Wolf CGU-2 / CGU-2K DATA SHEET (Doc. no. 4800589 GB 2018/07)

Page 1
30m3/h
WOLF CONVENTIONAL GAS BOILER
COMFORTLINE
CGU2 / CGU2K
Page 2
THE EXTENSIVE
EQUIPMENT RANGE
from system supplier WOLF oers the ideal solution for commercial and industrial buildings, new build and modernisation projects alike. The range of WOLF control units can meet any requirement for heating convenience. All equipment is easy to operate, highly energy ecient and reliable. Solar thermal technology can be swiftly integrated into existing systems.
WOLF equipment is easy and quick to install and maintain.
Page 3
COMFORTLINE CONVENTIONAL GAS BOILERS CGU-2(K) 04-05
APPLIANCE DESCRIPTION
06
SPECIFICATION 06-07
STANDARD CONTROL UNITS 08
CONTROL ACCESSORIES 09-10
ACCESSORIES 11
03
COMFORTLINE CONVENTIONAL GAS BOILER
Page 4
atmospheric premix burner for
natural gas E, LL and LPG
WOLF low NOx unit with Hydro Tec system
designed for very low emissions
Control unit with eBUS capability for connection
to WOLF digital control accessories
Electronic ignition and monitoring
Water-cooled,
Modulating controlled output
in heating and DHW mode
Equipped as standard with
modulating high eciency pump (EEI <0,20),
3-way changeover valve and
10Ltr. expansion vessel
High energy efficiency
and compact design
Straightforward installation and operation
Comfortable hot water quick start,
with CGU-2K-18/24 with high quality
stainless steel plate heat exchanger
04
Page 5
Tested according to the applicable EC directives
BENEFITS OF WOLF
CONVENTIONAL GAS BOILERS FROM 10 TO 24 KW
CGU-2-10 / CGU-2K-18 / CGU-2K-24
Emissions to NOx class 6
High standard seasonal efficiency [to DIN]
up to 94% (net cv)/ 85% (gross cv) for best possible energy eciency
05
COMFORTLINE CONVENTIONAL GAS BOILER
Page 6
CGU-2K-18, -24 CONVENTIONAL GAS COMBI BOILER FOR CENTRAL HEATING AND DHW CGU-2-10 CONVENTIONAL GAS BOILER FOR HEATING (NOT AVAILABLE AS COMBI BOILER)
Conventional, open flue, gas combi boiler for low temperature heating and DHW provision with integral DHW heat exchanger and electronic flue gas monitoring; tested in accordance with EC directives for connection to a chimney
* Programming unit as accessory
This boiler with natural ventilation is intended for connection exclusively in existing buildings to a flue system that is shared by multiple apartments and that routes the combustion residues from the installation room to the outside. Note: Type B1 units are excluded from the eciency requirements of the ErP Directive if used with multiple occupation chimneys. It draws the combustion air directly from the installation room and is equipped with a draught hood. This boiler should not be used for any other purpose due to its reduced eciency – this would lead to higher energy consumption and running costs.
CONVENTIONAL GAS COMBI BOILER SPECIFICATION
CGU-2(K)
393
216
344
366 (CGU-2K-18)
366 (CGU-2-10)
380 (CGU-2K-24)
694
30
58
14
70
120 200
440
70
855
Heating flow
DHW
Gas connection
50
73
180
Heating return
Cold water
DHW, cold water
Heating flow, heating return, gas connection
06
Page 7
CONVENTIONAL GAS COMBI BOILER
SPECIFICATION
CGU-2(K)
TYPE CGU-2-10 CGU-2K-18 CGU-2K-24
Energy eciency class, central heating
Energy eciency class, DHW heating -
C C C
A A
Output range kW 7.5-10 8-18 10.9-24
Input range kW 8.3-11.2 8.8-20.2 12.0-26.5
Standard seasonal eciency [to DIN] at 75/60°C (net cv/gross cv)
Width mm
% - 94/85 92/83
440
Height mm 855
Depth mm 393
Flue pipe/wall clearance mm 226
Flue connection Ø mm 110
Connection type for air/flue gas duct Type B
Gas category II
2ELL3P
(DE) / II
Gas connection, external Ø G
11BS
2H3P
(AT) II
2ELL3P
B
11BS
(DE) / II
¾"
(AT) II
2H3P
2ELL3P
B
11BS
(DE) / II
Heating flow, external Ø G ¾"
Heating return, external Ø G ¾"
Cold water connection G ¾"
DHW connection G ¾"
Expansion vessel, nominal capacity litres 10
Expansion vessel pre-charge pressure bar 0.75
Maximum outlet temperature
2)
°C - 55 55
At a draw-o rate of l/min - 2.7-5.8 2.7-7.7
Gas supply details:
Natural gas E/H (net cv = 9.5kWh/m3 = 34.0 MJ/ m3)
Natural gas LL (net cv = 8.1kWh/m3 = 29.2 MJ/ m3)
m/h 1.3 2.1 2.8
m/h 1.5 2.3 3.1
LPG (net cv = 12.9kWh/kg = 46.3 MJ/kg) kg/h 0.8 1.5 2.1
Gas supply pressure:
Natural gas mbar 20 20 20
LPG mbar 50 50 50
Max. overall pressure, heating bar - 3 3
2H3P
(AT)
Required draught for the heat generator Pa 1.5 1.5 1.5
Flue gas temperature
1)
°C 84/101 80/123 80/125
Flue gas mass flow rate g/s 12.8/13.1 12.8/13.9 15.0/19.0
Total weight kg 39 39 41
Integral fuse (medium time lag) A 3.15 3.15 3.15
IP rating IPX4D IPX4D IPX4D
Electrical connection 230V/50Hz 230V/50Hz 230V/50Hz
Power consumption / standby W 83 / 6 83 / 6 83 / 6
CE designation CE-0085BS0516 CE-0085BS0516 CE-0085BS0516
1)
Observe when connecting to a chimney
2)
Relative to a cold water temperature of 10°C
07
COMFORTLINE CONVENTIONAL GAS BOILER
Page 8
CONVENTIONAL GAS COMBI BOILER
9
1
2
8
3
7
4
6
5
2
8
3
7
4
6
5
°C
0 120
bar
04
2
13
STANDARD CONTROL UNITS
CGU-2(K)
ON/OFF Reset button
Heating water
temperature selector Thermometer
ILLUMINATED RING FOR STATUS DISPLAY
SETTING
DHW temperature
Pressure gaugeIlluminated ring
selector
Flashing green Standby (power supply on; no heat demand)
Constant green light Heat demand: pump running; burner o
Flashing yellow Emissions test mode
Constant yellow light Burner on; flame steady
Flashing red Fault
DHW TEMPERATURE SELECTOR
Settings 1-9 correspond to a cylinder temperature of 40-65°C. If an external temperature controller is used, settings made at the DHW temperature selector have no eect; they are made at the external temperature controller.
HEATING WATER TEMPERATURE SELECTOR
Settings 2-8 correspond to a heating water temperature of 20-75°C. If an external temperature controller is used, settings made at the heating water temperature selector have no eect; they are made at the external temperature controller.
WINTER MODE (POSITIONS 2 TO 8)
The circulation pump operates in heating mode.
SUMMER MODE
Switch is set to
circulation pump o (central heating o); only DHW heating, frost protection and pump anti-seizing (where the circulation pump runs for approx. 30s every 24hours) are active.
EMISSIONS TEST MODE
Turning the switch to
lets the appliance operate at maximum heating output. The illuminated ring flashes yellow for 15 minutes or until the maximum flow temperature has been exceeded.
THERMOMETER/PRESSURE GAUGE
The heating water temperature and the heating system water pressure are displayed.
08
Page 9
CONVENTIONAL GAS COMBI BOILER
CONTROL ACCESSORIES
CGU-2(K)
Standard control unit part of the standard delivery of the conventional gas boiler
BM programming unit (incl. outside
sensor) as weather-compensated
temperature controller
• Room temperature-dependent/weather-compensated temperature control
• Time programs for central heating and DHW heating
• Backlit LCD screen
• Simple user prompts via plain text display
• Operation by rotary selector with pushbutton function
• 4 function keys for frequently used functions (heating, DHW, setback, info)
• Installation either inside the heat generator control unit, or as a remote control in a wall mounting base
• Optional for MM mixer module
• Only one programming unit required for multi circuit systems
• Can be extended with MM mixer module (up to 7 circuits with mixer)
• Fault diagnosis
BM programming unit with wall
mounting base (accessory) as
remote control
2-wire eBus connection
MM MIXER MODULE
• Extension module to control one circuit with mixer
• Weather-compensated flow temperature control
• Easy controller configuration by selecting one of the preset system versions
• BM programming unit can be attached to the appliance or fitted to a wall mounting base for use as a remote control
• Rast 5 connection technology
• Incl. flow temperature sensor
ART
• Analogue room temperature controller with day program for central heating and DHW
• Room temperature-dependent flow temperature
• Display for showing the room temperature, time and fault messages
• Room temperature-dependent frost protection
AWT
• Analogue weather-compensated temperature controller with day program for central heating and DHW
• Weather-compensated flow temperature
• Display for showing the room temperature, outside temperature, time and fault messages
• Room temperature hook-up
• Frost protection function
• Automatic energy saving appliance
1 ... 7
09
COMFORTLINE CONVENTIONAL GAS BOILER
Page 10
CONVENTIONAL GAS COMBI BOILER CONTROL ACCESSORIES
CGU-2(K)
WIRELESS RECEIVER
for external wireless sensor
2-wire eBus connection
EXTERNAL WIRELESS SENSOR
(only in conjunction with receiver for external wireless sensor and remote control, part no. 27 44 209)
and wireless remote control incl. radio clock (DCF77 signal)
WIRELESS REMOTE CONTROL
(only in conjunction with receiver for external wireless sensor and remote control). Max. one wireless remote control per circuit with mixer.
WOLF
portal server
DSL router
(LAN / WiFi)
Local (home) network
WiFi
LAN / WiFi
LAN / WiFi
LAN
WOLF LINK PRO
LAN / WLAN interface module for accessing the control via the Internet as well as a local network with PC or smartphone
eBus
Interface module
10
Page 11
CONVENTIONAL GAS COMBI BOILER
ACCESSORIES
CGU-2(K)
CGU-2 Conventional gas boiler for central heating with option to connect a DHW cylinder
CGU-2K Conventional gas boiler for central heating and DHW heating
Tested in accordance with EC directives and EN297, 483 and 625, and for heating systems according to EN1282 with flow temperatures up to 95°C and 3bar permissible operating pressure. Suitable for modulating operation down to room temperature; modulating output control. Flue gas monitoring with CGU-2K. Premix burner equipped and adjusted at the factory for natural gas E and LL. When ordering for LPG a conversion set is enclosed (loose). CGU-2K for chimney connection for open flue operation.
Control unit with gas burner control unit, electronic ignition and ionisation flame monitor.
White RAL 9016 powder-coated casing.
Accessories
Control accessories
BM programming unit
Wall mounting base
MM mixer module
ART analogue room temperature-dependent controller with day program
AWT analogue weather-compensated controller
Wireless receiver – required for external wireless sensor and wireless remote control
WRS remote maintenance system
Hydraulic accessories and gas supply accessories
Gas ball valve (angle or straight-through version), chrome plated, with or without thermally activated shut-o device
Drain set, safety valve with hose, hose retainer, trap and pipe collar, transparent plastic
Accessories for flush mounting
Concealed mounting bracket for installation on unfinished walls
CGU-2(K)
Angle maintenance valve G¾", chrome plated
Angle maintenance valve G¾" with connection R½" for safety valve, chrome plated
DHW connector G½", chrome plated
Cold water connector G½", chrome plated
Accessories for surface mounting
Connection set for installation on finished walls
Straight-through maintenance valve Rp¾", chrome plated
Straight-through maintenance valve Rp¾" with connection R½" for safety valve, chrome plated
DHW connector R½", chrome plated
Cold water connector R½" with shut-o valve, chrome plated
Surface mounting bracket for installation on finished walls
Air and flue gas accessories
Aluminium flue pipe Ø 110 mm
Aluminium flue pipe Ø 130mm
11
COMFORTLINE CONVENTIONAL GAS BOILER
Page 12
Dealer address
WOLF GMBH / P.O. BOX 1380 / D84048 MAINBURG / TEL. +49.0.8751740 / FAX +49.0.8751741600 / www.WOLF.eu
Doc. no. 4800589 GB 2018/07