Worcester 24 SI II LPG User guide

Page 1
24Si II / 28Si II
WALL MOUNTED COMBINATION BOILERS FOR CENTRAL HEATING
AND MAINS FED DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
This appliance is for use with Natural Gas or LPG (Cat II 2H3P TYPE C12 & C32) 24SiII GC NUMBER 47 311 65 (N.G.) GC NUMBER 47 311 66 (L.P.G.) 28SiII GC NUMBER 47 311 67 (N.G.) GC NUMBER 47 311 68 (L.P.G.)
GB/IE
APPLIANCE OUTPUTS
Domestic Central Heating
Hot Water
24Si II 28Si II 24Si II 28Si II Minimum 6.9 kW 8.1 kW 6.9 kW 8.1 kW Maximum 24 kW 28 kW 24 kW 28 kW
IMPORTANT: THESE INSTRUCTIONS APPLY IN THE GB/IE ONLY
AND MUST BE LEFT WITH THE USER OR AT THE GAS METER
It is IMPORTANT to read the instructions before starting work - they have been
written to make the installation easier and prevent hold-ups.
Worcester supports the
Benchmark code of practice
Page 2
1.1 Gas Safety (Installation & Use) Regulations 1998:
The appliance is suitable for installation in GB/IE only and should be installed in accordance with the rules in force. It is the law in GB that a competent person in accordance with the above regulations installs all gas appliances. Failure to install appliances correctly could lead to prosecution. It is in your interest, and that of safety, to ensure compliance with the law.
1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations.
1.3 The compliance with a British Standard or European Norm does not, in itself, confer immunity from legal obligations.
1.4.1 The installation of the appliance must be in accordance with the relevant requirements of the Gas Safety Regulations, current IEE Regulations, Building Regulations, Building Standards (Scotland) and local water by-laws.
1.4.2 In Eire the installation must be carried out by a competent person and installed in accordance with IS 813, Domestic Gas Installations (Edition 2), the current building regulations and the electrical installation must follow the ETCI rules.
1.5 The installation should follow the recommendations of the following British Standards unless otherwise indicated. BS5440:1 - Flues and ventilation for gas appliances: Flues BS5440:2 - Flues and ventilation for gas appliances: Air supply. BS5449 - Central heating for domestic premises. BS5482 - Domestic propane gas burning installations. BS5546:1 - Installation of gas hot water supplies. BS6700 - Domestic water supply in buildings. BS6798 - Installation of gas fired hot water boilers. BS6891- Low pressure gas pipework installations upto 28mm (R1). BS7593 - Water treatment. BS7671 - Requirements for electrical installations.
1.6 The appliance does not contain any substances which are harmful to health.
1.7 In certain circumstances, the installer can be held responsible, not only for mistakes on his part but also for damage resulting from the use of faulty materials. We advise that, to avoid any risk, only quality approved branded fittings are used.
1.8 LPG Installation:
The appliance shall not be installed in a room or internal space below ground level when it is intended for use with LPG. This does not preclude the installation into rooms, which are basements with respect to one side of the building but open to the ground on the opposite side.
1.9 These instructions cover, as far as possible, the foreseeable situations, which may arise. Contact The Worcester Technical Department, Telephone: 08705 266241, for advice on specific installations.
2.1 The initiative is the new code of practice to encourage the correct installation, commissioning and servicing of domestic central heating boilers and system equipment.
The 'checklist' is a vital document that must be completed by the installer at the time of installation. It confirms that the boiler has been installed and commissioned according to the manufacturers instructions.
A declaration of conformity (Refer to IS 813 Annex D1) must be completed by the installer and a copy supplied to the appliance operator for boilers installed in Eire. Without the completion of the checklist and/or declaration, manufacturers may refuse to respond to a call-out from a householder, who will be advised that he or she must call back the installer, who has not fulfilled his obligations to record the information required by the initiative.
Service:
To ensure continued efficient operation of the appliance it must be checked at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but once per year should generally be adequate. The extent of the service required by the appliance is determined by the operating condition of the appliance when tested by fully qualified engineers. Any service work must be carried out by competent registered engineers (CORGI in GB).
2.2 General Information
The appliance is set to give the maximum output of 28 kW [28Si II] or 24kW [24Si II] to the domestic hot water and to the heating system. The hot water flow rate is limited to a nominal 10 l/min [28Si II] or 8 l/min [24Si II] at a maximum temperature rise of 40°C. The sanitary water section of the appliance is suitable for mains water pressure of upto 10bar. Kits are available to convert the appliance from Natural Gas to Propane operation and vice versa.
2.3 Electrical Supply
230V - 50Hz. Load 180 watts. External fuse 3A (to BS1362), Internal fuses F1 - 2A, F2 - 1.25A (20mm).
2.4 Gas Supply
The appliances require a maximum of 3.25 m
3
/h of natural gas
(G20) or 1.25 m
3
/h of propane (G31) [28Si II] or 2.8 m3/h of
natural gas (G20) or 1.08 m
3
/h of propane (G31) [24Si II]. The installation and the connection of the gas supply to the appliance must be in accordance with BS6891. The meter or regulator should deliver a dynamic pressure of 20 mbar (G20) or 37mbar (G31) at the appliance, which is equivalent to about 19 mbar or 36 mbar at the gas valve inlet pressure test point.
2.5 Installation
The appliance is suitable for indoor installation only and for use with a sealed system only. Do not place anything on top of the appliance. This is a room sealed appliance and a separate combustion air supply is not required in any room or compartment in which the appliance is fitted. If the appliance is fitted in a cupboard or a compartment is built around it after installation, then the structure must conform to the requirements of BS6798 and BS5440 Part 2. However, because of the low casing losses, there is no need for cooling ventilation openings in
2. Introduction1. Installation Regulations
2
1. Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 10. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 11. Installing the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 12. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 19
4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 13. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
5. Flue Terminal Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 14. Inspection and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
6. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 15. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 24
7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 16. Short Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 30
Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 17. Operational Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . Page 32
8. Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 34
9. Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 19. Conversion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . Page 42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
Page 3
the compartment provided the increased clearances are used. See Fig. 5. The spaces specified for servicing must be maintained.(See Table 8). There is space for the service pipes to pass at the back of the appliance.
2.6 Flue
Multi-Directional Horizontal Flue Kit.
Standard Flue Kit can be adjusted from 425mm to
725mm without cutting. The minimum length is 265 mm with cutting. Extended flue lengths are available upto a maximum of 4m for natural gas appliances and 2.5m for LPG. Optional 45° and 90° flue bend kits are available NOTE: When using flue bends the maximum flue length is reduced (see Section 11.12). If access to the flue terminal will be a problem then a kit is available to enable the horizontal flue to be fitted from inside the house. Do not allow the flue terminal to the outside wall to become obstructed or damaged. A Tower guard type K2 CG 393553 is available from Tower Flue Components, Vale Rise, Tonbridge TN9 1TB. A vertical flue system is available.
2.7 Controls
The appliance has controls for switching the appliance On or Off, [this does not electrically isolate the appliance] for adjusting the CH and DHW temperatures. The CH control knob also switches the CH off and on. A programmable 'wire free' room thermostat or a facia mounted programmer or clock is available. A room thermostat and/or an externally mounted programmer for mains voltage operation may be connected to the appliance.
2.8 System
All dirt must be flushed from the system before connecting the appliance. The system can be pre-piped and flushed before the appliance is fitted. The connections in the system must withstand an operating pressure of upto 3 bar. Radiator valves must conform to BS2767: 10:1977. Table 3 gives the pump head available for the system and the required temperature differential. A drain cock must be fitted to the lowest point and an air vent to the highest point of the system.
2.9 Showers, Bidets, Taps and Mixing Valves
All taps and mixing valves must be suitable for the available mains pressure and temperatures upto 65
o
C. It may be necessary to fit a pressure reducing valve. Hot and cold mains fed water can be supplied to overrim bidets but is subject to local water company requirements. The flow of water from individual outlets varies on all mains fed systems that are not fitted with flow balancing valves. Thermostatically controlled or pressure equalising shower valves give extra comfort and protection. If a pressure equalising valve is fitted then the domestic hot water temperature should be set to maximum.
2.10 Safety The appliance must not be operated with the inner casing cover removed or without being full of water and pressurised. The gas and electricity supplies must be turned off before working on the appliance.
Temperature monitoring controls are fitted to prevent overheating. Automatic frost protection is provided together with automatic pump seizure protection. The gas valve solenoids are automatically checked for gas soundness.
IMPORTANT: Where back-flow prevention devices, including water meters, are fitted the expansion of hot water into cold water main can be prevented. This can result in a pressure build-up that may cause damage to the boiler and household devices such as showers, washing machines etc.
In these cases we recommend that a mini-expansion vessel be fitted adjacent to the boiler in the cold water supply pipe.
2.11.1 Operation Central Heating:
A demand for heat will ignite the burner. It will operate at minimum pressure for 15 seconds before increasing to the maximum pressure over a period of 1 minute and then automatically match the system requirements. At the end of the demand the burner will go out, the pump will continue to run for upto 4 minutes or the fan for 15 seconds. There is an anti-cycle time of 3 minutes.
2.11.2 Domestic Hot Water:
A demand for hot water will light the burner. The pressure will immediately rise to maximum. At the end of the demand the fan will continue to run for 15 seconds if there is no heating demand. There is an anti-cycle time of 10 seconds.
2.11.3 Domestic Hot Water and Central Heating Mode.
The demand for hot water will override the CH function when the appliance is in the heating and hot water mode of operation. In winter it may be necessary to reduce the flow at the taps to maintain the delivery temperature.
Fig. 1. Facia controls
3
Fig. 2. Water flow diagram.
1
2 3
4
7 6
1. Mains On/Off control 5. Optional programmer
2. CH temperature control 6. Lockout indicator light and
3. DHW temperature control reset button
4. System pressure gauge 7. Burner indicator light
5
1
2 3 4
7
6
1. CH flow 7. Circulating pump
2. Domestic hot water flow 8. Expansion vessel
3. Domestic hot water supply 9. Primary heat exchanger
4. CH return 10. Automatic air vent
5. Pressure relife valve discharge 11. By pass
6. Domestic water flow turbine
5
8
9
10
11
Page 4
4
3. Technical Data
MAXIMUM AVAILABLE PUMP HEAD
BOILER OUTPUT HEAD MIN. FLOW RATE
kW Metres L/min. °C
6.9 5.2 9 11
24 1.8 22 15.5
28 1.8 22 18
Table 3
MECHANICAL SPECIFICATIONS 24Si II 28Si II
CENTRAL HEATING FLOW - COMPRESSION 22mm 22mm
RETURN - COMPRESSION 22mm 22mm
COLD WATER INLET - COMPRESSION 15mm 15mm
DOMESTIC WATER FLOW - COMPRESSION 15mm 15mm
GAS INLET Rp
3
4 Rp 3⁄4
RELIEF VALVE DISCHARGE (PUSH-IN) 15mm 15mm
CASING HEIGHT 740mm 740mm
CASING WIDTH 400mm 440mm
CASING DEPTH 360mm 360mm
WEIGHT - LIFT 36kg 36kg
WEIGHT - PACKAGED 48kg 50kg
WEIGHT - DRY 39kg 40kg
Table 4
FLUE DETAILS
HORIZONTAL FLUE G20 LPG
WALL HOLE DIAMETER EXTERNAL FIX mm 110 110
INTERNAL FIX mm 130 130
STANDARD FLUE MINIMUM LENGTH mm 275/*425 275/*425
MAXIMUM LENGTH mm 725 725
EXTENDED FLUE MAXIMUM LENGTH mm 4000 2500
FLUE ASSEMBLY DIAMETER mm 100 100
Table 2.
FLOW/RETURN
DIFFERENTIAL
* NOTE : Minimum uncut length
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
8.1 9.2 0.7 0.97
28 30.7 13.1 3.25
BOILER ADJUSTED FOR G31 (Propane)
8.1 9.2 2.8 0.38
28 30.7 34.5 1.25
Table 1. 28Si II
BURNER
PRESSURE
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
6.9 7.9 0.9 0.84
24 26.4 12.1 2.8
BOILER ADJUSTED FOR G31 (Propane)
6.9 7.9 3.1 0.32
24 26.4 35.0 1.08
Table 1. 24Si II
BURNER
PRESSURE
Natural Gas: Net Input = Gross Input x 0.901 LPG (Propane): Net Input = Gross Input x 0.922
NOTE: With longer flue lengths, not using a restrictor, the minimum burner pressure will rise, naturally due to the flue, to 1.1mbar on G20 appliances only.
Page 5
PERFORMANCE SPECIFICATIONS 24Si II 28Si II
PRIMARY WATER CAPACITY litres 2.0
IP RATING (WHOLE OF BOILER) IP 20
MAXIMUM MAINS INLET PRESSURE bar 10
MINIMUM MAINS INLET PRESSURE (WORKING) FOR MAXIMUM FLOW bar 1.0
MINIMUM MAINS INLET PRESSURE (WORKING) FOR OPERATION bar 0.25
DOMESTIC HOT WATER TEMPERATURE RANGE °C 40 - 60
MAXIMUM CENTRAL HEATING FLOW TEMPERATURE °C 82 (nom)
MAXIMUM CENTRAL HEATING SYSTEM SET PRESSURE bar 2.65
MINIMUM CENTRAL HEATING SYSTEM PRESSURE bar 0.5
OUTPUT TO CENTRAL HEATING & DHW kw NATURAL GAS (G20) 24 28
LPG - PROPANE (G31) 24 28
DOMESTIC HOT WATER SPECIFIC RATE - 30°C RISE l/min 11.5 13.5
MAXIMUM DOMESTIC HOT WATER FLOW RATE - 40°C RISE l/min 8.5 10
FLUE GAS MASS FLOW RATE 14.9 17.4
FLUE GAS TEMPERATURE °C 146.0
NOx CLASSIFICATION FOR BOTH 24 & 28Si II Class 3
SEDBUK NUMBER 78.0 78.2
SEDBUK NUMBER LPG 80.5 80
SEDBUK BAND* D D
5
GAS SUPPLY SYSTEM - BASED ON NG (G20)
TOTAL LENGTH OF GAS SUPPLY PIPE (COPPER) metres
3 6 9 12
GAS DISCHARGE RATE - PRESSURE DROP mbar. m
3
/h PIPE DIAMETER mm
8.7 5.8 4.6 3.9 22
18.0 12.0 9.4 8.0 28
Table 7
CLEARANCES (mm)
INSTALLATION SERVICE UNVENTILATED COMPARTMENT
ABOVE FLUE ELBOW 30 3 0 15 0 IN FRONT OF APPLIANCE 600 600 *240 BENEATH APPLIANCE 200 200 200 RIGHT AND LEFT HAND SIDE 10 10 80
Table 8
SYSTEM CAPACITY
TOTAL SYSTEM VOLUME litres
INITIAL INITIAL CHARGE PRESSURE bar PRESSURE bar 0.5 1.0 1.5
1.0 57 75 N/A
1.5 31 42 52
Table 9
Refer to Section 6. * Front clearance is to a removable panel (eg. door)
DOMESTIC HOT WATER TEMPERATURE RISE
DISCHARGE RATE l/min 7 8 9 10 TEMPERATURE RISE °C 24kw 49 43 38 34 TEMPERATURE RISE °C 28kw 57 50 45 40
Table 6
Table 5
* The value is used in the UK Government Standard Assessment Procedure [SAP] for the energy rating of dwellings. The test data from which it has been calculated have been certified by the GASTEC notified body.
Page 6
Fig. 4. Appliance casing dimensions and
required clearances (side view).
All dimensions in mm
Fig. 6. Side flue opening
24Si II 28Si II A CH Flow = 55 75 B DHW Flow = 120 140 C Gas = 185 205 D Cold Water Inlet = 250 270 E CH Return = 315 335 F Relief Valve Discharge = 375 395
Fig. 3. Appliance casing dimensions and required clearances for installation/servicing
All dimensions in mm
30
150
10
10
6
B
C
D
E
190
(A, B, C, D,)
20
A B C D E
F
View of underside of appliance showing
connections
Valves shown closed.
Fig. 7. Pipework connections
All dimensions in mm
24Si II = 400
11 4
600
740
230
360
200
200
F
All dimensions in mm
11 4
28Si II = 440
Fig. 5. Unventilated compartment clearances
230
200mm
150mm from the top of the flue elbow
80mm
80mm
240mm
From a removable panel eg. door
A
Page 7
The appliance may be installed in any room but refer to the requirements of the current IEE Regulations and, in Scotland, the relevant electrical provisions of the Building Regulations with respect to the installation of appliances in rooms containing baths or showers. In Eire refer to the ETCI rules for electrical installations. Where a room sealed appliance is installed in a room containing a bath or shower, any switch or appliance control using mains electricity must NOT be able to be touched by a person using the bath or shower. The IP rating of the appliance may only allow it to be located in specific 'zones'. Refer to, in GB, Electrical Regulations 16th Edition. The appliance is NOT suitable for external installation No special wall protection is required. The wall must be able to support the weight of the appliance. Refer to Table 4. The specified clearances must be available for installation and servicing. Refer to Table 8 and Fig.3, 4. The appliance can be installed in a cupboard/compartment to be used for airing clothes providing that the requirements of BS6798 and BS5440 Part 2 are followed. Refer to Section 2.5. The airing space must be separated from the boiler space by a perforated non-combustible partition. Expanded metal or rigid wire mesh is acceptable provided that the major dimension is less than 13mm. The clearance between the front of the appliance and the cupboard or compartment door should be not less than 75mm. LPG Installation. Refer to Section 1.8.
The flue system must be installed following the requirements of BS5440: 1. In Eire the flue termination must be sited as described in Table 5 of the current edition of IS 813. Standard horizontal flue kit length is 275 – 725mm with extension kits for flues upto 4m for natural gas and 2.5m for LPG. The terminal must not cause an obstruction or the combustion products a nuisance. Under some conditions the terminal might steam and positions where this might be a nuisance should be avoided. Refer to Fig 8. If the terminal is less than 2m above a surface to which people have access then a guard must be fitted. The guard must be evenly spaced about the terminal and fixed with plated screws. A Type K2 guard is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB.
5. Flue terminal positions4. Siting The Appliance
7
K
H
H
A
G
C
D,E.
J
N
Q
F
P
Q
B
I
L
N
N
M
M
Q
I
Fig. 8. Siting of the flue terminal.
TERMINAL POSITION MIN. DISTANCE
Aa– Directly below an opening, air brick,
opening windows etc. 300 mm
B– Above an opening, air brick,
opening windows etc. 300mm
C– Horizontally to an opening, air brick,
opening windows etc. 300mm D– Below gutters, soil pipes or drain pipes. 75mm E– Below eaves. 200 mm F– Below balconies or car port roof. (Lowest point) 200 mm G– From a vertical drain pipe or soil pipe. 150 mm H– From an internal or external corner. 300 mm I– Above ground, roof or balcony level. 300 mm J– From a surface facing the terminal. 600 mm K– From a terminal facing the terminal 1200 mm L– From an opening in a car port (e.g. door
window) into dwelling. 1200 mm M– Vertically from a terminal on the same
wall. 1500 mm N– Horizontally from a terminal on the same
wall. 300 mm O– From the wall on which the terminal
is mounted N/A
P– From a vertical structure on the roof N/A
Q– Above intersection with roof N/A
NOTE N/A = Not applicable
a
In addition, the terminal should be not nearer than 150mm (fanned draught) to an opening in the building fabric formed for the purpose of accommodating a built-in ele­ment such as a window frame.
Advice should be taken if the terminal is in close proximity to surfaces which may be of plastic materials ie. car-ports, gutters etc.
Page 8
6.1 A separate vent for combustion air is not required. Refer to BS5440:2. If the appliance is in a cupboard or compartment then, because of the low casing losses, it is not necessary to have any cooling ventilation for the boiler. Refer to Section 2.5. There must be increased clearance around the appliance to allow the free movement of the air. Refer to Table 8 and Fig 3, 4 and 5.
6.2 If the appliance is to be fitted in a cupboard or compartments with less clearance than the minimum clearances given in Section
4. (Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air.
6.4 The minimum free areas required are:
The system must comply with requirements of BS6798 and BS5449 and must not be operated without being full of water and correctly pressurised. Refer to Fig 8. The pressure relief valve will operate at 3 bar. The discharge pipe, of 15mm diameter, must be directed as such that the discharge of water or steam is visible, will not discharge onto the occupants of the premises or cause any damage to the premises, in particular any electrical components or wiring. The expansion vessel, to BS4814, has a capacity of 8 litres charged to 0.5 bar, which is suitable for a static head of 5 metres. A schraeder type valve allows the pressure to be increased if the static head is greater than 5 metres. If the expansion vessel fails then it must be replaced with the designated spare part. Refer to BS 7074:1, BS5449 and Table 9 for a guide to the available system capacity. The maximum system design pressure is 1.5 bar. If the pressure is above 2.65 bar when the appliance is at maximum temperature then an additional expansion vessel must be fitted as near to the appliance as possible in the return pipe. The pressure gauge shows the system pressure. Fill and pressurise the system through a WRAS approved filling kit. Refer to Fig. 10 and 11. An optional kit is available. Refer to Section 16. The system and the appliance must be fully vented. Repeated venting loses water from the system, which must be replaced. The make-up connection must be close to the appliance in the heating return pipe through an approved non-return valve. Refer to current building regulations or Good Practice Guide 302 which lists the requirements.
Plastic Pipes
Plastic pipes must not be directly connected to the boiler. A copper to plastic transition piece should be positioned a minimum of 600mm from the boiler. A plastic pipe with a polymeric barrier should be used. The connection to the mains water supply must have the approval of the local Water Company. The pump is set at maximum and should not be adjusted. All connections in the system must withstand a working pressure of up to 3 bar. The radiator valves must conform to BS 2767:10 and other valves to BS1010.
Open Vent System
This appliance is NOT suitable for connection to an open vent system.
7. Sealed System6. Air Supply
8
Fig. 9. Sealed primary water system.
Lockshield valve
Radiator valve
Heating return
Hot water out
Water main
British Standard stop valve. Fixed spindle type
NOTE: A drain cock should be installed at the lowest point of the heating circuit and below the level of the appliance.
Mains cold
water
Heating flow
APPLIANCE
Refer to
'Water Flow
Diagram'
Fig.2.
Cold water inlet
POSITION OF AIR FROM AIR DIRECT
AIR VENTS THE ROOM FROM OUTSIDE
HIGH LEVEL 307cm
2
154cm
2
LOW LEVEL 307cm
2
154cm
2
POSITION OF AIR FROM AIR DIRECT
AIR VENTS THE ROOM FROM OUTSIDE
HIGH LEVEL 264cm
2
132cm
2
LOW LEVEL 264cm
2
132cm
2
24 kW
28 kW
Page 9
It may be necessary to contact the local Water Company before connecting the appliance.
Where back-flow prevention devices, including water meters, are fitted the expansion of hot water into cold water main can be prevented. This can result in a pressure build-up that may cause damage to the boiler and household devices such as showers, washing machines etc. In these cases we recommend that a mini-expansion vessel be fitted adjacent to the boiler in the cold water pipe.
The last 600mm of mains water pipe before the appliance must be in copper. The domestic hot water circuit of the appliance is suitable for a mains pressure of upto 10bar. A pressure reducing valve must be fitted if necessary. A mains water supply isolating valve is fitted. The maximum hot water flow rate is set at the factory to 8 l/min [24Si II] and 10 l/min [28Si II] giving a nominal temperature rise of 40
o
C with the temperature control at maximum. This rate is equivalent to a Specific Rate of 11.5 l/min [24Si II] and 12.9 l/min [28Si II] at a rise of 30
o
C. Refer to Table 6. The temperature rise, upto the maximum set by the user, is maintained by the automatic modulation of the heat input. In winter, when the water temperature is lower it may be necessary to reduce the water flow at the tap or shower to maintain the maximum delivery temperature. It is recommended that long pipe runs to taps or showers are insulated to prevent the rapid cooling of the water. Hot and cold taps and mixing valves must be suitable for the available mains pressure. No anti-syphonage arrangements are necessary for fixed head showers. The hose of a loose-head shower must be fixed so that the shower head cannot get closer than 25mm to the top edge of the bath to prevent its immersion in the water. Alternatively the shower can be fitted with an anti-syphonage device at the flexible hose connection. Thermostatically controlled or pressure balancing shower valves will give extra comfort and guard against extreme temperature. Hot and cold mains water direct to a bidet is, subject to the approval of the local water company, permissible provided that the bidet is of the overrim flushing type. The outlets must be shrouded and unable to be fitted with a hand-held spray. No anti­syphon arrangements are needed. LIME SCALE: In areas of temporary hardness [>200ppm of calcium carbonate] it is suggested that a proprietary scale reducer is fitted in the mains cold water connection to the appliance. Installation of a scale inhibitor assembly must be in accordance with the requirements of the local Water Company. The water hardness can be determined by reference to the local Water Company. An isolating valve should be fitted to allow servicing.
The appliance requires a maximum of 2.8 m
3
/h [24Si II],
3.25m
3
/h [28Si II] of natural gas (G20) or 1.08 m3/h [24Si II],
1.25m
3
/h [28Si II] of propane (G31). Refer to Table 7. A natural gas appliance must be connected to a governed meter. The installation and connection of the gas supply to the appliance must be in accordance with BS6891. The meter (NG) or regulator (LPG) and the pipework to the appliance must be checked, preferably by the gas supplier, to ensure that a dynamic pressure of 20mbar for natural gas or 37mbar for propane is available at the appliance (contact gas supplier if in doubt) equivalent to about 19mbar [NG] or 36mbar [LPG] respectively at the gas valve inlet pressure connection and that the gas flow is adequate for all the installed gas appliances operating together.
Mains supply: 230V ~ 50 Hz 180watts. External fuse 3A to BS1362. Internal fuses F1-T2A, F2-TI.25A (20mm). Spare internal fuses are supplied with the appliance. The mains cable must be 0.75mm
2
(24x0.20 mm) to BS6500 ­Table 16 and must be connected to the terminal ST2 marked L (red or brown lead), N (black or blue lead) and the Earth stud (green or green/yellow lead) and secured with the cable clamp. The Earth lead must still be slack when the other leads are taut. Refer to Fig 14 and 15.
The appliance must be earthed.
The wiring between the appliance and the electrical supply shall comply with current IEE wiring regulations (and any local regulations which apply) for fixed wiring to a stationary appliance. NB. It must be possible to completely isolate the appliance with at least 3mm contact separation in both poles. A room thermostat or externally mounted programmer must be suitable for mains voltage operation. The leads must be securely fixed in the cable clamps (see Fig. 35) A facia mounted digital programmer or mechanical timer or receiver for wireless programmable room thermostat is available as an optional extra. Instructions are supplied with the product. On very rare occasions it may be necessary to fit an external frost thermostat to protect remote parts of the system. In this case refer to the WHS Technical Department for information, Tel: 08705 266241.
10. Electrical
8. Domestic Hot Water
9
9. Gas Supply
Fig 10 - System Fill
Fig 11 - System make up
1.Central Heating Return
2.Auto Air vent
3.Non-return Valve
4.Make-up Vessel
5.Stop Cock
6.Fill Point
4
1
2
3
5
6
300mm Above
the highest point
of the system
Heating
return
Stop cock
Hose union
Temporary hose
Non return
valve
Non return
valve
Test cock
Mains water
supply
Page 10
Control Board
10
Fig. 12. Wiring diagram.
Fan
Flame sense electrode
Spark electrode
Spark Generator
Mains in
Link
CH sensor (front of heat exchanger)
Flow turbine
ST16
2 blue
green
2 green
brown
blue
blue
brown
white
red
yellow
ST2
ST15
ST1
Pump
Gas valve
2 green
white
black
Overheat cut-off device
DHW sensor
Air
Pressure
Switch
black
black
green
Safety
valve
red
green/yellow
2 brown
Safety
valve
Regulator
valve
Earth tabs
small tab=L high speed (red) medium tab = L low speed (white) large tab=N (black)
ST5
Code Plug
black
red
black
blue
black
blue
Page 11
11
Fig. 13. Functional flow diagram.
On/Off
switch
ST2
(LS)
ST2
(L
R)
ST2
(N
S)
ST1
centre
pin
ST15
right
pin
Pump
Fan
ST2 Pin N
Optional link
Room
thermostat
Transformer
Fuse F2
(1.25A Slow)
Fuse F1
(2A Slow)
N
N
ST2 Pin L
LIVE
IN
Electronics
Electronics
Inputs
Outputs
Spark Indicators
Settings
Regulator valve
Spark
electrodes
Error
indicator/reset
Red
Main valve
Flow sensor
CH sensor
DHW sensor
Air pressure switch
Flame sense
Overheat cut-off
24V programmer (if applicable)
Gas valve mode switch
CH Control knob
DHW control knob
Convert AC to low
voltage electronics
Electronics/
microprocessor
(Safety Low Voltage)
Flame detect
indicator
Red
ST2
centre pole
(Ls)
(for other features)
low
high
Electronics
ST1
right
pin
Reset button
white
red
Page 12
NOTE: READ THIS SECTION FULLY BEFORE COMMENCING THE INSTALLATION.
11.1 General
The appliance is only suitable for fitting to a sealed system. The flue must be installed as specified in BS5440:1 and the current Building Regulations.
11.2 Unpacking
Remove the appliance from its packaging and check the contents against the packing list. Unscrew the service connections and remove the wall mounting assembly. NOTE: The wall mounting assembly can be removed from the carton without having to remove the boiler.
11.3 Site Preparation
Check that the correct position for the appliance has been chosen. Refer to Section 4 and Table 8. Check that the wall is flat and will support the weight of the appliance. Refer to Table 4.
11.4 Fixing Holes and Flue Opening
Hold the wall mounting assembly or template against the wall. Check that the assembly or template is level. Mark the position of the fixing holes and the flue opening. Refer to Fig 16. The diamond cut-out indicates the centreline of the appliance. Mark the centrelines of the pipe connections to aid the pre­plumbing of the system pipework. Pre-plumbing is not recommended if no movement in the pipes is available. Check the position of the fixing points and flue opening before drilling the fixing holes 60mm deep for the No. 12 size plugs and cutting the flue duct hole at 110mm diameter [150mm diameter for internally fitted flues].
11.5 Wall Mounting and Manifold Assembly
Fit the plugs and insert the bottom screws. Check that all service valves are closed. Offer the assembly to the wall utilising the keyhole slots on the manifold assembly and fix to the wall. Refer to Fig 16 and 17. Check that the assembly is properly aligned before tightening the screws.
11.6 Gas and Water Pipes
Remove the gas cock and fix the appropriate fitting to connect the inlet pipe and refit. Refer Fig 17. If it is necessary for any of the pipes to run up the back of the appliance then they must be arranged to pass behind the expansion vessel. Refer to Fig 3. Pipework must not run horizontally within the limits of the casing. It is important that the pipes are not fixed near the appliance using clips that put a strain on the connections.
Before the appliance is fitted to the wall thoroughly
flush the system and mains water supply.
11. Installing The Appliance
12
Fig. 16. Wall mounting assembly
20
218
75
480
60
60
65
338
740
367
All dimensions in mm
Fig. 14. Access to internal fuses and
electrical connections.
Fig. 15 . Mains electricity connections.
1
2
3
4
1. Connection cover fixing screws
2. Connection cover
3. Control panel
4. Connections
Ns
Ls
L
R
L
N
230V
MAINS
Ns
Ls
230V
Page 13
11.7 Install the Boiler
Pull off the clip on facia cover and remove the cabinet by unscrewing the two fixing screws, releasing the sides and lifting from the top location. Check that the gas and water valves are closed. Refer to Fig 17. Fit the new seals, in the hardware pack, to the service valves on the manifold.
Lift the appliance to the wall, engage in the top support and lower onto the manifold assembly. Tighten the gas and water connections. Fit a discharge pipe to the relief valve leading it away from any electrics or where it might be a hazard. Lower the facia to gain access. The pipe must not be less than 15mm in diameter and must run continuously downward outside the appliance. Refer to Fig 20.
13
65
65
65
65
Wall
Frame
Wall
Frame
CH
Flow
DHW
Flow
Gas
DHW
Cold Inlet
CH
Return
Fibre
Washer
Fig. 17 . Manifold assembly
All dimensions in mm
Fig. 20 . Relief valve drain connection
1
Fig. 18 . Facia cover
1
1. Appliance
2. Controls
3. Facia cover
4. Facia cover clips (4)
2
3
4
Fig. 19 . Wall mounting frame
1. Wall mounting frame
2. Hanging bracket
3. Appliance
4. Support hook
2
1
3
4
5
2
3
4
1. Pump
2. Boiler drain
3. Pressure gauge capillary
4. Relief valve
5. Relief valve drain connection (push fit)
Page 14
11.8 Air and Flue Duct Preparation
The method of installation of the flue system may be varied to suit the actual site conditions. The instructions for connecting and fixing the ducts must, however, be strictly followed.
Remove all packing material from the flue components.
Fit the flue restrictor ring by unscrewing the flue spigot from the boiler. Refer to Fig. 22. The standard telescopic flue assembly is suitable (without cutting) for flues from 425mm up to 725mm measured from the centre-line of the boiler flue outlet to the outer face of the wall. Refer to Fig.23. The minimum length of the standard flue, after cutting is 275mm. If L is greater than 725mm then extension duct kit/s will be required
- each kit extends the flue by 750mm up to a maximum of 4000 mm for natural gas boilers and 2500mm for LPG. See table below.
EXTENSION MAXIMUM FLUE LENGTH mm
1 1475 2 2225 3 2975 4 3725 5 4000
11.9 Measure and Cut the Ducts. General: Cut the ducts as necessary, ensuring that the cuts are
square and free from burrs. Always check the dimensions before cutting. Measure the distance L. Refer to Fig. 23, 24, 25 and 26.
The standard flue can be telescopically adjusted to any length between 425mm and 725mm measured from the centre of the turret without the need to cut the ducts. Fix the flue assembly together using the self-tapping screws provided. Refer to Fig. 23.
It will only be necessary to cut the standard assembly if L is less
than 425mm. Cut the flue turret assembly and
the terminal assembly by the same amount eg. if L=350 – remove 75mm (425-350) from each
assembly.
14
Fig. 22. Flue spigot and restrictor
1
2
3
4
Fig. 21. Inner case and facia fixing
Fig.23. Standard flue assembly
L
Fixing screw
Flue turret assembly
Appliance casing
Telescopic adjustment
Terminal assembly
3
1. Inner casing cover
2. Cabinet fixing screws (4)
3. Inner casing cover fixing screws (2)
4. Inner casing cover fixing screws (2)
5. Facia control panel
6. Controls connector cover
7. Controls connector cover fixing screws (2)
8. Programmer (optional)
9. Facia control panel fixing screw
10. Top support lug (2)
11. Bottom support lug (2)
1
4
5
7
2
6
7
10
9
8
2
11
RESTRICTOR RINGS
Flue length 24Si II 28Si II
Horizontal up to 725mm 76mm 78mm Horizontal above 725mm None None LPG Horizontal up to 725mm 76mm 77mm Vertical terminal length only 1200mm 78mm 82mm Vertical flue greater than 1200mm None None
1. Flue spigot fixing screws
2. Flue spigot
3. Restrictor ring
4. Flue spigot fixing holes
Page 15
It is not necessary to cut the ducts
If L is between 1175 - 1475mm (1 extension)
1925 - 2225mm (2 extension)
*2675 - 2975mm (3 extension)
3425 - 3725mm (4 extension)
(* Maximum length 2500mm for LPG boilers)
It will be necessary to cut the ducts
If L is between 725 - 1175mm (1 extension)
1475 - 1925mm (2 extension)
*2225 - 2675mm (3 extension)
2975 - 3425mm (4 extension) 3725 - 4000mm (5 extension)
(* Maximum length 2500mm for LPG boilers)
It is necessary to shorten the assembly by cutting the first extension duct assembly eg. L = 1000mm - remove 175mm from the air and flue ducts (1175 – 1000 = 175mm).
NOTE: Extension duct measurements do not include the socketed end. Unless specifically instructed the socketed end must not be removed.
Fix the flue ducts together before fixing the surrounding air duct, the cut ducts fit into the terminal assembly.
11.10 Fitting the Flue Assembly with Access to the Terminal.
Prepare the flue duct assembly as described in Section 11.8. Apply the plastic tape to the air duct to be in contact with the external brickwork. From inside push the assembly through the wall. Align the flue turret and push fully onto the spigot on the appliance. Tighten the clamping ring. Refer to Fig.27.
Make good the internal wall face and the external brickwork or rendering.
11.11 Fitting of the Flue Assembly without access to the Terminal.
The rubber gasket kit is available as a spare part. NOTE: A larger diameter opening in the wall is required. Refer to Table 2.
15
Fig. 24. Extension duct
L
Fixing screw
Flue turret assembly
Appliance casing
Terminal assembly
Fixing screw
Ducts of equal length
Fig. 25. Flue duct length - side
L
Flue turret assembly
Terminal assembly
Flue turret assembly
Terminal assembly
Fig. 26. Flue duct length - rear
L
Page 16
Prepare the flue assembly as described in Section 11.8.
Fit the rubber sealing gasket centrally onto the terminal assembly and tighten the clamp. Refer to Fig. 28.
Apply the plastic tape to the air duct to be in contact with the external brickwork.
From inside push the assembly through the wall so that the gasket flange is against the outer face. Refer to Fig. 28. It may be necessary to adjust the legs of the flue centering ring. Align the flue turret and push fully onto the socket on the appliance. Tighten the clamping ring. Refer to Fig 27. Seal the gap around the duct at the inner wall face with the flexible seal provided and make good.
11.12 Flue Bends.
90° and 45° bends are available. A maximum of two bends may be used in addition to the first bend on the flue turret. A 90° bend is equivalent to 750mm of straight duct. A 45° bend is equivalent to 375mm of straight duct.
A maximum flue assembly of 3250mm for natural gas and 1750mm for LPG is possible with 1 X 90° bend and 2500mm natural gas and 1000mm for LPG with 2 X 90° bends. Measure the lengths X,Y and Z. Refer to Fig.29. The maximum value of X using the turret assembly only is 506mm. Reduce the ducts to the appropriate length eg. X = 406mm, cut 100mm from the air duct and 120mm (to cover the entry into the 45° or 90° elbow) from the flue duct. Refer to Fig.30.
NOTE: The flue system ducts between the elbows, dimension Y, requires the socketed ends (of the first extension if two or more are used) to be removed and the air and flue tubes to be cut to the same length. Cut the ducts to a length Y – 162mm. Refer to Fig.29. The final section, dimension Z, of the flue system must include a section of plain duct assembly eg. an extension assembly with the sockets removed. Reduce the final section, including the terminal assembly, by the appropriate amount eg: Air duct Z - 81mm and the flue duct Z – 51mm. Refer to Fig.29.
If Z is less than 425mm it will be necessary to cut the air and flue ducts of the extension to a plain length of 100mm and reduce the length of the terminal assembly eg. Z=350mm - remove 75mm from the terminal assembly.
If Z is between 425 - 725mm it is not necessary to cut the terminal assembly or use a second extension duct as the length can be set telescopically.
16
Fig. 27 . Flue Turret Fixing
1
2
3
1. Flue turret assembly
2. Clamp
3. Appliance
Fig. 28 . Terminal assembly for internal
fitting of the flue.
Flue centering ring
Flue Terminal
Rubber sealing gasket
Clamping ring
Flue terminal
Air duct
Flue duct
Rubber sealing gasket
Fixing clamp
Fig. 29. Flue bends
X
Z
Y
Y-162
Plain tube
Page 17
If Z is greater than 725mm then two extension duct assemblies will be required, the first assembly being cut to length as plain tubes.
If more than two extension ducts are needed in any section to achieve the required length then the final section of the assembly must not be less than 275mm without cutting the terminal assembly. NOTE: The flue duct of the final extension must be 30mm longer than the air duct.
Each section must be connected to the previous section of the flue bend by fixing the flue ducts together and then similarly fixing the air ducts which engage the elbows.
Fit the assembly as described in Section 11.9, 11.10 as appropriate. Make good the internal and external brickwork or rendering.
11.13 Vertical Adapter for Horizontal Flues
An adapter is available for an initial short section of vertical flue. Refer to Fig. 31. Measure and cut the flue as described in Section 11.11. The first, vertical, section (equivalent to dimension X) is measured from the top of the boiler casing. Cut the vertical section of the extension duct to 167mm less than the measured distance. Do not remove the socketed ends. The minimum measured distance is 167mm. Seal the air duct to the spigot using silicone sealant.
11.14 Completion of the Installation
Check that all the gas and water connections on the manifold have been tightened. Undo the two screws and remove the connections cover panel. Refer to Fig 32.
Connect the mains supply lead to the appliance and secure in the cable clamp. Make sure that the lead is isolated before connection. Refer to Section 10. Check that there is sufficient loose lead to allow the release of the facia panel assembly and that the earth lead of the mains supply is longer than the live and neutral leads. Fit the facia-mounted clock or programmer. Full instructions are sent with the control. Refer to Fig 33 and 34. Connect any external controls ensuring that the leads pass through the appropriate cable clamp. Refer to Section 10 and Fig 35 and 36. Test for gas soundness as described in BS6891. If the appliance is not to be commissioned immediately, replace the connection cover panel and the cabinet. Check that the gas and electricity services have been turned off.
17
120mm
100mm
Fig. 30 - Elbow to Flue Turret
Assembly.
Fig. 31 Vertical Adapter.
Flue Duct
Air Duct
Adapter
Flue Spigot
Flue Turret
Bend
Fig. 32. Facia connections cover
Fig. 33. Programmer connection
1. Facia (gently pull forward to un-clip and remove)
2. Control panel (boiler outer casing in place)
3. Programmer cover (un-clip to remove. See Fig. 34)
4. Programmer location in detail
5. Programmer connections (See Fig. 34)
6. Programmer connector plug
7. Programmer
2
2
1
1. Controls connector cover
2. Controls connector cover fixing screws (2)
1
*5mm
*When connecting to an elbow the flue duct must be
5mm longer than the air duct.
2
3
5
6
4
7
Page 18
18
Fig. 34. Programmer cover
Fig. 35. Facia connections
Fig 36 - Mains Voltage External Controls
Connections
230 V room thermostat and Programmer Connections
Neutral
Live
Neutral
Live
Switched Live
Motor
1
2
3
1. Programmer connections
2. Boiler outer casing
3. Cover panel
3
4
5
15
ST2
6
Series
connection
point
7
8
9
8
10
11
12
13
14
2
2
1
1. Controls connector cover
2. Controls connector cover fixing screws (2)
3. Facia control panel
4. Earth connection (tags)
5. Earth connection (screws)
6. Cable clamp
7. Fuse F1 2A (slow)
8. Cable clamp
9. ST15 Pump
10. ST1 Fan
11. Fuse F2 1.25A (slow)
12. Code plug
13. Commissioning switch
(gas valve mode switch)
14. Internal controls connectors
15. Mains and external controls connectors
(230 Volt)
ST2
Remove Link
230 V Room Thermostat Connections
Ns Ls LR
ST2
Neutral
Live
Switched Live
Remove Link
spare
Neutral
ST2
Remove Link
Live
Switched Live
Motor
230 V Programmer Connections
Ns LsNLNsLsL
R
spare
Ns LsNL
Ns Ls L
R
spare
Ns LsNL
Page 19
Water Treatment: For optimum performance after installation, this boiler and its associated central heating system should be flushed in accordance with the guidelines given in BS7593: 1992 – Treatment of water in domestic hot water heating systems. Full instructions are supplied with proprietary cleansers sold for this purpose. If an inhibitor is to be used after flushing, it should be used in accordance with the manufacturers instructions. Remove all system cleanser before adding any inhibitor. Suitable flushing agents and inhibitors are available from Betz Dearborn on 0151 4209563 or Fernox on 01799 550811.
12.1 System Set up
Remove the cabinet by pulling off the clip-on facia cover. Unscrew the two fixing screws, release the sides and lift from the top location. Check that the electrical supply and the gas supply to the appliance are turned off and that all the water connections throughout the system are tight. Open the system valves at the appliance. Refer to Fig 17. Open all the radiator valves. Remove the automatic air vent cap. Refer to Fig 37.
Fill the system through an external WRAS approved filling loop or Worcester Filling Link and Key optional extra, Part N
o
: 7 716 192 281. Refer to Section 7, Sealed System. Vent each radiator in turn. The automatic air vent, cap removed, will vent the appliance. Refer to Fig 37. It is very imortant that the appliance and system are fully vented and that all air pockets are removed. Remove the cap from the pump and turn the shaft about half a turn. Replace the cap. Refer to Fig 38.
Check that the pressure relief valve operates by turning the knob anti-clockwise until it releases. Lower the facia to gain access to the relief valve. Refer to Fig 20. Water should be expelled from the discharge pipe. Refer also to Fig 54.
The appliance [as despatched] can accommodate a system volume of 100 litres. Refer to BS7074 Part 1, BS5449 and Table 8. If the system volume is greater then an extra vessel must be fitted as close as possible to the appliance central heating return connection and pressurised to the same figure as the integral vessel.
12.2 Set the Expansion Vessel Pressure
The charge pressure of the expansion vessel as dispatched is
0.5bar, which is equivalent to a static head of 5m. The charge pressure must not be less than the static head at the point of connection. A Schraeder type valve is fitted to the
expansion vessel to allow the charge pressure to be increased if necessary. Refer to Fig 37. The expansion vessel must be charged to 0.35bar less than the initial system design pressure.
Note: 1bar = 10.2m of water.
12.3 Set the System Pressure
Fill the system until the pressure gauge is at 2.5bar and check for leaks. Release water from the system using the relief valve test knob until the required system pressure is obtained, upto a maximum of 1.5bar. Set the pointer on the pressure gauge to record the set system pressure. If the pressure indicated on the gauge is greater than 2.65bar when operating at the maximum central heating temperature then an extra expansion vessel must be fitted to the system as close as possible to the appliance central heating return connection.
12.4 Clock/Programmer
The controls fitted to the appliance should be set up at this stage. Refer to the instructions sent with the control.
12.5 Checking the Burner Pressure
Check that the gas and electricity supplies are turned off. Connect pressure gauges to the gas valve to measure the inlet and burner pressures. Refer to Fig 39. The appliance is fully set up in the factory and no adjustment should be necessary.
12. Commissioning The Appliance
19
Fig. 37. Automatic air vent and combustion
test point
Fig. 38. Pump venting.
Pump
Pump cap
Electrical connections cover
Fig. 39. Gas valve.
Automatic air vent
Flue connections
Expansion vessel charg­ing point
Expansion vessel
Wall mounting frame
Combustion products test point (front cap)
Max
2mm
Allen key
Min
3mm
Allen key
Gas valve sealing cap
Burner pressure test point
Electrical connections modulator (Blue:Blue)
Minimum / Maximum pressure adjuster ­Allen key* (see Note)
Inlet pressure test point
Main gas valve connections
*Note: Clockwise to increase and anti-clockwise to decrease the pressure.
Page 20
Unscrew and remove the control connector cover to display the mode switch. Refer to Fig 32. Check that all the radiator valves are open. Check that the system is fully vented, pressurised and set to the required pressure as indicated on the gauge. Set the temperature control knobs to maximum and the clock/programmer to operate continuously. Fully open a hot tap.
Set the mode switch to MAX. Refer to Fig 40. Turn on the gas and electricity supplies. A continuous spark will occur until the burner is alight and sensed by the control circuit. The burner will remain at its maximum domestic hot water pressure for 1 minute. Refer to Table 1. It should not be necessary for the gas valve to be adjusted. Note: The burner pressure is factory set and if, after checking that the dynamic (working) supply pressure is sufficient i.e. 19.0mb approx. [NG] or 36mbar approx. [LPG] at the gas valve inlet pressure test point, the correct pressure cannot be obtained then The Worcester Service Department should be contacted. If the appliance does not light then check that it is not in the ‘lock-out’ state by gently pressing the reset button for 5 seconds. Refer to Fig 41. Set the mode switch to Normal. Turn off the hot tap. The burner pressure will drop to the minimum setting and will ramp up to the maximum central heating pressure appropriate to the appliance and the gas. Refer to Table 1. Set the mode switch to MIN. The burner pressure will drop to the minimum burner pressure appropriate to the appliance and the gas for both the central heating and domestic hot water modes. Refer to Table 1. Test for gas soundness at the joint between the burner and the gas valve with leak detection fluid. Set the mode switch back to Normal. Turn the electricity supply off and then back on to reset the controls. Replace the controls connector panel.
12.6 Operation of the appliance
Domestic Hot Water Turn the central heating temperature control knob fully anti­clockwise. Open a hot tap near the appliance. The burner will light and go to the maximum burner pressure appropriate to the appliance and the gas. Refer to Table 1. Gradually close the tap and check that the burner pressure falls. Fully open the tap and check that the pressure rises. Close the tap and check that the burner goes out. The fan and pump may continue running until the appliance has cooled to a pre-set temperature.
12.7 Central Heating
Check that all the radiator valves are open. Check that the system is fully vented, pressurised and set to the required pressure as indicated on the gauge. Check that the clock/programmer is set to operate continuously. Set the room thermostat and the central heating temperature control to maximum. The burner will light and the appliance will modulate its output from minimum to maximum over a period of about two minutes. Check that all the radiators are heating up evenly. Shut down all but one of the radiators and observe the burner pressure fall. Open all the radiators and check that the burner pressure rises.
Balance the system to give the required temperature differential. Refer to Table 3.
Set the room thermostat to minimum and check that the burner goes out. Reset the room thermostat to maximum and the burner will re­light and follow the normal operating procedure.
12.8 Check flame failure device
Turn off the gas service cock. The burner will go out but sparking from the electrode will continue for 10 seconds when the appliance will ‘lock-out’. After 60 seconds carefully open the gas service cock, press the reset button and observe the burner re­light and follow the normal sequence of operation. Refer to Fig 17 and 41. Turn off the gas service cock and the electricity supply to the appliance.
Drain the system while the appliance is hot.
Refill, vent and re-pressurise the system as described in Section
12.1 preceding, adding, if necessary, a suitable proprietary inhibitor. Further information is available from Betz Dearborn on 0151 4209563 or Fernox on 01799 550811.
12.9 Domestic Hot Water and Central Heating
Set all controls to maximum. Turn on the electricity supply to the appliance and open the gas service cock at the appliance. The burner will light and heat will pass into the system. Turn on a hot tap and check that hot water is soon discharged from the tap. Close the tap and the burner will go off. The appliance will then return to the central heating mode and automatically balance with the system requirements.
12.10 Completion of Commissioning
Turn off the appliance and disconnect the pressure gauge and tighten the test point screw. Restart the appliance and check for gas soundness around the test point screw. Refit the cabinet. If the appliance is to be passed over to the user immediately then set the controls to the users requirements. If the appliance is to be left inoperative in frosty conditions then set the programmer, if fitted, to off. Do not turn the electricity or gas supplies off. The appliance will operate under the control of the integral frost protection facility. If there is any possibility of the appliance being left totally unused in freezing conditions then switch off the gas and electricity and drain the appliance and the system. The appliance must be fully re-commissioned when it is returned to service. The venting of the appliance is very important.
20
Fig.40. Mode adjustment
Betrieb
Max
S4
Min
Page 21
Hand over the User Booklet and the completed Benchmark Checklist. Explain how to operate the appliance safely and efficiently. Tell the user what to do if the appliance is not to be used in very cold conditions. Tell the user what to do if the system pressure falls. Explain that regular servicing will maintain the safe and efficient operation and extend the life of the appliance. WHS or their agent can offer a comprehensive maintenance contract. Tell the user that any work on the appliance must only be carried-out by a competent, registered, person (CORGI in GB).
14.1
To ensure continued efficient operation of the appliance it must be checked at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but once per year should generally be adequate. The extent of the service required by the appliance is determined by the operating condition of the appliance when tested by fully qualified engineers. Any service work must be carried out by competent registered engineers (CORGI in GB).
14.2 Inspection
Check that the terminal and the terminal guard, if fitted, are clear and undamaged. If the appliance is in a compartment or cupboard check that the specified service space around the appliance is clear. Refer to Table 8. Check all the joints and connections in the system and remake any that show signs of leakage. Refill and re-pressurise as described in Section 12-Commissioning. Operate the appliance and take note of any irregularities. Refer to Section 18-Fault Finding for rectification procedures. If the combustion performance is to be checked: Remove the cap from the sample point on the top of the appliance. Refer to Fig 37. Connect an approved sampling meter. With the appliance at maximum rate and stable in the DHW mode expect readings of:
24kW NG CO
2 5.3—6.2% CO 0.002—0.010%
LPG CO
2 6.4—7.4% CO 0.004—0.010%
28kW NG CO
2 5.6—6.4% CO 0.006—0.010%
LPG CO
2 6.3—7.3% CO 0.003—0.010%
NB For flues greater than 725mm without a restrictor the CO
2
may be up to 0.5% lower.
These figures cover all flue conditions. Refit the cap after the test. Disconnect the electrical supply at the mains and turn off the
gas supply at the gas service cock on the appliance before starting any service procedures. Always test for gas soundness after the service has been completed.
14.3 Component Access
To service the appliance it may be necessary to remove some or all of the following parts to gain access to components which may need to be checked or replaced. Cabinet Pull off the clip-on facia cover. Unscrew the two
screws and release the sides. Lift up and away from the top locating pegs.
Facia Panel Unscrew the single screw, lift off and lower onto the
lower support lugs. Refer to Fig 42 & 43.
14. Inspection And Service
13. Handover
21
Fig. 42. Inner case and facia fixing
3
1. Inner casing cover
2. Cabinet fixing screws (4)
3. Inner casing cover fixing screws (2)
4. Inner casing cover fixing screws (2)
5. Facia control panel
6. Controls connector cover
7. Controls connector cover fixing screws (2)
8. Programmer (optional)
9. Facia control panel fixing screw
10. Top support lug (2)
11. Bottom support lug (2)
12. Sight glass
1
4
5
7 2
6
7
10
9 8
2
11
Fig. 41. Facia controls
1
2
3
1. Mains On/Off control 5. Optional programmer
2. CH temperature control 6. Lockout indicator lamp and
3. DHW temperature control reset button
4. System pressure gauge 7. Burner indicator lamp
4
6
5
7
Fig. 43. Facia in service position
12
Page 22
22
Fig. 44. Inner case components
1. Flue hood
2. Primary sensor
3. Heat exchanger
4. Combustion chamber assembly
5. Spark electrode assembly
6. Inner case cover fixing (bottom)
7. Burner assembly
8. Combustion chamber fixing screw
3
1
4
5
8
2
6
7
9
10
11
9. Inner case
10. Fan assembly
11. Inner case cover fixing (top)
12. Air pressure switch
13. Combustion sensing point
14. Fan harness
15. Main wiring harness
12
15
13
14
Page 23
Inner Case Cover Unscrew the four screws and remove. Refer to Fig 42. Combustion Chamber Unscrew the two screws at the top and
the two wing nut extended screws at the sides, pull forward and remove. Refer to Fig 44.
Fan Carefully pull off the electrical connections and the
tubes from the airflow-sensing device. Unscrew the four screws and remove the fan assembly. Refer to Fig 45.
Flue Hood Remove the fan. Unscrew the four screws and slide
out the hood. Refer to Fig 47.
Burner Remove the combustion chamber. Carefully pull-off
the connections to the spark electrodes. Pull off the connection to the flame sense electrode. Unscrew the support bracket. Release the union nut beneath the burner and carefully remove the burner. Refer to Fig 46.
14.4 Component Cleaning
Only use a non-metallic brush to clean components. Do not use a metal probe to clean the injectors. Clean the fan taking care not to block air flow detector. Clean the burner to ensure that the blades and injectors are clear. Clean the electrodes, replace if there is any sign of deterioration. Clean the heat exchanger. Cover the gas inlet tube and remove any deposits from the heat exchanger from the top and bottom. Carefully straighten any distorted fins on the heat exchanger. Check the combustion chamber insulation and replace if there is any sign of damage or deterioration. Refer to Section 15.5. Clean the controls in-situ using a non-metallic brush. Carefully refit any components removed in the reverse order. Check that all screws are tight and the connections properly remade with the appropriate gaskets/O-rings. Re-commission, as necessary, for correct operation to the users requirements. Refer to Section 12 Commissioning.
23
Fig. 45. Fan assembly
Fig. 47. Flue hood
Fig. 46. Burner assembly
1
2
3
1. Flue hood fixing screws (4)
2. Flue hood
3. Flue hood/Heat exchanger guide
1
2
3
4
1. Fan assembly
2. Fan assembly fixing screws (4)
3. Flue hood
4. Flue hood fixing screws (4)
5. Air flow detector
2
3
1
4
5
1. Burner assembly
2. Spark electrode assembly
3. Spark electrode assembly fixing screw
4. Flame sense elctrode
5. Flame sense elctrode fixing screw
5
Page 24
IMPORTANT: Turn off the gas supply and electrically isolate the appliance before replacing any components.
After the replacement of any components always check for gas soundness where relevant and carry out functional checks as described in Section 12-Commissioning. Any O-ring or gasket that appears damaged must be replaced. Complete gasket and O-ring packs are available for gas and water connections on the appliance.
Component Access
Refer to Section 14, Inspection and Servicing for access to components.
Draining the Appliance
Primary System: Turn off the heating flow and return valves at the appliance. Refer to Fig 17.
Open the drain tap a short tube is already connected to the drain point. Refer to Fig. 20. Close the drain tap when the flow from the appliance has stopped.
DHW Circuit: Turn off the mains cold water supply at the appliance. Refer to Fig 16. Open a hot tap below the level of the appliance to drain the domestic hot water from the appliance.
Important: A small quantity of water will remain in some components even after the appliance has been drained. Protect any electrical components when removing items from the water circuits.
Component Replacement
Refer to Fig 42 and 44 for an indication of the location of the various components. Replace any components removed from the appliance in the reverse order using new gaskets/O-rings/sealant/heat transfer paste where necessary. Always check that any electrical connections are correctly made and that all screws are tight. Remove casing and cover panels and lower the facia onto lower lugs, as necessary, to gain access to the components. Refer to Section 14, Inspection and Servicing.
15.1 Gas Valve
Unscrew the union connections above and below the gas valve and remove the assembly. Disconnect/unplug the electrical connections from the valve. Use new gaskets when replacing the valve. Refer to Fig 48. Set the Gas Valve: Connect a pressure gauge to the burner and inlet pressure test points on the valve. Refer to Fig 39. Switch on the gas and electricity supplies. Check for gas tightness at the gas valve inlet. Refer to Section 12.5 Commissioning for the method of checking/setting the pressures. Check for gas soundness at the gas valve outlet. Adjust the maximum and start pressure [minimum], as necessary, to obtain the required pressures. Switch off the appliance and disconnect the pressure gauge. and tighten the screw. Refer to Section 12.5 and Fig 39 for setting instructions. Check for gas soundness at the test point.
15. Replacement Of Parts
24
Fig. 48 . Lower casing - gas and water
controls.
1
9
8
7
6
5
4
3
2
1. Gas valve
2. Pump
3. Pressure guage
4. Relief valve
5. Manifold assembly
6. Control panel in lowered position
7. DHW sensor
8. DHW flow turbine
9. Control panel top support
10. Drain tap
11. Drain tube
Fig. 49. Spark electrode assembly
1
3
2
1. Spark electrode assembly
2. Fixing screw
3. Burner blade assembly (LH)
11
10
Page 25
15.2 Spark Electrode
Remove the inner casing cover and the combustion chamber. Carefully pull off the lead from the electrode. Unscrew the screw and remove the assembly. Refer to Fig 49. Ensure that the electrode is at the correct height above the burner blade. 6.5mm ±1mm.
15.3 Flame Sense Electrode
Remove the inner casing cover and the combustion chamber. Remove burner as in 15.4. Carefully pull off the leads from the electrode assembly. Unscrew the screw and remove the assembly. Refer to Fig 50. Ensure that the sense electrode is at the correct height above burner blade. 6.5mm ±1mm.
15.4 Burner
Remove the inner casing cover and the combustion chamber. Remove the spark electrode connections. Unscrew the two burner bracket fixing screws. Release the union connection beneath the burner and remove the burner from the appliance. Refer to Fig. 46. and 51. Do not omit the gasket when fitting the new burner.
25
Fig. 50. Flame sense electrode
1
3
2
1. Flame sense electrode
2. Fixing screw
3. Burner blade assembly (RH)
Fig. 51. Burner
1. Flame sense elctrode
2. Spark electrode assembly
3. Burner blade assembly (LH)
4. Burner manifold
5. Burner blade assembly location points
6. Burner blade assembly (RH)
7. Cross- lighting strip fixing screws (2)
6
2
3
1
4
7
5
5
8
9
10
10
13
12
11
8. Cross-lighting strip
9. Cross-lighting strip fixing holes (2)
10. Burner assembly
11. Burner support bracket
12. Burner fixing screw
13. Bracket fixing screws (2)
Page 26
15.5 Combustion Chamber Insulation, Front &Sides
Remove inner casing door and combustion chamber. Remove damaged insulation, replacement is the reverse of removal. See Fig 52.
Combustion Chamber Insulation, Rear
Remove heat exchanger as described in 15.21. Remove side panels first. Pull insulation forward and up to remove. Replacement is the reverse of removal. Refer to Fig 52.
15.6 Pressure Gauge
Remove the clip-on facia cover, cabinet and lower the facia panel onto the lower support lugs. Refer to Fig 43. Check that the appliance has been fully drained. Withdraw the clip and remove the pressure-sensing head. Refer to Fig 53. Unclip the gauge head from its mounting bracket and remove. Refer to Fig 53. Do not omit the washer from the pressure capillary when fitting the replacement gauge.
15.7 Relief Valve
Remove the clip-on facia cover, cabinet and lower the facia onto the lower support lugs. Check that the appliance has been fully drained. Unclip and pull-out the valve body. Refer to Fig 54
15.8 Flow Turbine
Drain the DHW circuit as described at the start of Section 15 preceding. Remove the clip on facia cover, cabinet and lower the facia panel onto the lower support lugs. Separate the in-line connector. Remove the two fixing clips and withdraw the turbine. Refer to Fig 48 and 55. Do not omit the gaskets when fitting the replacement turbine.
26
Fig. 53. Pressure Gauge head
Fig. 54. Relief valve boiler drain connection
Fig. 52. Combustion Chamber Insulation
Front and Sides.
2
3
1
1. Insulation panel-side
2. Insulation panel-front 3. Combustion chamber assembly
1
2
4
3
1. Pump
2. Pressure gauge capillary
3. Pressure gauge head
4. Mounting bracket
1
6
2
3
5
1. Pump
2. Boiler drain
3. Pressure gauge capillary
4. Boiler Drain ON/OFF
5. Relief valve
6. Relief valve drain connection (push fit)
Fig. 55. Water flow turbine.
2
2
1
1. Flow turbine
2. Flow turbine clips
3. Inlet
3. Outlet
4
3
4
Page 27
15.9 Inlet Water Filter
Remove the flow turbine as described in 15.8 preceding. Taking care, remove flow restrictor assembly from the flow turbine inlet. Refer to Fig 55 Carefully clean wire mesh by back flushing with water or replace assembly if necessary. Refer to Fig 56.
15.10 Control Board
Remove the clip-on facia cover, cabinet and the connections cover. Carefully disconnect all the electrical connections. Refer to Fig 35 and 43. Remove the facia panel and unscrew the four screws and remove the cover from the rear of the facia. Refer to Fig 57. Lift out the control board. Refer to Fig 57 Pull out and transfer the transformer to the new board. Re-commission the appliance to check and set the burner pressures. Refer to Section 12, Commissioning.
15.11 Transformer
Unscrew the four screws and remove the cover from the rear of the facia as described in 15.10 preceding. Refer to Fig 57. Pull out and transfer the transformer to the new board. Refer to Fig 57.
15.12 Clock/Programmer
Remove the facia by gently pulling it away from the boiler to release the clips. Remove the clock/programmer assembly by releasing the clip at the top of the clock/programmer and ease away from the control panel being careful not to pull on the connector lead. Unplug the connector at the control board. Refer to Fig 58. Comprehensive instructions are sent with the new control.
15.13 Fan
Remove the inner casing cover. Remove the fan as described in Section 14.3, Inspection and Servicing. Ensure that all the connections are correctly made to the new fan.
15.14 Air Flow Detector
Remove the fan as described in 15.13 preceding. Unscrew and withdraw, through the fan outlet, the airflow detector. Refer to Fig 45.
27
Fig. 57. Control board
Fig. 56.Inlet water filter and flow restrictor
1
2
3
4
5
1. Control panel 4. Transformer
2. Rear cover 5. Control board
3. Rear cover fixing screws (4)
Fig. 58. Programmer connection
1. Facia (gently pull forward to un-clip and remove)
2. Control panel (boiler outer casing in place)
3. Programmer cover (un-clip to remove. See Fig. 34)
4. Programmer location in detail
5. Programmer connections (See Fig. 34)
6. Programmer connector plug
7. Programmer
1
2
3
5
6
4
7
1
2
1. Flow restrictor
2. Inlet water filter
Page 28
15.15 Primary [ch] Sensor
Remove the clip-on facia cover, cabinet and inner casing cover. Carefully pull-off the connections. Release the clip and lift out the sensor. Refer to Fig 59 and 62. Do not omit the heat transfer paste when fitting the replacement sensor.
15.16 Overheat Thermostat
Remove the clip-on facia cover, cabinet and the inner casing cover. For the position of the overheat thermostat refer to Fig 62. Carefully pull-off the connections. Unscrew the two screws and remove the thermostat and fixing bracket. Refer to Fig 60. Apply a small quantity of heat transfer paste to the face of the replacement thermostat. Carefully position the thermostat so that the connections are away from the flue hood.
15.17 DHW Sensor
Remove the clip-on facia cover, cabinet and lower the facia onto the lower support lugs. Carefully pull off the connections. Unscrew the clip and remove the sensor. Apply a small quantity of heat transfer paste to the face of the replacement sensor. Refer to Fig 61.
15.18 Pump
Check that the primary circuit has been fully drained. Use a 4mm Allen key to release the four pump head fixing screws and remove the pump head. Refer to Fig 48. Disconnect and transfer the electrical connections to the new pump head. Take care not to scratch the mating surfaces.
15.19 Expansion Vessel
It will be necessary to remove the appliance from the wall to replace the expansion vessel. Refer to Fig 37. Alternatively the specified replacement can be fitted into the heating system return as close to the appliance as possible. Re-fill and pressurise the system as described in Section 13 Commissioning.
15.20 Auto Air Vent
Drain the primary circuit. Unscrew and remove the auto air vent. Do not omit the sealing washer when fitting the replacement air vent. Remove the cap. Refer to Fig 37.
15.21 Primary Heat Exchanger
Check that the appliance has been fully drained. Remove the temperature sensors as described in 15.15, 16 and 17 preceding. Remove the combustion chamber, fan and flue hood as described in Section 14.3, Inspection and Servicing and burner as described in 15.4. NOTE: The heat exchanger is unsupported when both the combustion chamber and flue hood are removed. Undo the four union connections and remove the heat exchanger. Do not omit the sealing washers when fitting the replacement heat exchanger. Refer to Fig 62.
28
Fig. 59. Primary (CH) sensor.
1. CH Sensor
2. Clip
2
1
Fig. 60. Overheat thermostat
1
2
3
1. Overheat thermostat
2. Fixing bracket
3. Overheat thermostat fixing screw
Fig. 61. DHW sensor
1
2
3
1. DHW sensor
2. DHW sensor fixing bracket and screw
3. DHW outlet pipe
Page 29
15.22 Air pressure Switch
The air pressure switch is held in position by a fixing bracket. In order to remove the switch: Gently move outwards the securing clips holding the switch to the bracket. Remove the air pressure tubes and wires from the switch. Push the replacement switch, with the tube connectors pointing forwards, into the bracket and then replace the wires and pres­sure tubes. If the fixing bracket needs replacing, remove the switch as described above then remove the two screws holding the bracket to the top of the appliance. Refer to Fig 63 and 64.
15.23 Sight Glass
Remove and replace the inner casing cover complete. Refer to Section 14.3, Inspection and Servicing. Refer to Fig 42.
29
Fig. 62. Primary heat exchanger
1
2
3
4
5
6
1. Heat exchanger
2. CH flow/return pipes
3. DHW inlet/outlet pipes
4. Seal
5. Overheat thermostat
6. Primary sensor
Fig. 64. Air flow pressure switch
1
2
3
4
5
1. Electrical connections
2. Air pressure switch
3. Screws
4. Air pressure switch fixing clip
5. Securing clip
6. Tube connectors
Fig. 63. Air flow pressure switch location
3
6
5
4
1. Air pressure switch
2. Fixing bracket
3. Air pressure switch fixing clip
1
4. Combustion sensing point location
5. Negative pressure tube (–)
6. Positive pressure tube (+)
2
6
+Ve
—Ve
Page 30
1 E88-141 Burner 24Si II NG RSF 1 8 716 101 900 0 2 E88-142 Burner 24Si II LPG RSF 1 8 716 102 396 0 3 E88-143 Burner 28Si II NG RSF 1 8 716 105 008 0 4 E88-144 Burner 28Si II LPG RSF 1 8 716 105 009 0 5 E88:450 Gas Valve NG Dungs BN771SL040 - 239675 1 8 716 102 673 0 6 E88:451 Gas Valve LPG Dungs BN771SL040 - 239676 1 8 716 102 868 0 7 E88-146 Air Pressure Switch 1 8 716 104 896 0 8 E88-169 E lectrode Set (Flame and Ignition) 1 8 716 101 901 0
9 E88-170 Overheat Stat 1 8 717 206 200 0 10 375-696 NTC/Thermistor DHW 1 8 716 142 302 0 11 E88-171 NTC/Thermistor CH 1 8 714 500 029 0 12 378-809 Air Vent Manual
1
/4BSP 1 8 716 140 516 0 13 299-363 Air Flow Sensor 1 8 716 141 000 0 14 E88-172 Heat Exchanger 24Si II 1 8 715 406 670 0 15 E88-173 Heat Exchanger 28Si II 1 8 715 406 814 0 16 E88-174 Insulation Pack 24Si II 1 8 716 101 877 0 17 E88-175 Insulation Pack 28Si II 1 8 761 105 010 0 18 E88-176 Pressure Gauge 1 8 716 142 398 0 19 E27-580 Pressure Relief Valve 1 8 716 156 764 0 20 E88-177 Pump 1 8 716 143 116 0 21 E27-587 Expansion Vessel 1 8 715 407 154 0 22 H02-152 Control Board 1 8 748 300 488 0 23 E88-179 Fan Assembly - 24Si II 1 8 716 104 814 0 24 E88-180 Fan Assembly - 28Si II 1 8 716 104 815 0 25 E88-181 Flow Sensor 1 8 716 146 164 0 26 E88-182 Seal-Door Extrusion 1 8 716 104 609 0 27 E88-183 Transformer 1 8 747 210 294 0 28 E88-184 Flow Regulator 24Si II 1 8 716 141 255 0 29 E88-185 Flow Regulator 28Si II 1 8 716 141 253 0 30 H02-155 Code Plug 24Si II RSF 1 8 714 421 166 0 31 H02-157 Code Plug 28Si II RSF 1 8 714 421 167 0
A001 Charging Link Assembly 1 7 716 192 281 A002 Installer Pre-Filling Kit 1 7 716 192 282 A004 Gas Conversion Kit NG to LPG 24Si II 1 7 716 192 288 A005 Gas Conversion Kit NG to LPG 28Si II 1 7 716 192 289 A006 Simplefit Telescopic Flue Kit - F105H500 1 7 716 191 068 A007 Vertical Flue Kit 1 7 716 191 079 A008 90° Flue Elbow - F106E90 1 7 716 191 013 A009 45° Flue Elbow (Pair) - F 106E45 2 7 716 191 014
A010 Vertical Flue Adaptor Kit 1 7 716 191 016 A011 Security Kit 1 7 716 192 246
A012 Mechanical Programmer 1 7 716 192 027 A013 Digital Programmer 1 7 716 192 028
Key G.C. No. Part Qty WHS No. Part No.
30
16. Short Parts List
Accessories and Kits
Page 31
31
1 - 4
5/6
7
8
11
9
10
12
13
14 -15
16 -17
18
8
21
22
25
20
23 - 24
26
28 - 29
30 - 31
27
19
Page 32
Room
thermostat
and/or mains
programmer
(or link) On
facia
programmer
(if fitted) On
CH control
knob On
32
17. Operational Flow Diagrams
MAIN SWITCH
ON
CENTRAL
HEATING
DEMAND
Pump on.
Fan ON/
ignition
sequence.
Burner Light
On.
Three minute
wait
Gas valve Off.
Burner light
off. (Pump still
On)
Over tempera-
ture shut­down if flow temperature
5°C above set
value
Fifteen second
minimum
burner
pressure then
ramp up
pressure over
next one
minute
Modulate gas
to maintain
flow
temperature
set by control
knob
(50-82°C)
DEMAND
END
Overrun function
(see overleaf)
CENTRAL HEATING FUNCTION
AND
AND
DOMESTIC HOT WATER FUNCTION
MAIN SWITCH
ON
Flow sensor
signal
(Tap open)
DOMESTIC
HOT WATER
DEMAND
(Priority over
CH demand)
Pump continue
4 seconds if
primary temp
above DHW
setting. Burner
to MAX.
Modulate gas
to maintain
delivered
water
temperature
set by control
knob
(40-60°C)
Is CH
interrupted?
DHW temp
drops to user
set point
Over
temperature
shut-down if
water
temperature
above 80°C
Primary
temperature
94°C
DEMAND
END
Overrun
function
(see overleaf)
YES
NO
Ignition
sequence and
burner to MAX
Gas valve off.
Primary
78°C
Gas valve off.
Pump on
Page 33
Commence normal
central heating mode
until temperature
reaches 20°C
33
Pump overrun
function active
for 3 minutes
OVERRUN FUNCTION
Run pump
END DHW
DEMAND
END CH
DEMAND
Pump runs
for
3 minutes
Pump on if
primary temp
above 80°
until temp
below 75°C
AUTOFROSTAT FUNCTION
Monitor
central
heating
sensor
Below
5°C
5°C
to
9°C
Above
9°C
No demand and primary temperature
below 8°C
Internal
"Autofrostat"
demand
Return to
normal off
state
Fan low speed
35 seconds
Fan low speed if
primary temp
above 80°C until
below 75°C.
Page 34
Note: This fault-finding information is for guidance only. Worcester, Bosch Group cannot be held responsible for costs incurred by persons
not deemed to be competent.
By flashing at various rates, the oval shaped facia light will indicate specific fault conditions. If this is used with other observations during a fault, then every normal fault can be identified.
To use the fault finding system, use the table below to select the failure condition during your fault. The most common causes are listed, then refer to the test in the following section. This fault finding system assumes that the appliance has been operating normally until the time of failure (ie not a first installation fault).
PRELIMINARY CHECKS
Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of the Service/Fault-Finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY, (b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH.
18. Fault Finding
34
(reset lockout by gently pressing reset button for 5 seconds)
FAULT LIST
OBSERVED FAULT COMMON CAUSES SEE TEST
No lights and no functions (with demand)
No CH function (DHW OK)
No mains Voltage supply. Fuse F1 or F2 blown. Transformer or connector failed. Board fault.
No link at ST2 Ls to Lr, or failed external control input to Lr.
Failed programmer. Board fault.
A
B
No DHW function (CH OK)
Flash once per second
Ignition lockout Overheat lockout Internal error
Flash 4 times per second
Flow sensor failure. DHW sensor (LED 4 flash/second). Board fault.
No gas or low gas pressure. Weak spark or spark not across elecrodes. Gas valve leaking or failed. Low water pressure or boiler dry. Pump fail. Primary sensor position. Flame sensor fail or connector. Overheat stat tripped or disconnected or faulty. Blocked burner. Blocked heat exchanger. Faulty harness. Board fault.
Code plug missing or failed. CH or DHW Sensor fault or out of position. Air pressure switch fault or condense in tubes. Fan fail or stiff. Blocked flue. Faulty harness. Board fault.
C
D
E
Flash 8 times per second
GV mode switch
Burner on with no demand
Water temperature too hot
Water temperature too cool
Gas Valve mode switch on min or max.
Autofroststat. Board fault.
Sensor off pipe.
Low gas pressure. Pot P1 not turned up. Stiff/sticking gas valve. Stiff/sticking flow sensor. Board fault.
F
G H
I
Page 35
35
Is there a 230V AC live
supply across
Terminal ST2 pins L
and N?
Switch off electrical
power.
Has fuse F1 blown?
Caused by mains 230V
parts external to the
control board ie (wiring
to or faults within)
pump, fan, transformer
or other external
controls connected to
ST2. Check all these
parts for malfunction.
Repair/replace part, replace fuse and run
boiler.
Note: tracks on board
may also be damaged.
Replace board if
necessary
Check electrical
supply to boiler.
Has fuse F2 blown?
TEST A
No
Yes
Yes
No
Likely to be caused by control board internal
fault or low voltage wiring (eg shorts to
chassis). Replace fuse
F2 and check wiring
or replace control
board.
Remove control board from facia
and separate transformer from
board. Measure resistance across
the two pairs of adjacent pins on
the transformer. Is any coil above
120 ohms?
Replace transformer.
Yes
Yes
No
Replace
control
board.
No
NOTE: It is normal for
there to be no facia
lights if the boiler is in
normal overtempera-
ture condition.
Continue this test if
this fault occurs when
the appliance is cold.
Is there a 230V AC live
supply across
Terminal ST2 pins Lr
and N?
TEST B
No
Yes
Yes
Replace
control
board.
NOTE: Lights will be
off and pump will run
if boiler is in 3min
anticycle condition.
With CH control knob
fully clockwise, if
there is still no CH
function, continue:
There is no heat
demand. Check room
thermostat or external
programmer (or link).
Is there a facia
mounted programmer
at connection ST5 at
right-hand end of
board?
No
No
Remove programmer
connector from edge
of board. Does the
boiler now ignite?
Correctly set or
replace programmer.
Yes
Page 36
36
Re-connect the 3-way connector and open a tap to run the turbine.
Is there between 1.5
and 4.5VDC across
the green and black
wires/terminals?
Is there continuity in
the main harness?
Disconnect the 3 way
in-line connector to
the turbine.
Is there 5VDC between
the two outer pins
(main harness side)?
Take care not to
damage the pins.
No No
Yes
Yes
Replace control
board.
Replace main
harness.
TEST C
Yes
Replace turbine.
No
Page 37
37
Is the boiler fully
water pressurised and
is all air vented?
Rectify fault.
No
No
Reset and restart the
boiler in CH mode.
Does the pump run?
Yes
Remove front panel.
Reset and restart the boiler. Can a flame be seen through the spy
glass?
Remove inner cover.
Reset and restart the
boiler. Does a spark
occur across the
electrodes?
Turn off boiler. Remove
the multiway
connector from board
position ST16.
Test resistance across
connector contact
pins 1 and 2 (green wires)
and 8 and 9
(brown wires).
Are both reading
below 100 ohms?
Replace gas valve.
Are the electrodes and
gap and connections
in good order?
Replace
control board.
Remove both
connectors from gas
valve.
Is there continuity
from these
to multiway
connector?
Repair or replace
harness.
Repair or replace
spark electrode
or HT leads
Is the gas supply
connected and at the
correct pressure?
Rectify gas supply
problem.
No
No No
No No
No
Yes
Yes
Yes
Yes
Yes
Yes
Replace control board.
If problem not solved
replace gas valve.
Yes
Replace or repair
pump.
Yes
TEST D
Test resistance of each
ignition cable.
Is it 2000-3000 ohms?
Yes
No
Replace (both) ignition
cables
Is there continuity
between pins 6 and 7?
(green wires to HL
stat)
Replace overheat stat
or wiring to it.
No
Page 38
38
Remove combustion
chamber cover.
Is the sense electrode
and lead in good
condition and is gap
correct?
Replace flame sensor
or wiring.
No
No
Remove multiway
connector from board
position ST16.
Is there continuity from pin 10 (green
wire) to flame sensor?
Yes
Yes
Yes
Relace control board.
NOTE: It is not
possible to reliably
check the cross-light
performance of the
burner, or the
efficiency of the
gas/water heat
exchanger.
If there is still a
problem, investigate
flue problems or
replace burner or
injector or heat
exchanger.
Does the flashing fault
signal occur at the
start of a demand?
If flashing occurs at
the end of a demand.
Gas valve leak is
detected.
Replace gas valve.
No
Yes
If flashing occurs during a
demand.
Pump could be partially
blocked.
Clean pump & flush system.
Re-fix sensor to pipe.
No
Turn off boiler. Remove inner casing cover and
inspect the primary
sensor (on heat
exchanger in front of
overheat thermostat).
Is it correctly fixed to
pipe?
Yes
Page 39
39
Remove multiway
connector from board
position ST16. Test
resistance across
contacts 15 and 16
(black & yellow wires).
Is it between 1 kOhm
and 30 kOhm?
Test resistance across
contacts 12 and 13
( red & black wires). Is
it between 1 kOhm
and 30 kOhm?
Is there continuity
from individual
contacts 15 and 16 to
DHW sensor?
Check or replace
DHW sensor.
Is there continuity
from individual
contacts 12 and 13 to
CH sensor?
Repair or replace
harness.
Repair or replace
harness.
Is the multiway
connector at board
position ST16 pushed
fully home on to the
board?
Push fully home
No
No
No
No
No
Yes
Yes
Yes
Check the DHW
sensor. Is it correctly
fitted onto the pipe
with heat conductive
paste between the
pipe and sensor?
Yes
No
Re-fix sensor onto pipe
Is the Code plug fitted
and
fully home?
Fit/push fully home
Yes
No
TEST E
Check or replace
CH sensor.
Test resistance across
contacts 13 and 14
(black & blue wires).
Is it open circuit?
Turn off electrical
supply.
Remove fan connector
from board position
ST1.
Test resistance across
contacts to black &
white cables.
Is it between 75 and
175 ohms?
Check/repair fan
harness or repalce fan.
Air pressure switch
is shorting.
Check tubes for
blockage or replace
switch.
No
No
Yes
Yes
Yes
Test resistance across
contacts to black &
red cables. Is it
between 20 and 60
ohms?
Yes
Yes
No
Page 40
40
Replace control board.
In the unlikely event of this not solving the problem replace code
plug.
Pressure switch has
opened during
operation.
Check flue for
blockage.
Also investigate sense
tubes and pressure
switch.
Replace fan connector
ST1.
Remove electrical
connectors from air
pressure switch and
reset/restart boiler.
Is there continuity
between C and NO
terminals (where wires
were fitted) when the
fan runs?
(Test within 30
seconds).
Pressure switch has
not closed. Are the silicon tubes in good condition and free of
condensation.
Replace air pressure
switch.
Note: In the unlikely
event of this not solving the problem inspect the pressure
pick-up (Venturi) in the
fan or fan may not be
running freely.
Inspect the flue. Is it
free of any
restrictions?
Rectify flue problem.
Does the burner ignite
(burner light on) and run for a short priod
before the fault
occurs?
Replace control board.
Repair cables or
replace main harness.
Replace tubes. If
condensation has
occurred, also replace
pressure switch and
check condition of
Venturi in the fan.
No
No
No
No
Yes
Yes
Yes
Yes
Turn to 'NORM'
position
The gas valve mode
switch (concealed by
the facia side panel)
is not set correctly
TEST F
Replace multiway
connector to position
ST16 (but not fan
connector at ST1) and
reset/restart the
boiler.
Is there mains 230V
across the right (L)
and left (N) tracks at
board position ST1?
NOTE: Take care not to
short L to N.
Yes
Remove multiway
connector from board
position ST16.
Is there continuity of
black & blue cables to
the air pressure
switch?
No
No
Yes
Yes
Page 41
41
Boiler is running in
“Autofrost stat” mode.
See Section 17.
Replace control board.
Note: A damp board
could cause this fault.
Is the boiler in a very
cold environment (less
than 5°C)?
TEST G
No
Yes
Is the CH limit potentiometer
(concealed behind
facia bottom panel)
set to maximum?
Does the problem occur in CH mode
only?
Water flow
temperature very low
(with all knobs set at
maximum).
TEST I
No
Yes
It is not possible to easily isolate the fault. The most likely causes are control board (fail),
heat exchanger
(blocked) or
gas valve (sticking).
Hot water
temperature always
too hot during a
demand (not
regulating).
TEST H
Hot water sensor
could be off or poorly
fixed to pipe.
Repair or replace.
Yes
Yes
No
Turbine sticking or
seized.
Replace the turbine.
Increase
potentiometer to
allow more gas in CH
mode.
No
Check flow sensor:
with boiler cool,
slowly open a HW tap.
Does the boiler ignite
with a flow of about
3 l/min?
(Check using a
measuring jug and
stop watch i.e 500ml
in 10 sec.
No
Replace gas valve or
check wiring.
Remove multiway
connector from board
position ST16. Is the
resistance across
contacts 4 and 5 (blue
wires) below 60
ohms?
Yes
Could be
domestic hot
and cold pipes
crossed.
Page 42
ONLY COMPONENTS SUPPLIED BY WORCESTER SHOULD BE USED. ONLY COMPETENT PERSONNEL SHOULD ATTEMPT THE CONVERSION. CONVERSION FROM NATURAL GAS TO LPG SHOULD NOT BE CARRIED OUT ON APPLIANCES INSTALLED IN A ROOM OR INTERNAL SPACE BELOW GROUND LEVEL
24kW 28kW
Conversion Kit NG to LPG 7 716 192 288 7 716 192 289
1. Ensure the gas service cock is turned OFF and the electrical supply is ISOLATED.
2. Refer to the Installation and Service Instructions Section14: Inspection and Servicing to remove the cabinet front panel and outer casing.
3. Follow the dismantling instructions to remove the burner. Refer to Section: 14.3 Inspection and Servicing.
4. Remove the burner blades as shown in 15.4.
5. Replace the burner manifold with a new one supplied in the kit.
6. Refit burner blades taking care to assure that the cross
lighting strip and blades are correctly fitted and aligned.
7. Remove the gas valve and replace with the gas valve supplied in the kit. Refer to the Installation and Servicing Instructions Section 15- Replacement of Parts. NOTE: Replace the fibre washer with one of those supplied in the kit.
8. Refit the burner assembly to the gas valve using the other fibre washer supplied in the kit.
9. Ensure that the sealing grommet around the burner manifold is correctly sealed to the boiler casing.
9. Remove plastic anti-tamper seal and plastic cap from the gas valve.
10. Turn on the gas and electricity supplies and follow the commissioning procedure to confirm gas soundness and correct boiler operation.
11. Check and adjust the setting pressures to the values in Table 1 and adjust if necessary. Refer to the Installation and Service Instructions Section 12.5 for the setting of the gas valve and refer to Fig 1.
Ensure that the joints on the gas valve to the burner and inlet are both checked for gas soundness.
12. Refit the plastic sealing cap to the gas valve modulating valve
and seal with a dab of paint or similar.
13. Turn off the boiler and when cool peel off the arrow from the
data plate on the combustion box front panel and re-stick against the gas type for which the boiler has been converted and adjusted.
13. Replace the boiler front panel.
The conversion is now complete.
42
19. Conversion Instructions
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
8.1 9.2 0.7 0.97
28 30.7 13.1 3.25
BOILER ADJUSTED FOR G31 (Propane)
8.1 9.2 2.8 0.38
28 30.7 34.5 1.25
Table 1. 28Si II
BURNER
PRESSURE
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
6.9 7.9 0.9 0.84
24 26.4 12.1 2..8
BOILER ADJUSTED FOR G31 (Propane)
6.9 7.9 3.1 0.32
24 26.4 35.0 1.08
Table 1. 24Si II
BURNER
PRESSURE
Natural Gas: Net Input = Gross Input x 0.901 LPG (Propane): Net Input = Gross Input x 0.922
NOTE: With longer flue lengths, not using a restrictor, the minimum burner pressure will rise, naturally due to the flue, to 1.1mbar on G20 appliances only.
Injector sizes and markings
G20 Natural gas G31LPG
24kW 1.07 mm 0.65 mm
(marked 107) (marked 65)
28kW 1.12 mm 0.69 mm
(marked 113) (marked 69)
Max
2mm
Allen key
Min
3mm
Allen key
Gas valve sealing cap
Burner pressure test point
Electrical connections modulator (Blue:Blue)
Minimum / Maximum pressure adjuster ­Allen key* (see Note)
Inlet pressure test point
Main gas valve connections
*Note: Clockwise to increase and anti-clockwise to decrease the pressure.
Gas valve bracket
Fig 1. Gas Valve
Page 43
BENCHMARK No.
COLLECTIVE MARK
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No. NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/ST AT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT W ATER CYLINDER T/STAT & PROGRAMMER/TIMER
HEA TING ZONE VAL VES FITTED NO T REQUIRED
HOT W ATER ZONE V ALVES FITTED NO T REQUIRED
THERMOSTATIC RADIA TOR VALV E S FITTED
AUT O M ATIC BYPASS TO SYSTEM FITTED NOT REQUIRED
COMBI BOILER
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURERS INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBIT O R USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
CENTRAL HEATING FLOW TE MPERATURE ¡C
CENTRAL HEATING RETURN T E MPERATURE ¡C
m3/hr
N/A
FOR COMBINATION BOILERS ONLY
HAS A W A TER SCALE REDUCER BEEN FITTED?
W H AT TYPE OF SCALE REDUCER HAS BEEN FITTED?
YES NO
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
COLD WATER INLET T E MPERATURE ¡C
HO T W ATER OUTLET TEMPERATURE ¡C
W ATER FLOW RATE
m
N/A
3
/hr
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INST ALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS? YES
FOR ALL INST ALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT W ATER SYSTEM COMPLIES WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A YES CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURERS LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
lts/min
COMMISSIONING ENGS NAME PRINT CORGI ID No.
SIGN DATE
Page 44
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below .
Service Provider. Before completing the appropriate Service Interval Record below , please ensure you have carried out the service
as described in the boiler manufacturer s instructions. Always use the manufacturer s specified spare part when replacing all controls
SERVICE 1
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SERVICE 2
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SIGNATURE
SERVICE 7
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
SIGNATURE
SERVICE 8
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
Page 45
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests
of continued improvement.
All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
PUBLICATION 8 716 114 750a (11/07)
This manual is to be used in conjunction with the variant part number of the bar code below:
Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW.
Telephone: 01905 754624. Fax: 01905 753130.
Technical Helpline 08705 266241.
Worcester, Bosch Group is a trading name of BBT Thermotechnology UK Limited.
www.worcester-bosch.co.uk
Bosch Group
Loading...