worcester Greenstar Heatslave External 12/18 User guide

INSTRUCTION MANUAL
INSTALLATION, COMMISSIONING & SERVICING
FLOOR STANDING EXTERNAL OIL FIRED CONDENSING COMBINATION BOILER USING BALANCED FLUE SYSTEM
GREENSTAR HEATSLAVE EXTERNAL 12/18, 18/25 & 25/32
FOR SEALED CENTRAL HEATING SYSTEMS WITH MAINS FED DOMESTIC HOT WATER
UK
THE APPLIANCE IS FOR USE WITH KEROSENE (28 SECOND OIL) ONLY
INSTALLATION & SERVICING INSTRUCTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
2
SYMBOLS USED IN THIS MANUAL:
INSTALLATION & SERVICING INSTRUCTIONS
IMPORTANT HANDLING INSTRUCTIONS: It is advised that more than one person is involved in the transfer of the packaged appliance from the van to the point of installation. It is advised that no attempt should be made to move the packaged appliance without the use of a suitable truck. At all times the correct method for handling heavy objects should be strictly observed.
GENERAL HANDLING GUIDELINES:
• Lift only a manageable weight, or ask for help.
• When lifting, bend the knees, and keep the back straight and feet apart.
• Do not lift and twist at the same time.
• Lift and carry items close to the body.
• Wear protective clothing and gloves to protect from any sharp edges.
WATER TREATMENT:
FERNOX 01799 550811
fernox.com
SENTINEL 0800 389 4670
sentinel-solutions.net
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
THESE INSTRUCTIONS ARE APPLICABLE TO THE WORCESTER APPLIANCE MODEL(S) STATED ON THE FRONT COVER OF THIS MANUAL ONLY AND MUST NOT BE USED WITH ANY OTHER MAKE OR MODEL OF APPLIANCE.
THE INSTRUCTIONS APPLY IN THE UK AND EIRE ONLY AND MUST BE FOLLOWED EXCEPT FOR ANY STATUTORY OBLIGATION.
THIS APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON. FAILURE TO INSTALL CORRECTLY COULD LEAD TO PROSECUTION.
COMPLYING WITH THE BUILDING REGULATIONS:
This heating appliance forms part of the controlled services for the building. It is law that all controlled services for buildings must comply with building regulations. You must be able to satisfy your Local Authority Building Control Body (LABC) that the work carried out concerning the installation and commissioning of this heating appliance has been carried out to a satisfactory standard.
OFTEC operate a competent persons scheme and registered installers are able to certify that their work complies with building regulations. Under the scheme;
l OFTEC must be informed about every installation. l OFTEC will issue a building regulations compliance certificate to the householder and will
notify the LABC.
OFTEC provide controlled document forms CD10 and CD11 for use during installation and commissioning respectively.
Other organisations operate self-certification schemes e.g. NAPIT and BESCA Ltd. and it may be possible for installers who are members of these organisations to self certify their work.
Alternatively you must submit a building control notice to the LABC before installing any boiler. The LABC will then arrange regular inspection visits during the work to ensure that the installation complies with the regulations.
IF YOU ARE IN ANY DOUBT CONTACT THE WORCESTER TECHNICAL HELPLINE ON: 0844 892 3366. DISTANCE LEARNING AND TRAINING COURSES ARE AVAILABLE FROM WORCESTER.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE COMPLETED COMMISSIONING FORM AND THE USER MANUAL WITH THE OWNER OR WITH THE APPLIANCE AFTER INSTALLATION OR SERVICING. THE SERVICE INTERVAL RECORD CAN BE FOUND ON THE BACK PAGE OF THIS MANUAL.
ABBREVIATIONS USED IN THIS MANUAL: Ø Diameter CH Central Heating DHW Domestic Hot Water DCW Domestic Cold Water TRV Thermostatic Radiator Valve IP Ingress Protection CF Conventional flue BF Balanced flue N/A Not allowed SEDBUK Seasonal Efficiency of Domestic Boilers in the United Kingdom OFTEC Oil Firing Technical Association for the Petroleum Industry IEE Institute of Electrical Engineers LABC Local Authority Building Control Body
STORE THE APPLIANCE IN A DRY AREA PRIOR TO INSTALLATION.
SAFETY & REG ULATIONS
IMPORTANT INFORMATION AND SYMBOLS 2
SAFETY PRECAUTIONS AND INSTALLATION REGULATIONS 4
APPLIANCE INFORMATION
GENERAL INFORMATION 5
TECHNICAL DATA 6
LAYOUT & COMPONENTS 7
PRE-INSTALLATION
CLEANING PRIMARY SYSTEMS 8
MAINS SUPPLIES 9
OIL SUPPLY 10
WATER SYSTE MS & PIPEWORK 12
CONDENSATE PIPEWORK 14
PRESSURE RELIEF PIPEWORK 16
CABINET MOUNTED LOW LEVEL FLUE TERMINAL POSITIONS 17
HIGH LEVEL FLUE TERMINAL POSITIONS 18
BOILER LOCATION & CLEARANCES 19
BALANCED EXTERNAL OILFIT FLUE OPTIONS 20
CABINET MOUNTED BALANCED HORIZONTAL FLUE OPTIONS 21
INSTALLATION
UNPACKING THE BOILER 22
PIPEWORK & FLUE POSITIONS 23
BOILER INSTALLATION 24
FLUE INSTALLATION 25
COMBUSTION CHAMBER 26
PIPEWORK CONNECTIONS 27
OIL BURNER AND PUMP 29
REFITTING COMPONENTS 30
ELECTRICS 31
COMMISSIONING
PRE-COMMISSIONING CHECKS - APPLIANCE 33
FILLING THE SYSTEM 34
STARTING THE APPLIANCE 35
WATER TREATMENT 40
FINISHING COMMISSIONING - APPLIANCE 31
SERVICING & SPARES
INSPECTION AND SERVICE 42
SHORT PARTS LIST RIELLO RDB 1 - 12/18 46
SHORT PARTS LIST RIELLO RDB 2.2 - 18/25 47
SHORT PARTS LIST RIELLO RDB 2.2 - 25/32 48
FAULT FINDING & DIAGNOSIS
ELECTRICAL SCHEMATIC 49
FAULT FINDING 50
FAULT FINDING LOGIC FOR RIELLO DIGITAL CONTROL BOXES 52
COMMISSIONING & SERVICE RECORDS
OIL BOILER COMMISSIONING CHECKLIST 54
SERVICE INTERVAL RECORD 55
CONTENTS
CONTENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
3
SAFETY &
REGULATIONS
APPLIANCE
INFORMATION
PRE -
INSTALLATION
INSTALLATIONCOMMISSIONING
SERVICING
& SPARES
FAULT FINDING
& DIAGRAMS
SAFETY PRECAUTIONS & INSTALLATION REGULATIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
4
SAFETY &
REGULATIONS
SAFETY PRECAUTIONS INSTALLATION REGULATIONS
OIL FUMES OR LEAKS FROM THE APPLIANCE:
4
Extinguish any naked flames.
4
Isolate the electrical supply.
4
Isolate the fuel supply to the boiler.
4
Rectify fault.
HEALTH & SAFETY:
The appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations (Control of Substances Hazardous to Health Regulations 1988). Where applicable, the CE mark indicates compliance with relative EU Directives.
COMBUSTIBLE AND CORROSIVE MATERIALS: Do not store or use any combustible materials (paper, thinners, paints etc.) inside or within the
vicinity of the appliance. The combustion air must be free from chemically aggressive substances which can corrode the appliance and invalidate any warranty.
FITTING & MODIFICATIONS:
Fitting the appliance and any controls to the appliance may only be carried out by a competent engineer in accordance with these instructions and the relevant Installation Regulations. Flue systems must not be modified in any way other than as described in the fitting instructions. Any misuse or unauthorised modifications to the appliance, flue or associated components and systems could invalidate the warranty. The manufacturer accepts no liability arising from any such actions, excluding statutory rights.
SERVICING:
Advise the user to have the system regularly serviced by a competent, qualified engineer (such as OFTEC registered personnel) using approved spares, to help maintain the economy, safety and reliability of the appliance.
IMPORTANT:
This boiler must only be operated by a responsible adult who has been instructed in, understands and is aware of the boiler’s operating conditions and effects.
Failure to install appliances correctly could lead to prosecution.
The appliance should be installed by a competent person. The person installing the appliance should be aware of the Health and Safety at Work Act and take appropriate action to ensure that the regulations are adhered to. In order to give optimum efficiency and trouble free operation the appliance must be commissioned by a qualified OFTEC engineer.
The compliance with a British Standard does not, in itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following British Standards and regulations in respect of the safe installation of equipment: BS 5410: part 1: Code of practice for Oil Fired Boilers. BS 799: part 5: Specification for Oil Storage Ta nk s . BS 7593: Code of Practice for treatment of water in domestic hot water central heating systems. BS 5449: part 1: Specification for forced circulation hot water central heating for domestic premises. BS 5955: part 8: Specification for the installation of thermoplastic pipes and associated fittings for use in domestic hot and cold water services and heating systems. BS 7291: Thermoplastic pipes and associated fittings for hot and cold water for domestic purposes and heating installations in buildings. BS 7074: part 1: Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS 1254-2: Copper and copper alloys plumbing fittings part 2: Fittings with compression ends for use with copper tubes. BS 7671: IEE Wiring Regulations, current edition. BS 1362: Specification for general purpose fuse links for domestic and similar purposes. The Building Regulations Part G, Part J and L1 England and Wales; Part F and Part J Section III Scotland; Part L and Part F Northern Ireland. Local water company bye-laws. The Control of Pollution (Oil) Regulations. OFTEC Standards. Where no specific instruction is given, reference should be made to the relevant codes of practice.
Installations in Eire (Republic of Ireland)
The Installation must be performed by a competent and suitably trained person in accordance with the following Eire regulations.
Current building regulations - Part J Republic of Ireland
ETCI rules for electrical installation
For further guidance see:
OFTEC Technical book three ­Regional requirements: Republic of Ireland
GENERAL INFORMATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
5
APPLIANCE
INFORMATION
GENERAL INFORMATION
STANDARD PACKAGE:
A - Floor standing oil fired condensing boiler for
open vent and sealed domestic central heating and mains fed hot water.
B - Literature pack.
C -100mmØ services duct.
D - Cabinet key
Check List
Item Qty
Greenstar Heatslave External Installation/Servicing Instructions........1
Users Instructions ..........................................................................................1
100mm Ø Services Duct...............................................................................1
Cabinet Key.......................................................................................................1
TECHNICAL DATA
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
6
TECHNICAL DATA
Central Heating
Primary water capacity (total) litres
Available pump head (20°C difference) at max. output metres water
Max. permissible system operating pressure bar
in accordance with WRAS guidelines
Flow restrictor colour
Domestic Hot Water
Optimum flow rate (±15%) litres/min
Minimum inlet pressure (dynamic) for optimum flow rate bar
Maximum hot water rise for 90 litres draw off (@optimum flow rate) °C
Flue
Exit flue gas mass flow kg/hr
Pipework connections
Fuel line (compression) mm
CH flow mm
CH return mm
Water main inlet mm
DHW outlet mm
Condensate (polypropylene) mm
Electrical
Electrical power supply voltage AC...V
Frequency Hz
Max. power consumption W
Thermostats
CH control thermostat range (cut in/cut out) °C
DHW control thermostat range (cut in/cut out) °C
CH & DHW control thermostat differential °C
Boiler high limit thermostat set point °C
Boiler manual reset overheat thermostat set point °C
Tank manual reset overheat thermostat set point °C
Flue reset overheat thermostat set point °C
DHW pipe thermostat °C
General Data
Maximum hearth temperature °C
SEDBUK (Band A) %
Appliance protection rating IP
Weight (excluding packaging) kg
DESCRIPTION UNITS 12/18 18/25 25/32
APPLIANCE
INFORMATION
69
4.7
2.5
Lime
15
1. 5
40
29
10
22
22
15
22
21. 5
230
50
240
55/81
55/72
5
92
10 5
94
110
70
<100
90.2
45
19 5
69
4.0
2.5
18
1. 2
40
40
10
22
22
15
22
21. 5
230
50
240
55/81
55/72
5
92
105
94
110
70
<100
90.1
45
19 5
72
4.2
2.5
22
0.9
40
51
10
28
28
15
22
21. 5
230
50
263
55/81
55/72
5
92
105
94
110
70
<100
90.3
45
206
LAYOUT & COMPONENTS
The diagram opposite excludes the top, front and RH side casing panels.
1. CONTROL BOX ASSEMBLY
2. DIVERTER VALVE
3. PRESSURE GAUGE
4. AUTO AIR VENT
5. CH CONTROL AND MANUAL RESET OVER H EAT THER MOSTAT PHIAL
6. CASING SIDE PANEL
7. CIRCULATING PUMP
8. AUTO-RESET HIGH LIMIT THERMOSTAT PHIAL
9. PUMP AUTO AIR VENT (under protective cap)
10. DHW FLOW SWITCH
11. PRESSURE RELIEF VALVE
12, DHW PIPE THERMOST A T
13. DHW HEAT EXCHANGER
14. FLUE GAS SAMPLING POINT
15. FLUE OVERHEAT THERMOSTAT PHIAL
16. CASING SUPPORT PANEL
17. FLUE MANIFOLD ACCESS COVER
18. AIR INLET DUCT AND CASING
19. SECONDARY HEAT EXCHANGER BLEED POINT (ONE ON EITHER SIDE)
20. SECONDARY HEAT EXCHANGER
21. SECONDARY HEAT EXCHANGER DRAIN
22. EXPANSION VESSEL
23. COMBINED FEED & EXPANSION & OPEN SAFETY VENT PIPE OUTLET
24. CONDENSATE OUTLET
25. PRIMARY HEAT EXCHANGER
26. TRAY
27. OIL ISOLATION VALVE
28. COND ENSATE TRAP
29. CONDENSATE TRAP BRACKET
30. PRIMARY HEAT EXCHANGER DRAIN COCK
31. COMBUSTION CHAMBER ACCESS DOOR
32. HEATSLAVE TANK DRAIN
33. HEATSLAVE TANK
34. DATA LABEL
35. MODE SWITCH
36. BOILER MODE INDICATOR
37. LOCKOUT INDICATOR
38. MANUAL RESET TANK OVERHEAT THERMOSTAT (behind plastic cover)
39. OVERHEAT RESET BUTTONS (boiler & flue temperature)
40. LOCKOUT RESET BUTTON
41. SERVIC E CON NECTION
42. CH TEMPERATURE CONTROL
43. DHW TEMPERATURE CONTROL
44. FROST THERMOSTAT SENSORS
45. RIELLO RDB 1 (12/18) &
RDB 2.2 (18/25 & 25/32) i) CONTROL BOX ii) MOTOR iii) AIR INTAKE CASING iv) OIL PUM P v) COMBUSTION HEAD
46. CLIP - AIR INTAKE HOSE
47. AIR INTAKE HOSE
LAYOUT & COMPONENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
7
APPLIANCE
INFORMATION
1
6
2
4
8
7
5
10
22
13
16
3
15
17
14
18
19
21
23
30
24
20
25
26
31
34
32
33
35
36
9
39/40
43
42
45
46
47
iv)
v)
iii)
i)
ii)
44
27
28
29
41
38
11
37
12
CLEANING PRIMARY SYSTEMS
BEFORE CLEANING THE SYSTEM:
ENSURE THE SYSTEM AND PIPEWORK IS IN GOOD WORKING ORDER.
FLUSH THE EXISTING SYSTEM WITH A POWER FLUSHING MACHINE OR WITH A CHEMICAL CLEANER BEFORE INSTALLING NEW COMPONENTS.
CLEANING THE PRIMARY SYSTEM: 4 Cleanse the system in accordance with
BS 7593.
4 Fill the system with cold mains water to the
recommended pressure and check for leaks.
4 Open all drain cocks and drain the system.
4 Close drain cocks and add a suitable flushing
agent at the correct strength for the system condition in accordance with the manufacturer's instructions.
4 Circulate the flushing agent before the boiler
is fired up.
4 Run the boiler and system at normal operating
temperature in accordance with the manufacturer's instructions.
4 Drain and thoroughly flush the system to
remove the flushing agent and any debris.
IMPORTANT: All the following Pre-Installation sections must be read and requirements met before starting boiler or flue installation.
CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
CLEANING PRIMARY SYSTEMS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
8
PRE -
INSTALLATION
MAINS SUPPLIES
ELECTRIC SUPPLY:
• Supply: 230V - 50Hz.
• Cable: PVC insulated 0.75mm
2
(24 x
0.2mm) temperature rated to 90°C.
• Protection IP45.
• External 5A fuse to BS 1362.
• The appliance must be earthed.
• Please refer to IEE regulations for cross bonding requirements.
• It must be possible to isolate the appliance from the electrical supply with at least a 3mm contact separation in both poles supplying the appliance.
• Wiring between the appliance and the
electrical supply must comply with IEE wiring regulations and any local regulations which may apply for fixed wiring to a stationary appliance.
• Any system connected to the boiler must not
have a separate electrical supply.
WATER SUPPLY:
The following are general requirements and if necessary the advice of the local water company should be sought before fitting the appliance.
• The appliance cold water supply should be the first connection off the water main where possible.
• Maximum mains fed water pressure 10 bar. If necessary, fit a pressure reducing valve.
IMPORTANT: Non-return, back flow prevention devices (including those associated with water meters) fitted to the mains water supply can cause a pressure build up which could damage the boiler and other household appliances.
• Where the water main supply has a non­return, back flow prevention valve fitted, a mini expansion vessel (A) must be connected to the mains water inlet pipe (B) between the non-return valve (C) and the boiler (D) as shown opposite.
Use in hard water areas:
Normally there is no need for water treatment to prevent scale formation as the maximum temperature of the heat exchanger is limited by the control circuit. In areas where the temporary water hardness exceeds 200ppm, consideration may need to be given to the fitting of a scale prevention device. In such circumstances, the advice of the local water authority should be sought.
MAINS WATER EXPANSION VESSEL:
A - Mini expansion vessel, part No. 7 716 192 105 B - Mains water inlet C - Non-return valve D - Boiler
A
B
C
D
MAINS SUPPLIES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
9
PRE -
INSTALLATION
12/18 kW
Water Mains Pressure:
Minimum dynamic mains water pressure for
optimum performance.
1.5 bar 1.2 bar
0.9 bar
18/25kW 25/32kW
IMPORTANT: The appliance provides a permanent external electrical supply for servicing and must therefore be fed via a circuit breaker incorporating earth leakage protection.
OIL SUPPLY
OIL SUPPLY:
This appliance is suitable for kerosene (28 second oil) only, no other fuel must be used.
• Plastic or steel tanks should be installed to BS 5410. A steel tank should conform to BS 799: part 5 and have a slope of 1 in 24 away from the outlet valve with a sludge cock at its lower end.
• Do not use galvanised steel tanks or pipework for the oil supply system.
• Do not use soldered joints on the oil supply pipework.
a) Single pipe gravity feed system:
The oil storage tank (A) must be positioned so that the oil level does not exceed 4 metres above the level of the burner oil pump (J) and in addi­tion the oil level must be at least 300mm above the oil pump (J). Where the maximum oil level in the oil storage tank exceeds 4 metres, a head breaking device must be installed between the tank (A) and the burner oil pump (J).
b) Double pipe sub-gravity feed system:
Maximum suction height 3.5 metres. Non-return valves must be fitted to the inlet and return oil line between the oil pump (J) and oil storage tank (A).
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
10
PRE -
INSTALLATION
A - Oil storage tank B - Isolating valve C - Oil strainer & water separator D - Fire valve to BS5410 E - External casing F - Fire valve sensor G - Oil burner
H - Oil supply pipe J - Oil pump K - Full base (plastic tanks) L - Non-return valve M - De-aerator N - Oil filter (70μm max filtration size)
NOTE: All dimensions are in metres unless stated otherwise. The maximum pipe run figures are based on using copper pipe with an inside diameter of 2mm less than the Ø.
HEAD 10mmØ 12mmØ
0.5 12 30
1. 0 25 69
1. 5 37 91
2.0 49 100
HEAD 10mmØ 12mmØ
2.5 62 100
3.0 74 100
3.5 87 100
4.0 99 100
HEAD 10mmØ 12mmØ
050 100
0.5 44 100
1. 0 3 8 9 5
1. 5 3 2 80
HEAD 10mmØ 12mmØ
2.0 26 66
2.5 20 50
3.0 14 37
3.5 8 22
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
11
PRE -
INSTALLATION
OIL SUPPLY
c) Single pipe suction lift with de-aerator
Maximum suction height 3.5 metres. The oil tank (A) must be positioned below the oil pump (J). Create an inlet and return loop between the de-aerator (M) and oil pump (J).
A non-return valve must be incorporated within the de-aerator or fitted to the oil line between the oil storage tank (A) and the de-aerator (M).
A top feed oil tank fitted with a de-aerator using an internal non-return valve should have any non-return valves fitted in the base of the tank to the suction line removed to assist purging air from the oil line.
Pipework
4 Use copper pipe of the correct diameter
according to the information shown opposite.
• If using soft copper pipe (R220) with a compression fitting, an insert must be used to prevent the pipe from collapsing or distorting when the fitting is tightened.
4 Slide nut (P) and olive (R) onto the oil
supply pipe (H).
4 Slide insert (S) into the pipe. 4 Offer the pipe to the fitting (T) and tighten the
nut (P).
4 Use flexible hoses to connect to the oil pump (J).
4 Lay the oil supply pipe (H) as straight and
level as possible to avoid air pockets and unnecessary friction losses. Route away from the boiler access door or other hot surfaces.
4 Install a manual isolating valve (B) to the oil
supply pipe (H), as close to the oil storage tank (A) as possible.
4 Fit an oil strainer and water separator (C) to
the oil supply pipe, near the oil storage tank. Fit an additional oil filter (N, 70μm max filtration size) close to the boiler, but not inside the boiler casing.
4 Fit a fire valve in accordance with BS 5410.
The fire valve (D) should be fitted externally to the building with the fire valve sensor (F) located within the appliance case.
A fire valve with a shut off temperature of 85°C or higher must be fitted to avoid the possibility of nuisance shut offs.
A capillary type valve provides a neat and simple installation. Alternatively, a fusible link or electrical system may be used.
Under no circumstances should a combination isolating/fire valve be used as the sole fire protection device.
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
0 100 55 26 100
0.5 95 4523100
1.0 8 0 40 20 90
1. 5 70 3 5 17 7 5
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
2.0 60 30 14 65
2.5 45 25 11 50
3.0 35 15 8 35
3.5 25 10 5 20
The table and illustration above is a guide only and does not in any way override the de­aerator manufacturers instructions.
INSTALLATIONCOMMISSIONING
WATER SYSTEMS & PIPEWORK
PRIMARY SYSTEM PLASTIC PIPEWORK:
• Any plastic pipework used for the CH system must have a polymeric barrier, complying with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Plastic pipework used for underfloor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approx. 50°C with 1000mm (minimum) length of copper or steel pipe connected to the boiler, and a 20k differential must be maintained at the appliance.
PRIMARY SYSTEM/CONNECTIONS/VALVES:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• On new installations TRVs must be used on all radiators except the radiator where the room thermostat is sited, this must be fitted with lockshield valves and left open. All installations should have TRVs fitted to radiators within the sleeping accommodation.
• An automatic bypass valve must be connected between the heating flow and return pipes where TRVs are used on radiators. This must be fitted to give at least a 3m circuit when activated.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
SEALED PRIMARY SYSTEM:
• Where the system volume is more than 180 litres at 0.5 bar or exceeds 2.65 bar at maximum heating temperature an extra expansion vessel (B) must be fitted as close as possible to the appliance in the central heating return.
• Pressurise the extra expansion vessel (B) to the same figure as the expansion vessel (A) built into the appliance.
IMPORTANT: The boiler should not be allowed to operate with a return temperature of less than 40°C when the system is up to operating temperature.
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
12
PRE -
INSTALLATION
A - Appliance expansion vessel B - Extra expansion vessel C - Automatic bypass valve D - Drain cock E - Appliance
L - Lockshield valve P - Pressure relief discharge R - Radiators T - TRV
TYPICAL SEALED SYSTEM
WATER SYSTEMS & PIPEWORK
INSTALLATIONCOMMISSIONING
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
13
PRE -
INSTALLATION
FILLING PRIMARY SEALED SYSTEMS:
• Filling the system must comply with one of the methods shown opposite.
• The filling point must be at low level and must never be a permanent direct fixing to the mains water supply.
• Filling links must be WRAS approved.
SHOWERS/BIDETS:
• If a shower head can be immersed in water or comes closer than 25mm from the top edge of a bath or shower tray spill over level then an anti-siphon device must be fitted to the shower hose.
Only thermostatically controlled showers are
suitable for use with this appliance.
• Bidets with direct hot & cold mains water can be used (with the approval of the local water authority) and must be the over rim flushing type with shrouded outlets to prevent the fitting of hand held sprays.
DOMESTIC HOT WATER:
• Taps and mixing valves must be capable of sustaining a pressure up to 10 bar in accordance with the Water Regulations as they will be operating at mains water pressure.
• Hot water temperature and flow rate are affected by the size and insulation of pipework making up the distribution system and are controlled by the hot water tap and the water main inlet pressure. A mixing valve can be fitted if a more permanent setting is required.
• If using more than one outlet at once causes water flow starvation, fit flow balancing valves or Ball-O-Fix valves to the appropriate outlets.
Plastic pipework
• Any plastic pipework used for the DHW system must have a polymeric barrier, complying with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Before installing plastic pipework, the pipe manufacturer’s literature should be consulted.
• To prevent the temperature & pressure exceeding the limits advised by the pipe manufacturer, a pressure reducing valve should be used to prevent the incoming water pressure exceeding 3 bar (maximum). Also a mini expansion vessel must be fitted to absorb the expanding water.
• When selecting plastic pipework for use with domestic water supply, it should be ensured that it is compliant with all current local & national legislation & regulations, including building regulations part G, BS 7291 - 1,2 & 3: 2006, BS 8000 - 15-15: 1990 and information.
CONDENSATE PIPEWORK INTERNAL CONNECTION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
14
PRE -
INSTALLATION
CONDENSATE PIPEWORK
Key to diagrams:
1. Condensate dischange from boiler
2. Universal connector
3. Soil and vent stack
4. Minimum 450mm and up to three storeys
5. Pipe work transition
6. Insulate and increase pipe size
7. External rain water pipe into foul water
8. External air brake
9. Air gap
10. PVCu starp on fitting
11. 43mm 90° male/female bend
CONDENSATE PIPEWORK:
• Where a new or replacement boiler is being installed, access to an internal “gravity discharge” point should be one of the factors considered in determining boiler location.
• The condensate pipe must be a minimum of 22mm Ø plastic pipe.
• The condensate pipe work must fall at least 52mm per metre towards the outlet and should take the shortest practicable route.
• Ensure there are no blockages in the pipe run.
CONDENSATE PIPEWORK RUN EXTERNALLY:
• Pipe work length should be kept to a minimum and the route as vertical as possible.
• Weather proof insulation must be used.
• Care should be taken when siting a soakaway to avoid obstructing existing services.
• The condensate pipe work must fall at least 52mm per metre towards the outlet and should take the shortest practicable route.
• Ensure there are no blockages in the pipe run.
4 The external run be kept as short as possible and
not exceed three metres.
4 The pipe diameter should be increased to 32mm. 4 The pipe should be insulated using suitable
waterproof and weather resistant insulation.
4 The external pipe should take the shortest and least
exposed route to the discharge point, and should "fall" as steeply as possible away from the boiler, with no horizontal runs in which condensate might stand.
4 The use of fittings, elbows etc. should be kept to a
minimum and any internal “burrs” on cut pipe work should be removed so that the internal pipe section is as smooth as possible.
CONDENSATE PIPEWORK
EXTERNAL CONNECTION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
15
PRE -
INSTALLATION
CONDENSATE PIPEWORK
Fitting an external air brake:
• When a rain water down pipe is used to dispose of condensate, an air break must be installed in the 43mm pipe work, between the boiler condensate outlet and the drainpipe, outside the property, to avoid flooding during adverse weather conditions.
NOTE: Condensate drainage pipe can be run above
or below ground.
• Where the pipe terminates over an open drain or gully, the pipe should terminate below the grating level, but above water level, in order to minimise “wind chill” at the open end.
• The use of a drain cover (such as those used to prevent blockage by leaves) may offer further protection from wind chill.
• Pipe drainage will be improved if the end is cut at 45° as opposed to a straight cut.
CONDENSATE SOAK AWAY:
Key to diagrams:
12. 100mm Ø minimum plastic pipe
13. Drainage holes
14. Limestone chippings
15. Bottom of sealed tube
• All national and, where appropriate, local regulations for the discharge and neutralisation
of condensate should be followed.
• The condensate drainage pipe may be run
above or below the ground to the soak away. The examples shown on this page run above ground.
• The soak away must use a 100mm Ø plastic
tube with two rows of three 12mm holes on 25mm centres and 50mm from the bottom of the tube. The holes must face away from the house.
• The tube must be surrounded by at least
100mm of limestone chippings to a depth of 400mm.
NOTE: Minimum hole size for the condensate soak away must be 400mm deep by 300mmØ .
• In situations where there are likely to be
extremes of temperature or exposure, the use of a proprietary trace heating system for
external pipe work, incorporating an external
frost thermostat, should be considered. If such a system is used, the requirement to use 32mm pipe does not apply. However, all other guidance above and the
instructions for the trace heating system,
should be closely followed.
NOTE: Internal pipe runs in unheated areas such as lofts, basements and garages should be treated as external runs.
Making it safe:
• Condensate pipework must not leak, freeze or block up.
• Condensate traps must be filled before starting up the boiler to prevent potentially harmful flue products escaping via the condensate route.
• Do not dispose of condensate into water recovery systems.
UNSUITABLE FOR CLAY SOIL TYPES
PRESSURE RELIEF PIPEWORK:
• The pressure relief drain pipe (2) should be at least 15mm diameter copper pipe and run
downwards away from the boiler and discharge
away from any electrics or other hazard, preferably to an external drain or soakaway.
• Pipe (2) should be finished with a partial bend, near the outlet to face the external wall (as shown) to help prevent freezing.
IMPORTANT: The pressure relief valve is a safety device for the boiler and if activated may discharge boiling water or steam through the relief valve drain pipe. Care should be taken when siting the outlet pipe so that it does not cause an obstruction or discharge into a public area where it could cause a hazard.
CONDENSATE & PRESSURE RELIEF PIPEWORK
16
PRE -
INSTALLATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 106 389c (01/2009)
PRESSURE RELIEF PIPEWORK
1 - Boiler casing. 2 - Drain pipe.
CABINET MOUNTED
LOW LEVEL FLUE TERMINAL
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 6 720 802 433 issue A 04/2012
17
PRE -
INSTALLATION
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H)
A 1Directly below an opening, air brick, opening windows, etc 600mm
B 1Horizontally to an opening, air brick, opening window, etc 600mm
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm
combustible material protected
D 2Below a plastic/painted gutter, drainage pipe or eaves without 600mm
protection to combustible material
E From vertical sanitary pipework 300mm
F From an external or internal corner or from a surface or boundary 300mm
alongside the terminal
G Above ground or balcony level 300mm*
H AFrom a surface or boundary facing the terminal with 2500mm 1200mm
clearance to both sides of the terminal
H
B
From a surface or boundary facing the terminal with less than 2500mm
2500mm clearance to either side of the terminal
I AFrom a terminal facing the terminal with 2500mm clearance to 1200mm
clearance to both sides of the terminal
I
B
From a terminal facing the terminal with less than 2500mm 2500mm clearance to either side of the terminal
J Vertically from a terminal on the same wall 1500mm
K Horizontally from a terminal 750mm
B(H) Balanced Horizontal flue
1 An opening means an openable
element, such as an openable window, or a permanent opening such as a permanently open air vent.
Notwithstanding the dimensions above, a terminal should be at least 300mm from combustible material, e.g. a window frame.
2 A way of providing protection of
combustible material would be to fit a heat shield at least 750mm wide.
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of B S5 410.
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access.
Stainless steel terminal guard. Part No: 7 716 190 050
• The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
HIGH LEVEL FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
6 720 802 433 issue A 04/2012
18
PRE -
INSTALLATION
HIGH LEVEL FLUE TERMINAL
POSITIONS
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of B S 5410 .
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access. The guard must be spaced equally (minimum 50mm) around the flue and fixed to the wall with plated screws.
Stainless steel terminal guard. Part No: 7 716 190 050
The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
• **Minimum distance of the flue terminal to a facing wall, fence, building or property boundary is 2500mm.
Key: — Not applicable, N/A Not allowed, B(H) Balanced Horizontal flue, B(V) Balanced Vertical flue.
Notes:
1. Terminals should be positioned so as to avoid products of combustion accumulating in stagnant pockets around the building or entering into buildings.
2. Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers etc.
3. Terminating positions should be at least 1.8m from an oil storage tank unless a wall with at least 30 min fire resistance and
extending 300mm higher and wider than the tank is provided between the tank and the terminating position.
4. Where a flue is terminated less than 600mm away from a projection above it and the projection consists of plastics or has a combustible or painted surface, then a heat shield of at least 750mm wide should be fitted.
5. If the lowest part of the terminal is less than 2m above the ground, balcony, flat roof or other place to which any person has access, the terminal should be protected by a guard.
6. Notwithstanding the dimensions given above, a terminal should not be sited closer than 300mm to combustible material. In the
case of a thatched roof, double this separation distance should be provided. It is also advisable to treat the thatch with a fire retardant material and close wire in the vicinity of the flue.
7. It is essential that a flue or chimney does not pass through the roof within the shaded area delineated by dimensions Q and R.
8. Where protection is provided for plastic components, such as guttering, it is essential that this is to the standard specified by
the manufacturer of the plastic components.
TERMINAL POSITION B(H) B(V)
A
1 4
Directly below an opening, air brick, opening window, etc 600mm N/A
B
1 4
Horizontally to an opening, air brick, opening window, etc 600mm N/A
C8Below a plastic/painted gutter, drainage pipe or eaves if
combustible material protected
75mm N/A
D8Below a plastic/painted gutter, drainage pipe or eaves with-
out protection to combustible material
600mm N/A
E From vertical sanitary pipework 300mm N/A
F 3From an external or internal corner or from a surface or
boundary alongside the terminal
300mm N/A
G3Above ground or balcony level 300mm* N/A
H3From a surface or boundary facing the terminal 600mm** N/A
J From a terminal facing the terminal 1200**mm
K Vertically from a terminal on the same wall 1500mm N/A
L Horizontally from a terminal on the same wall 750mm
M Above the point of highest intersection with the roof 600mm
N2From a vertical structure on the side of the terminal 750mm
O2Above a vertical structure less than 750mm from the side of the
terminal
600mm
P2From a ridge terminal to a vertical structure on the roof
Q Above or to the side of any opening on a flat or sloping roof 300mm
R Below any opening on a sloping roof 1000mm
Minimum dimensions of flue terminal positions for oil fired appliances:
Loading...
+ 40 hidden pages