Wolf CRL evo max Series, CRL-iD-9000, CRL-iD-4800, CRL-iD-6200, CRL-iH-1300 Installation And Maintenance Instructions Manual

...
Page 1
GB
Installation and maintenance instructions
COMFORT VENTILATION UNIT WITH THERMAL WHEEL HEAT EXCHANGER
CRL / CRL evo max (Translation of the original)
English | subject to modications!
3064361_201811
Page 2
Table of contents
Table of contents
1 General / Safety information ................................................................... 3
2 Standards, regulations / disposal ........................................................... 5
3 CRL-iD unit layout .................................................................................. 6
4 CRL-iD appliance versions ..................................................................... 8
5 CRL-iH unit layout .................................................................................. 9
5.1 CRL-iH evo max unit layout ...................................................................11
6 CRL-iH appliance versions ................................................................... 13
7 CRL-iDH unit layout .............................................................................. 14
8 CRL-iDH appliance versions ........................................................................16
9 CRL-A unit layout ................................................................................. 17
9.1 CRL-A evo max unit layout ................................................................... 19
10 CRL-A appliance versions .................................................................... 21
11 Delivery / Handling ............................................................................... 22
12 Unit splitting for handling purposes - CRL ............................................ 24
13 Assembly - CRL evo max ..................................................................... 29
14 Installation information for external units .............................................. 32
15 Siting .................................................................................................... 33
16 Electrical connection ............................................................................ 35
17 Commissioning .................................................................................... 37
18 Maintenance shutdown ........................................................................ 46
19 Hygiene checklist ................................................................................. 47
20 Maintenance ......................................................................................... 48
21 Notes .................................................................................................... 51
Page 3
1 General / Safety information
General information These installation and maintenance instructions only apply to WOLF CRL / CRL
evo max ventilation units. Authorised personnel should read these instructions
before any commissioning or maintenance work. Comply with the specications
in this document. Installation, commissioning and maintenance work must only be carried out by trained personnel.
These instructions should be considered an integral part of the unit supplied, and should always be easily accessible.
Failure to observe these installation and maintenance instructions voids any WOLF GmbH warranty.
Reference symbols The following reference symbols are used in these instructions. This
important information concerns personal and operational safety as well as operational reliability.
“Safety information" identies instructions that must be observed to the letter, to prevent risks and injuries to individuals and damage to the
appliance.
Danger through 'live' electrical components. Please note: Turn off the ON/OFF switch before removing the casing.
Never touch electrical components or contacts when the ON/OFF switch
is in the ON position. There is a danger of electrocution, resulting in a
risk to health or death.
The main terminals are 'live', even when the ON/OFF switch is in the OFF
position.
Note
Safety information In addition to installation and maintenance instructions, there are notes attached
"Please note" designates technical instructions which you must observe to prevent the unit malfunctioning or being damaged.
to the unit in the form of labels. These must also be observed.
Only qualied and trained personnel may be appointed for the installation,
commissioning, maintenance and operation of the unit.
Only qualied electricians are permitted to work on the electrical system.
VDE regulations [or local regulations] and those of your local power supply utility are applicable to electrical installation work. Only operate the unit within its output range, which is stated in the technical documentation supplied by WOLF. Only operate the appliance if it is in perfect technical condition. Any faults or damage that impact or might impact upon the safety or correct function of the
unit must be remedied immediately by qualied personnel.
Only replace faulty components and equipment with original WOLF spare parts.
Note
It may only be used for handling air. This air must not contain any harmful,
combustible, explosive, aggressive, corrosive or otherwise dangerous
substances, as these would be distributed throughout the duct system
or building, where they could cause a risk to the health of, or even kill the occupants, animals or plants living there.
33064361_201811
Page 4
1 General / safety information
In accordance with DIN 1886, tools are required to open the unit. Wait for the fan to reach standstill (2 minutes wait). When the doors are opened, negative pressure may draw in loose objects, which could destroy the fan or even cause a risk to life if items of clothing are drawn in.
Electrical connection Make the electrical connection in accordance with local regulations.
Once electrical connection work is complete, the installation must be subjected to a safety test in accordance with VDE 0701-0702 and VDE 0700 part 500, as otherwise there would be a risk of electric shock that could result in injury or death.
Before working on the unit, shut it down via the isolator.
Even when the unit has been shut down, voltage will still be present at terminals and connections of the EC fans. This means there is a risk of electric shock that could result in injury or death.
Do not touch the EC fans for ve minutes after disconnecting the power across
all poles.
Intended use Wolf CRL / CRL evo max ventilation units are designed to heat and lter normal
air. Max. Max. air intake temperature: +40 °C. The use of these units in wet rooms or rooms with explosive atmospheres is not permissible. Handling very dusty or aggressive media is not permissible.
Any onsite modication or improper use of the unit is not permissible and WOLF
GmbH accepts no liability for any damage caused as a result. Ventilation units intended for internal installation must be placed in rooms that meet the requirements of VDI 2050 (VDI 2050, Requirements for technical equipment rooms - Planning and execution).
Fire The unit does not present a direct risk of re.
The small numbers of seals tted inside the unit can burn away if subjected to external inuences. Wear respiratory equipment if you ght a re. The usual
extinguishing agents such as water, extinguishing foam or extinguishing powder
can be used to extinguish res. As there are only a small number of ammable seals, the level of pollutants that could be released in a re is minimal.
Warnings
Recommended temperatures The ventilation unit is designed for air intake temperatures between -20 °C
Other technical documents - Operating instructions WRS-K
Removal and disabling of safety and monitoring equipment is prohibited. The system must only be operated if it is in perfect technical condition. Ensure
that any faults or damage that may impact on safety are rectied immediately.
and +40 °C. For safety reasons, the room temperature in technical equipment rooms must not fall below 5 °C (risk of frost) or exceed 40 °C. The unit should be operated in room conditions of between 22 °C and 28 °C at approx. 55 % relative humidity.
- MicroMax 370W TWHE control unit operating instructions
- Wiring diagram
- Conguration assistant WRS-K
- Commissioning report / parameter list
Page 5
2 Standards, regulations / disposal
Standards and regulations - Machinery Directive 2006/42/EC
- Low Voltage Directive 2014/35/EU
- EMC Directive 2014/30/EU
- ErP Directive 2009/125/EC
- EN ISO 12100 Safety of machinery; general principles
- DIN EN ISO 13857: Safety of machinery; safety distances
- DIN EN 349 Safety of machinery; minimum
- DIN EN 953 Safety of machinery; Guards
- DIN EN 1886 Ventilation for buildings; central air-
- DIN ISO 1940-1 Mechanical vibration; balance quality
- VDMA 24167 Fans; safety requirements
- DIN EN 60204-1 Safety of machinery - Electrical
for design
clearances
handling units
requirements
equipment of machines
- DIN EN 60730 Automatic electrical controls
- DIN EN 61000 -6-2+3 Electromagnetic Compatibility
In addition, ÖVE regulations and the local building code apply to Austria.
The following standards and regulations apply to installation and operation:
- DIN EN 50106 (VDE 0700-500) Safety of electrical appliances; tests
- DIN VDE 0100 Regulations regarding the installation of high voltage systems up to 1000 V
- DIN EN 50110-1 (VDE 0105-1) Operation of electrical installations
- DIN VDE 0105-100 Operation of electrical systems; general stipulations
Disposal and recycling When the unit reaches the end of its service life, it must only be dismantled by
qualied personnel. Before starting to dismantle the unit, disconnect the power supply. Power cables must be removed by qualied electricians. Sort and dispose
of metal and plastic parts according to material types and in compliance with local regulations. Dispose of electrical and electronic components as electrical waste.
53064361_201811
Page 6
3 CRL-iD unit layout
CRL-iD Comfort thermal wheel heat exchanger ventilation unit for internal installation with vertical/
horizontal duct connection (example provided is CRL-iD-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air
11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional
for CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
Page 7
3 CRL-iD unit layout
1 3
L2*
128
122
2
1 Outdoor air 2 Exhaust air
4
L1
L2
3 Supply air
L1
TWHE with boost
damper
4 Extract air
Total
H
H
170
T
L
Type CRL-iD-1300 CRL-iD-2500 CRL-iD-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1315 1722 1722 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
mm Intl 596x307 Intl799x307 Intl1019x408
470 / 490*
Weight kg 266 / 266* 381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iD-4800 CRL-iD-6200 CRL-iD-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1722 1722 1925 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
mm intl 1222 x 510 intl 1527 x 612 intl 1934 x 714
590
(180+230+180)
715
(220+275+220)
845
(275+295+275)
Nominal flow rate m³/h 4800 at 450 Pa (ext.) 6200 at 680 Pa (ext.) 9000 at 1000 Pa (ext.)
73064361_201811
Page 8
4 CRL-iD appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1
1
1
1
1
For CRL-1300/-2500/-3500, these versions are available with a boost damper.
Page 9
5 CRL-iH unit layout
CRL-iH Comfort thermal wheel heat exchanger ventilation unit for internal installation with horizontal duct
connection (example provided is CRL-iH-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air
11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional
for CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
93064361_201811
Page 10
5 CRL-iH unit layout
L2*
4
2
1
3
H
122
Total
H
L1
L2
L1
170
T
L
TWHE with boost
1 Outdoor air 2 Exhaust air
3 Supply air 4 Extract air
damper
Type CRL-iH-1300 CRL-iH-2500 CRL-iH-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1309 1716 1716 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
470 / 490*
Weight kg
266 / 266*
381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iH-4800 CRL-iH-6200 CRL-iH-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1716 1716 1919 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
590
(180+230+180)
715
(220+275+220)
845
(275+295+275)
Nominal flow rate m³/h 4800 at 450Pa (ext.) 6200 at 680Pa (ext.) 9000 at 1000Pa (ext.)
Page 11
11
13
17
5.1 CRL-iH evo max unit layout
CRL-iH evo max Comfort thermal wheel heat exchanger ventilation unit for internal installation with
horizontal duct connection (example provided is CRL-iH-11000 evo max with boost damper)
4
5
6 7
8
9
3
10
2
12
1
1 Outdoor air damper with servomotor 2 Differential pressure switch for lter monitoring 3 Ventilation air damper with servomotor 4 EC fan, extract air 5 TWHE thermal wheel heat exchanger 6 Repair switch 7 Panel for onsite cable entry 8 Differential pressure switch for lter monitoring 9 control panel
18
16
10 Extract air lter 11 BMK programming unit 12 EC fan, supply air 13 Base frame 14 Test connector for ow rate calculation 15 Boost damper with servomotor (optional) 16 Control TWHE 17 Outdoor air lter 18 Filter pre-dryer incl. control cabinet (accessory)
15
14
113064361_201811
Page 12
5 CRL-iH evo max unit layout
H
1
1
4
H
H
Total
H
2
2
1 Outdoor air 2 Exhaust air
3
L1
L2
L3
3 Supply air 4 Extract air
250
L
T
Type CRL-iH-11000 evo max CRL-iH-13500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3 mm 712 712 Depth D (incl. locks) mm 1970 1970 Total height mm 2284 2894 Height H mm 2034 2644 Internal frame (optional) mm 250 250 Height H1 / H2 mm 1017 1322 Duct connection dimensions,
horizontal air routing
Weight of standard unit kg
mm Intl 1832x917 Intl 1832x1222
1370
(590+460+320)
1550
(660+490+400) Weight of base frame kg 60 90 Nominal flow rate m³/h 11000 at 1000 Pa (ext.) 13500 at 800Pa (ext.)
* with boost damper
Type CRL-iH-16500 evo max CRL-iH-19500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3
712 712
Depth D (incl. locks) mm 2275 2580 Total height mm 2894 2894 Height H mm 2644 2644
Internal frame (optional) mm 250 250 Height H1 / H2 mm 1322 1322
Duct connection dimensions, horizontal air routing
Weight of standard unit kg
mm Intl 2137x1222 Intl 2442x1222
1790
(710+630+450)
2020
(790+720+510) Weight of base frame kg 110 120 Nominal flow rate m³/h 16500 at 750 Pa (ext.) 19500 at 950 Pa (ext.)
* with boost damper
Page 13
6 CRL-iH appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1, 2
1, 2
1, 2
1, 2
1For CRL-iH-1300/-2500/-3500, these versions are available with a boost damper. 2CRL-IH evo max types are available in these versions
133064361_201811
Page 14
7 CRL-iDH unit layout
CRL-iDH Comfort thermal wheel heat exchanger ventilation unit energy efcient and comfortable
ventilation with vertical/horizontal duct connection (example provided is CRL-iDH-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air 11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional for
CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
Page 15
7 CRL-iDH unit layout
L1
L2
L1
1
L2*
128
3
H
H
H
2
4
Total
170
T
L
122
1 Outdoor air 2 Exhaust air
3 Supply air 4 Extract air
TWHE with boost
damper
Type CRL-iDH-1300 CRL-iDH-2500 CRL-iDH-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1315 1722 1722 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
mm Intl 596x307 Intl799x307 Intl1019x408
470 / 490*
Weight kg 266 / 266* 381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iDH-4800 CRL-iDH-6200 CRL-iDH-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1722 1722 1925 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
mm intl 1222 x 510 intl 1527 x 612 intl 1934 x 714
590
(180 + 230 + 180)
715
(220 + 275 + 220)
845
(275 + 295 + 275)
Nominal flow rate m³/h 4800 at 450 Pa (ext.) 6200 at 680 Pa (ext.) 9000 at 1000 Pa (ext.)
153064361_201811
Page 16
8 CRL-iDH appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1
1
1
1
Other versions available; see the WOLF sizing program.
1
For CRL-1300/-2500/-3500, these versions are available with a rapid heat-up damper.
Page 17
9 CRL-A unit layout
CRL-A Comfort thermal wheel heat exchanger ventilation unit for external installation (weather-resistant)
with horizontal duct connection (example provided is CRL-A-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 control panel 8 TWHE control unit 9 Compact lter, extract air
10 Differential pressure switch for lter monitoring
11 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory)
12 EC fan, supply air 13 Base frame 14 Boost damper with servomotor optional for
CRL-1300/-2500/-3500
15 TWHE thermal wheel heat exchanger 16 Compact lter, outdoor air 17 Connectors for DN 50 trap
173064361_201811
Page 18
9 CRL-A unit layout
T
1
4
Total
2
H
H
1
H
1
L
T
L
1
L
2
1
3
1 Outdoor air 2 Exhaust air 3 Supply air 4 Extract air
L
Type CRL-A-1300 CRL-A-2500 CRL-A-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D mm 712 915 1118 Total depth T1 mm 812 1015 1218 Total height mm 1457 1864 1864 Height H mm 1017 1424 1424 Base frame H1 mm 305 305 305 Duct connection dimensions,
horizontal air routing Weight kg Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
mm int. 612x409 Intl 815x612 Intl 1019x612
320 / 320*
445 /445* 530 / 550*
Type CRL-A-4800 CRL-A-6200 CRL-A-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D mm 1322 1626 2034 Total depth T1 mm 1422 1726 2134 Total height mm 1864 1864 2067 Height H mm 1424 1424 1627 Base frame H1 mm 305 305 305 Duct connection dimensions,
horizontal air routing Weight kg 660 800 960 Nominal flow rate m³/h 4800 at 450Pa (ext.) 6200 at 680Pa (ext.) 9000 at 1000Pa (ext.)
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
Page 19
9.1 CRL-A evo max unit layout
15
19
3
6
1
20
21
CRL-A evo max Comfort thermal wheel heat exchanger ventilation unit for external installation
(weather-resistant) with horizontal duct connection (example provided is CRL-A-11000 with boost damper)
7
5
4
2
8 9 10
11
12
13
14
1 Condensate pan 2 Intake hood with mist eliminator 3 Outdoor air damper with servomotor 4 Differential pressure switch for lter monitoring 5 Intake hood 6 Ventilation air damper with servomotor 7 EC fan, extract air 8 TWHE thermal wheel heat exchanger 9 Repair switch
10 Panel for onsite cable bushing
18
11 Differential pressure switch for lter monitoring 12 control panel 13 Extract air lter 14 EC fan, supply air 15 Base frame 16 Test connector for ow rate calculation 17 Boost damper with servomotor (optional) 18 TWHE control unit 19 Outdoor air lter 20 Filter pre-dryer incl. control cabinet (accessory) 21 Connectors for R 1
1/4
17
trap
16
193064361_201811
Page 20
9 CRL-A evo max unit layout
T
1
2
4
H
Total
3
1
300
L1
1 Outdoor air 2 Exhaust air
L2
3 Supply air 4 Extract air
L3
T L
Type CRL-A-11000 evo max CRL-A-13500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3 mm 712 712 Depth D mm 1932 1932 Depth T1 (incl. roof overhang) mm 2032 2032 H1 / H2 mm 1017 1322 Total height mm 2214 2824 Height H mm 2034 2644 Base frame height mm 180 180 Duct connection dimensions,
horizontal air routing
Weight of standard unit kg
mm Intl 1832x917 Intl 1832x1222
1520
(710+470+340)
1720
(810+510+400) Weight of base frame kg 100 100 Nominal flow rate m³/h 11000 at 1000 Pa (ext.) 13500 at 800 Pa (ext.)
* with boost damper
180
H
1
H
H
2
Type CRL-A-16500 evo max CRL-A-19500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3 mm 712 712 Depth D mm 2237 2542 Depth T1 (incl. roof overhang) mm 2337 2642 H1 / H2 mm 1322 1322 Total height mm 2824 2824 Height H mm 2644 2644 Base frame height mm 180 180 Duct connection dimensions,
horizontal air routing
Weight of standard unit kg
mm Intl 2137x1222 Intl 2442x1222
1990
(890+640+460)
2260
(990+750+520) Weight of base frame kg 110 120 Nominal flow rate m³/h 16500 at 750 Pa (ext.) 19500 at 950 Pa (ext.)
* with boost damper
Page 21
10 CRL-A appliance versions
ZUL/ SUP
ABL/ ETA
AUL/ ODA
FOL/ EHA
-L1
ABL/ ETA
ZUL/ SUP
FOL/ EHA
AUL/ ODA
-L3
ABL/ ETA
ZUL/ SUP
FOL/ EHA
AUL/ ODA
-L5
ABL/ ETA
ZUL/ SUP
FOL/ EHA
AUL/ ODA
-L4
ZUL/ SUP
ABL/ ETA
AUL/ ODA
FOL/ EHA
FOL/ EHA
AUL/ ODA
ABL/ ETA
ZUL/ SUP
FOL/ EHA
AUL/ ODA
ABL/ ETA
ZUL/ SUP
FOL/ EHA
AUL/ ODA
ABL/ ETA
ZUL/ SUP
-R1
-R3
-R5
-R4
Access side in supply air direction, left Access side in supply air direction, right
1, 2 1, 2
3 3
1
For CRL-A-1300/-2500/-3500, these versions are available with a boost damper.
2
CRL-A evo max types are available in these versions
3
These versions are only available for CRL-A evo max units
213064361_201811
Page 22
11 Delivery / Handling
Delivered condition
Delivery CRL / CRL evo max ventilation units are supplied in packaging that protects them
from dirt and damage. Upon receipt of the goods, check the unit for possible transport damage. If there is any damage or even a suspicion of damage, the recipient must indicate this on the consignment note and have it countersigned by the haulier. The recipient of the goods must notify WOLF of the relevant facts without delay. Dispose of the transport packaging in accordance with local regulations.
Storage Only store the ventilation unit in dry rooms at an ambient temperature between
-25 °C and +55 °C. If it is stored for a long time, ensure that all apertures are sealed against air and water ingress.
General handling information
Units are supplied fully assembled and fully wired. Only transport units in their installation position. Never tilt the unit when transporting it through doorways or in narrow stairwells (lifts). Failure to observe these instructions can damage internal components irreparably.
Page 23
11 Delivery/Handling
Transport external units
Transport ropes with a minimum length equivalent to the eye bolt distance L must be used when transporting external CRL units with eye bolts. The same applies to the individual transport units of the CRL evo max units. External CRL evo max units may only be lifted as an entire unit with a lifting beam when pulling equally and vertically on all available eye bolts.
Lifting beam
90° 90°
max. 60°
L
Min. L
113,61 mm
Transport Internal units
The 3500, 4800, 6200 and 9000 versions of the CRL internal units can be split into three sections for easier handling. (Delivered as a transport unit) CRL evo max internal units are delivered in 3 transport units as standard. The procedure for connecting the units together is described in Item 13. Unit connectors, hexagon bolts and nuts are used to connect the parts together. Electric lines and control cables can be disconnected and connected again quite simply by means of plug-in connections in the control unit casing.
Control unit cover
Unit connector
233064361_201811
Page 24
12 Unit splitting for handling purposes - CRL
Disassembly of internal units
CRL-3500/-4800/-6200/-9000
Undo the unit connector bolts with an SW13 spanner to dismantle the unit.
Remove lters before dismantling in order to reach the rear unit connectors.
It may be necessary to remove the dampers in order to gain better access to the rear unit connectors in this area.
Remove damper
Unit connector
Remove lter
xing screws
Fig. 1 Fig. 2 Fig. 3
Assembling unit sections
Before dismantling the unit, disconnect the wiring harnesses from the control
unit.
- Remove control unit cover
- Undo cable plug-in connections (g. 1)
- Pull wiring harnesses into the slant of the thermal wheel heat exchanger
(g. 2)
- Pull wiring harnesses left and right into the external parts (g. 3)
Before assembling the individual unit sections, ensure that they are
pushed together completely.
The assembly of cube components can be simplied by using lashing straps.
Position unit sections next to each other and pull them together with lashing straps. Then screw the components together via the unit connectors. In order to ensure a secure threaded connection, screw the hexagon bolts manually into the captive nuts during assembly. Only then should they be tightened, for example, with an electric screwdriver. Subsequently, route the wiring harnesses back to the control unit and plug them
in (observe the cable designations)!
Page 25
12 Unit splitting for handling purposes - CRL
1 2
3 4
253064361_201811
Page 26
12 Unit splitting for handling purposes - CRL
1 2
3 4
Page 27
12 Unit splitting for handling purposes - CRL
1 2
3 4
273064361_201811
Page 28
12 Unit splitting for handling purposes - CRL
1 2
3 4
Page 29
13 Assembly - CRL evo max
A1
4x
293064361_201811
Page 30
13 Assembly - CRL evo max
B1
4x
B1
A1
4x
Page 31
13 Assembly - CRL evo max
313064361_201811
Page 32
14 Installation information for external units
Weatherproof units must not be used for any load-bearing building functions or as a replacement for any part of the roof
(VDI 3803 5.1 / DIN EN 13053 6.2).
A level, horizontal load-bearing surface is required for siting and installing the external units.
Base frames must be levelled horizontally (check with a spirit level).
To prevent the inspection doors from jamming, the entire base frame must sit on the foundation; point loads are not permissible.
To prevent structure-borne noise transmission from the CRL to the building, insert a permanently flexible intermediate layer between the foundation and the base frame. This intermediate layer should preferably take the form of insulation strips, fitted lengthwise below the base frame.
Insulation (if required)
Insulation against structure­borne noise
Insulation against structure-borne noise
Roof seal
The WOLF base frame and its integration into the roof membrane must be insulated onsite.
In the case of elevated positioning (CRL on onsite framework), the CRL must be secured against wind load.
Page 33
Minimum clearance between
outdoor air intake and exhaust air aperture to prevent an "air short circuit" (DIN 13779)
15 Siting
Outdoor
air
Exhaust
air
Outdoor
air
Exhaust
air
Extract
air
Supply
air
Extract
air
Supply
air
Supply air
Extract
air
Outdoor
air
Exhaust
air
Functional illustration of air inow:
CRL-iD
Exhaust air
Outdoor air
Functional illustration of air inow:
CRL-iH
Extract air
Supply air
Exhaust air
Outdoor air
Extract air
Supply air
333064361_201811
Page 34
15 Siting
Installation location CRL Indoor unit
Clearance for opening the inspection doors
Clearance for changing the thermal wheel heat exchanger
Clearance for air duct connections above the unit
* Unit with boost damper
Duct connections (ons-
ite)
The installation location must be level and have adequate load bearing capacity (see data sheets for individual unit weights). Level the unit horizontally (align using the adjustable feet). The installation site must be able to bear the load of the ventilation unit without vibrations on a long term
basis. Provide sufcient space at the front of the unit for maintenance work. Site the unit in a room that is free from the risk of frost!
CRL 1300 2500 3500 4800 6200 9000 11000 13500 16500 19500
mm 700 700
700 / 900*
700 800 900 900 900 900 900
mm 800 1000 1200 1400 1700 2100 2000 2000 2300 2600
mm 500 500 600 700 800 900 - - - -
The unit connectors are rectangular.
Round ducts can be connected directly to the connectors using an adaptor insulating collar (from square to round). Insulate the ducts in accordance with applicable regulations and industry standards.
Air duct connections are identied
with the following labels:
Hydraulic connection
Heating coil: Hydraulic
connection example
Adaptor insulating collar for round duct connection on internal unit with vertical and horizontal duct connection (accessory)
Outdoor air:
Extract air:
AUL / ODA
AUL / ODA
6801059 48/10
ABL /ETA
ABL /ETA
6801061 48/10
Exhaust air:
6801062 48/10
Supply air:
6801060 48/10
FOL/EHA
FOL/EHA
ZUL/SUP
ZUL/SUP
Admixing circuit
Benets: good control
characteristics, low risk of freezing
ϑ1 =ϑ2
Cooling coil: Hydraulic
connection example
Diverting circuit
Benets: constant ow
temperature in cooling coil,
good dehumidication even at
partial load
Note: Positioning valves close to the heat exchanger improves the control characteristics
Page 35
16 Electrical connection
Electrical connection The electrical connection may only be made by electricians in accordance with
local regulations.
Inlet for onsite cables
CRL
When connecting the control unit and control accessories, observe the instructions and wiring diagrams provided.
Once electrical connection work is complete, the installation must be subjected to a safety test in accordance with VDE 0701-0702 and VDE 0700 part 500, as otherwise there would be a risk of electric shock that could result in injury or death.
Before working on the unit, shut it down via the isolator.
The control panel has cable entries for connecting the onsite cables.
Entry for onsite cables
CRL evo max
Standard units without
Size
CRL-1300 3 x 1.5 mm² 16 A 5 x 1.5 mm² 10 A
CRL-2500 5 x 1.5 mm² 16 A 5 x 2.5 mm² 20 A
CRL-3500 5 x 2.5 mm² 20 A 5 x 6.0 mm² 35 A
CRL-4800 5 x 2.5 mm² 20 A - -
CRL-6200 5 x 4.0 mm². 25 A - -
CRL-9000 5 x 6.0 mm² 35 A - -
CRL-11000 5 x 4.0 mm². 25 A - -
CRL-13500 5 x 6.0 mm² 35 A - -
CRL-16500 5 x 6.0 mm² 35 A - -
CRL-19500 5 x 10 mm². 50 A - -
Integral Elec. heating coil
Power cable
Onsite fuse/
MCB
Standard units with
Integral Elec. heating coil
Power cable
Onsite fuse/
MCB
Even when the unit has been shut down, voltage will still be present at terminals and connections of the EC fans. This means there is a risk of electric shock that could result in injury or death.
Do not touch the EC fans for ve minutes after disconnecting the power across
all poles.
Use a rubber mat if working on the unit when it is electrically charged. Only use cables that meet local wiring regulations with regard to voltage, current,
insulation material, load etc. Always t an earth conductor.
RCDs
Only AC/DC-sensitive fault current safety devices, type B, with 300 mA are
permissible. There is no personal safety protection if the unit is operated with RCDs.
Regularly check the perfect function of all electrical equipment.
Observe the specied electrical fuse/MCB protection ratings. Any damage or loss resulting from technical modications to WOLF control
units is excluded from our warranty.
353064361_201811
Page 36
16 Electrical connection
Size Rated voltage
CRL-1300
CRL-2500
CRL-3500
CRL-4800
CRL-6200
CRL-9000
CRL-11000
CRL-13500
1 x 230V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
max. Fan power
consumption
1.0kW 4.6A 3080 rpm IP55 / Iso F
2.1kW 3.2A 3400 rpm IP55 / Iso F
5.0kW 8.0A 2970 rpm IP 54 / Iso F
3.4kW 5.2A 2600 rpm IP 54 / Iso F
6.0kW 9.2A 2550 rpm IP 54 / Iso F
11.0kW 17A 2200 rpm IP 54 / Iso F
11.4kW 18A 2250 rpm IP 54 / Iso F
14.4kW 23.2A 2260 rpm IP 54 / Iso F
max. Current
consumption
fans
Fan speed
IP rating /
protection class
CRL-16500
CRL-19500
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
13.8kW 21.2A 1910 rpm IP 54 / Iso F
21.6kW 34.4A 2130 rpm IP 54 / Iso F
Page 37
17 Commissioning
Commissioning regulations
Commissioning and maintenance work must only be carried out by trained personnel.
Only work on the unit with it being at zero volt.
According to EN 50110-1, only qualied electricians may carry out the installation
and commissioning of the ventilation control unit and connected accessories.
Observe all local EMC regulations and all VDE regulations.
DIN VDE 0100 regulations regarding the installation of high voltage systems up to 1000 V
DIN VDE 0105-100 Operation of electrical systems
Only original WOLF accessories may be used (electric coils, servomotors, etc.), otherwise WOLF cannot accept any liability.
In addition, ÖVE regulations and the local building code apply to Austria.
Before commissioning, check whether the operating data on the type plate is
adhered to.
The unit must not be operated before all necessary safety equipment has been
tted and connected. Intake and discharge apertures must be connected to
ensure contact protection.
The unit must be level and safely secured.
Commissioning Procedure
Commissioning must be carried out by authorised personnel (WOLF service).
Record the date of commissioning, e.g. in a log book.
In accordance with DIN 1886, tools are required to open the unit. Wait for the fans to come to a complete standstill before opening the inspection doors. When opening the doors, negative pressure may draw in loose objects, which could damage the fan irreparably or even cause a risk to life if items of clothing are drawn in. Use tools to tightly seal the doors before commissioning (unit tightness).
Connect the power cable and accessories in accordance with the wiring diagram provided.
A high leakage current can be expected due to the EC motors. Ensure that a secure earth connection is in place before connecting the power supply and commencing commissioning.
If control voltage is present or a set speed is saved, the EC fans will restart automatically after power failure.
- Switch ON the unit isolator.
- Wait until the BMK programming unit initialises and switches to display
mode.
- Select the required operating mode at the BMK; the system will start with
the preset parameters.
- To modify functions and parameters, see the installation and operating instructions provided.
373064361_201811
Page 38
17 Commissioning
Where the system is not commissioned by WOLF, check all inputs and outputs for correct wiring and function.
- Frost protection function
- Fan rotational direction
- Outdoor air/extract air damper rotational direction
- Plausible sensor values (room sensor, supply air sensor, extract air sensor, outdoor air sensor)
- Check motor currents
- Motor protection (thermal cut-outs / thermistors)
- Air ow monitoring
- Filter monitor
- Actuator, heating / cooling
- Heating circuit pump / cooling circuit pump
- As well as all other system-specic functions
The WOLF warranty will be void if the function test is not carried out
correctly.
Fans
Use tools to tightly seal the doors before commissioning (unit tightness), otherwise there is a risk of motor overload.
Carry out air ow rate tests with the doors closed. Route test hose connections out of the unit (see ow rate calculation).
Note
Changes are made via the BMK programming unit (see relevant operating
instructions).
Filter pre-dryer (accessory) To prevent the electric heating coil from switching off, never operate the CRL
below its minimum air ow rate.
Follow the relevant safety regulations for electric heating coils. The electric heating coil must be protected from moisture and water.
The lter pre-dryer starts automatically at outside temperatures below 5 °C.
Type CRL 1300 2500 3500 4800 6200 9000
Recomm. Minimum air volume
m³/h 600 1200 1800 2400 3100 4500
Type CRL evo max 11000 13500 16500 19500
Recomm. Minimum air volume
m³/h 5500 6500 8000 9500
Page 39
17 Commissioning
Electric reheating coil (accessory) To prevent the electric heating coil from switching off, never operate the CRL
below its minimum air ow rate.
Follow the relevant safety regulations for electric heating coils. The electric heating coil must be protected from moisture and water.
Type CRL 1300 2500 3500
Recomm. Minimum air volume
Condensate pan Provide a trap for the condensate drain and route the condensate into the
sewerage system. Protect the condensate drain from frost. Fill the trap with water.
m³/h 600 1200 1800
Trap The effective height of the trap h (mm) must exceed the maximum underpressure
or overpressure at the condensate connector (1mm WC = 10Pa).
h = 1.5 x p (mmWC) + 50 mm (min.)
p = Under- or overpressure in mmWC according to appliance design 50 mm (WC) = Reserve (imprecision in design, evaporation)
1.5 = Additional Safety factor
The trap drain line must not be connected directly to the public sewage system, but rather must be able to run out freely. Vent longer drain lines to prevent condensate backing up in the line (provide additional vent in trap drain line).
h
393064361_201811
Page 40
17 Commissioning
Heat recovery function
with thermal wheel heat exchanger
Layout and function of the TWHE control unit
Rotor control unit
Rotor motor
A rotating cylinder mass (rotor material corrosion-resistant aluminium alloy,
wound in corrugated and smooth layers) absorbs heat from the extract air ow
and transfers it to the outdoor air. The rotor mass is sealed by a circumferential labyrinth seal. Output is controlled by varying the speed of the drive motor. Force is transmitted from the motor to the rotor by a circumferential V-belt. There is no need for frost protection, a defrosting device or air preheating.
The MicroMax 370W rotor control unit includes the following functions:
- Automatic interval mode
- Variable speed control
- Acceleration and deceleration ramp
- Motor brake on standstill
- Rotation monitor with rotation sensor
- Alarm relay
- Test switch
In principle, the thermal wheel heat exchanger is maintenance-free. The rotational direction of the TWHE has no effect on heat recovery. When the TWHE control unit is switched off, interval mode ensures further rotation
in order to prevent n soiling.
Function for mode
Quick heat-up (optional for CRL-1300/-2500/-3500 and CRL evo max units)
100 % of the extract air ows over the rapid heat-up damper and is routed directly
back into the room. In order to achieve the required set room temperature as quickly as possible, the air temperature is raised to a maximum via a reheating coil. In this operating mode, the ODA and EHA dampers are completely closed; the ETA fan and heat recovery (TWHE) are not operational. The SUP fan is running
and delivers the required ow rate.
When the set room temperature has been achieved, the unit switches back into standard control mode.
Page 41
17 Commissioning
Flow rate calculation
V = k Dp
in [m³/h] and Dp
V
w
in [Pa]
w
CRL-1300 effective pressure
The ow rate is calculated using the effective pressure method. This involves
comparing the static pressure upstream of the inlet nozzle with the static pressure in the inlet nozzle.
The ow rate can be calculated from the effective pressure Δp
w
(differential pressure of the two static pressures) using the following equation.
The doors must be closed to determine the correct ow rate. Guide the test
hoses over the test connectors towards the outside.
The fans used for the CRL-1300 have a k value of 76.
320.0
= 76 x √Dp
270.0
220.0
170.0
120.0
Effective pressure Δp [Pa]
70.0
V
w
20.0 450 550 650 750 850 950 1050 1150 1250 1350
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp [Pa] 43 62 85 111 140 173 209 249 293
[m³/h] 500 600 700 800 900 1000 1100 1200 1300
V
CRL-2500 effective pressure The fans used for the CRL-2500 have a k value of 77.
1110.0
1010.0
= 77 x √Dp
910.0
810.0
710.0
610.0
510.0
410.0
Effective pressure Δp [Pa]
310.0
210.0
110.0
850 1050 1250 1450 1650 1850 2050 2250 2450 2650
V
w
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp [Pa] 137 204 285 379 487 609 744 892 1054
[m³/h] 900 1100 1300 1500 1700 1900 2100 2300 2500
V
413064361_201811
Page 42
1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500 3700
2000 2500 3000 3500 4000 4500 5000
17 Commissioning
CRL-3500 effective pressure
Δp = effective pressure
(symbolic representation)
The fans used for the CRL-3500 have a k value of 121.
950.0
850.0
750.0
650.0
550.0
450.0
350.0
Effective pressure Δp [Pa]
250.0
150.0
V = 121 x √Dp
w
Flow rate [m³/h]
Δp [Pa] 197 247 301 361 427 498 574 656 744 837
[m³/h] 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
V
CRL-4800 effective pressure The fans used for the CRL-4800 have a k value of 148.
1160.0
1060.0
960.0
860.0
760.0
660.0
560.0
460.0
360.0
Effective pressure Δp [Pa]
260.0
160.0
V = 148 x √Dp
w
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp [Pa] 201 263 333 411 497 592 694 805 924 1052
[m³/h] 2100 2400 2700 3000 3800 3600 3900 4200 4500 4800
V
Page 43
17 Commissioning
CRL-6200 effective pressure The fans used for the CRL-6200 have a k value of 188.
1150.0
1050.0
950.0
850.0
750.0
650.0
550.0
450.0
Effective pressure Δp [Pa]
350.0
250.0
V = 188 x √Dp
3000 3500 4000 4500 5000 5500 6000 6500
w
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp [Pa] 290 347 409 476 548 625 707 795 887 985 1088
[m³/h] 3200 3500 3800 4100 4400 4700 5000 5300 5600 5900 6200
V
CRL-9000 effective pressure The fans used for the CRL-9000 have a k value of 240.
1500.0
1400.0
1300.0
1200.0
1100.0
1000.0
900.0
800.0
700.0
600.0
Effective pressure Δp [Pa]
500.0
400.0
300.0
200.0
3250 4500 5750 7000 8250 9500
V = 240 x √Dp
w
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp [Pa] 278 352 434 525 625 734 851 977 1111 1254 1406
[m³/h] 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000
V
433064361_201811
Page 44
17 Commissioning
CRL-11000 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
The fans used for the CRL-11000 have a k value of 281.
1600.0
1500.0
1400.0
1300.0
1200.0
1100.0
1000.0
900.0
800.0
700.0
600.0
Effective pressure Δp [Pa]
500.0
400.0
300.0
V = 281 x √Dp
5000 6000 7000 8000 9000 10000 11000 12000
w
Flow rate [m³/h]
Δp [Pa] 397 487 586 694 811 937 1072 1216 1370 1532
[m³/h] 5600 6200 6800 7400 8000 8600 9200 9800 10400 11000
V
CRL-13500 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
The fans used for the CRL-13500 have a k value of 197.
1200.0
1100.0
1000.0
900.0
800.0
700.0
600.0
500.0
Effective pressure Δp [Pa]
400.0
300.0
200.0 6000 7000 8000 9000 10000 11000 12000 13000 14000
V = (197 x √Dpw) x 2
Flow rate [m³/h]
Δp [Pa] 294 362 438 522 612 710 815 928 1047 1174
[m³/h] 6750 7500 8250 9000 9750 10500 11250 12000 12750 13500
V
Page 45
150.0
250.0
350.0
450.0
550.0
650.0
750.0
850.0
950.0
7000 8250 9500 10750 12000 13250 14500 15750 17000
17 Commissioning
CRL-16500 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
The fans used for the CRL-16500 have a k value of 281.
= (281 x √Dpw) x 2
V
Effective pressure Δp [Pa]
Flow rate [m³/h]
Δp [Pa] 178 229 286 349 419 495 577 666 761 862
[m³/h] 7500 8500 9500 10500 11500 12500 13500 14500 15500 16500
V
CRL-19500 evo max effective
pressure
Δp = effective pressure
(symbolic representation)
The fans used for the CRL-19500 have a k value of 252.
1600.0
1400.0
1200.0
1000.0
800.0
600.0
V = (252 x √Dpw) x 2
Effective pressure Δp [Pa]
400.0
200.0 8000 9500 11000 12500 14000 15500 17000 18500 20000
Flow rate [m³/h]
Δp [Pa] 268 355 455 567 691 828 977 1138 1311 1497
[m³/h] 8250 9500 10750 12000 13250 14500 15750 17000 18250 19500
V
Further settings for the BMK and accessories
Further settings for the BMK programming unit can be found in the operating
instructions for the WRS-K control unit. Accessories are installed in accordance with separate instruction manuals which are provided with the relevant accessories.
453064361_201811
Page 46
18 Maintenance shutdown
Decommissioning Before starting any maintenance work, switch OFF the isolator and safeguard
against unauthorised reconnection. If the isolator is switched back on unintentionally, maintenance staff or others in the vicinity could be at risk from rotating parts. Wait for the fans to come to a complete standstill before opening the doors (approx. 2 minutes). When the doors are opened, negative pressure may draw in loose objects, which could destroy the fan or even cause a risk to life.
Even when the unit has been shut down, voltage will still be present at terminals and connections of the EC fans. This means there is a risk of electric shock that could result in injury or death.
- Do not touch the EC fans for ve minutes after disconnecting the power
across all poles.
- Use a rubber mat if working on the unit when it is electrically charged.
3
1
2
0
I
4
min
2
Open inspection doors with quadrant key
6074238
Repair switch
Page 47
19 Hygiene checklist
Maintenance Regularly check that the ventilation unit is functioning correctly.
Replace the air lters in the unit at least once a year.
Wear a suitable dust mask when handling the air lters. Dispose of the air lters
in accordance with local regulations.
Hygiene checklist (extract from VDI 6022, sheet 1)
System commissioning: date__________________________
Activity Action
Hygiene inspection X
Outdoor air intakes
Check for contamination, damage and corrosion
Structural units / unit casing
Check for contamination, damage and corrosion on the air side
Check for condensation Clean X Check casing for contamination, damage
and corrosion
Air vents
Check air vents, integral perforated plates, wire mesh or sieves for contamination, damage and corrosion (spot check)
Spot check lter eece Replace X Spot check air vents with indoor air
induction and extract air intakes for deposits
Air lters
Check for impermissible contamination, damage (leaks) and odours
Longest lter replacement interval X
Air ducts
Check accessible air duct sections for damage
Check inner air duct surface for contamination, corrosion and condensation at two or three representative points
Silencer
Check silencers for contamination, damage and corrosion
Fan
Check for contamination, damage and corrosion
Heat exchanger (including heat recovery)
Visual inspection of air/air plate heat exchanger for contamination, damage and corrosion
Heating coil: Check for contamination, damage, corrosion and tightness
Check condensate pan for contamination, corrosion, damage and tightness
Check the function of the drain and trap Clean and repair X
if required
Clean and repair X
Clean and repair X
Clean and repair X
Clean or replace X
Clean X
Changing the affected lters Never operate the unit without lters!)
Repair X
Inspect the duct network at further points and decide whether cleaning is necessary (not only the visible areas)
Repair or replace; contact spotting if required
Clean and repair X
Visual inspection X Clean, remove if necessary (undo
spacer and clean out countercurrent heat exchanger)
Clean and repair X
Clean and repair X
1
month3 months6 months
X
12
months
X
X
X
months
24
Repairs
Only qualied personnel may remove faults or repair damage. Replace faulty
components only with original WOLF spare parts.
473064361_201811
Page 48
20 Maintenance
Fan motor unit Motor and bearing are maintenance-free.
If necessary, clean the impeller with a soapy solution.
Note
Electrical equipment - Regularly check the electrical equipment of the unit
Check that the test lead is seated rmly at the test connector on the inlet nozzle.
Loose seating can result in faulty measurements.
- Replace loose connections and faulty cables immediately
- Regularly check the earth conductor
Thermal wheel heat exchanger
(TWHE)
In normal operating conditions, the actuator and rotor bearing are maintenance­free.
Before starting any maintenance work, disconnect the power supply across
all poles and secure against reconnection, so that the persons charged with maintenance work cannot be exposed to any risk of crushing or abrasion injuries due to the rotor starting up suddenly if it is switched on unintentionally, the automatic cleaning run commences or the rotor restarts automatically after power failure.
Maintenance work (approx. every 3 months or more frequently if required)
- Check rotor cylinder mass for hygienic condition, damage, corrosion, contamination and foreign bodies, and clean if required.
Compressed air (max. pressure 5 bar) or, for stubborn contamination, a
pressure washer (water only; no chemical additives) may be used for cleaning the rotor cylinder mass.
When cleaning, ensure that the cleaning jet hits the cylinder mass at an angle
of 90°. Remove dirty water carefully.
- Check seals for hygienic condition, contamination and foreign bodies, and clean if required.
- Check drive belt for wear and tension. If necessary, have it adjusted or replaced by a contractor or the manufacturer.
- Check rotor for imbalance and lateral trueness, and balance or realign it if required.
- Check bearing for impermissible heating, vibration and bearing noise. If necessary, have it replaced by a contractor or the manufacturer.
Page 49
20 Maintenance
electric coil (accessories) Check and clean at regular intervals.
Cleaning the electric coils:
- Vacuum, taking care not to bend the heating coils
- Blast with compressed air, max. 1 bar
Note
Air dampers Check the dampers for ease of movement. Never lubricate the dampers.
If the cleaning pressure is too high, there is a risk of irreparable mechanical damage to the electric coils. The electric coils must be protected from moisture and water.
This could destroy the plastic used and compromise the damper function. To clean, wipe down with a soapy solution; otherwise maintenance-free.
Filter The lters are not renewable. They must be replaced when they are dirty, or
no later than after 12 months.
The lters can be removed from the unit once the inspection doors have been
opened (see spare parts).
The clamping levers must be opened (pulled) before pulling out the lters for
the CRL evo max units.
Never operate the CRL ventilation unit without lters!
493064361_201811
Page 50
20 Maintenance
Servomotors on the dampers The motors are maintenance-free.
At regular intervals, check that the connection from the servomotor to the
damper drive is rmly seated.
Condensate pan Regularly check the condensate pan for possible soiling and clean if required
(see checklist).
Trap Regularly check the DN 50 trap (accessory) for possible soiling and clean if
required (see checklist).
Rell the trap with water before returning into use.
h
Page 51
21 Notes
513064361_201811
Page 52
WOLF GmbH / Postfach 1380 / D-84048 Mainburg Tel. +49.0.87 51 74- 0 / Fax +49.0.87 51 74- 16 00 / www.WOLF.eu
Loading...