Worcester 28I RSF User guide

Page 1
28i RSF
WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING
AND MAINS FED DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
This appliance is for use
with Natural Gas
2H
GC NUMBER
N.G. 47 311 54
BOILER OUTPUT
To Domestic Hot Water – To Central Heating –
Modulated Control Modulated Control
Minimum 8.5 kW Minimum 10.5 kW Maximum 27.5 kW Maximum 27.5 kW
THESE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE LEFT WITH THE
USER OR AT THE GAS METER.
READ THE INSTRUCTIONS BEFORE STARTING WORK - THEY HAVE BEEN
WRITTEN TO MAKE THE INSTALLATION EASIER AND PREVENT HOLD-UPS.
This appliance must be installed by a competent person in accordance
with the Gas Safety (Installation and Use) Regulations 1998
Page 2
1.1 Gas Safety (Installation and Use) Regulations, October 1998
All gas appliances must be installed by a competent person in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution.
1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations.
1.3 The compliance with a British Standard does not, of itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following; Gas Safety (Installation and Use) Regulations 1998 as amended. Current IEE Wiring Regulations BS 7671. Local Building Regulations. Building Standards (Scotland)(Consolidation). Bylaws of the local Water Company. Health and Safety Document No. 635 (Electricity at Work Regulations). The British Gas Material and Installation Specification for central heating and hot water It should be in accordance with the relevant recommendations of the following British Standards. BS6798:1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kW. BS5449:1990 Central Heating for Domestic Premises. BS5546:1990 Installation of gas hot water supplies for domestic purposes. BS5440:1:2000 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Flues. BS5440:2:2000 Flues and Ventilation for gas appliances of rated input not exceeding 70kW: Air Supply. BS6891:1988 Installation of low pressure gas pipework installations up to 28mm (R1). BS7593:1993 Central Heating system cleansing and flushing.
1.4 To ensure that the installation will perform to the highest standards, the system and components should conform to any other relevant British Standards in addition to those mentioned in the instructions.
1.5 The appliance complies with the Essential Requirements of the Gas Appliance Directive and other Directives currently applicable.
1.6 This appliance contains no asbestos products. There is no potential hazard due to the appliance being electrically unsafe. There are no substances used that are a potential hazard in relation to the COSHH Regulations 1988.
1.7 The advice and instructions given in this document covers, as far as possible, the foreseeable situations which may arise. Contact Worcester Heat Systems Technical Helpline for advice on specific installations.
1.8 Product Liability regulations indicate that, in certain circumstances, the installer can be held responsible, not only for mistakes on his part but also for damage resulting from the use of faulty materials. We advise that, to avoid any risk, only quality approved branded fittings be used.
The Benchmark initiative is the new code of practice to
encourage the correct installation, commissioning and servicing of domestic central heating boilers and system equipment.
The 'Log-book' is a vital document that must be completed by the installer at the time of installation. It confirms that the boiler has been installed and commissioned according to the manufacturers instructions.
Without the completion of the Log-book, manufacturers may refuse to respond to a call-out from a householder, who will be advised that he or she must call back the installer, who has not fulfilled his obligations to record the information required by the initiative.
It is important that:
The services and the system are properly flushed as specified. The User is clearly instructed on the correct operation of the appliance. The benefits of regular servicing are explained - to maintain the efficiency and extend the life of the appliance.
2.1 General Information The appliance is set to give the maximum output of 27.5 kW to the domestic hot water and to the heating system. The hot water flow rate is limited to a nominal 10 l/min at a maximum temperature rise of 40°C. The sanitary water section of the appliance is suitable for mains water pressure of up to 10bar.
2.2 Electrical Supply 230V - 50Hz. Load 180 watts. External fuse 3A, Internal fuses F1
- 2A, F2 - 1.0A (20mm).
2.3 Gas supply The appliance requires a maximum of 3.17 m
3
/h of natural gas (G20). The installation and the connection of the gas supply to the appliance must be in accordance with BS6891. The meter or regulator should deliver a dynamic pressure of 20 mbar (G20) at the appliance, which is equivalent to about 19-
19.5 mbar at the gas valve inlet pressure test point.
2.4 Installation The appliance is suitable for indoor installation only and for use with a sealed system only. Do not place anything on top of the appliance. It is a room sealed appliance and a separate combustion air supply is not required in any room or compartment in which the appliance is fitted. If the appliance is fitted in a cupboard or a compartment is built around it after installation, then the structure must conform to the requirements of BS6798 and BS5440 Part 2. However, because of the low casing losses, there is not a need for the cooling ventilation openings in the compartment. The spaces
specified in Section 6.3 must be maintained.
There is space for the service pipes to pass at the back of the appliance.
2.5 Flue
The appliance has a multi-directional fanned flue system. The standard telescopic flue assembly length is from 330mm to 725mm. Extension flue kits are available for flue lengths up to 2500mm.
2. Introduction1. Installation Regulations
2
1. Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 11. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 12. Installing the Appliance. . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 13. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 18
4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 14. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
5. Siting the Flue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 15. Inspection and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
6. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 16. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22
7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 17. Operational Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . Page 27
8. Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 29
9. Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 19. Component Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 37
10. Gas Suppy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
Contents
Page 3
An optional vertical flue kit to provide for flue lengths up to 3400mm including vertical flue terminal. A terminal guard, Type K2, GC 393 553, is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB. Do not allow the flue terminal fitted to the outside wall to become obstructed or damaged. A kit for internal fixing of the flue is available separately.
2.6 Controls Central Heating Temperature control knob. A facia mounted programmer is provided. A room thermostat and/or an externally mounted programmer for mains voltage operation may be connected to the appliance.
2.7 System
All dirt must be flushed from the system before operating the appliance. The connections in the system must withstand a pressure of upto 3 bar. Radiator valves must conform to BS2767: 10:1977. Table 3 gives the pump head available for the system and the required temperature differential. A drain cock must be fitted to the lowest point and an air vent to the highest point of the system.
2.8 Showers, Bidets, Taps and Mixing Valves All taps and mixing valves must be suitable for the available mains pressure and temperatures up to 55°C. It may be necessary to fit a pressure reducing valve. Hot and cold mains fed water can be supplied to over-rim bidets but is subject to local water company requirements. The flow of water from individual outlets varies on all mains fed systems that are not fitted with flow balancing valves. If a pressure equalising valve is fitted then the domestic hot water temperature should be set to maximum. Thermostatically controlled shower valves give extra comfort and protection.
2.9 Safety The appliance must not be operated with the inner casing cover removed. The gas and electricity supplies must be turned off before working on the appliance. Temperature monitoring controls are fitted to prevent overheating. Automatic frost protection is provided together with automatic pump seizure protection. The gas valve solenoids are automatically checked for gas soundness.
IMPORTANT: Where back-flow prevention devices, including water meters, are fitted the expansion of hot water into cold water main can be prevented. This can result in a pressure build-up that may cause damage to the boiler and household devices such as showers, washing machines etc.
In these cases we recommend that a mini-expansion vessel be fitted adjacent to the boiler in the cold water pipe.
2.10 Operation Domestic Hot Water: With a demand for hot water the burner
will light at its maximum setting and then automatically adjust its output to maintain the temperature of the delivered water.
When hot water is no longer required, the burner will extinguish. The fan and pump will continue to run for a short period to dissipate the residual heat from the appliance. Central Heating: With a demand for heating the burner will light at its minimum setting and gradually increase to give a controlled temperature rise. When the required heating temperature is achieved the output of the appliance is then automatically adjusted to maintain the temperature of the system. The output can reduce down to a minimum of 10.5 kW. If the system no longer requires even the minimum output to maintain the desired room temperature the burner will extinguish. The fan and pump will continue to run to dissipate the residual heat from the appliance. The appliance will remain off for a fixed period before re-lighting to automatically meet the system requirements. Domestic Hot Water and Central Heating: The appliance will supply heat to the central heating system as required. A demand for domestic hot water at a tap or shower will override the central heating requirement for the period of the domestic hot water demand. When hot water is no longer required the appliance will return to the central heating state and its normal mode of operation. The fan will continue to run to dissipate the residual heat from the appliance as necessary.
3
Fig. 1. Facia controls
1
2
3
1 Mains Indicator Light 2 System Pressure Gauge 3 Central Heating Temperature Control
Fig. 2. Water flow diagram.
1 2 4 5
3
6
7
8
9
10
11
12
1 Safety Discharge 10 Bi-thermal Gas to Water 2 C.H. Flow Heat Exchanger 3 Domestic Hot Water Out 11 Domestic Water Flow 4 Domestic Cold Supply Turbine 5 C.H. Return 12 Pressure Relief Valve 6 Fixed By-pass 7 Circulating Pump 8 Sealed System Expansion
Vessel
9 Automatic Air Vent
Page 4
The data plate is fixed to the inner casing cover.
3. Technical Data
4
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
8.5 10.5 1.0 1.11
10.5 13.5 1.5 1.38
27.5 30.0 13.5 3.17
Table 1.
BURNER
PRESSURE
MAXIMUM AVAILABLE PUMP HEAD
BOILER OUTPUT HEAD MIN. FLOW RATE
kW Metres L/min. °C
10.5 4.19 13.7 11
27.5 2.0 27.5 14
Table 3
MECHANICAL SPECIFICATIONS
CENTRAL HEATING FLOW - COMPRESSION 22mm
RETURN - COMPRESSION 22mm
COLD WATER INLET - COMPRESSION 15mm
DOMESTIC WATER FLOW - COMPRESSION 15mm
GAS INLET Rp
1
2
RELIEF VALVE DISCHARGE (PUSH FIT) 15mm
CASING HEIGHT 800mm
CASING WIDTH 450mm
CASING DEPTH 360mm
WEIGHT - LIFT 42.3kg
WEIGHT - UNPACKED (DRY) 45.8kg
WEIGHT - PACKAGED 52kg
Table 4
FLUE DETAILS
HORIZONTAL FLUE mm
WALL HOLE DIAMETER EXTERNAL FIX 110
INTERNAL FIX 150
STANDARD FLUE MINIMUM LENGTH 330/425 *
MAXIMUM LENGTH 725
EXTENDED FLUE MAXIMUM LENGTH 2500
FLUE ASSEMBLY DIAMETER 100
Table 2.
FLOW/RETURN
DIFFERENTIAL
Natural Gas: Net Input = Gross Input x 0.901 * Hot water setting - manual adjustment **Central heating setting - non adjustable
* NOTE : Flue lengths between 330 and 425mm require the flue to be cut
* **
Page 5
5
GAS SUPPLY SYSTEM
Table 7
CLEARANCES (mm)
INSTALLATION SERVICE
ABOVE APPLIANCE AND/OR FLUE ELBOW 30 30 IN FRONT OF APPLIANCE 600 600 BENEATH APPLIANCE 200 200 RIGHT AND LEFT HAND SIDE 10 10
Table 8
SYSTEM CAPACITY
TOTAL SYSTEM VOLUME litres
INITIAL INITIAL CHARGE PRESSURE bar PRESSURE bar 0.5 1.0 1.5
1.0 57 75 N/A
1.5 31 42 52
Table 9
PERFORMANCE SPECIFICATIONS
PRIMARY WATER CAPACITY litres 3.0
MAXIMUM MAINS INLET PRESSURE bar 10
MINIMUM MAINS INLET PRESSURE (WORKING) FOR MAXIMUM FLOW bar 0.9
MINIMUM MAINS INLET PRESSURE (WORKING) FOR OPERATION bar 0.1
MAXIMUM CENTRAL HEATING FLOW TEMPERATURE °C 82 (nom)
MAXIMUM CENTRAL HEATING SYSTEM PRESSURE (OPERATING) bar 2.5
MINIMUM CENTRAL HEATING SYSTEM PRESSURE bar 0.5
OUTPUT TO DOMESTIC HOT WATER kw NATURAL GAS (G20) 8.5 - 27.5
OUTPUT TO CENTRAL HEATING kw NATURAL GAS (G20) 10.5 - 27.5
DOMESTIC HOT WATER SPECIFIC RATE - D 30°C RISE l/min 13.1
MAXIMUM DOMESTIC HOT WATER FLOW RATE - 40°C RISE l/min 9.8
NOx CLASSIFICATION Class 2
SEDBUK NUMBER 78.1
SEDBUK BAND D
BURNER INJECTOR mm 4.5
Table 5
Refer to Section 6.
DOMESTIC HOT WATER TEMPERATURE RISE
DISCHARGE RATE l/min 7 8 9 10 TEMPERATURE RISE °C 56 49 44 39
Table 6
Total length of gas supply pipe Pipe size
(metres) (Ømm)
36912
Natural Gas
8.7 5.8 4.6 22
18.0 12.0 9.4 28
Gas
Discharge
Rate
(m
3
/hr)
Note: Each fitting used in the gas line from the meter is equivalent to a length of straight pipe which must be added to the straight pipe length to give total length. i.e: Bend=0.5 metre, Tee=0.5 metre, 90° Bend=0.3 metre.
Page 6
4.1 The appliance may be installed in any room but refer to the requirements of the current IEE Wiring Regulations BS 7671 and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of appliances in rooms containing baths or showers. Where a room sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control using mains electricity must NOT be able to be touched by a person using the bath or shower.
4.2 The appliance is NOT suitable for external installation.
4.3 NO special wall protection is required.
4.4 The wall must be capable of supporting the weight of the
appliance. See Table 4.
4.5 The specified clearances must be available for installation and for servicing. See Fig. 3 and 4. (note the clearances at the front are for a removable panel e.g. a door).
4.6 The appliance can be installed in a cupboard used for airing clothes provided that the requirements of BS 6798 and BS 5440:2 are followed. Notwithstanding the instructions given in BS 5440:2, this appliance may be fitted in a compartment with no vents as long as the minimum clearances stated in Section 6: Air Supply, are maintained.
4.7 The airing space must be separated from the boiler space by a perforated non-combustible partition. Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm. See BS 6798:1987.
4.8 No combustible surface must be within 75mm of the casing. See BS476:4.
4.9 Always consider the possible need to disconnect the pipes from the appliance after installation.
4. Siting The Appliance
6
Fig.4. Appliance casing dimensions and
required clearances (side view).
All dimensions in mm
Fig. 5. Side flue opening
Fig. 3. Appliance casing dimensions and
required clearances (front view).
All dimensions in mm
30
170
10
10
All dimensions in mm
450
106
600
200
800
222
360
200
222
200
Fig. 6. Appliance pipework connections.
100mm
36.5mm
(B)
(C)
(D)
(E)
(F)
A Safety Relief = 50mm
B CH Flow = 95mm
C DHW Out = 160mm
D Gas Inlet = 225mm
E Mains Cold Water In = 290mm
F CH Return = 355mm
(A)
Page 7
5.1 The flue must be installed as specified in BS 5440:Part 1.
5.2 The terminal must not cause an obstruction nor the
discharge cause a nuisance. Refer to Fig. 7.
5.3 If a terminal is fitted less than 2 metres above a surface to which people have access then a guard must be fitted. The guard must be evenly spaced around the terminal and fixed with plated screws. A type K2 guard is available from Tower Flue Components, Vale Rise, Tonbridge, TN19 1TB.
5.4 The terminal guard must be evenly spaced about the flue terminal and fixed to the wall using plated screws.
5.5 In certain weather conditions a terminal may steam and siting where this could cause a nuisance should be avoided.
5.6 Take care to ensure that combustion products do not enter ventilated roof voids.
5.7 The standard flue kit is horizontal and extends from 425 to 725mm in length. It can be shortened to 330mm (for single brick wall applications) by cutting the flue ducts if required. Extension kits are available for flue lengths up to 2500mm. A vertical flue system for heights upto 2.3m plus the terminal assembly. Refer to Table 2. 45° and 90° bends are available.
6.1 A separate vent for combustion air is not required.
6.2 The appliance can be fitted in a cupboard with no vents for
cooling but the minimum clearances must be increased to those given below (note the clearances at the front are for a removable panel e.g. a door).
6.3 If the appliance is to be fitted in a cupboard or compartments with less clearance than those above (minimum clearances given in Section 4. Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air.
6.4 The minimum free areas required are given below.
6.5 Refer to BS 6798 and BS 5440:2 for additional information.
6. Air Supply5. Siting The Flue
7
L
L
K
K
F
F
G
A
M
EJF
HI
D
G
A
B,C
Fig. 7. Siting of the flue terminal.
TERMINAL POSITION MIN. DISTANCE TERMINAL POSITION MIN. DISTANCE
A– directly below an openable window or I– From a terminal facing a terminal 1200mm
other opening e.g. air brick. 300mm J– From an opening in a car port (e.g. door B– Below gutters, soil pipes or drain pipes. 75mm window) into dwelling. 1200mm C– Below eaves. 25mm K– Vertically from a terminal on the same D– Below balconies or car port roof. 25mm wall. 1500mm E– From vertical drain pipes and soil pipes. 25mm L– Horizontally from a terminal on the same F– From internal or external corners. 25mm wall. 300mm G– Above ground, roof or balcony level. 300mm M–From door, window or air vent H– From a surface facing a terminal. 600mm 300mm
Above the Turret 30mm
In front 250mm
Below 200mm
Right-hand side 75mm
Left-hand side 75mm
POSITION OF AIR FROM AIR DIRECT
AIR VENTS THE ROOM FROM OUTSIDE
HIGH LEVEL 300cm
2
150cm
2
LOW LEVEL 300cm
2
150cm
2
Page 8
7.1 The system must comply with the requirements of BS 6798 and BS 5449 and the appliance must not be operated without the system being full of water, properly vented and pressurised.
7.2 The pressure relief valve operates at 3 bar (45lb/in
2
). The discharge must be directed away from electrical components or where it might be a hazard to the user.
7.3 The pressure gauge indicates the system pressure which must be maintained.
7.4 The 8 litre expansion vessel is charged to 0.5 bar and is suitable for a static head of 5 metres (17.5ft). The pressure can be increased if the static head is greater than 5 metres (17.5ft).
7.5 With an initial system pressure of 0.5 bar, a system capacity of up to 100 litres can be accommodated. For system capacities greater than this an extra expansion vessel must be fitted. Refer to BS 7074 Pt. 1 for more information. The charge pressure can be increased but with a consequent decrease in system volume.
7.6 The filling point must be at low level. Refer to Fig. 8.
7.7 Water loss must be replaced. See Fig 4. The connection
should be made in the central heating return as close to the appliance as possible. A filling loop kit is supplied.
7.8 Repeated venting loses water from the system. It is essential that this water is replaced and the system pressure maintained.
7.9 Connections to the mains water supply must not be made without the authority of the local Water Company.
7.10 The pump is set at maximum and should not be adjusted.
7.11 Connections in the system must sustain a pressure of up to
3 bar.
7.12 Radiator valves must conform to BS 2767:10.
7.13 Other valves used should conform to the requirements of
BS 1010.
7.14 The appliance is fitted with a fixed internal by-pass. But it is advisable to keep one radiator permanently open.
The appliance is NOT suitable for connection to an open vented system.
8. Open Vent System
8
Fig. 8. Sealed primary water system.
Hot water out
Water main
Heating return
Heating flow
Radiator
valve
Lockshield valve
Mains cold
water
British Standard stop valve. Fixed spindle type
NOTE: A drain cock should be installed at
the lowest point of the heating circuit and beneath the appliance.
Refer to
Fig. 2.
7. Sealed System
Page 9
9.1 The following are general requirements and, if necessary, reference should be made to the local Water Company before fitting the appliance.
9.2 MAINS COLD WATER INLET. Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made.
A mini expansion vessel kit is available which contains the necessary parts for fitting an internal expansion vessel to the appliance. Refer to Section 19. A thread sealant compatible with potable water must be used. An external expansion vessel may be fitted on the mains cold water connection to the appliance.
9.3 The final 600mm of the mains cold water connection to the appliance should be made in copper tube only.
9.4 The appliance is suitable for a mains pressure of up to 10 bar (150 lb/in
2
) and is fitted with a mains supply isolating valve.
9.5 The maximum domestic hot water flow rate is 11.4 litres/min (±15%).
9.6 In winter (when the mains inlet water temperature is lower) a reduced flow rate at the taps may be required to achieve the type of hot water delivery temperature available in warmer weather.
9.7 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off.
9.8 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 55°C. Note: The maximum domestic hot water outlet temperature is fixed at 55°C and it is not adjustable.
9.9 No anti-syphonage arrangements are necessary except for some loose head showers. See also Section 9.11 following.
9.10 Thermostatically controlled or pressure equalising shower valves will guard against the flow of water at too high a temperature.
9.11 The head of a loose head shower must not fall closer than 25mm (1in.) above the top edge of the bath to prevent its immersion in bath water. Alternatively the shower must be fitted with an anti-syphonage device at the point of the flexible hose connections.
9.12 The supply of hot and cold mains water direct to a bidet is permitted, (subject to local water company requirements), provided that the bidet is of the over-rim flushing type. The outlet(s) should be shrouded and unable to have any temporary hand held spray attached. No anti-syphonage arrangements are necessary.
9.13 LIME SCALE. In temporary hard water areas (more than 350mg/litre or 200ppm calcium bicarbonate) it is recommended that a proprietary scale reducer is fitted in the mains cold water connection to the appliance. Consult the local water company for additional advice. Installation of a scale inhibitor assembly should be in accordance with the requirements of the local water company. An isolating valve should be fitted to allow servicing. The water hardness can be determined by reference to the local water company.
9.14 NOTE: HOT WATER ONLY. If required the appliance may be used for Hot Water only before the Central Heating is connected. A 22mm copper by­pass pipe at least 4 metres long must be connected between the Central Heating Flow and Return, but it is advisable to connect a small radiator instead. IT IS NOT RECOMMENDED TO USE THE BOILER IN THIS CONDITION FOR EXTENDED PERIODS.
The boiler requires 3.17m
3
/h (112ft3/hr) of natural gas with a
calorific valueof 37.78MJ/m
3
. The meter govenor should deliver a dynamic pressure of 20 mbar (8in w.g.) at the appliance, equivalent to a pressure of 19-19.5 mbar at the gas valve on natural gas. The gas meter and supply pipes must be capable of supplying this quantity of gas in addition to the demand from any other appliances being served. The table below gives an indication of limiting gas pipe lengths and the allowance to be made for fittings. Refer to BS6891 for further information. The complete installation, including the gas meter, must be tested for soundness and purged. Refer to BS6891.
9. Domestic Hot Water
9
10. Gas Supply
Page 10
11.1 MAINS SUPPLY.
230 V ~, 50 Hz, 180 watts. External Fuse: 3A. Internal Fuses: 2A SLOW (F1), and 1A FAST(F2). Spare fuses are supplied with the appliance and are fixed adjacent to the pressure gauge.
11.2 It must be possible to completely isolate the appliance.
11.3 The following connection alternatives must be used:
A 3 amp fused three-pin plug and unswitched shuttered socket outlet (both complying with the requirements of BS 1363) or a double pole isolator with a contact separation of 3mm in all poles and supplying the appliance and controls only.
11.4 The appliance must be earthed.
11.5 Mains Cable. 0.75mm
2
(24 x 0.20mm) to BS 6500 Table 16.
The mains cable must be connected into the terminal X1, marked L (Brown or Red lead), N (Blue or Black lead) and the earth stud and be held securely in the cable clamp. For access undo the three bottom screws and remove the facia access cover. See Fig. 11. The earth lead must be slack when the others are taut.
11.6 The wiring between the appliance and the electrical supply shall comply with current IEE Wiring Regulations and any local regulations which apply.
11.7 If a room thermostat and/or external programmer is to be fitted refer to Figs 12 and 13. The devices must be suitable for use with mains voltage.
11.8 A facia mounted mechanical programmer is available as an optional extra. Instructions are supplied with the programmer kit.
11.9 A time switch or programmer can be fitted externally to the appliance.
11.10 The boiler provides automatic frost protection, the use of a frost thermostat is not recommended. However if an external frost thermostat is considered necessary then it must be used in conjunction with a programmer.
Important: To provide external frost protection the appliance must have the Central Heating Temperature Control Knob set to
supply heating (the appliance may then be left with the central heating turned off at the programmer). Connection must be made at X2 terminals RI and CL. refer to Fig.
28. For advice on external frost thermostats contact Worcester Heat Systems Technical Helpline
11.11 SAFETY CHECK.
After installation or in the event of an electrical fault the electrical system shall be checked for short circuits, fuse failure, incorrect polarity of connections, earth continuity and resistance to earth.
11. Electrical
10
Fig. 9. Wiring diagram.
Overheat
thermostat
DHW sensor
CH
sensor
Gas
valve
Pump
Main
Reg
Flow turbine
Air
pressure
switch
Spark transformer
Mains in
2 Blue
2 Red
2 Yellow
2 Orange
Blue
Blue
Brown
Link
Link
X1
X2
X3
X6
X5
X4
Flame sense electrode
Spark electrode
Brown
White
Green
COM
NC
NO
Yellow
Blue
Fan
Brown
Brown
Brown
Black
Green
White
1
2
3
Page 11
11
Fig. 10. Functional flow diagram.
F1 2A
F2 1AT
Optional links
Spark
Flame sense
Outputs Inputs
Mains indicator
Modulating
valve
Overheat stat
X6 Pins 8 & 9
X6 Pins 15 & 16
X6 Pins 5,6 & 7
X6 Pins 14,17 & 18
X6 Pins 19 & 20
X6 Pins 3 & 4
Flow signal
CH temp. sensor
DHW temp. sensor
CH control POT
Air pressure switch
MAINS PROGRAMMER/CLOCK
FULL SEQUENCE
CONTROLLER
GA S VALVE
LOW VOLTAGE
ELECTRONICS
(Microcontroller)
ROOM STAT
X1
X2
3
2
1
1
2
3
4
6
5
RL1
X3 Pin 1
X3 Pin 2
X4 Pin 3
X5 Pin 3
X5 Pin 1
X4 Pin 1
FAN
PUMP
RL3
RL4
N
N
N
N
L
Page 12
12
Fig. 11. Mains electricity connections.
Brown
Strain relief clamp
Blue
Brown
Green/yellow
Green/yellow
Programmer and room
thermostat
230V
X1
X2
NL
Blue
Fig. 12. 230V room thermostat connections.
Fig. 13. 230V programmer connections.
RN RI
X2
Remove link
Neutral
Switched live
Live
RL
CN
Motor
CI
X2
Neutral
Switched live
Live
CL
Remove link
Page 13
Technical Helpline.
Note: READ THIS SECTION FULLY BEFORE COMMENCING INSTALLATION.
12.1 General
The appliance is only suitable for fitting to a sealed system. The flue must be installed as specified in BS5440:1. Check that the appliance is suitable for the local conditions. i.e. gas supply.
12.2 Unpacking
Remove the appliance from its packaging and check the contents against the packing list.
12.3 Site Preparation
Check the correct position for the appliance has been chosen. Refer to Section 4 and Table 8. Check that the wall is flat and and will support the weight of the appliance. Refer to Table 4.
12.4 Fixing Holes ad Flue Opening
Hold the template against the wall. Check that the template is level. Mark the position of the fixing holes and the flue opening. Refer to Fig. 14 and 15.
Mark the centre-lines of the pipe connections to aid the pre­plumbing of the system pipework. Check the position of the fixing points and the flue opening before drilling the fixing holes 60mm deep for the No.12 size plugs and cutting the flue duct hole at 110mm diameter (150mm diameter for internally fitted flues.
12.5 Wall Mounting Plate and Manifold
Fit the plugs and fix the top support to the wall. Refer to Fig. 14. Check the top support is properly aligned before tightening the screws.
12.6 Gas and Water Pipes
Remove the gas cock and fix the appropriate fitting to connect the inlet pipe and re-fit. Pre-plumbing is not recommended if no movement in the pipes is available. If it is necessary for the pipes to run up the back of the appliance then they must be arranged to pass behind the expansion vessel. Pipework must not run horizontally within the limits of the casing. It is important that the pipes are not fixed near the appliance using clips that put a strain on the connections.
Before the appliance is fitted to the wall thoroughly
flush the system and mains water supply.
12.7 Install the Boiler
Remove the cabinet by releasing the sides and lifting from the top location. Check that the gas and water valves are closed. Lift the appliance to the wall, engage in the top support. Fix and tighten the bottom screws. Refer to Fig. 14. Tighten the gas and water connections. Fit a discharge pipe to the relief valve leading it away from any electrics or where it might be a hazard. The pipe must not be less than 15mm in diameter and must run continuously downward outside the appliance. Refer to Fig. 6.
12. Installing The Appliance
13
Fig. 14. Appliance mounting plate and flue position.
Fig. 15. Marking out the side flue position.
Mounting wall
Rear flue hole 110mm dia. (150mm dia. for internal fixing)
Side flue hole 110mm dia. (150mm dia. for internal fixing)
Appliance casing
Mounting plate
Fixing holes (alternatives)
Mounting wall
Mounting plate
222mm
Side wall
166mm
740mm
400mm
Rear flue position
Side flue position
60mm
Appliance casing
Side flue hole 110mm dia. (150mm dia. for internal fixing)
Mounting wall
Side wall
222mm
166mm
Page 14
12.8 Air and Flue Duct Preparation
The method of installation of the flue system may be varied to suit the actual site conditions. The instructions for connecting and fixing the ducts must, however, be strictly followed.
Remove all packing material from the flue components.
Horizontal Flues up to 725mm Length
Fit the flue restrictor ring by unscrewing the flue spigot from the boiler. Refer to Fig. 17.
The standard telescopic flue assembly is suitable for flues from 425mm (without cutting) up to 725mm measured from the centre-line of the boiler flue outlet to the outer face of the wall. Refer to Fig. 18.
If L is greater than 725mm then flue extension kits will be required - each kit extends the flue by 750mm up to a maximum of 2-5m. See table below.
EXTENSION MAXIMUM FLUE LENGTH mm
1 1475 2 2225 3 2500
12.9 Measure and Cut the Ducts General: Cut the ducts as necessary, ensuring that the ducts are
square and free from burrs. Always check the dimensions before cutting. Measure the distance L. Refer to Fig. 20 and 21 .
The standard flue can be telescopically adjusted to any length between 425mm and 725mm. Fix the flue assembly together using the self-tapping screw provided. Refer to Fig. 18.
It will only be necessary to cut the standard assembly if L is less
than 425mm. Cut the flue turret assembly and
the terminal assembly by the same amount i.e L=350 - remove 75mm from each
assembly.
Minimum side flue length = 335mm (accommodating a 10mm Service clearance and a 100mm wall)
Minimum rear flue length = 322mm (accommodating a 100mm wall)
If L is between 1175 - 1475mm (1 extension)
1925 - 2225mm (2 extension)
it is not necessary to cut the ducts.
14
Fig.16. Appliance casing and control
equipment fixings.
Inner casing cover screws (4)
Side casing fixing screws (4)
Facia panel fixing screws (2)
Connections cover fixing screws (3)
Fig.17. Flue turret fixing and automatic
air vent.
1
2
3
4
5
6
1. Flue spigot fixing screws
2. Flue spigot
3. Restrictor ring
4. Flue spigot fixing holes
5. Reset button
6. Flue gas test point
Restrictor Ring Size
75mm horizontal flue up to 725mm.
Fig.18 . Standard flue assembly.
Appliance casing
Fixing screw
Turret assembly
Terminal assembly
L
Telescopic
adjustment
Page 15
If L is between:
725 - 1175mm (1 extension) 1475 - 1925mm (2 extension) 2225 - 2500mm (3 extension)
it is necessary to shorten the assembly by cutting the first extension duct assembly i.e. L = 1000mm - remove 175mm from the air and flue ducts. NOTE: Extension duct measurements do not include the socketed end. Unless specifically instructed the socketed end must not be removed.
Fix the flue ducts together before fixing the surrounding air duct, the cut ducts fit into the flue assembly.
12.10 Fitting the Flue Assembly with Access to the Terminal
Prepare the flue duct assembly as described in Section 12.9. Apply the plastic tape to the air duct in contact with the external brickwork. From inside push the assembly through the wall. Align the flue turret and push fully onto the spigot on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig.
22.
Make good the internal wall face and the external brickwork or rendering.
Replace the inner casing.
12.11 Fitting of the Flue Assembly without access to the Terminal
A rubber gasket kit is available from Worcester Heat Systems. NOTE: A larger diameter opening in the wall is required. Refer to Table 2.
Prepare the flue assembly as described in Section 12.9.
Fit the rubber sealing gasket centrally onto the terminal assembly and tighten the clamp. Refer to Fig. 23. Apply the plastic tape to the air duct in contact with the external brickwork.
From inside push the assembly through the wall so that the gasket flange is against the outer face. Refer to Fig. 23. It may be necessary to adjust the legs of the flue centering ring. Align the flue turret and push fully onto the socket on the appliance. Tighten the clamping ring and fix with the screw provided. Refer to Fig 22. Seal the gap around the duct at the inner wall face with the flexible seal provided and make good. Replace the inner casing.
15
Fig. 19. Extension Duct.
L
Appliance casing
Fixing screws
Fixing screw
Turret assembly
Terminal assembly
Ducts of equal length
Shorten first extension fitted
to the turret assembly if more
than one extension is fitted
Fig. 20. Flue duct length (side flue).
L
Flue Turret assembly
Terminal assembly
Fig. 21 . Rear flue.
Rear face of appliance and face of mounting wall
External wall face
L
Indents in line with wall face
Terminal assembly
Page 16
12.12 Flue Bends
90° and 45° bends are available. A maximum of two bends may be used in addition to the first bend on the flue turret. A 90° bend is equivalent to 750mm of straight duct. A 45° bend is equivalent to 375mm of straight duct.
A maximum flue assembly of 2.5m is possible with 1 X 90° bend and 2m with 2 X 90° bends. Measure the lengths X,Y and Z. Refer to Fig. 24. The maximum value of X using the turret assembly only in 506mm. Reduce the ducts to the appropriate length i.e. X = 406mm, cut 100mm from the air duct and 120mm (to cover the entry into the 45° or 90° elbow) from the flue duct. Refer to Fig.24. NOTE: The flue system ducts between the elbows, dimension Y, requires the socketed ends (of the first extension if two or more are used) to be removed and the air and flue tubes to be cut to the same length. Cut the ducts to a length Y - 162mm. Refer to Fig. 24. The final section, dimension Z, of the flue system must include a section of plain duct assembly i.e . an extension assembly with the sockets removed. Reduce the final section, including the terminal assembly, by the appropriate amount i.e. Air duct Z ­81mm and the flue duct Z - 51mm. Refer to Fig. 24.
If Z<425mm it will be necessary to cut the air and flue ducts of the extension to a plain length of 100mm and reduce the length
of the terminal assembly i.e Z=350mm - remove 75mm from the terminal assembly. If Z in 425 - 725mm it is not necessary to cut the terminal assembly or use a second extension duct as the length can be set telescopically. If Z>725mm then two extension duct assemblies will be required, the first assembly being cut to length as plain tubes.
If more than two extension ducts are needed in any section to achieve the required length then the final section of the assembly must not be less than 325mm without cutting the terminal assembly. NOTE: The flue duct of the final extension must be 30mm longer than the air duct.
Each section must be connected to the previous section of the flue bend by fixing the flue ducts together and then similarly fixing the air ducts which engage the elbows.
Fit the assembly as described in Section 12.10, 12.11 as appropriate. Make good the internal and external brickwork or rendering.
16
Fig. 22. Flue Turret Fixing .
Fig. 23. Terminal assembly for internal
fitting of the flue.
5
4
1
3
2
1. Flue centering ring
2. Air duct
3. Flue duct
4. Rubber sealing gasket
5. Flue Terminal
Fig. 24. Flue bends.
Air Z – 81mm
Flue Z – 51mm
Z
Y
X
Y – 162mm
(plain tube)
1
4
2
3
1. Flue turret
2. Clamp
3. Appliance
4. Fixing Screw
Rubber sealing gasket
Clamping ring
Flue terminal
Page 17
12.13 Vertical Adapter for Horizontal Flues
An adapter is available for an initial short section of vertical flue. Refer to Fig. 26. Measure and cut the flue as described in Section 12.12. The first, vertical, section (equivalent to dimension X) is measured from the top of the boiler casing. Cut the vertical section of the extension duct to 167mm less than the measured distance. Do not remove the socketed ends. The minimum measured distance is 167mm. Seal the air duct to the turret using silicone sealant. Fix the adapter with the clamp and screw provided.
12.14 Completion of the Installation
Check that all the connections on the appliance have been tightened. Remove the facia bottom panel. Refer to Fig. 27.
Connect the mains electricity supply lead to the appliance and secure the cable clamp. Refer to Fig. 27. and 28. Check there is sufficient loose lead to allow the release of the facia panel assembly and that the earth lead of the mains supply cable is longer than the live and neutral leads.
Fit the facia mounted clock. Full instructions are sent with the programmer. Refer to Fig. 28. and 29.
Connect any external controls ensuring that the leads pass through the appropriate clamps. Refer to Fig.18.
Test for gas soundness as described in BS6891.
If the appliance is not to be commissioned immediately, replace the cabinet and facia bottom panel. Check that the gas and electricity services have been turned off.
17
120mm
100mm
Fig. 25 - Elbow to Flue Turret
Assembly.
Fig. 26 Vertical Adapter.
Flue Duct
Air Duct
Adapter
Clamp
Flue Spigot
Flue Turret
Bend
Fig. 27 - Facia Connections Cover.
1
2
3
4
5
1. Control Panel Fixing Screws
2. Facia
3. Control Panel Pivot Point
4. Connection Cover
5. Connection Cover Fixing Screws
Fig. 28 -
N. L.
Mains
Fuse 2A Slow Blow
Earth
C
N CI CL
Programmes
RN RI RL
Room Thermostat
Gas Valve
Fan
Pump
Page 18
Benchmark Water Treatment: For optimum performance after installation, this boiler and its associated central heating system should be flushed in accordance with the guidelines given in BS7593:1992 - Treatment of water in domestic hot water systems. Full instructions are supplied with proprietary cleansers sold for this purpose. If an inhibitor is to be used after flushing, it should be used in accordance with the inhibitor manufacturers instructions. Suitable flushing agents and inhibitors are available from Betz Dearborn Tel: 0151 4209563 and Fernox Tel: 01799 550811. Instructions for use are supplied with these products.
13.1 Remove the appliance cabinet
Check that the electrical supply and the gas supply to the appliance are turned off and that all the water connections throughout the system are tight. Open the system valves at the appliance. Refer to Fig.6 . Remove the automatic air vent cap. Refer to Fig. 30 . Fill the system through the external filling loop. Refer to Section 7, Sealed System. Vent each radiator in turn. The automatic air vent will vent the appliance. Remove the cap from the pump and turn the shaft about a half turn. Replace the cap. Refer to Fig. 31. Switch on the electricity supply (not the gas) and set the controls to give continuous operation in the CH mode. When the air is expelled turn off the electrical supply and the CH control to off. Check the pressure relief valve operates by turning the knob anti­clockwise until it releases. Lower the facia to gain acces to the relief valve. Refer to Fig. 32. Water should be expelled from the discharge pipe.
13.2 Set the Expansion Vessel Pressure
The charge pressure of the expansion vessel as despatched is
0.5bar, which is equivalent to a static head of 5m (17ft). The charge pressure must not be less than the static head at the point of connection. A Schraeder type valve is fitted to the expansion vessel to allow the discharge pressure to be increased if necessary. The expansion vessel must be charged to 0.35bar less than the initial system design pressure.
13. Commissioning
18
Fig. 30. Appliance components and fixings (upper assembly).
Flue hood
Overheat
thermostat
Burner fixing screw
Combustion
chamber
cover fixing
clips (2)
Auto air vent
Fan assembly
fixing screws (4)
Flue Gas Test Point
Fig. 29 - Programmer Connection - Facia Position
4
3
1
1. Programmer
2. Programmer Fixing Clip
3. Pressure Gauge
4. Programmer Connector
2
Fig. 31. Pump venting.
1
2
3
1. Electrical Connections Cover
2. Pump
3. Cap
Reset Button
Page 19
Note: 1 bar = 10.2m = 33.5ft of water.
13.3 Set the System Pressure
Fill the system until the pressure gauge is at 2.5 bar and check for leaks. Release water from the system using the relief valve test knob until the required system pressure is obtained, upto a maximum of 1.5 bar. Set the pointer on the pressure gauge to record the set system pressure. If the pressure indicated on the gauge is greater than 2.65 bar when operating at the maximum central heating temperature, an extra expansion vessel must be fitted to the system as close as possible to the appliance central heating return conection. The appliance (as despatched) can accomodate a system volume of 100 litres. Refer to BS7074 Part 1, BS5449 and table 8. If the system volume is greater then an extra vessel must be fitted as close as possible to the appliance central heating return connection and pressurised to the same figure as the integral vessel.
13.4 Clock/Programmer
The controls fitted to the appliance should be set up at this stage.
13.5 Operation
Check that the gas and electricity supplies are turned off. Connect a pressure gauge to the gas valve inlet and outlet pressure test points. Refer to Fig. 33. Set the temperature control to maximum and the clock/programmer to operate continuously. Turn on the gas and electricity supplies. Turn on a hot tap to give a maximum flow rate. A continuous spark will occur until the burner is alight and sensed by the control circuit. The burner will remain at its maximum domestic hot water pressure. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Note: The burner pressure is factory set and if, after checking that the dynamic (working) supply pressure is sufficient i.e 19-
19.5 mb approx, at the gas valve inlet pressure test point, the correct pressure cannot be obtained then Worcester Heat Systems Service Department should be contacted. If the appliance does not light then check that it is not in the 'Lock-out' state by pressing the reset button. Refer to Fig. 34. Turn off the hot tap. The burner pressure will drop to the minimum CH setting and will ramp up to the maximum central heating pressure.
It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Switch the appliance off and then on to reset the control. The burner pressure will remain at the minimum CH pressure for a period. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Refer to Section 16.4.11. Test for gas soundness at the joint between the burner and the gas valve with leak detection fluid.
Turn the electricity supply off then back on to reset the controls.
13.6 Domestic Hot Water
Turn the central heating temperature control knob fully anti­clockwise. Open a hot tap near the appliance. The burner will light and go to the maximum burner pressure appropriate to the appliance and the gas. Refer to Table 1. Gradually close the tap and check that the burner pressure falls. Fully close the tap and check that the burner goes out. The fan will continue running until the appliance has cooled to a pre-set temperature.
13.7 Central Heating
Check that all the radiator valves are open. Check that the system is pressurised and set to the required pressure as indicated on the gauge. Check that the clock/programmer is set to operate continuously. Set the room thermostat and the central heating control to maximum. The burner will light and the appliance will modulate its output from minimum to satisfy the required heating load. Check that all the radiators are heating up evenly. Shut down all but one of the radiators and observe the burner pressure fall. Open all the radiators and check that the burner pressure rises.
19
Fig. 32. Pressure relief valve.
Pressure relief valve. (Turn knob anti-clockwise to test).
Fig. 33. Gas valve.
1
2
3
4
5
6
1 Burner pressure test point 2 Electrical connections – modulator (Blue : Blue) 3 Modulating solenoid
4 Minimum / Maximum pressure adjuster - Allen key
Note: Clockwise to increase and anti-clockwise to decrease
the pressure
5 Inlet pressure test point 6 Main gas valve connections
Max
2mm
Allen key
Min
3mm
Allen key
Gas valve sealing cap
Page 20
13.8 Balance the system to give a temperature differential of 11°C or 13°C. A non-adjustable by-pass is fitted to the appliance. Refer to Table 3.
13.10 Set the room thermostat to minimum and check that the burner goes out. Reset the room thermostat to maximum and the burner will re­light and follow the normal operating procedure. Turn off the gas service cock. The burner will go out but sparking from the electrode will continue for 10 seconds when the appliance will 'Lock-out'. After 60 seconds carefully open the gas service cock. Switch mains electricity off and on and observe the burner re­light and follow the normal sequence of operation. Turn off the gas service cock and electricity supply to the appliance. Drain the system while the appliance is hot. Refill, vent and re-pressurise the system as described in Section
13.1 preceding, adding, if necessary, a suitable proprietary inhibitor. Further information is available from Betz Dearborn, 0151 4209563 or Fernox 01799 550811.
13.11 Domestic Hot Water and Central heating
Set all controls to maximum. Turn on the electricity supply to the appliance and open the gas service cock at the appliance. The burner will light and heat will pass into the system. Turn on a hot tap and check that hot water is soon discharged from the tap. Close the tap and the burner will go off. The appliance will then return to the central heating mode and automatically balance with the system requirements.
13.12 Completion of Commissioning
Disconnect the pressure gauge and tighten the test point screw. Refit the cabinet. If the appliance is to be passed over to the user immediately then set the controls to the users requirements. If the appliance is to be left inoperative in frosty conditions then set the programmer, if fitted, to off. Do not turn electricity or gas supplies off. The appliance will operate under the control of the integral frost protection facility. If there is any possibility of the appliance being left totaly unused in freezing conditions then switch off the gas and electricity supplies and drain the appliance and system.
14.1 Tell the user how to operate the appliance and
hand over the Users Instructions leaflet.
14.2 Tell the user what to do if the heating system is not to be used in frosty weather.
14.3 Tell the user the sealed system set pressure.
14.4 Tell the user of the importance of regular servicing.
Worcester Heat Systems Ltd. offer a comprehensive maintenance contract.
14.5 Set the system controls to the user’s requirements.
14.6 Complete and hand over to the user the Benchmark Log-Book.
14. Handover
20
Fig. 34. User controls.
1
4
2
3
1 Reset Button 2 Mains Indicator 3 C.H. Temperature Control
4 System Pressure Gauge
Page 21
15.1 SERVICING
To ensure continued efficient operation of the appliance it must be checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but once per year should generally be adequate. The extent of the service required by the appliance is determined by the operating condition of the appliance when tested by fully qualified engineers. Any service work must be carried out by competent engineers such as British Gas or Corgi registered personnel.
15.2 PRE-SERVICE INSPECTION
Check that the flue terminal and the terminal guard, (if fitted), are clear. If the appliance is in a compartment, check that the ventilation openings in the compartment door or walls are clear. See Section 6 - Air Supply. Check the system and remake any joints or fittings which show signs of leakage. Refill, vent and re-pressurise as described in Section 13.2. Operate the appliance and the system taking note of any faults.
Measurement of the Flue Gases
For consistency of results of the flue gas measurements it is necessary to have a constant output and for the appliance to be at equilibrium. Turn on a tap to create a hot water demand. Wait until the appliance reaches thermal equilibrium (approx. 10 minutes). Remove the test point sealing screw on the appliance top panel. See Fig. 17 and 30. Connect to the test point with a piece of tubing. Expected measurements should be between:
For Natural Gas: 7.0 - 7.5% Carbon Dioxide
0.003 - 0.007% Carbon Monoxide
After taking the measurement replace the sealing cap.
IMPORTANT
Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock on the appliance before servicing. After completing the service always test for gas soundness as indicated in BS 6891.
15.3 DISMANTLE THE APPLIANCE
To carry out a full and comprehensive service of the appliance remove the following parts to gain access to the components which need to be checked or serviced.
(a) Cabinet Front Panel. Remove by lifting off the supports. (b) Inner Casing Cover. Check that the electricity supply to the
appliance is turned off. Remove the cabinet front panel. Unscrew the four screws securing the cover to the casing and lift off. See Fig. 35. (c) Facia Panel. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel. Unscrew the two upper screws as shown in Fig. 35. and hinge down the facia taking care not to damage the pressure gauge capillary tube or electrical connections.
(d) Bottom panel. Unclip and remove the appliance bottom panel. (e) Fan. Remove the inner casing cover as detailed in Section
15.3(b) above. Carefully unplug the electrical connections and pull off the sensing tubes. Unscrew the four fixing screws and remove the fan assembly. See Fig. 36. (f) Combustion Chamber Front. Remove the inner casing cover. Undo the spring clips fixing the combustion chamber front taking care not to damage the insulation on removal. See Fig. 36. (g) Flue Hood Assembly. Remove the fan assembly as described in Section 15.3(e). Remove the combustion chamber front taking care not to damage the insulation. Lift and slide the flue hood assembly from the appliance. See Fig. 36. When refitting the hood ensure that the rear return edge passes under the lip at the rear of the combustion chamber.
15. Inspection And Service
21
Inner casing cover screws (4)
Side casing fixing screws (4)
Facia panel fixing screws (2)
Bottom facia panel fixing screws (3)
Fig.35. Appliance casing and control
equipment fixings.
Fig. 36. Appliance components and fixings (upper assembly).
1
7
5
6
4
3
2
1 Flue hood 2 Flue Gas Test Point 3 Fan assembly fixing screws (4)
4 Auto air vent 5 Burner fixing screw 6 Combustion chamber cover fixing clips (2) 7 Overheat thermostat
Page 22
(h) Burner Assembly. Remove the combustion chamber front as described in Section 15.3(f). Pull off the two spark electrode leads, disconnect the flame sense lead at the connector and remove the grommet. Undo the burner fixing screw. Lift up and remove the burner assembly from the appliance. See Fig. 37
15.4 SERVICE OF COMPONENTS Clean the Fan. Any dust or fluff should be removed with a soft
brush or by blowing. Take care not to distort the pressure sensing device. Clean the Main Burner. Brush the blade tops and mixing tube with a soft brush and check that all the flame ports are clear. Remove any blockages with a non-metallic brush. Inspect the injector and clean with a soft brush. Replace the injector if it appears damaged. Do not use a wire brush or anything likely to cause damage. Replace the spark and sense electrodes if they appear damaged. Clean the Gas to Water Heat Exchanger. Clean the heat exchanger using a soft brush. Remove the deposits from the bottom of the combustion chamber. Do not distort any of the blades. Combustion Chamber Insulation. Examine and replace any pads that are damaged. Remove any dust or deposits using a soft brush. Re-assemble the appliance in the reverse order. Check that all components are in place and correctly fixed. Leave the cabinet front panel to be fitted after checking the operation of the appliance.
15.5 TEST THE APPLIANCE
On completion of the service and reassembly of the appliance, check for gas soundness and the correct operation of the appliance as described in Section 13 - Commissioning. Refit the cabinet front panel and reset the controls to the users requirements.
16.1 IMPORTANT
Switch off the electricity and gas supplies before replacing any components. After the replacement of any components, check for gas soundness where relevant and carry out functional checks as described in Section 13 - Commissioning
16.2 COMPONENT ACCESS
To replace components it is necessary to remove one or more sections of the cabinet and cover plates within the appliance as described in Section 15.3. The facia panel may also need to be hinged down as described in Section 15.3 (c).
16.3 DRAINING THE APPLIANCE
Check that the electricity supply to the appliance is turned off. Before removing any component holding water it is important that as much water as possible is removed from the appliance. (a) Central Heating Circuit. Turn off the central heating flow and return valves at the appliance. Open the pressure relief valve, make sure that the dust cap on the auto air vent is removed. See Fig. 31. Close the pressure relief valve when the flow has stopped. Some water will remain in the expansion vessel, pump and Gas to Water heat exchangers and extra care must be taken when removing these components. (b) Domestic Hot Water Circuit. Turn off the mains cold supply valve at the appliance and open the lowest hot water tap. A quantity of water will remain in the Gas to Water heat exchanger, extra care must be taken when removing this component.
16.4 COMPONENT REPLACEMENT
1. Automatic Air Vent. See Fig. 36 and 38.
Remove the inner casing cover as described in Section 15.3 (b). Drain the central heating circuit as described in Section 15.3 (a). Unscrew air vent from the heat exchanger. Fit the replacement assembly ensuring thread sealant is applied and the dust cap is removed. Open the valves and fill and re-pressurise the system as described in Section 13.2.
2. Air Pressure Switch. See Fig. 41. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel as described in Section 15.3 (a) and lower the facia. Section 15.3(c). Carefully pull off the sensing tubes and the electrical connections from the switch. Remember to note their positions. Unscrew the two screws behind the Air Pressure Switch and remove the switch from the appliance. Fit the replacement switch in the reverse order ensuring that the electrical connections have been made to the correct terminals on the switch. Check that the sensing tubes are fitted correctly.
3. Fan. See Fig. 36. Check that the electricity supply to the appliance is turned off. Remove the fan assembly as described in Section 15.3(e). Fit the replacement fan in the reverse order.
4. Overheat Thermostat. See Fig. 30 and 36. Check that the electricity supply to the appliance is turned off. Remove the inner casing cover as described in Section 15.3 (b). Carefully pull off the two wires from the thermostat head. Undo the retaining nut on the top of the appliance and remove the retaining clip from the heat exchanger. Carefully withdraw the thermostat from the appliance. Fit the replacement thermostat in the reverse order ensuring that some heat sink compound is between the thermostat and the heat exchanger.
5. Gas to Water Heat Exchanger. See Fig. 38. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit and domestic circuits as described in Section 15.3 (a) and (b). Remove the inner casing cover, fan, flue hood assembly, combustion chamber front, overheat thermostat, automatic air vent and combustion chamber side insulation as described in Sections 15.3 (b, e, f and g), 15.4 and 16.4 (4). Fit the replacement heat exchanger in the reverse order ensuring that all the fibre washers are correctly fitted and a layer of heat sink compound is on the thermostat.
16. Replacement Of Parts
22
Fig. 37. Burner and electrode assembly.
Spark electrode
Injector Flame sense electrode
Page 23
Fig. 39. Spark & flame sense electrode assembly.
Open the valves and fill and re-pressurise the system as described in Section 13.2.
6. Combustion Chamber Insulation.
Check that the electricity supply to the appliance is turned off. If replacing the rear insulation the appliance must be drained as described in Section 16.3(a) and 16.3(b) and the gas to water heat exchanger removed (see 16.4.5). If changing the front or side pieces it is not necessary to drain the appliance. Remove the inner casing cover, combustion chamber front, fan and flue hood assembly as described in Sections 15.3 (b,e,f & g). Remove the fibre insulation pads to be changed and fit the replacements taking care not to damage them. If the system has been drained, open the valves and fill and re­pressurise the system as described in Section 13.2.
7. Burner. See Fig. 37. Check that the electricity and gas supplies to the appliance are turned off. Remove the burner assembly as described in Section 15.3 (h). Fit the replacement burner in the reverse order taking care not to damage the electrode leads.
8. Burner Injector. See Fig. 37. Remove the burner as described in Section 15.3 (h). Unscrew the brass injector from the manifold. Fit the replacement injector in the reverse order.
9. Spark Electrode Assembly. See Fig. 39. Remove the combustion chamber front as described in 14.3 (g) Carefully pull off the two electrode leads, Undo the M4 extended nut and remove the spark electrode assembly from the burner. Fit the replacement electrode in the reverse order, checking that the spark gap is 3.5 to 4.5mm.
10. Flame Sensor. See Fig. 39. Remove the burner as described in section 15.3(h). Undo the M3 screw and remove the sense electrode from the burner. Fit the replacement electrode in the reverse order, checking that the sense gap is 5 to 6mm.
11. Gas Valve. See Figs. 33. and 40. Check that the electricity and gas supplies to the appliance are turned off. Hinge down the control box assembly in the servicing position as described in Section 15.3(c). Note: The adjuster sealing cap should be fitted after setting the burner pressure and coated with a small amount of paint to make any subsequent adjustment obvious. Whilst supporting the valve unscrew the plug retaining screw and carefully pull off the electrical solenoid plug connection and the two modureg leads. Undo the 8 manifold screws and remove the gas valve. See Fig. 40. Fit the replacement gas valve in the reverse order ensuring the “O” rings are correctly fitted. Turn on the gas supply and check for soundness.
23
3.5-4.5mm
2.5-5mm
Fig. 38. Combustion chamber.
Heat exchanger
Overheat Thermostat
Hot water connections
Cut-outs in combustion chamber sides
Pump bulk-head connector
Central heating connections
Auto air vent
Flame Sense Electrode
Spark Electrode Assembly Burner
Spark electrode assembly from side and above
Flame sense electrode detail
5-6mm
Fig. 40. Gas valve.
1
2
3
4
5
6
1 Burner pressure test point 2 Electrical connections – modulator (Blue : Blue) 3 Modulating solenoid
4 Minimum / Maximum pressure adjuster - Allen key
Note: Clockwise to increase and anti-clockwise to decrease
the pressure
5 Inlet pressure test point 6 Main gas valve connections
Min
3mm
Allen Key
Max
2mm Allen
Key
Gas valve sealing cap
Page 24
To set the burner pressure. See Fig. 40. The minimum and maximum burner pressures must be set after a new gas control has been fitted. The maximum burner pressure must be set first, as any adjustment of the maximum pressure influences the minimum pressure setting. Start the appliance in the domestic hot water mode as described in section 13.6. - Appliance Operation. Adjust the maximum pressure adjustment (2mm Allen screw on the gas valve) to give a burner pressure of 13.5 mbar on natural gas. End the demand and reset the appliance by interrupting the mains electricity supply. (Otherwise there is a four minute anti­cycle delay at the end of a demand). Open a hot tap. Remove one of the blue leads from the modulating solenoid on the gas valve to ensure that the burner pressure remains at the minimum setting. See Fig. 40. Adjust the minimum pressure to 1 mbar using a 3mm Allen key. Replace the blue lead and re-check the pressures. After completing the adjustments, check the minimum and maximum pressures and re-adjust as necessary.
Re-fit the adjuster sealing cap and coat with a small amount of paint to seal the cap to make any subsequent adjustment obvious.
12. Central Heating Sensor. See Fig. 41.
Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 15.3(c and d). Carefully pull off the two leads from the sensor. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in reverse order with a layer of heat sink compound between the faces. Refit the leads.
13. Domestic Hot Water Sensor. See Fig. 41. Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 15.3(c and d). Carefully pull off the two leads from the sensor.
Undo and remove the clamping screw. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in the reverse order ensuring a layer of heat sink compound is between the faces. Refit the leads.
14. Circulating Pump. See Fig. 41. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 16.3(a). Hinge the facia assembly in the servicing position as described in Section 15.3(c). Remove the burner assembly as described in Section 15.3(h). Undo the two union nuts and the pipe to the expansion vessel, remove the pump from the pipe-work. Support the pump and remove the electrical cover. Disconnect the electrical wires taking note of their positions. Fit the replacement pump in the reverse order using new sealing washers. (Alternatively replace the pump head only by removing the four Allen screws on the pump, remove the head and support whilst removing the electrical connections. Refit the new head). Open the valves and fill and re-pressurise the system as described in Section 13.2 Note: The direction of flow should be upwards. The speed should always be set to maximum.
15. Expansion Vessel.
Drain the central heating circuit as described in Section 16.3(a). Isolate the gas supply at the mains. Then either fit a separate expansion vessel on the central heating return to the appliance or replace the existing vessel as described below. Drain the domestic circuit as described in Section 16.3(b). Disconnect the flue system at the boiler. Disconnect the appliance pipework at the appliance entry points ensuring precautions are taken to cope with any water remaining in the appliance. Remove the appliance from the wall. Disconnect the expansion vessel from the appliance by undoing the fitting nut at it’s base. Fit the replacement vessel in the reverse order. Open the valves and fill and re-pressurise the system as described in Section 13.3
16. Pressure Relief Valve. See Fig. 41 and 42. Drain the central heating circuit as described in Section 16.3(a). Hinge down the facia assembly as described in Section 15.3(c). Remove the Bottom panel as described in Section 15..3(d). Undo the discharge pipe connection and remove the valve retaining clip. Remove the valve taking care not to distort the pipework. Fit the replacement valve in reverse order. Reconnect the discharge pipe. Open the valves and fill and re-pressurise the system as described in Section 13.3.
17. Water Flow Turbine. See Fig. 41 and 43. Check that the electricity supply to the appliance is turned off. Drain the domestic hot water circuit as described in Section
16.3(b). Remove the two upper screws and hinge down the facia panel as described in Section 15.3(c). Disconnect the electrical connection.
Unscrew the securing nuts and remove the turbine housing from the pipework.
Fit the replacement water flow turbine in the reverse order ensuring new fibre washers are fitted to the new turbine body. Check that the correct, blue, flow restrictor is fitted.
NOTE: Washers are different
Inlet = Outlet =
24
Fig. 41. Appliance Components (Lower Assembly)
1 Pressure relief valve 2 Domestic hot water sensor 3 Water flow turbine 4 Gas valve 5 Pump 6 Air pressure switch 7 Air pressure switch connecting tubes 8 Pressure gauge connection 9 Gas valve electrical connections 10 By-pass pipe 11 Fixing disc and screw 12 Central heating sensor
4 5 6
1
2 3
98
7
1110
12
Page 25
19. Pressure Gauge. See Fig. 34. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 16.3(a). Remove the two upper screws and hinge down the facia panel as described in Section 15.3(c). Prise back the retaining clips securing the gauge to the facia panel. Unscrew the fixing disk and unplug the gauge from the pump inlet pipe. Fit the replacement gauge in the reverse order ensuring the “O” ring is in place. Open the valves and fill and re-pressurise the system as described in Section 13.3.
20. Control Board. See Fig. 44. Check that the electricity supply to the appliance is turned off. Undo the 3 screws and remove the facia bottom panel. Remove the two upper screws and hinge down the facia assembly. Carefully pull off all the connectors. Disconnect the mains supply lead at terminal X1 and unscrew the earth lead from the left and side panel.
Remove the four corner screws on the rear of the facia and separate the metal back panel from the plastic facia. Remove the flame sense and ignitor leads from the control board. Remove and retain the brass nut and washer. Release the six pillars on the control board and pull the control board forward off the back panel. Fit the replacement board in the reverse order ensuring it is pushed firmly onto the six pillars and clicks into place. Special care should be taken with the brass post and nut to ensure a good earth contact. (Check earth continuity between the incoming earth and the appliance chassis). Refit the facia panel and hinge the control box assembly in the servicing position as described in Section 15.3 (c).
21. Gauze Filter. See Fig. 45. Remove the water flow turbine as described in section 16.4-17. Undo the lower union nut on flow switch housing. Undo the nut on the isolating valve and remove the mains water inlet pipe. Carefully extract the filter from the valve end of the pipe. Replace the filter and refit the pipe in reverse order using a new fibre washer.
25
Fig. 43. Water Flow turbine.
1
1 Flow turbine 2 Flow restrictor (10l Blue) 3 Fibre washer (inlet) 4 Electrical connection 5 Direction of flow 6 Fibre washer (outlet)
Fig. 42. Pressure relief valve.
Pressure relief valve. (Turn knob anti-clockwise to test).
2
6
5
3
4
Fig. 44. Control board.
Fig. 45. Gauze Filter.
Gauze Filter
Isolating Valve
1 Facia 2 Control board 3 Rear cover 4 Fixing screws
4
3
2
1
Type
Type
Fibre Washer
Page 26
22. Flue flow sensor. See Fig. 46. Check that the electricity supply to the appliance is turned off. Remove the fan assembly as described in Section 15.3(e). Unscrew the single central retaining screw and withdraw the sensor from the fan. Fit the new sensor ensuring the correct orientation and carefully tighten the retaining screw. Refit the fan assembly in reverse order.
26
Positive
Fig. 46. Flue flow sensor.
Page 27
27
End of a domestic
hot water overrun
Escape pause by
resetting the mains
electricity supply
OFF-ON
Anti-cycle delay
Main gas valve
OFF
6
EITHER
AUTOMATIC START-UP SEQUENCE
1. Central Heating Mode
NO
PASS
PRESENT
PRESENT
ABSENTABSENTFAIL
YES
Central heating
temperature 6°C
above set point
Operating Switch
(or programmer)
OFF
Continue
pump and fan
for 4 mins plus
extra 4 mins
pump.
Gas valve OFF
Room thermostat
OFF
Burner pressure
CH min (1.5 mbar )
Burner pressure
automatically
adjusted for range
rating and then
modulated to
maintain set flow
temperature
AUTOMATIC
START-UP
SEQUENCE
CENTRAL
HEATING
DEMAND
SATISFIED
Water flow
temperature
monitored by central
heating sensor
Pump on
Operating Switch
(or programmer)
and room
thermostat on
CENTRAL HEATING
DEMAND
Internal
"Autofrostat"
demand
Is fan in
overrun mode?
Air pressure
switch test
Fan ON
Sense air
pressure
Main valve
opens
Sense
flame
Initiate
sparking
Stop
sparking
Wait
(fan or fan and
pump on)
Ignition Time -
out (after 9secs)
Ignition
Lock-out
Wait
(fan or fan and
pump on)
Wait (pump on
in central
heating mode)
17. Operational Flow Diagrams
Page 28
28
Signal from the
flow turbine
HOT WATER
DEMAND
(Overrides all other
overrun modes
and functions)
No demand and
primary
temperature below
6°C monitored by
the central heating
sensor
Internal
"Autofrostat"
Demand
Run pump
Below 4°C
Above 8°C
4°C to 8°C
Monitor central
heating sensor
Burner pressure
at 1.5 mbar
Burner pressure adjusted
based on the temperature
rise over the previous
minute. Aiming at 4°C
rise/minute.
Burner never to be
extinguished
irrespective of the
rate of temperature
rise
At the set point
change to a wide
band proportional
control
Commence normal central
heating mode until heating
temperature reaches 20°C
Return to normal
OFF state
Pump on until
primary temperature
drops to 55°C
No demand and central
heating temperature above
50°C monitored by the
central heating sensor
End of demand or central
heating temperature above
70°C monitored by the
central heating sensor
Pump and Fan on
for 4 minutes
Inhibit operations
for approximately
1 second. 6 second
delay before re-
ignition from any
other demand.
Is the central
heating mode
interrupted?
AUTOMATIC
START-UP
SEQUENCE
HOT WATER
DEMAND
SATISFIED
Pump OFF
Wait for flow
greater than
2.9 l/min
Gas valve OFF.
Fan remains ON
Modulate heat
input to maintain
hot water
temperature at the
factory pre-set
level
Gas valve OFF
Operating
Switch (or
programmer
OFF)
Domestic hot water
temperature
monitored by hot
water sensor
3. "Autofrostat" Function
4. Pump Overrun Function
5. Over run Function
2. Domestic Hot Water Mode
6. Central Heating ramp control
Flow less than
3.5 l/min
min burner pressure
Flow <2.7 l/min
gas valve off
If burner on less than
3 min;
10 sec pump and fan
over-run
If burner on more than
3 min;
10 sec over-run
80 sec fan over run
10 sec pump over run
80 sec fan over run
Pump on
for
4 minutes
Page 29
29
F1 2A
F2 1AT
Optional links
Spark
Flame sense
Outputs Inputs
Mains indicator
Modulating
valve
Overheat stat
X6 Pins 8 & 9
X6 Pins 15 & 16
X6 Pins 5,6 & 7
X6 Pins 14, 17 & 18
X6 Pins 19 & 20
X6 Pins 3 & 4
Flow signal
CH temp. sensor
DHW temp. sensor
CH control POT
Air pressure switch
MAINS PROGRAMMER/CLOCK
FULL SEQUENCE
CONTROLLER
GAS VALVE
LOW VOLTAGE ELECTRONICS
(Microcontroller)
ROOM STAT
X1
X2
321
1
2
3
4
6
5
RL1
X3 Pin 1 X3 Pin 2
X4 Pin 3
X5 Pin 3
X5 Pin 1
X4 Pin 1
FAN
PUMP
RL3
RL4
N
N
N
N
L
18. Fault Finding
Note: This fault-finding information is for guidance only. Worcester Heat Systems cannot be held responsible for costs incurred by persons not deemed to be competent.
PRELIMINARY CHECKS
Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of the Service/Fault-Finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY, (b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH.
Page 30
30
Fault in
Central Heating
Fault in
Domestic Hot Water
Is mains LED flashing?
Is mains LED
iluminated?
Turn control knob
fully clockwise
Set room stat to
call for heat
Ensure link is fitted at
X2 pins 2 & 3
Set clock to call for heat
Has overheat
thermostat tripped?
Ensure link is fitted at
X2 pins 5 & 6
Is mains LED flashing?
GO TO
CHECK D
GO TO
CHECK K
GO TO
CHECK K
GO TO
CHECK E
GO TO
CHECK F
GO TO
CHECK O
GO TO
CHECK C
Is control knob
set for demand?
Is a room thermostat
fitted?
Is room thermostat
calling for heating?
Is programmer fitted?
Is programmer calling
for heat?
Is pump running?
Has overheat
thermostat tripped?
Is mains LED
illuminated?
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Page 31
31
No mains LED
Connect mains
supply
Replace fuseIs Fuse F1 OK?
Is F2 (1.25AT) OK?
Faulty PCB
Replace
Flashing mains LED
Remove X6
Open circuit?
Replace thermistor
Replace harness
Short circuit
Faulty PCB
Replace
Is resistance between
pins 3 & 4 between
690ohms & 33k?
Is resistance between
pins 19 & 20 between
690ohms & 33k?
Replace fuse
Is mains present at
X1 pins 1 & 3?
GO TO
CHECK H
GO TO
CHECK I
GO TO
CHECK H
GO TO
CHECK J
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
OK
OK
OK
OK
Faulty
Faulty
Faulty
Faulty
NO
Page 32
32
The overheat thermostat can be
reset by pressing the reset button,
but if it trips immediately or on a
regular basis a serious problem has
occurred therefore contact your
installer
Reset thermostat
Overheat Thermostat Check
Pump Check
Fan Check
Does button hold in?
Secure Connector
Secure Connector
Faulty pump
Is pump connector
secure on the PCB (X3)?
Is fan connector
secure on the PCB (X4)?
Is mains present at the
pump connector
(X3 pins 1 & 2)?
Is mains present at the
fan connector
(X4 pins 1 & 2)?
ATTAC H to heat
exchanger
Is capillary broken?
Ensure appliance is
cool and retest
Replace overheat
thermostat
Is capillary firmly
ATTACHED
to exchanger?
GO TO
CHECK I
GO TO
CHECK O
GO TO
CHECK L
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
Faulty Harness
Faulty fan
YES
Mains at fan
NO
Page 33
33
Thermistor Check
Harness Continuity Check
Harness Short Check
Remove connectors
from thermistor
Thermistor OK
Remove appropriate
connectors
Is continuity observed
between each end of
wire in question?
Faulty harness
or connector
Harness OK
Remove appropriate
connectors
Faulty harness
Harness OK
Is short circuit
observed between pair
of wires in question?
Is resistance between
terminals of thermistor
between 690ohms & 33k?
Faulty thermistor
YES
YES
YES
YES
NO
NO
YES
YES
NO
Page 34
34
Ignition Check
Is fan running?
Is sparking present at
the electrodes?
Faulty PCB
Replace
Connect ignition leads
securely
Are leads breaking
down?
Ignition coil faulty
replace PCB
Replace leads
Does burner continue?
Does gas pressure
modulate?
Ignition OK
Faulty PCB
Replace
Is flame sense
electrode in flame?
Is lead secure
both ends?
Secure lead
Ensure flame sense
electrode in flame at
minimum burner
pressure
Are ignition leads
connected both
ends securely?
Does sparking occur?
Does ignition occur?
YES
YES
YES
YES
YES
HARNESS OK
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
GO TO
CHECK G
GO TO
CHECK E
GO TO
CHECK M
GO TO
CHECK I
GO TO
CHECK N
GO TO
CHECK L
Page 35
35
Remove BROWN and
WHITE terminals
from air pressure
switch
Air pressure switch
faulty
With no demand, is a
short-circuit observed
at exposed APS
terminals?
Reconnect the
WHITE & BROWN
wire and remove the
GREEN wire. Initiate
a demand.
Does the fan run?
PCB faulty
Air pressure switch
faulty
APS OK
Is gas pressure present
at input to gas valve?
Ensure gas supply
Faulty board
Replace
It is not possible to
seperately test the gas
valve and the supply
lead.
Relpace the gas valve or
the lead.
Is live output present at
X5 pins 1 & 2 relative to
neutral at pin 3?
Note: Readings to be
taken within 9 seconds
of a demand.
Is gas pressure present
at input to burner?
Gas valve OK
With fan running
disconnect BROWN
wire. (DO NOT touch
chassis with it). Is a
short circuit observed
across exposed APS
terminals?
Gas Valve Check
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
Air Pressure Switch Check
Is there mains 230V
at fan connector X4
pins 1 and 3?
YES
Fan or fan cable
faulty
NO
YES
L
Page 36
With pressure above
minimum, remove Modureg
Lead. Does pressure drop to
minimum?
36
Is minimum pressure
observed at burner at all
times?
Modulating Valve Check
Flow turbine Check
GO TO
CHECK I
YES
YES
YES
YES
NO
YES
YES
NO
NO
NO
NO
Is pressure at burner
always the same?
Is resistance
nominally 125ohms?
Does voltage
go above 6.25V?
Faulty PCB.
Replace
Reconnect X6 and measure
voltage across modulating
valve during operation
Gas valve OK
Does the boiler ignite at a higher flow rate?
Faulty turbine.
Replace.
Faulty PCB.
Replace
Disconnect the 3 way in-line
connector.
Check that there is 5V DC output
from the PCB at the connector.
Red +5V Black 0V
Faulty modulating valve .
Replace gas valve
Remove X6, measure
resistance between
pins 15 & 16
N
YES
NO
O
Re-connect the 3 way connector
and open a tap to run the turbine.
Check that there is between 1.5 and
4.5 V DC across the green and black wires/terminals.
With boiler cold, slowly open HW
tap. When flow reaches 3l/min does boiler ignite? (Flow can be
checked using a measuring jug and
stop watch)
YES
NO
GO TO
CHECK I
HARNESS OK
YES
Faulty turbine.
Replace
Turbine OK
NO
NO
Page 37
1 Burner Assembly Natural Gas Aeromatic AC 23/053595 1 8 716 142 652 0 2 Injector Natural Gas Stereomatic O 4.5mm 1 8 716 140 208 0 3 E01-892 Gas valve Natural Gas Dungs BM771 1 8 716 150 766 0 4 Air Pressure Switch Huba 605.99530 1 8 716 146 159 0 5 375-697 Spark Electrode Assembly Buccleuch 1 8 716 142 100 0 6 E01-612 Flame Sensor Buccleuch 1 8 716 120 345 0
E01-930 Flame sensor Harness Buccleuch 1 8 716 120 126 0 7 E01-598 Ignition Harness Buccleuch 1 8 716 120 236 0 8 E01-599 Gas to Water Heat Exchanger Giannoni 1 8 716 142 905 0 9 E01-600 Insulation Pack WHS 1 8 716 192 216 0
10 E01-601 Auto Air Vent Intermes 1 8 716 140 5040
11 299-506 Pressure Gauge Cewal 1 8 716 142 300 0 12 375-699 Pressure Relief Valve Caleffi 3141 3bar 1 8 716 142 404 0 13 E01-602 Pump with Harness Grundfos 15 60 Special 1 8 716 143 107 0 14 E01-603 Expansion Vessel Winkelman Panhof (8Ltr) 389mm Dia 1 8 716 142 502 0 15 E58-079 PCB Boiler Control Pactrol 423100 1 8 716 146 329 0 16 E04-582 Temperature Thermistors Elmwood 2 8 716 142 384 0
E01-900 CH Thermistor Clip 1 8 716 148 313 0
299-495 DHW Thermistor Clip 1 8 716 148 303 0 18 E01-605 DHW Flow Regulator Blue 1 8 716 141 052 0 19 324-822 Gauze Filter WHS 1 8 716 148 401 0 20 Flow Turbine SIKA VTY 1 8 716 146 160 0 21 Fan Assembly FIME 1 8 716 121 681 0 22 E01-607 Overheat Thermostat Ranco LM7 1 8 716 142 307 0 23 299 357 Fuse Pack WHS 1 7 716 192 206 0 24 E01-610 Gasket Pack WHS 1 7 716 192 281 0
ACCESSORIES
299-360 Mechanical Programmer Kit DIEHL 7 716 192 002
E05-341 Mini Expansion Vessel Kit Including new pipe and Expansion Vessel 7 716 192 188
FLUE OPTIONS
Telescopic Horizontal Flue Kit 425 - 725mm 7 716 191 068 E01-943 Extension Flue Kit 750mm 7 716 191 006 E01-944 Vertical Flue Kit 7 716 191 069 E01-945 Vertical Flue Adaptor 7 716 191 016 E01-946 Internal Fixing Kit Telescopic Flue 7 716 191 019 E01-058 Flue Elbow Kit 90 deg. 7 716 191 013 E01-059 Flue Elbow Kit 45 deg. 7 716 191 014
Key G.C. No. Part Manufacturer’s Reference Qty WHS No. Part No.
37
19. Component Parts List
Page 38
38
9
24 23
20
3
5
8
14
12
13
10
3
21
1
15
22
4
11
23
20
7
6
25 24
2
19
18
16
Page 39
39
Page 40
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests
of continued improvement.
All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
PUBLICATION 8 716 114 751a (11/07)
Worcester Heat Systems Limited (Bosch Group), Cotswold Way, Warndon, Worcester WR4 9SW.
Telephone: (01905) 754624. Fax: (01905) 754619.
Technical Helpline (08705) 266241.
www.worcester-bosch.co.uk