from system supplier WOLF oers the ideal solution for commercial and
industrial buildings, new build and modernisation projects alike.
The range of WOLF control units can meet any requirement for heating convenience.
All equipment is easy to operate, highly energy ecient and reliable.
Solar thermal technology can be swiftly integrated into existing
systems.
WOLF equipment is easy and quick to install and maintain.
Page 3
COMFORTLINE CONVENTIONAL GAS BOILERSCGU-2(K)04-05
APPLIANCE DESCRIPTION
06
SPECIFICATION06-07
STANDARD CONTROL UNITS08
CONTROL ACCESSORIES09-10
ACCESSORIES11
03
COMFORTLINE CONVENTIONAL GAS BOILER
Page 4
atmospheric premix burner for
natural gas E, LL and LPG
WOLF low NOx unit with Hydro Tec system
designed for very low emissions
Control unit with eBUS capability for connection
to WOLF digital control accessories
Electronic ignition and monitoring
Water-cooled,
Modulating controlled output
in heating and DHW mode
Equipped as standard with
modulating high eciency pump (EEI <0,20),
3-way changeover valve and
10Ltr. expansion vessel
High energy efficiency
and compact design
Straightforward installation and operation
Comfortable hot water quick start,
with CGU-2K-18/24 with high quality
stainless steel plate heat exchanger
04
Page 5
Tested according to the applicable EC directives
BENEFITS OF WOLF
CONVENTIONAL GAS BOILERS
FROM 10 TO 24 KW
CGU-2-10 / CGU-2K-18 / CGU-2K-24
Emissions to NOx class 6
High standard seasonal efficiency [to DIN]
up to 94% (net cv)/ 85% (gross cv) for best possible energy eciency
05
COMFORTLINE CONVENTIONAL GAS BOILER
Page 6
CGU-2K-18, -24 CONVENTIONAL GAS COMBI BOILER FOR CENTRAL HEATING AND DHW
CGU-2-10 CONVENTIONAL GAS BOILER FOR HEATING (NOT AVAILABLE AS COMBI BOILER)
Conventional, open flue, gas combi boiler for low temperature heating and DHW provision with integral DHW heat exchanger
and electronic flue gas monitoring; tested in accordance with EC directives for connection to a chimney
* Programming unit as accessory
This boiler with natural ventilation is intended for connection exclusively in existing buildings to a flue system that is shared by multiple
apartments and that routes the combustion residues from the installation room to the outside.
Note: Type B1 units are excluded from the eciency requirements of the ErP Directive if used with multiple occupation chimneys.
It draws the combustion air directly from the installation room and is equipped with a draught hood.
This boiler should not be used for any other purpose due to its reduced eciency – this would lead to higher energy consumption and
running costs.
CONVENTIONAL GAS COMBI BOILER
SPECIFICATION
CGU-2(K)
393
216
344
366 (CGU-2K-18)
366 (CGU-2-10)
380 (CGU-2K-24)
694
30
58
14
70
120
200
440
70
855
Heating flow
DHW
Gas connection
50
73
180
Heating return
Cold water
DHW,
cold water
Heating flow,
heating return,
gas connection
06
Page 7
CONVENTIONAL GAS COMBI BOILER
SPECIFICATION
CGU-2(K)
TYPECGU-2-10CGU-2K-18CGU-2K-24
Energy eciency class, central heating
Energy eciency class, DHW heating-
CCC
AA
Output rangekW7.5-108-1810.9-24
Input rangekW8.3-11.28.8-20.212.0-26.5
Standard seasonal eciency [to DIN] at 75/60°C (net cv/gross cv)
CE designationCE-0085BS0516 CE-0085BS0516 CE-0085BS0516
1)
Observe when connecting to a chimney
2)
Relative to a cold water temperature of 10°C
07
COMFORTLINE CONVENTIONAL GAS BOILER
Page 8
CONVENTIONAL GAS COMBI BOILER
9
1
2
8
3
7
4
6
5
2
8
3
7
4
6
5
°C
0120
bar
04
2
13
STANDARD CONTROL UNITS
CGU-2(K)
ON/OFF Reset button
Heating water
temperature selectorThermometer
ILLUMINATED RING FOR
STATUS DISPLAY
SETTING
DHW temperature
Pressure gaugeIlluminated ring
selector
Flashing greenStandby (power supply on; no heat demand)
Constant green lightHeat demand: pump running; burner o
Flashing yellowEmissions test mode
Constant yellow lightBurner on; flame steady
Flashing redFault
DHW TEMPERATURE SELECTOR
Settings 1-9 correspond to a cylinder temperature of 40-65°C. If an external
temperature controller is used, settings made at the DHW temperature selector have
no eect; they are made at the external temperature controller.
HEATING WATER TEMPERATURE SELECTOR
Settings 2-8 correspond to a heating water temperature of 20-75°C. If an external
temperature controller is used, settings made at the heating water temperature
selector have no eect; they are made at the external temperature controller.
WINTER MODE (POSITIONS 2 TO 8)
The circulation pump operates in heating mode.
SUMMER MODE
Switch is set to
circulation pump o (central heating o); only DHW heating, frost
protection and pump anti-seizing (where the circulation pump runs for approx. 30s
every 24hours) are active.
EMISSIONS TEST MODE
Turning the switch to
lets the appliance operate at maximum heating output. The
illuminated ring flashes yellow for 15 minutes or until the maximum flow temperature
has been exceeded.
THERMOMETER/PRESSURE GAUGE
The heating water temperature and the heating system water pressure are displayed.
08
Page 9
CONVENTIONAL GAS COMBI BOILER
CONTROL ACCESSORIES
CGU-2(K)
Standard control unit part of the standard delivery of the conventional gas boiler
BM programming unit (incl. outside
sensor) as weather-compensated
temperature controller
• Room temperature-dependent/weather-compensated temperature control
• Time programs for central heating and DHW heating
• Backlit LCD screen
• Simple user prompts via plain text display
• Operation by rotary selector with pushbutton function
• 4 function keys for frequently used functions
(heating, DHW, setback, info)
• Installation either inside the heat generator control unit, or as a remote control
in a wall mounting base
• Optional for MM mixer module
• Only one programming unit required for multi circuit systems
• Can be extended with MM mixer module (up to 7 circuits with mixer)
• Fault diagnosis
BM programming unit with wall
mounting base (accessory) as
remote control
2-wire eBus connection
MM MIXER MODULE
• Extension module to control one circuit with mixer
• Weather-compensated flow temperature control
• Easy controller configuration by selecting one of the
preset system versions
• BM programming unit can be attached to the appliance
or fitted to a wall mounting base for use as a remote control
• Rast 5 connection technology
• Incl. flow temperature sensor
ART
• Analogue room temperature controller with
day program for central heating and DHW
• Room temperature-dependent flow temperature
• Display for showing the room temperature,
time and fault messages
• Room temperature-dependent frost protection
AWT
• Analogue weather-compensated temperature
controller with day program for central heating
and DHW
• Weather-compensated flow temperature
• Display for showing the room temperature,
outside temperature, time and fault messages
• Room temperature hook-up
• Frost protection function
• Automatic energy saving appliance
1 ... 7
09
COMFORTLINE CONVENTIONAL GAS BOILER
Page 10
CONVENTIONAL GAS COMBI BOILER
CONTROL ACCESSORIES
CGU-2(K)
WIRELESS RECEIVER
for external wireless sensor
2-wire eBus connection
EXTERNAL WIRELESS SENSOR
(only in conjunction with receiver for external wireless sensor
and remote control, part no. 27 44 209)
and wireless remote control incl. radio clock (DCF77 signal)
WIRELESS REMOTE CONTROL
(only in conjunction with receiver for external wireless sensor and remote
control). Max. one wireless remote control per circuit with mixer.
WOLF
portal server
DSL router
(LAN / WiFi)
Local (home) network
WiFi
LAN / WiFi
LAN / WiFi
LAN
WOLF LINK PRO
LAN / WLAN interface module for
accessing the control via the Internet
as well as a local network with PC or
smartphone
eBus
Interface module
10
Page 11
CONVENTIONAL GAS COMBI BOILER
ACCESSORIES
CGU-2(K)
CGU-2 Conventional gas boiler for central heating with option to connect a DHW cylinder
CGU-2K Conventional gas boiler for central heating and DHW heating
Tested in accordance with EC directives and EN297, 483 and 625, and for heating systems according to EN1282 with flow temperatures up to 95°C
and 3bar permissible operating pressure. Suitable for modulating operation down to room temperature; modulating output control. Flue gas monitoring
with CGU-2K. Premix burner equipped and adjusted at the factory for natural gas E and LL. When ordering for LPG a conversion set is enclosed (loose).
CGU-2K for chimney connection for open flue operation.
Control unit with gas burner control unit, electronic ignition and ionisation flame monitor.
White RAL 9016 powder-coated casing.
Accessories
Control accessories
BM programming unit
Wall mounting base
MM mixer module
ART analogue room temperature-dependent controller with day program
AWT analogue weather-compensated controller
Wireless receiver – required for external wireless sensor and wireless remote control
WRS remote maintenance system
Hydraulic accessories and gas supply accessories
Gas ball valve (angle or straight-through version), chrome plated, with or without thermally activated
shut-o device
Drain set, safety valve with hose, hose retainer, trap and pipe collar, transparent plastic
Accessories for flush mounting
Concealed mounting bracket for installation on unfinished walls
CGU-2(K)
Angle maintenance valve G¾", chrome plated
Angle maintenance valve G¾" with connection R½" for safety valve, chrome plated