 12/18, 18/25 & 25/32
FOR SEALED CENTRAL HEATING SYSTEMS WITH MAINS FED DOMESTIC HOT WATER
UK
THE APPLIANCE IS FOR USE WITH KEROSENE (28 SECOND OIL) ONLY
INSTALLATION & SERVICING INSTRUCTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
2
SYMBOLS USED IN THIS MANUAL:
INSTALLATION & SERVICING INSTRUCTIONS
IMPORTANT HANDLING INSTRUCTIONS: It is advised that more than one person is involved in the transfer of the packaged appli­ance from the van to the point of installation. It is advised that no attempt should be made to move the packaged appliance without the use of a suitable truck. At all times the correct method for handling heavy objects should be strictly observed.
GENERAL HANDLING GUIDELINES:
• Lift only a manageable weight, or ask for help.
• When lifting, bend the knees, and keep the back straight and feet apart.
• Do not lift and twist at the same time.
• Lift and carry items close to the body.
• Wear protective clothing and gloves to protect from any sharp edges.
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
THESE INSTRUCTIONS ARE APPLICABLE TO THE WORCESTER APPLIANCE MODEL(S) STATED ON THE FRONT COVER OF THIS MANUAL ONLY AND MUST NOT BE USED WITH ANY OTHER MAKE OR MODEL OF APPLIANCE.
THE INSTRUCTIONS APPLY IN THE UK AND EIRE ONLY AND MUST BE FOLLOWED EXCEPT FOR ANY STATUTORY OBLIGATION.
THIS APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON. FAILURE TO INSTALL CORRECTLY COULD LEAD TO PROSECUTION.
COMPLYING WITH THE BUILDING REGULATIONS:
This heating appliance forms part of the controlled services for the building. It is law that all controlled services for buildings must comply with building regulations. You must be able to satisfy your Local Authority Building Control Body (LABC) that the work carried out concerning the installation and commissioning of this heating appliance has been carried out to a satisfactory standard.
OFTEC operate a competent persons scheme and registered installers are able to certify that their work complies with building regulations. Under the scheme;
l OFTEC must be informed about every installation. l OFTEC will issue a building regulations compliance certificate to the householder and will
notify the LABC.
OFTEC provide controlled document forms CD10 and CD11 for use during installation and commissioning respectively.
Other organisations operate self-certification schemes e.g. NAPIT and BESCA Ltd. and it may be possible for installers who are members of these organisations to self certify their work.
Alternatively you must submit a building control notice to the LABC before installing any boiler. The LABC will then arrange regular inspection visits during the work to ensure that the installation complies with the regulations.
IF YOU ARE IN ANY DOUBT CONTACT THE WORCESTER TECHNICAL HELPLINE ON: 0844 892 366.
DISTANCE LEARNING AND TRAINING COURSES ARE AVAILABLE FROM WORCESTER.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE COMPLETED COMMISSIONING FORM AND THE USER MANUAL WITH THE OWNER OR WITH THE APPLIANCE AFTER INSTALLATION OR SERVICING. THE SERVICE INTERVAL RECORD CAN BE FOUND ON THE BACK PAGE OF THIS MANUAL.
ABBREVIATIONS USED IN THIS MANUAL: Ø Diameter CH Central Heating DHW Domestic Hot Water DCW Domestic Cold Water TRV Thermostatic Radiator Valve IP Ingress Protection CF Conventional flue BF Balanced flue N/A Not allowed SEDBUK Seasonal Efficiency of Domestic Boilers in the United Kingdom OFTEC Oil Firing Technical Association for the Petroleum Industry IEE Institute of Electrical Engineers LABC Local Authority Building Control Body
STORE THE APPLIANCE IN A DRY AREA PRIOR TO INSTALLATION.
WATER TREATMENT:
FERNOX 01799 550811
fernox.com
SENTINEL 0800 389 4670
sentinel-solutions.net
Domestic hot water
Central heating
Room thermostat
Frost thermostat
Wait time period
Programmer/timer OFF
Programmer ON CH only
Programmer ON DHW only
Programmer ON CH and DHW
Cold water main supply
Electricity supply
SAFETY & REG ULATIONS
IMPORTANT INFORMATION AND SYMBOLS 2
SAFETY PRECAUTIONS AND INSTALLATION REGULATIONS 4
APPLIANCE INFORMATION
GENERAL INFORMATION 5
TECHNICAL DATA 6
LAYOUT & COMPONENTS 7
PRE-INSTALLATION
CLEANING PRIMARY SYSTEMS 8
MAINS SUPPLY 9
OIL SUPPLY 10
WATER SYSTE MS & PIPEWORK 12
CONDENSATE PIPEWORK INTERNAL CONNECTION 14
CONDENSATE PIPEWORK EXTERNAL CONNECTION 15
CONDENSATE TO SOAK AWAY & PRESSURE RELIEF PIPEWORK 16
BOILER LOCATION & CLEARANCES 17
FLUE TERMINAL POSITIONS 19
CONVENTIONAL FLUE 20
ROOM SEALED FLUE OPTIONS 21
INSTALLATION
UNPACKING THE BOILER 22
PIPEWORK POSITIONS / FLUE OPENING 23
BOILER INSTALLATION 24
FLUE INSTALLATION 25
COMBUSTION CHAMBER 26
PIPEWORK CONNECTIONS 27
OIL BURNER AND PUMP 28
REFITTING COMPONENTS 29
ELECTRICS 30
COMMISSIONING
PRE-COMMISSIONING CHECKS - APPLIANCE 32
FILLING THE SYSTEM 33
STARTING THE APPLIANCE 34
WATER TREATMENT 39
FINISHING COMMISSIONING - APPLIANCE 40
SERVICING & SPARES
INSPECTION AND SERVICE 41
SHORT PARTS LIST RIELLO RDB 1 - 12/18 46
SHORT PARTS LIST RIELLO RDB 2.2 - 18/25 47
SHORT PARTS LIST RIELLO RDB 2.2 - 25/32 48
FAULT FINDING & DIAGNOSIS
ELECTRICAL SCHEMATIC 49
FAULT FINDING 50
FAULT FINDING LOGIC FOR RIELLO DIGITAL CONTROL BOX 52
COMMISSIONING CHECKLIST 54
SERVICE INTERVAL RECORD 55
CONTENTS
CONTENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
3
SAFETY &
REGULATIONS
APPLIANCE
INFORMATION
PRE -
INSTALLATION
INSTALLATIONCOMMISSIONING
SERVICING
& SPARES
FAULT FINDING
& DIAGRAMS
NOTES
SAFETY PRECAUTIONS & INSTALLATION REGULATIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
4
SAFETY &
REGULATIONS
SAFETY PRECAUTIONS INSTALLATION REGULATIONS
OIL FUMES OR LEAKS FROM THE APPLIANCE:
Extinguish any naked flames.
Open windows and doors.
Isolate the electrical supply.
Isolate the fuel supply to the boiler.
Rectify fault.
HEALTH & SAFETY:
The appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations (Control of Substances Hazardous to Health Regulations 1988). Where applicable, the CE mark indicates compliance with relative EU Directives.
COMBUSTIBLE AND CORROSIVE MATERIALS: Do not store or use any combustible materials (paper, thinners, paints etc.) inside or within the
vicinity of the appliance. The combustion air must be kept clear of chemically aggressive substances which can corrode the appliance and invalidate any warranty.
FITTING & MODIFICATIONS:
Fitting the appliance and any controls to the appliance may only be carried out by a competent engineer in accordance with these instructions and the relevant Installation Regulations. Flue systems must not be modified in any way other than as described in the fitting instructions. Any misuse or unauthorised modifications to the appliance, flue or associated components and systems could invalidate the warranty. The manufacturer accepts no liability arising from any such actions, excluding statutory rights.
SERVICING:
Advise the user to have the system regularly serviced by a competent, qualified engineer (such as OFTEC registered personnel) using approved spares, to help maintain the economy, safety and reliability of the appliance.
IMPORTANT:
This boiler must only be operated by a responsible adult who has been instructed in, understands and is aware of the boiler’s operating conditions and effects.
Failure to install appliances correctly could lead to prosecution.
The appliance should be installed by a competent person. The person installing the appliance should be aware of the Health and Safety at Work Act and take appropriate action to ensure that the regulations are adhered to. In order to give optimum efficiency and trouble free operation the appliance must be commissioned by a qualified OFTEC engineer.
The compliance with a British Standard does not, in itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following British Standards and regulations in respect of the safe installation of equipment: BS 5410: part 1: Code of practice for Oil Fired Boilers. BS 799: part 5: Specification for Oil Storage Ta nk s . BS 7593: Code of Practice for treatment of water in domestic hot water central heating systems. BS 5449: part 1: Specification for forced circulation hot water central heating for domestic premises. BS 5955: part 8: Specification for the installation of thermoplastic pipes and associated fittings for use in domestic hot and cold water services and heating systems. BS 7291: Thermoplastic pipes and associated fittings for hot and cold water for domestic purposes and heating installations in buildings. BS 7074: part 1: Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS 1254-2: Copper and copper alloys plumbing fittings part 2: Fittings with compression ends for use with copper tubes. BS 7671: IEE Wiring Regulations, current edition. BS 1362: Specification for general purpose fuse links for domestic and similar purposes. The Building Regulations Part G, Part J and L1 England and Wales; Part F, Part G and Part J Section III Scotland; Part L and Part F Northern Ireland. Local water company bye-laws. The Control of Pollution (Oil) Regulations. OFTEC Standards. Where no specific instruction is given, reference should be made to the relevant codes of practice.
Installations in Eire (Republic of Ireland)
The Installation must be performed by a competent and suitably trained person in accordance with the following Eire regulations.
Current Building Regulations - Republic of Ireland
ETCI rules for electrical installation
For further guidance see:
OFTEC Technical book three ­Regional requirements: Republic of Ireland
GENERAL INFORMATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
5
APPLIANCE
INFORMATION
GENERAL INFORMATION
STANDARD PACKAGE:
A - Floor standing oil fired condensing boiler for
open vent and sealed domestic central heating and mains fed hot water.
B - Literature pack.
855mm
600mm
A
520mm
B
Check List
Hardware/Literature pack
Item Qty
Greenstar Heatslave Installation/Servicing Instructions........................1
Users Instructions ..........................................................................................1
Fascia Information Card.................................................................................1
Flue Trim ...........................................................................................................1
Top Panel Inset Plate......................................................................................1
Edge Clips .......................................................................................................1
TECHNICAL DATA
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
6
TECHNICAL DATA
Central Heating
Primary water capacity (total) litres
Available pump head (20°C difference) at max. output metres water
Max. permissible system operating pressure bar
in accordance with WRAS guidelines
Flow restrictor colour
Domestic Hot Water
Maximum flow rate (±15%) litres/min
Minimum inlet pressure (dynamic) for maximum flow rate bar
Maximum hot water temperature rise for 90 litres draw off (@max flow rate) °C
Flue
Exit flue gas mass flow kg/hr
Pipework connections
Fuel line (compression) mm
CH flow mm
CH return mm
Water main inlet mm
DHW outlet mm
CH drain hose connection
Condensate (polypropylene) mm
Electrical
Electrical power supply voltage AC...V
Frequency Hz
Max. power consumption W
Thermostats
CH control thermostat range (cut in/cut out) °C
DHW control thermostat range (cut in/cut out) °C
CH & DHW control thermostat differential °C
Boiler high limit thermostat set point °C
Boiler manual reset overheat thermostat set point °C
Flue reset overheat thermostat set point °C
Tank manual reset overheat thermostat set point °C
DHW pipe thermostat °C
General Data
Maximum hearth temperature °C
SEDBUK (Band A) %
Appliance protection rating (with programmer blanking plate fitted) IP
Appliance protection rating (with fascia programmer fitted) IP
Weight (excluding packaging) kg
DESCRIPTION UNITS 12/18 18/25 25/32
APPLIANCE
INFORMATION
69
4.7
2.5
Lime
15
1. 5
40
29
10
22
22
15
22
21. 5
230
50
240
55/81
55/80
5
92
10 5
110
98
70
<100
90.2
20
20
177
69
4.0
2.5
18
1. 2
40
40
10
22
22
15
22
21. 5
230
50
240
55/81
55/80
5
92
105
110
98
70
<100
90.1
20
20
177
72
4.2
2.5
22
0.9
40
51
10
28
28
15
22
21. 5
230
50
263
55/81
55/80
5
92
105
110
98
70
<100
90.3
20
20
179
LAYOUT & COMPONENTS
1 CONTROL BOX ASSEMBLY 2 CASING SIDE PANEL 3 FLUE 'KNOCK-OUT' SECTION 4 DIVERTER VALVE 5 AUTO AIR VENT 6 CH CONTROL & MANUAL RESET
OVER H EAT THERMOSTATS 7 CIRCULATING PUMP 8 HIGH LIMIT THERMOSTAT
(AUTOMATIC RESET) 9 PRESSURE RELIEF VALVE 10 PUMP AUTO AIR VENT ( Under
protective cap) 11 DHW FLOW SWITCH 12 DHW PIPE THERMOSTAT 13 DHW HEAT EXCHANGER 14 EXPANSION VESSEL 15 CASING SUPPORT PANEL 16 MANUAL RESET FLUE OVERHEAT
THERMOSTAT 17 CLIP FOR FIRE VALVE SENSOR 18 CLIP FOR POWER CABLE 19 AIR INLET PIPE & CASING 20 SECONDARY HEAT EXCHANGER
MANUAL AIR VENT 21 SECONDARY HE AT EXCH A N GER D RA IN 22 1” BSP 23 OIL ISOLATION VALVE 24 FLEXIBLE CONDENSATE OUTLET PIPE 25 SECONDARY HEAT EXCHANGER 26 PRIMARY HEAT EXCHANGER 27 CONDENSATE TRAP 28 CONDENSATE DRAIN PIPE WITH
PUSH FIT CONNECTOR 29 PRIMARY HEAT EXCHANGER DRAIN
COCK 30 TRAY 31 COMBUS TION CH AMBER ACCESS DOOR 32 HEATSLAVE TANK DRAIN COCK 33 HEATSLAVE TANK 34 FLUE MANIFOLD ACCESS COVER 35 FLUE GAS SAMPLING POINT 36 DATA LABEL 37 PRESSURE GAUGE 38 QUICK REFERENCE GUIDE SLOT 39 LOCK-OUT INDICATOR 40 MANUAL RESET TANK OVERHEAT
THERMOSTAT (behind plastic cover) 41 POWER ON INDICATOR 42 OVERHEAT RESET BUTTONS 43 LOCK-OUT RESET BUTTON 44 CH TEMPERATURE CONTROL 45 DHW TEMPERATURE CONTROL 46 RIELLO RDB 1 (12/18)
RIELLO RDB 2.2 (18/25, 25/32) i) Control box ii) Motor iii) Air intake casing iv) Oil pump
v) Combustion head 47 CLIP - AIR INTAKE HOSE 48 AIR INTAKE HOSE
OPTIONA L ACCESSORIES (not supplied)
a - 7 day TWIN CHANNEL DIGITAL
PROGRAMMER
Part No. 7 716 192 033 0
LAYOUT & COMPONENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
7
APPLIANCE
INFORMATION
The diagram below excludes the top, front and RH side casing panels.
14
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43 42
41
40
39 38
37
36
a
35
34
33
32
48
47
i)
iv)
ii)
46
16
15
31
30
29
17
18
19
20
28
27
iii)
v)
21
22 23
24 25
26
CLEANING PRIMARY SYSTEMS
IMPORTANT: All the following Pre-Installation sections must be read and requirements met before starting boiler or flue installation.
CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
CLEANING PRIMARY SYSTEMS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
8
PRE -
INSTALLATION
BEFORE CLEANING THE SYSTEM:
ENSURE THE SYSTEM AND PIPEWORK IS IN GOOD WORKING ORDER.
FLUSH THE EXISTING SYSTEM WITH A POWER FLUSHING MACHINE OR WITH A CHEMICAL CLEANER BEFORE INSTALLING NEW COMPONENTS.
CLEANING THE PRIMARY SYSTEM: 4 Cleanse the system in accordance with
BS 7593.
4 Fill the system with cold mains water to the
recommended pressure and check for leaks.
4 Open all drain cocks and drain the system.
4 Close drain cocks and add a suitable flushing
agent at the correct strength for the system condition in accordance with the manufacturer's instructions.
4 Circulate the flushing agent before the boiler
is fired up.
4 Run the boiler and system at normal operating
temperature in accordance with the manufacturer's instructions.
4 Drain and thoroughly flush the system to
remove the flushing agent and any debris.
IMP ORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
MAINS SUPPLY
ELECTRIC SUPPLY:
• Supply: 230V - 50Hz.
• Cable: PVC insulated 0.75mm
2
(24 x
0.2mm) temperature rated to 90°C.
• Protection IP20.
• External 5A fuse to BS1362.
• The appliance must be earthed.
• Refer to IEE regulations for cross bonding requirements.
• It must be possible to isolate the appliance from the electrical supply with at least a 3mm contact separation in both poles supplying the appliance.
• Wiring between the appliance and the
electrical supply must comply with IEE wiring regulations and any local regulations which may apply for fixed wiring to a stationary appliance.
• Any system connected to the boiler must not
have a separate electrical supply.
WATER SUPPLY:
The following are general requirements and if necessary the advice of the local water company should be sought before fitting the appliance.
• The appliance cold water supply should be the first connection off the water main where possible.
• Maximum mains fed water pressure 10 bar. If necessary, fit a pressure reducing valve.
IMPORTANT: Non-return, back flow prevention devices (including those associated with water meters) fitted to the mains water supply can cause a pressure build up which could damage the boiler and other household appliances.
• Where the water main supply has a non­return, back flow prevention valve fitted, a mini expansion vessel (A) must be connected to the mains water inlet pipe (B) between the non-return valve (C) and the boiler (D) as shown opposite.
Use in hard water areas:
Normally there is no need for water treatment to prevent scale formation as the maximum temperature of the heat exchanger is limited by the electronic control circuit. In areas where the temporary water hardness exceeds 200ppm, consideration may need to be given to the fitting of a scale prevention device. In such circumstances, the advice of the local water authority should be sought.
MAINS SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
9
PRE -
INSTALLATION
12/18kW
Water Mains Pressure:
Minimum dynamic mains water pressure for
maximum performance.
1.5 bar 1.2 bar
0.9 bar
18/25kW 25/32kW
MAINS WATER EXPANSION VESSEL:
A - Mini expansion vessel, part No. 7 716 192 105 B - Mains water inlet C - Non-return valve D - Boiler
A
B
C
D
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
10
PRE -
INSTALLATION
OIL SUPPLY
OIL SUPPLY :
This appliance is suitable for kerosene (28 second oil) only, no other fuel must be used.
• Plastic or steel tanks should be installed to BS 5410. A steel tank should conform to BS 799: part 5 and have a slope of 1 in 24 away from the outlet valve with a sludge cock at its lower end.
• Do not use galvanised steel tanks or pipework for the oil supply system.
• Do not use soldered joints on the oil supply pipework.
a) Single pipe gravity feed system:
The oil storage tank (A) must be positioned so that the oil level does not exceed 4 metres above the level of the burner oil pump (J) and in addi­tion the oil level must be at least 300mm above the oil pump (J). Where the maximum oil level in the oil storage tank exceeds 4 metres, a head breaking device must be installed between the tank (A) and the burner oil pump (J).
b) Double pipe sub-gravity feed system:
Maximum suction height 3.5 metres. Non-return valves must be fitted to the inlet and return oil line between the oil pump (J) and oil storage tank (A).
A
F
BN
GJ
4m max.
K
a)
H
300mm
min.
B DB C
MAXIMUM PIPE RUN FOR SINGLE PIPE GRAVITY FEED SYSTEM
B
A
DB
C
E
K
3.5m max.
L
L
b)
H
F
G
B
MAXIMUM PIPE RUN FOR DOUBLE PIPE SUB-GRAVITY FEED SYSTEM
N
J
E
A - Oil storage tank. B - Isolating valve. C - Oil strainer & water separator. D - Fire valve to BS 5410. E - External wall. F - Fire valve sensor. G - Oil burner.
H - Oil supply pipe. J - Oil pump. K - Full base (plastic tanks). L - Non-return valve. M - De-aerator. N - Oil filter (70μm max filtration size)
NOTE: All dimensions are in metres unless stated otherwise. The maximum pipe run figures are based on using copper pipe with an inside diameter of 2mm less than the Ø.
HEAD 10mmØ 12mmØ
0.5 12 30
1. 0 2 5 6 9
1. 5 3 7 91
2.0 49 100
HEAD 10mmØ 12mmØ
2.5 62 100
3.0 74 100
3.5 87 100
4.0 99 100
HEAD 10mmØ 12mmØ
050 100
0.5 44 100
1. 0 3 8 9 5
1. 5 3 2 8 0
HEAD 10mmØ 12mmØ
2.0 26 66
2.5 20 50
3.0 14 37
3.5 8 22
c)
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
11
PRE -
INSTALLATION
OIL SUPPLY
c) Single pipe suction lift with de-aerator
Maximum suction height 3.5 metres. The oil tank (A) must be positioned below the oil pump (J). Create an inlet and return loop between the de-aerator (M) and oil pump (J).
A non-return valve must be incorporated within the de-aerator or fitted to the oil line between the oil storage tank (A) and the de-aerator (M).
A top feed oil tank fitted with a de-aerator using an internal non-return valve should have any non-return valves fitted in the base of the tank to the suction line removed to assist purging air from the oil line.
Pipework
4 Use copper pipe of the correct diameter
according to the information shown opposite.
• If using soft copper pipe (R220) with a compression fitting, an insert must be used to prevent the pipe from collapsing or distorting when the fitting is tightened.
4 Slide nut (P) and olive (R) onto the oil
supply pipe (H).
4 Slide insert (S) into the pipe. 4 Offer the pipe to the fitting (T) and tighten the
nut (P).
4 Use flexible hoses to connect to the oil pump (J).
4 Lay the oil supply pipe (H) as straight and
level as possible to avoid air pockets and unnecessary friction losses. Route away from the boiler access door or other hot surfaces.
4 Install a manual isolating valve (B) to the oil
supply pipe (H), as close to the oil storage tank (A) as possible.
4 Fit an oil strainer and water separator (C) to
the oil supply pipe, near the oil storage tank. Fit an additional oil filter (N, 70μm max filtration size) close to the boiler, but not inside the boiler casing.
4 Fit a fire valve in accordance with BS 5410.
The fire valve (D) should be fitted externally to the building with the fire valve sensor (F) located within the appliance case.
A fire valve with a shut off temperature of 85°C or higher must be fitted to avoid the possibility of nuisance shut offs.
A capillary type valve provides a neat and simple installation. Alternatively, a fusible link or electrical system may be used.
Under no circumstances should a combination isolating/fire valve be used as the sole fire protection device.
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
0 100 55 26 100
0.5 95 4523100
1.0 80 40 20 90
1. 5 7 0 3 5 17 75
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
2.0 60 30 14 65
2.5 45 25 11 50
3.0 35 15 8 35
3.5 25 10 5 20
The table and illustration above is a guide only and does not in any way override the de-aerator manufacturers instructions.
F
M
A
B
C
H
D
B
N
G
J
3.5m max.
K
MAXIMUM PIPE RUN FOR SINGLE PIPE SUCTION LIFT WITH DE-AERATOR
FUEL FLOW RATE
P
P
T
R
H
E
FUEL FLOW RATE
S
WATER SYSTEMS & PIPEWORK
PRIMARY SYSTEM PLASTIC PIPEWORK:
• Any plastic pipework used for the CH system must have a polymeric barrier, complying with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Plastic pipework used for underfloor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approx. 50°C with 1000mm (minimum) length of copper or steel pipe connected to the boiler, and a 20k differential must be maintained at the appliance.
PRIMARY SYSTEM/CONNECTIONS/VALVES:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• On new installations TRVs must be used on all radiators except the radiator where the room thermostat is sited, this must be fitted with lockshield valves and left open. All installations should have TRVs fitted to radiators within the sleeping accommodation.
• An automatic bypass valve must be connected between the heating flow and return pipes where TRVs are used on radiators. This must be fitted to give at least a 3m circuit when activated.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
SEALED PRIMARY SYSTEM:
• Where the system volume is more than 180 litres at 0.5 bar or exceeds 2.65 bar at maximum heating temperature an extra expansion vessel (B) must be fitted as close as possible to the appliance in the central heating return.
• Pressurise the extra expansion vessel (B) to the same figure as the expansion vessel (A) built into the appliance.
A - Appliance expansion vessel B - Extra expansion vessel C - Automatic bypass valve D - Drain cock E - Appliance
L - Lockshield valve P - Pressure relief discharge R - Radiators T - TRV
TYPICAL SEALED SYSTEM
IMP ORTANT: The boiler should not be allowed to operate with a return temperature of less than 40°C when the system is up to operating temperature.
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
12
PRE -
INSTALLATION
IMPORTANT: The Greenstar Heatslave boiler is for use with sealed central heating systems only.
P
A
E
B
U
C
R R
T
L
D
L
R R
L
T
T
L
L
D
WATER SYSTEMS & PIPEWORK
FILLING PRIMARY SEALED SYSTEMS:
• Filling the system must comply with one of the methods shown opposite.
• The filling point must be at low level and must never be a permanent direct fixing to the mains water supply.
• Filling links must be WRAS approved.
SHOWERS/BIDETS:
• If a shower head can be immersed in water or comes closer than 25mm from the top edge of a bath or shower tray spill over level then an anti-siphon device must be fitted to the shower hose.
Only thermostatically controlled showers are
suitable for use with this appliance.
• Bidets with direct hot & cold mains water can be used (with the approval of the local water authority) and must be the over rim flushing type with shrouded outlets to prevent the fitting of hand held sprays.
DOMESTIC HOT WATER:
• Taps and mixing valves must be capable of sustaining a pressure up to 10 bar in accordance with the Water Regulations as they will be operating at mains water pressure.
• Hot water temperature and flow rate are affected by the size and insulation of pipework making up the distribution system and are controlled by the hot water tap and the water main inlet pressure. A mixing valve can be fitted if a more permanent setting is required.
• If using more than one outlet at once causes water flow starvation, fit flow balancing valves or Ball-O-Fix valves to the appropriate outlets.
Plastic pipework
• Any plastic pipework used for the DHW system must have a polymeric barrier, complying with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Before installing plastic pipework, the pipe manufacturer’s literature should be consulted.
• To prevent the temperature & pressure exceeding the limits advised by the pipe manufacturer, a pressure reducing valve should be used to prevent the incoming water pressure exceeding 3 bar (maximum). Also a mini expansion vessel must be fitted to absorb the expanding water.
• When selecting plastic pipework for use with domestic water supply, it should be ensured that it is compliant with all current local & national legislation & regulations, including building regulations part G, BS 7291 - 1,2 & 3: 2006, BS 8000 - 15-15: 1990 and information.
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
13
PRE -
INSTALLATION
Incoming mains
stop valve
non return valve
Heating return
MCW
Check valve/
Hose
return
Stop cock
Temporary hose
3 bar pressure
reducing
valve
Non return
valve
Mini expansion
vessel
0.75Ltr capacity
Non return
valve
Test cock
Hot water supply
to property
Water main
supply
Stop cock
Greenstar Heatslave
oil fired combination boiler
Balanced cold water
supply to property
CONDENSATE PIPEWORK INTERNAL CONNECTION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
14
PRE -
INSTALLATION
CONDENSATE PIPEWORK INTERNAL CONNECTION
Key to diagrams:
1. Condensate dischange from boiler
2. Universal connector
3. Soil and vent stack
4. Minimum 450mm and up to three storeys
5. Visible air break at plug hole
6. Sink or basin with integrated overflow
7. 75mm sink waste trap
8. Condensate pump
CONDENSATE PIPEWORK:
• Where a new or replacement boiler is being installed, access to an internal “gravity discharge” point should be one of the factors considered in determining boiler location.
• The condensate pipe must be nominally 22mm Ø plastic pipe.
• The condensate pipe work must fall at least 52mm per metre towards the outlet and should take the shortest practicable route.
• Ensure there are no blockages in the pipe run.
Internal connections:
• In order to minimise risk of freezing during prolonged cold spells, the following methods of installing a condensate drainage pipe should be adopted, in order of priority.
• Wherever possible, the condensate drainage pipe should be routed and terminated so that the condensate drains away from the boiler, under gravity, to a suitable internal foul water discharge point such as an internal soil and vent stack.
• A suitable permanent connection to the foul waste pipe should be used.
• Alternatively if the first option is not possible an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. can be used.
Condensate pump:
• Where “gravity discharge” to an internal termination is not physically possible, or where very long internal runs would be required to reach a suitable discharge point, condensate should be removed using a proprietary condensate pump, of a specification recommended by the boiler or condensate pump manufacturer.
• The pump outlet pipe should discharge to a suitable internal foul water discharge point such as an internal soil and vent stack, internal kitchen or bathroom waste pipe, washing machine waste pipe etc.
• A suitable permanent connection to the foul waste pipe should be used.
CONDENSATE PIPEWORK
EXTERNAL CONNECTION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
15
PRE -
INSTALLATION
CONDENSATE PIPEWORK EXTERNAL CONNECTION
Key to diagrams continued:
9. Pipe work transition
10. Insulate and increase pipe size
11. External rain water pipe into foul water
12. External air break
13. Air gap
14. PVCu starp on fitting
15. 43mm 90° male/female bend
CONDENSATE PIPEWORK RUN EXTERNALLY:
• Pipe work length should be kept to a minimum and the route as vertical as possible.
• Weather proof insulation must be used.
• Care should be taken when siting a soakaway to avoid obstructing existing services.
• The condensate pipe work must fall at least 52mm per metre towards the outlet and should take the shortest practicable route.
• Ensure there are no blockages in the pipe run.
External connections:
• If no other discharge method is possible then the use of an externally run condensate drainage pipe terminating at a suitable foul water discharge point, or purpose designed soak away, may be considered.
• If this method is chosen then the following measures should be adopted:
4 The external run be kept as short as possible and
not exceed three metres.
4 The pipe should be run internally as far as possible
before going externally and the pipe diameter should be increased to 32mm before it passes
through the wall to the exterior.
4 The pipe should be insulated using suitable
waterproof and weather resistant insulation.
4 The external pipe should take the shortest and least
exposed route to the discharge point, and should "fall" as steeply as possible away from the boiler, with no horizontal runs in which condensate might stand.
4 The use of fittings, elbows etc. should be kept to a
minimum and any internal “burrs” on cut pipe work should be removed so that the internal pipe section is as smooth as possible.
Fitting an external air brake:
• When a rain water down pipe is used to dispose of condensate, an air break must be installed in the 43mm pipe work, between the boiler condensate outlet and the drainpipe, outside the property, to avoid flooding during adverse weather conditions.
NOTE: Condensate drainage pipe can be run above
or below ground.
• Where the pipe terminates over an open drain or gully, the pipe should terminate below the grating level, but above water level, in order to minimise “wind chill” at the open end.
• The use of a drain cover (such as those used to prevent blockage by leaves) may offer further protection from wind chill.
• Pipe drainage will be improved if the end is cut at 45° as opposed to a straight cut.
CONDENSATE TO SOAK AWAY & PRESSURE RELIEF PIPEWORK
Key to diagrams continued:
16. 100mm Ø minimum plastic pipe
17. Drainage holes
18. Limestone chippings
19. Bottom of sealed tubed
CONDENSATE SOAK AWAY:
• All national and, where appropriate, local regulations for the discharge and neutralisation of condensate should be followed.
• The condensate drainage pipe may be run above or
below the ground to the soak away. The examples shown on this page run above ground.
• The soak away must use a 100mm Ø plastic tube
with two rows of three 12mm holes on 25mm centres and 50mm from the bottom of the tube. The holes must face away from the house.
• The tube must be surrounded by at least 100mm of
limestone chippings to a depth of 400mm.
NOTE: Minimum hole size for the condensate soak
away must be 400mm deep by 300mmØ .
• In situations where there are likely to be extremes of
temperature or exposure, the use of a proprietary trace heating system for external pipe work, incorporating an external frost thermostat, should be considered. If such a system is used, the requirement to use 32mm pipe does not apply. However, all other guidance above and the instructions for the trace heating system, should be closely followed.
NOTE: Internal pipe runs in unheated areas such
as lofts, basements and garages should be treated as external runs.
Making it safe:
• Condensate pipework must not leak, freeze or block up.
• Condensate traps must be filled before starting up the boiler to prevent potentially harmful flue products escaping via the condensate route.
• Do not dispose of condensate into water recovery systems.
PRESSURE RELIEF PIPEWORK:
• The pressure relief valve is a safety device for the boiler
and if activated may discharge boiling water or steam through the relief valve drain pipe.
• Care should be taken when siting the outlet pipe so
that it does not cause an obstruction or discharge above a window, entrance or other public access where it could cause a hazard.
• The pressure relief drain pipe (1) from the boiler
should be at least 15mm diameter copper pipe and run downwards, away from any electrical equipment or other hazard, preferably to an external drain or soak away.
• The pressure relief drain pipe (1) should be finished
with a partial bend, near the outlet to face the external wall (as shown) to help prevent freezing.
3 - Outside wall. 1_3 Drain pipe. 4 - External drain.
CONDENSATE TO SOAK AWAY & PRESSURE RELIEF PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
16
PRE -
INSTALLATION
UNSUITABLE FOR CLAY SOIL TYPES
• This boiler is only suitable for installing internally within a property at a suitable location onto a fixed rigid surface of the same size as the boiler and capable of supporting the boiler weight.
• The boiler must be installed on a flat level surface to ensure condensate does not enter the primary heat exchanger.
• The boiler is not suitable for external installation unless a suitable enclosure is provided.
• Roof space installations must fully conform to BS 5410 part 1 section 4.6.9.
Open flue model (CF):
• In order to ensure clean and efficient combustion an adequate supply of air must be delivered to the combustion chamber.
• To provide sufficient air a suitable inlet must be provided into the room or space in which the boiler is situated.
An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air.
• If the appliance is to be installed in a confined space or compartment two air vents are required, one at high level and one at low level.
The minimum free area of each vent is shown opposite and depends whether the air is taken from another room or from outside the building.
• Where the air is taken from another room that room must contain an air inlet as described above.
Room sealed balanced flue model (RS):
The appliance does not require a separate vent for combustion air.
• Installation in cupboards or compartments require permanent vents for cooling purposes, one at high level and one at low level, either direct to outside air or to a room.
• Both vents must pass to the same room or be on the same wall to the outside air.
The minimum air vent free area is given in the table opposite.
a: INSTALLATION CLEARANCES:
Diagram (a) shows the minimum space recommended to install the boiler only.
b: SERVICE CLEARANCES:
Diagram (b) shows the minimum space required to carry out an annual service.
c: MAINTENANCE & REPAIR CLEARANCES:
The appliance is suitable for an under worktop installation providing that the worktop above the boiler (min 10mm clearance) is removable for maintenance and repair and the front of the boiler is not enclosed.
* Remove the flue 'knock-out' panel sections if this clearance is less than 75mm.
** Due to changes to BS 5410 and modern building design, these figures no longer incorporate the adventitious ventilation allowance.
a: RECOMMENDED
MINIMUM AIR VENT AREA (cm2) FOR APPLIANCES INSTALLED IN A COMPARTMENT:
1
Internal air to and from a space/room inside the building. 2External air to and from directly outside the building.
12/18kW
CF minimum air inlet sizes**
99 138
176
18/25kW 25/32kW
Output
Size cm
2
BOILER LOCATION &
CLEARANCES
Conventional flue
kW
Internal1ventilation External2ventilation
High
Level
Low
Level
High
Level
Low
Level
12 /18 198 279 99 19 8
18/25 275 413 138 275
25/32 352 528 17 6 352
Room Sealed flue:
kW
Internal1ventilation External2ventilation
High
Level
Low
Level
High
Level
Low
Level
12 /18 198 198 99 99
18/25 275 275 13 8 13 8
25/32 352 352 17 6 17 6
BOILER LOCATION &
CLEARANCES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32 6 720 802 432 issue A 04/2012
17
PRE -
INSTALLATION
INSTALLATION CLEARANCES
1200mm
100mm
1155mm
600mm
720mm
300mm
100mm
b: ANNUAL SERVICE CLEARANCES
1200mm
5mm*
865mm
600mm
530mm
10mm
5mm*
c: MAINTENANCE & REPAIR CLEARANCES
300mm
530mm
5mm*
1200mm
5mm*
1155mm
600mm
COMPARTMENTS:
Follow the requirements of BS 5410 and note:
• Minimum clearances must be maintained.
• An access door is required to install, service and maintain the boiler and any ancillary equipment.
• If fitting the boiler into an airing cupboard use a non-combustible material (if perforated, maximum hole sizes of 13mm) to separate the boiler from the airing space.
Venting compartments:
There must be sufficient clearance around the appliance to allow proper circulation of ventilation air. The clearances required for installation and servicing will normally be adequate for ventilation.
• Ventilation must be provided for boilers fitted into compartments as described in B S 5410 .
• Combustion air must not be taken from a room or internal space containing a bath or shower and must not communicate with a protected area such as a hall, stairway, landing, corridor, lobby, shaft etc.
• Air vents must allow access for clean free air and must be sited to comply with the flue terminal position requirements.
• Air ducting runs must not exceed 3m.
• Low level air vents must be less than 450mm from the floor.
• A warning label must be added to the vents with a statement to the effect: ''Do not block this vent. Do not use for storage.”
SHOWER / BATHROOMS:
The boiler must not be installed in zones 0, 1 or 2 (the shaded areas shown on the diagrams o ppo­site).
IMPORTANT: conventional flued boilers must not be fitted in a bathroom.
IMPORTANT: any appliance control using mains electricity must not be able to be touched by a person using the bath or shower.
Electrical switches, fused spur and socket outlets must not be fitted in the bath­room.
In all cases the IEE wiring regulations must be consulted.
All pipework in bathrooms and shower rooms must be cross bonded.
BOILER LOCATION &
CLEARANCES
1
2
1
2
0
1
2
1
2
0
BOILER LOCATION & CLEARANCES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
6 720 802 432 issue A 04/2012
18
PRE -
INSTALLATION
2250m m
600mm
600m m
7 50m m
2250m m
2250m
m
600mm radius
600m m
7 50m m
2250m m
Loading...
+ 42 hidden pages