Conguration wizard
WRS-K
WOLF GMBH / POSTFACH 1380 / D-84048 MAINBURG / TEL. +49(0) 87 51 74- 0 / FAX +49(0)87 51 74- 16 00 / www.WOLF.eu
Part no.: 3062933_201707
Subject to technical modications
GB

2
3062933_201707
Contents
Contents ................................................................................................................... 2
Installation / commissioning / operating overview .................................................... 3
Post-conguration, air quality / CO
2
sensor .............................................................. 4
Post-conguration remote control............................................................................. 5
Post-conguration, LON / BacNet / ModBus / Ethernet / KNX interface .................. 6
Post-conguration, pressure control / ow rate control / cooling function ................ 7
New conguration controller ..................................................................................... 8
System conguration .............................................................................................. 12
Conguration for pressure or ow rate control ....................................................... 15
Notes ...................................................................................................................... 19

3
3062933_201707
1 Displaying and acknowledging active fault messages
2 Displaying the system operating data (set / actual values)
3 Access to the main menu
4 Forward scrolling within a menu and increasing values
5 Switching the system ON and OFF, selecting menu points, conrming inputs
6 Backwards scrolling within a menu and reducing values
1. Commissioning
- According to EN 50110-1, only qualied electricians may carry out the installation and commissioning of
the ventilation control unit and connected accessories.
- Observe all regulations stipulated by your local power supply utility and all VDE or local regulations.
- DIN VDE 0100 regulations regarding the installation of high voltage systems up to 1000 V.
- DIN VDE 0105-100 operation of electrical systems.
- Only original Wolf accessories may be used (electric heater bank, condensate pump, servomotors, etc.),
otherwise, Wolf cannot provide a warranty.
Installation / commissioning /
operating overview
1
2
3
4
5
6
Operating overview

4
3062933_201707
2. When retrotting an air quality sensor (mixed gas or VOC, CO2) follow the instructions below.
Post-conguration, air quality / CO2 sensor
Conguration Activation
Other
Air quality sensor
No
Using ↑ ↓ select "Air quality sensor"
and press Enter to activate re-
conguration.
Select "Yes" with and conrm with
Enter
Other
Air quality sensor
available? >Yes
U08 KLM-M/L
Type 0-10V
Version VOC
Use Enter to conrm the input port
"U8" and type "0-10 V"
Use to select the variant "VOC" or
"CO2"
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
button
Select 1234 with
and conrm with
Enter
wolf-heiztechnik.de
Contractor
Password: 1234
Continue with
Select "Heating contractor" with and
conrm with Enter
Main menus
Standard settings
Displays
Time functions
Contractor
DISPLAYSSELECTIONEsc BACK
Alarm management
Service
Other
Contractor - menus
DISPLAYSELECTIONEsc BACK
Select "Other" with and conrm with
Enter
DISPLAYSELECTIONEsc BACK
DISPLAYSAVEEsc BACK

5
3062933_201707
Post-conguration remote control
Backup mode
Night ventilation
Other
Contractor - menus
DISPLAYSELECTIONEsc BACK
Select "Other" with and conrm with
Enter
Select "Remote control" with and
conrm with
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? No
Select "Yes" with and conrm with
Enter
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? Yes
Switch power supply to control unit OFF
and ON again
The remote control is enabled
Conguration
Restart system
(mains OFF/ON)
System restart
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
button
Select 1234 with
and conrm with
Enter
wolf-heiztechnik.de
Contractor
Password: 1234
Continue with
3. Proceed as follows to re-congure a remote control
Select "Heating contractor" with and
conrm with Enter
Main menus
Displays
Time functions
Contractor
DISPLAYSSELECTIONEsc BACK

FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
button
Main menus
Standard settings
Displays
Time functions
Contractor
DISPLAY
SELECTION
Esc BACK
Select "Heating contractor" with and
conrm with Enter
Select 1234 with and conrm with
Enter
Contractor
Password: 1234
Continue with
wolf-heiztechnik.de
4. Proceed as follows for the re-conguration of a LON / BacNet / Modbus / Ethernet / KNX
interface.
Post-conguration, LON / BacNet /
Modbus / Ethernet / KNX interface
Conrm with
Other...
BMS protocol
>LON-Works
Transfer speed
>4800 (RS485/RS422)
BMS address: 001
VALUESAVEEsc CANCEL
Select required connection with
- No proto
- pCO Manager
- LON-Works
- Bac-Net
- Modbus Stave Standard
- Ethernet
- KNX
and conrm with Enter
Other...
Protocol type:
BacNet
VALUESAVEEsc CANCEL
BMS protocol has been set
Hold down
button until you jump to
the standard screen
Select "Other" with
and conrm with
Enter
Alarm management
Service
OtherNight ventilation
Limits
Contractor - menus
DISPLAYSELECTIONEsc BACK