Wolf CGU-2-18, CGU-2-24, CGG-2-18, CGG-2-24, CGU-2 K-18 Installation And Maintenance Instructions Manual

...
Part no. 30 62 347 Subject to modications
03/09 GB
Wolf GmbH · Postfach 1380 · D-84048 mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztechnik.de
Installation and maintenance instructions
Wall mounted gas red combi boilers and wall mounted gas red boilers
CGU-2-18/24 CGG-2-18/24 CGU-2 K-18/24 CGG-2 K-18/24
Illustration:
Wall mounted gas red boiler with auxiliary equipment BM
2
3062347_0309
General information
Safety instructions / Standards and regulations ............. 3-5
Installation and commissioning
Dimensions .......................................................................6
Layout / Equipment code ............................................... 7-9
Positioning information / Installation dimensions ........10-11
Installation on nished walls /
Installation on unnished walls ........................................12
General boiler installation ................................................13
Electrical connection ................................................. 14-17
Fill / Vent the system. .......................................................18
Guidelines for commissioning ..........................................19
Control / Function / Commissioning ........................... 20-21
Setting and adjusting the boiler
Displaying / Modifying control parameters ................ 22-30
DHW connection versions / Resetting control unit ...........31
Setting the eBUS address for cascade mode ..................32
Commissioning gas connection .......................................33
Conversion to other gas types / Nozzle change ..............34
Setting the control unit after converting the gas type .......35
Checking nozzle pressure .......................................... 36-37
Resetting gas valve / Setting nozzle pressure .................38
Adjusting the ue lengths CGG-2(K) ................................39
Flue gas test CGU-2(K) CGG-2(K) .................................40
Limiting the maximum output ...........................................41
Selecting the pump stage / Bypass ............................ 42-43
Checking the ue gas monitoring CGU-2(K) ....................44
Notes on planning ventilation /
Flue gas system CGU-2(K) ........................................ 45-49
Commissioning report ......................................................50
Maintenance and additional information
Inspection and maintenance steps ..................................51
Service report ...................................................................52
Maintenance .............................................................. 53-57
Wiring diagram CGU-2(K) ................................................58
Wiring diagram CGG-2(K) ................................................59
Specication ............................................................... 60-61
Fault / Cause / Remedy ...................................................62
Resistance table ..............................................................63
Notes ................................................................................64
Keyword index ........................................................... 65-67
EC declaration of conformity ............................................68
Contents
3
3062347_0309
"Safety instructions" are instructions with which you must comply exactly, to prevent risks and injuries to individuals and material losses.
The following symbols and reference symbols
are used in this description. These important instructions concern personal safety, as well as
operational reliability.
"Note" indicates technical instructions
that you must observe to prevent material losses and boiler malfunctions.
Note
D a n g e r t h r o u g h ' l i v e ' e l e c t r i c al components. Please note: Switch OFF the ON / OFF
switch before removing the casing.
Never touch electrical components or contacts when the ON / OFF switch is in the ON position. This results in a risk of electrocution that poses a danger of injury or death.
The main supply terminals are 'live' even when the ON / OFF switch is in the OFF position.
Fig.: Terminal box: Danger from electric current
Fig.: Gas connection: Escaping gas may cause poisoning or the risk of explosion
Fig.: Ignition transformer, high voltage ignition electrode, combustion chamber Risk through 'live' electrical components, risk of burning through hot components
Fig.: Gas combination valve: Danger from electric current Escaping gas may cause poisoning or the risk of explosion
Balanced flue operated gas bo i l er s
must only be installed in a room that
complies with the appropriate ventilation requirements. Otherwise there is a risk of asphyxiation or poisoning. Read these installation and maintenance instructions
before installing the boiler. Also take the
technical guide into consideration.
Safety instructions / Standards and regulations
4
3062347_0309
Safety instructions / Standards and regulations
Please follow these safety instructions closely to prevent accidents and material losses.
Commissioning - Commissioning must only be carried out by the system installer or a
commissioning engineer designated by him. All actual values must be recorded in a commissioning/service report that should be kept with these instructions.
Safety regulations - Observe all national safety regulations and installation requirements.
- Installation, commissioning, inspection, maintenance and repairs must only be carried out by a competent person (heating engineer / installation contractor).
- Before working on the equipment / heating system, switch OFF the power supply (e.g. by removing a separate mains fuse or by means of a main electrical isolator) and safeguard against unauthorised reconnection.
- Disconnect the system by means of an appliance that isolates all non-earthed conductors simultaneously with at least 3 mm contact separation.
- It is not permitted to carry out repairs on parts that full a safety function.
- Use only original WOLF replacement parts or those that are equivalent and that have been approved by the manufacturer.
Instructing the system user
- The system installer must hand the operating instructions to the system user and instruct them in the operation of the system.
Only use propane compliant with local regulations, otherwise
faults may arise with the starting characteristics and operation
of the wall mounted gas red boiler; this in turn, may lead to boiler damage and risk of injury.
Poorly vented LPG tanks can lead to ignition problems. In such
cases, contact your local LPG supplier.
Note: Please read these instructions carefully before the installation
and keep them in a safe place. Please also note the technical information in the appendix.
Any damage or loss resulting from technical modications to
the control unit or to the control components are excluded from
our liability. Incorrect use can lead to a risk to life and limb or to a risk of
material losses.
Obtain the permission of your gas supply utility, the ue gas inspector
and the lower water authority [where appropriate] prior to the installation
of Wolf gas red boilers.
5
3062347_0309
Safety instructions / Standards and regulations
Standards and regulations
Category: II2ELL3P<DE> and II2H3P<AT> NOx class: 5 Efciency: *** star rating according to 92/42/CEE) for balanced ue operation Flue types: CGG-2: C12x, C32x, C42x, C52, B32 CGU-2: B11BS Operating mode: open / balanced ue To be connected to: chimney, ue chimney / balanced ue system
- Obtain the permission of your mains gas supplier and all relevant authorities prior to the installation of Wolf gas red combi boilers.
- Open ue gas red boilers must only be installed in a room that complies with the appropriate ventilation requirements.
The gas red boiler meets with the following regulations
EC Directives
- 2006/95/EC Low Voltage Directive
- 2004/108/EC EMC Directive
- 90/396/EEC Gas user equipment
- 92/42/EEC Efciency directive
DIN / EN Standards
- EN 297; EN298; EN 483; EN 625; EN 55014-2; EN 60335-1; EN 60335-2-102; EN 60529; EN 61000-3-2; EN 61000-4-3
The following regulations, rules and guidelines must
be observed during installation:
- Boiler room guidelines or Building Regulations
relating to the construction and installation of central boiler rooms and fuel storage facilities
- Technical regulations for gas and DHW installations DVGW-TRGI 1996 and TRF 1996
(in the currently applicable form)
DIN / EN Standards
- EN 437 Test gases; test pressures; appliance categories
- DIN EN 1283 Procedure for calculating the standard heating load
- DIN EN 12828 Heating systems in buildings
- DIN EN 1717 Protection of DHW against contaminations in DHW installations
- DIN EN 50156-1 (VDE 0116 part 1)
Electrical equipment for combustion systems
- On site regulatio ns from building and indust ry
regulatory agencies (mainly covered by the emission test switch)
- On site regulations from the gas supply utility
6
3062347_0309
440
Dimensions
Gas red combi boilers
Gas red boilers
1 Heating ow Heating ow
2 DHW DHW ow 3 Cold water DHW return 4 Heating return Heating return
5 Gas connection Gas connection
Installation inside a cupboard
For installation of the gas red boiler inside a cupboard note the following:
Never install the gas red boiler on the back wall of the cupboard, as it may not be substantial enough to take the boiler's weight. This would create the risk of water and gas leaks which in turn would result in a risk of explosion and ooding.
- Removing the rear wall of the cupboard Minimum lateral clearance between the gas red boiler
and the cupboard sides 25 mm.
A cutout of 410 x 550 mm is required in the cupboard top. Otherwise there is a risk of suffocation and poisoning
With open ue gas red boilers the ventilation grill in the cupboard door must be installed with a free minimum diameter
of 600 cm
2
Otherwise there is a risk of suffocation and poisoning
3
1
2
4
5
3
1
2
4
5
Min.400
Min.400
>25
694
366 CGU-2(K) 18
380 CGU-2(K) 24
258 CGG-2(K) 18/24
344
120 176
170
39
49
855
393
190
226
(CGG-2)
(CGU-2)
73
134
7
3062347_0309
Layout CGU-2(K) 18/24
Combustion
chamber
Internal lling equipment (optional) not <DE><AT>
Gas combination
valve
Expansion vessel
Three-way diverter valve
Flow sensor 2
Limit thermostat
Monitoring
electrode
Ignition electrode
Heating water heat
exchanger
Safety valve
Drain valve
DHW Flow & temperature sensor
Flow sensor 1
Draught hood
Gas burner
Heating circuit
strainer
Cold water strainer
with throughput
limiter
Heating circuit pump
Air vent
Bypass
Flue gas temperature limiter
HZ - VL
HZ - RL
8
3062347_0309
Layout CGG-2(K) 18/24
Flue gas fan
with speed
regulation
Combustion
chamber
Internal lling equipment (optional) not <DE><AT>
Gas combination
valve
Expansion vessel
Three-way diverter valve
Flow sensor 2
Limit thermostat
LAF connection
Monitoring
electrode
Ignition
electrode
Heating water heat
exchanger
Differential pressure switch
Safety valve
Drain valve
DHW Flow & temperature sensor
Flow sensor 1
Flue gas
collector
box
Gas burner
Heating circuit
strainer
Cold water strainer
with throughput
limiter
Heating circuit pump
Air vent
Bypass
HZ - VL
HZ - RL
9
3062347_0309
Layout / Equipment code
Heating water heat
exchanger
Gas burner
Gas
combination
valve
Expansion vessel
Air vent
Heating circuit
pump
DHW heat exchanger
Safety valve
Drain valve
Heating circuit strainer
Cold water strainer with
throughput limiter
Limit thermostat ow
Flow sensor 2
Flow sensor 1
Three-way diverter valve
DHW ow & temperature sensor (only combi boilers)
Bypass valve
Hydro Tec system (integrated components)
Overow valve
Flue gas temperature limiter
Wolf Low NOx unit with hydro tec system (plug-in technology for quick installation)
compactly designed for low emissions, high energy efciency.
DHW heat exchanger and DHW ow temperature sensor only with combi boilers
CGU-2 - 18/24 Open ue gas red boiler with integrated cylinder connection
CGU-2 K - 18/24 Open ue gas red combi boiler
CGG-2 - 18/24 Balanced ue gas red boiler with integrated cylinder connection
CGG-2 K - 18/24 Balanced ue gas red combi boiler
Equipment codes
10
3062347_0309
Balanced ue gas red boilers must only be installed in a room that complies with
the appropriate ventilation requirements. Otherwise there is a risk of asphyxiation or poisoning. Read these installation and
operating instructions before installing the gas red boiler. Also take the technical
guide into consideration.
Sound insulation:
Under certain critical installation conditions (e.g. installation on a drywall) additional
measures may be necessary to soundproof the boiler. In this case use soundproof plugs and, if necessary, rubber buffers or
insulation strips.
Positioning information / Installation dimensions
l.h. turnbuckle
r.h. turnbuckle
Fig.: Opening the turnbuckle
- Determine the installation location for the gas red boiler; maintain the specied minimum clearances (see dimensions).
- Fit the supplied installation template (paper poster) to the wall.
- Transfer the xing hole and connection positions marked on the installation template to the wall (e.g. with a power drill).
- Remove the installation template.
- Drill Ø 12 mm holes for the mounting bracket and secure the bracket using the rawl plugs and screws supplied. (Before securing the bracket, check that the rawl plugs are suitable for the wall construction.)
- Remove the casing lid of the gas red boiler. For this, pivot the control unit lid down, hook in the r.h. and l.h. turnbuckle, undo the bottom of the casing lid and unhook at the top.
- Hang the gas red boiler with the hook-in brace on the back of the boiler onto the mounting bracket.
General
The gas red boiler may only be installed in rooms that are protected from frost.
During the boiler installation ensure that all xings are sufciently strong to carry its weight. Also consider the wall consistency, otherwise gas or water may escape which could lead to explosions and ooding. It can also lead to noise developing.
During the boiler installation, ensure that
no contaminants (e.g. drilling swarf) enter
the gas red boiler otherwise faults may
develop.
The combustion air supplied to the boiler must be free from chemicals, e.g. uoride, chlorine or sulphur. Such materials are contained in sprays, solvents and cleaning agents. Under the most unfavourable conditions, these may lead to corrosion, even in the ue gas system.
Note
500
25 25
(CGU-2-18) Ø110
(CGU-2-24) Ø130
(CGU-2) min.400
(CGG-2)
min.200
(CGG-2-18) Ø100
1212
344
min.200
1478
11
3062347_0309
Positioning information / Installation dimensions
270-420
790
694
1754-1904
810
5
=
=
100
547
Installation dimensions of the boiler with freestanding cylinder SW-120 / CSW-120 Installation on unnished walls
Installation dimensions of the boiler with freestanding cylinder SW-120 / CSW-120 Installation on nished walls
12
3062347_0309
Installation on nished / unnished walls
Fig.: View from below, connection set for installation on nished walls
Installation on unnished walls (accessory)
Fig.: Front view, connection set for installation on unnished walls
Fig.: View from below, connection set for installation on unnished walls
Installation on nished walls (accessory)
Fig.: Front view, connection set for installation on nished walls
Heating ow Rp ¾" DHW Rp ¾" (gas combi boilers) Cold water Rp ¾" (gas combi boilers) Heating return Rp ¾" Gas connection Rp ½" Drain for safety valve R 1"
With boilers that are not used for DHW, seal the cold and DHW connections with locking cap G ¾" (accessory). If this is not done then the building and equipment may be damaged through uncontrolled water leakages.
Heating ow R ¾" DHW R ¾" (gas combi boilers) Cold water R ¾" (gas combi boilers) Heating return R ¾" Gas connection R ¾" Drain for safety valve R 1"
164
94
84
120
176
164
64
55
120
200
7
190
107
73
55
134
13
3062347_0309
General boiler installation
Gas connection
Laying the gas pipe, as well as making the gas connections, must only be carried out by a licensed gas  tter. Close the gas ball valve on the gas  red combi boiler to pressure test the gas pipe. Remove all residues from the heating pipework and the gas pipe prior to connecting the gas  red boiler, particularly in older systems. Prior to commissioning, test all pipe and gas connections for leaks. Inappropriate installation or using unsuitable components or assemblies may lead to gas escaping, which results in a risk of poisoning and explosion.
The gas valve can be subj ecte d to a maximum pressure of 150 mbar. Higher
pressure may dam age the gas valve, resulting in a risk of explosion, asphyxiation
or poisoning. Close the gas ball valve on the gas  red boiler to pressure test the
gas pipe.
Install a tested and certified pressure reducer, if the cold water supply pressure is
above the maximum permissible operating pressure of 10 bar. Otherwise water could escape resulting in a risk of  ooding.
Fig.: Cold water connection
Cold water and DHW connection
For the cold water and DHW connection, we recommend installation in accordance with the diagram below.
- Wolf connection sets (accessories) are available for installation on  nished and un nished walls. The connection pipes are Cu 18x1.
Hydraulic connections
Note:
As standard, a combined cold water strainer
with throughput controller  is  tted at the cold water connection of the boiler (see Fig.).
Fig.: Throughput controller with cold water strainer
Installation inside a cupboard
For installation of the gas  red boiler inside a cupboard note the following:
Never install the gas  red boiler on the back wall of the cupboard, as it may not be substantial enough to take the boiler's weight. This would create the risk of water and gas leaks which in turn would result in a risk of explosion and  ooding.
Removing the rear wall of the cupboard Minimum lateral clearance between the gas
 red boiler and the cupboard sides 25 mm.
A cutout of 410 x 550 mm is required in the cupboard top. Otherwise there is a risk of suffocation and poisoning
With open  ue gas  red boilers the ventilation grille in the cupboard door must be installed with a free minimum diameter of
600 cm2.
Otherwise there is a risk of suffocation and poisoning.
As the cold water strainer may need to be cleaned, provide a facility for its
removal in site.
Otherwise there is a risk of faults.
Drain
Drain
Shut-off valve
Pressure
reducing valve
Shut-off valve
Cold water inlet
Pressure gauge port
DHW  lter
Safety valve
Note
14
3062347_0309
Electrical connection CGU-2(K) / CGG-2(K)
General notes
The installation must be carried out by a licensed electrical contractor. Observe
the regulations of the relevant authorities and the local regulations of the power supply company.
The power supply terminals are 'live'
even when the ON/OFF switch has been
switched OFF.
Terminal box
Terminal box
The control, regulating and safety equipment are fully wired and tested. You only need to connect the power supply and the external accessories.
Power supply connection
Connect the power supply permanently or with a safety plug (no plug connection in protective areas 1 and 2, i.e. near a bath or shower).
Provide the power supply via a mains isolator (e.g. fuse, heating system emergency stop), which ensures at least 3 mm contact separation for all poles. Connection cable exible, 3 x 1.0 mm² or rigid, max. 3 x 1.5 mm². The plug must be accessible when using a power supply cable with safety plug. Flexible power supply cable 3 x 1.0 mm².
15
3062347_0309
Flue gas damper connection (230 V; max.200 VA)
Insert the cable glands into the terminal box. Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N,
and .
Fig.: Flue gas damper connection
Changing a fuse
Isolate the boiler from the main supply prior
to changing a fuse. The ON/OFF switch on
the boiler does not provide separation from
the power supply.
Danger through 'live' electrical components.
Never touch electrical components or
contacts if the boiler has not been isolated
from the power supply. Danger of death.
Fig.: Pivot the control unit forward, terminal box cover open
Fuse
Electrical connection CGU-2(K)
Connection to Output A1 (230 VAC; max.200 VA)
Insert the cable glands into the terminal box. Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N and .
Fig.: Connection output A1
Installation information, electrical connection
- Isolate the system from the power supply before opening the casing.
- Pivot the control unit to the side.
- Open the terminal box.
- Insert the strain relief into the holes provided.
- Strip approx. 70 mm off the power supply cable insulation.
- Push the cable through the strain relief and secure the strain relief.
- Pull the Rast-5 plug.
- Terminate the appropriate cores at the Rast-5 plug.
- Push the inserts back into the terminal box casing.
- Push the Rast-5 plugs back into the correct positions.
A
Mains connection 230 VAC/50 Hz
C
Programmable output A1
G
Flue gas damper connection
D
Programmable input E1 zero volt
E
2-wire eBUS connection, digital Wolf control accessories
F
Outside temperature sensor
A C G D E F
.
230 V < 24 V
230 V < 24 V
16
3062347_0309
Electrical connection CGU-2(K)
Fig.: Connection DHW circulation pump / external accessories
Changing a fuse
Isolate the boiler from the main supply prior
to changing a fuse. The ON/OFF switch on
the boiler does not provide separation from
the power supply.
Danger through 'live' electrical components.
Never touch electrical components or
contacts if the boiler has not been isolated
from the power supply. Danger of death.
Fig.: Pivot the control unit forward, terminal box
cover open
Fuse
Connection to Output A1 (230 VAC; max. 200 VA)
Insert the cable glands into the terminal box. Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N and .
Fig.: Connection output A1
Installation information, electrical connection
- Isolate the system from the power supply before opening the casing.
- Pivot the control unit to the side.
- Open the terminal box.
- Insert the strain relief into the holes provided.
- Strip approx. 70 mm off the power supply cable insulation.
- Push the cable through the strain relief and secure the strain relief.
- Pull the Rast-5 plug.
- Terminate the appropriate cores at the Rast-5 plug.
- Push the inserts back into the terminal box casing.
- Push the Rast-5 plugs back into the correct positions.
Power supply for external accessories
(230 VAC; max. 200 VA)
Insert the cable glands into the terminal box. Insert and secure the connecting cable through the cable gland. Connect the connecting cable to terminals L1, N and .
Netz
Z
A1
N
N
N
L1
L1
L1
L1
L1
L1
N
N
N
3
Z
A1
N
N
NL1
L1
L1
L1 L1
L1
NN
N
3
Netz
A
Mains connection 230 VAC/50 Hz
B
Power supply, ext. Accessories 230 VAC/50 Hz/max. 200 VA
C
Programmable output A1
D
programmable input E1 zero volt
E
2-wire eBUS connection, digital Wolf control accessories
F
Outside temperature sensor
A B C D E F
230 V < 24 V
230 V < 24 V
17
3062347_0309
Connection, analogue outside temperature sensor
The analogue outside temperature sensor for digital control accessory (e.g. BM) may be connected to the terminal strip of the gas red boiler at the connection AF or the terminal strip of the BM.
Fig.: Connection, analogue outside temperature sensor
Connection of digital Wolf control accessories (e.g. BM, MM, SM1, SM2, KM)
Only connect control units from the Wolf accessory range. Eac h accessory is supplied with its own connection diagram. Use a 2-core cable (cross-section > 0.5 mm²) as the connecting cable between the control unit accessory and the gas red boiler.
Fig.: Digital Wolf control accessories connection (eBUS interface)
Electrical connection CGU-2(K) CGG-2(K)
Fig.: Connection, programmable input
Connection, programmable input E1 (<24 V)
Connect the connecting cable for input 1 at terminals E1 in accordance with the wiring diagram; rst remove the jumper between a and b from the respective terminals.
The functions of input E1 can only be scanned and adjusted with Wolf control accessories with eBUS capability.
DHW tank sensor connection
- When a cylinder is to be connected, the blue socket of the cylinder sensor must be connected to the blue plug of the control unit.
- Observe the cylinder installation instructions.
Fig.: Blue plug, cylinder sensor connection
Blue plug
Note
Pay attention + , ­to polarity
18
3062347_0309
Fill / vent the system
Procedure for boilers with internal lling facility
not for <DE> <AT>
- Fill the entire heating system and boiler via the lling facility or an on-site
ll & drain valve up to approx. 0.5 - 1 bar, whilst simultaneously venting the
heating system.
- Close the shut-off valves on the heating water side of the boiler (ow and return).
- Push the drain hose onto the drain valve of the hydraulic assembly.
- Clean the heat exchanger by opening the internal lling facility and the
drain valve simultaneously on the hydraulic assembly (make sure there is
no air remaining in the heat exchanger).
Procedure for boilers without internal lling facility
Filling the system
Fill the system and vent it thoroughly to safeguard the perfect
function of the gas red boiler.
Otherwise there is a risk of faults.
The heating water must not be mixed with inhibitors or antifreeze; otherwise leaks and ooding could result.
- Close the gas ball valve.
- Before connecting the gas red boiler to the heating system, ush the entire
system to remove residues such as welding pearls, hemp, putty, etc. from the pipework and to remove air that may have collected.
- Fill the DHW system of the boiler until water ows out of a DHW draw-off point.
- To ll the heating system use the ll & drain connections. Open the cap of the automatic air vent valve on the heating circuit pump by approx. 2 revolutions, but do not remove the cap.
- Open all radiator valves and the shut-off valves on the heating water side of the
boiler.
- Fill the entire heating system and boiler via the ll & drain valves (Wolf accessory) up to approx. 0.5 bar, whilst simultaneously venting the heating
system.
- Close the return shut-off valve on the heating water side of the boiler.
- Attach drain hose to the drain valve on the hydraulic assembly (alternative, if only a ll & drain connection is provided).
- Clean the heat exchanger by opening the ll & drain valve and/or the
drain valve simultaneously on the hydraulic assembly (make sure there is no air remaining in the heat exchanger).
- Remove the drain hose and open the boiler shut-off valve(s) on the heating water side again.
- After venting, raise the system pressure to 2.5 bar.
- Start the boiler, set the heating water temperature selector to position "2" (pump running, illuminated signal ring (status display) constantly green).
- Vent the pump; for this, briey open and then retighten the air vent
screw, optimum venting in pump stage 3.
Top up with water when the system pressure falls severely.
- Open the gas shut-off valve. Press the reset button.
- When in constant use the heating circuit vents automatically via the heating circuit pump, venting optimum at pump stage 3. After venting set to pump stage 1 or 2 for reduced noise, depending on customer preference.
- At system pressure below 1.0 bar the boiler may experience faults. If necessary ll on heating side.
Internal lling facility not for
<DE><AT>
Drain valve
Fig.: Shut off valves (accessory)
Gas shut-off valve
Heating ow (incl. ll & drain connection)
Heating return (incl. ll & drain connection)
Automatic
air-vent valve
Fill & drain
Connection
Note
19
3062347_0309
- Instruct the customer about energy-saving options.Saving energy
Commissioning guidelines
Only qualied personnel must carry out the commissioning and initial start-up of the boiler as well as instruct the user.
Guidelines for commissioning
- Flush and vent boiler (use shut-off valve with ll & drain valve from Wolf
accessory range), ll boiler and system and test for tightness. Normal operating pressure when system is cold 1.5 bar. Prevent water leaks.
- Check location and seating of the installation.
- Check the gas supply pressure.
- Check all connections and component links for leaks.
- If tightness cannot be ensured then there is a danger of water damage.
- Check that all ue gas accessories have been correctly installed.
- Open the water and shut-off valves on ow and return.
- Open gas connection.
- Switch ON emergency heating switch and switch ON the ON/OFF switch on
the control unit.
- Check the adjustment of the ue length, resetting if required.
See chapter "Adjusting the ue length".
- Check the ignition and ame structure of the burner.
- The illuminated ring shows a yellow colour, if the boiler starts correctly.
- Instruct the customer in the operation of the boiler, with the aid of the
installation instructions.
- Complete the commissioning report and hand over the instructions to the
customer.
- Implement the "Installation" and "Electrical connection" of the boiler
and all extension and programming modules in accordance with the instructions in the associated manuals.
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 8
Step 9
Step 10
Step 11
Step 12
Step 13
Step 14
Step 15
Note
Otherwise there is a risk of faults.
e e
e e
e e
e e
e e e
e e e e
20
3062347_0309
Control / Function / Commissioning
ON / OFF switch
DHW
temperature
selector
Pressure
gauge
Reset
button
Heating water
temperature
selector
Illuminated
signal ring
Thermometer
9
1
2
8
3
7
4
6
5
DHW temperature selector
Settings 1-9 correspond with a DHW temperature of 40-65 °C with gas combi boilers, or 15-65 °C with gas boilers with a cylinder. Combined with a control thermostat for wall mounted gas  red boilers, the adjustment at the DHW temperature selector is disabled; instead the temperature is selected at the boiler control thermostat.
2
8
3
7
4
6
5
Heating water temperature selector
Settings 2-8 correspond to a heating water temperature of 40-80 °C. Combined with a temperature controller for wall mounted gas  red boilers, the adjustment at the heating water thermostat is disabled; instead the temperature is selected at the boiler temperature controller.
Signal ring as status display
Display Explanation
Flashing green Standby (power supply ON, burner OFF)
Constant green light Heat demand: pump running, burner OFF
Flashing yellow Emissions test mode
Constant yellow light
Burner ON,  ame steady
Flashing red
Fault
Reset
A fault is reset by pressing the reset button which will also restart the system. Pressing the reset button reactivates the system, if there was no fault.
21
3062347_0309
In conjunction with the accessory controllers BM / AWT / ART, the settings at the boiler relating to DHW and heating water are disabled.
Note:
Setting
Winter mode (position 2 to 8)
In winter mode, the boiler heats to the temperature selected at the heating water temperature controller. According to the pump operating mode, the circulation pump operates constantly (factory setting) or only in parallel with the burner activation / run-on period.
Summer mode
The winter mode is deactivated by rotating the heating water temperature selector into position . In other words, the boiler will then operate in summer mode. Summer mode (heating OFF) means, only DHW heating. Frost protection for the heating system and pump anti-seizing protection, however, remain
enabled.
In summer mode, the circulation pump operates for approx. 30 seconds after a maximum idle period of 24 hours.
Anti-seizing pump protection
Thermomanometer
The current heating water temperature is displayed in the upper area. The water pressure in the heating system is displayed in the lower area. In normal use, the water pressure should be between 2.0-2.5 bar.
Emissions test mode
The emissions test mode is activated by rotating the heating water temperature selector into position . The signal ring  ashes yellow. After the emissions test mode has been activated, the boiler will heat with the selected maximum heating output. Any previous cycle block will be cancelled. The emissions test mode terminates after 15 minutes or when the maximum  ow temperature has been exceeded. For a renewed activation, turn the heating water temperature selector anti-clockwise and then back into position .
Control / Function / Commissioning
Loading...
+ 47 hidden pages