Witt HR 1, HR 3, HS 30, HR 4, HS 40 Installation And Operating Instructions Manual [de, en]

...
Page 1
Hochdruckschwimmer­Regler
Montage- und Betriebsanleitung
High side float regulator
Installation- and operating instructions
HR/HS
Page 2
Montage- und Betriebsanleitung
HR / HS
operation and service manual
2
Page 3
MONTAGE- UND BETRIEBSANLEITUNG
INHALTSVERZEICHNIS CONTENTS
1. EINLEITUNG............................................................................ 4
1.1 VERWENDUNGSZWECK.............................................. 4
1.2 SICHERHEITSBESTIMMUNGEN .................................. 4
1.3 HAFTUNGSAUSSCHLUß.............................................. 4
HR / HS
1. INTRODUCION .........................................................................4
1.1 INTENDED USE .............................................................4
1.2 SAFETY REQUIREMENTS.............................................4
1.3 MANUFACTURER DISCLAIMER....................................4
OPERATION & SERVICE MANUAL
2. GEWÄHRLEISTUNGSBESTIMMUNGEN................................ 5
3. TECHNISCHE INFORMATION................................................. 5
3.1 TYPENBEZEICHNUNG ................................................. 5
3.2 LIEFERUMFANG........................................................... 6
3.3 ABNAHMEN/BESCHEINIGUNGEN ............................... 7
3.4 BESTELLANGABEN...................................................... 8
3.5 STEUEREINHEIT .......................................................... 9
4. TECHNISCHE DATEN ............................................................11
4.1 MATERIALIEN ..............................................................11
4.2 DRUCK/TEMPERATUR BEREICHE.............................11
4.3 ÜBERBLICK..................................................................12
4.4 ABMESSUNGEN ..........................................................17
4.5 GEÄNDERTE VENTILSTELLUNGEN...........................22
5. FUNKTIONSBESCHREIBUNG...............................................24
5.1 FUNKTION INNERHALB DER ANLAGE.......................24
5.2 SCHWIMMER-REGELUNG ..........................................27
5.3 FUNKTION DER UNTERDRUCKDÜSE........................27
6. PLANUNGSHINWEISE...........................................................30
6.1 ALLGEMEINES.............................................................30
6.2 AUSWAHLKRITERIEN .................................................30
6.3 ANORDNUNG...............................................................30
6.4 ZULAUFLEITUNG.........................................................33
6.5 EINSPRITZLEITUNG....................................................34
7. TRANSPORT UND LAGERUNG.............................................35
2. TERMS OF WARRENTY...........................................................5
3. TECHNICAL INFORMATION....................................................5
3.1 DESCRIPTION OF TYPES:............................................5
3.2 SCOPE OF DELIVERY...................................................6
3.3 INSPECTIONS/CERTIFICATES .....................................7
3.4 ORDERINFORMATION ..................................................8
3.5 CONTROL UNIT.............................................................9
4. TECHNICAL DATA .................................................................11
4.1 MATERIALS..................................................................11
4.2 PRESSURE/TEMPERATURE RANGE.........................11
4.3 OVERVIEW...................................................................12
4.4 DIMENSIONS ...............................................................17
4.5 MODIFIED VALVE POSITIONS....................................22
5. DESCRIPTION OF OPERATION ............................................24
5.1 OPERATION WITHIN THE PLANT...............................24
5.2 FLOAT REGULATION ..................................................27
5.3 FUNCTION OF THE LOW PRESSURE NOZZLE .........27
6. HINTS FOR PLANNING..........................................................30
6.1 GENERAL.....................................................................30
6.2 SELECTION CRITERIA................................................30
6.3 LOCATION ...................................................................30
6.4 LIQUID FEED LINE.......................................................33
6.5 LOW PRESSURE LINE FROM THE REGULATOR ......34
7. TRANSPORT AND STORAGE ...............................................35
8. MONTAGE .............................................................................35
8.1 MONTAGEVORBEREITUNG........................................35
8.2 MONTAGEANLEITUNG................................................36
9. INBETRIEBNAHME ................................................................36
9.1 VORBEREITUNG DER INBETRIEBNAHME.................36
9.2 INBETRIEBNAHME ......................................................37
10. BETRIEB.................................................................................37
11. WARTUNG UND INSTANDHALTUNG....................................37
11.1
11.2
11.3
11.4
11.5
11.6
12. FEHLERSUCHE......................................................................41
12.1
12.2
12.3
12.4
12.5
12.6
12.7
FUNKTIONSKONTROLLE.......................................37
AUSTAUSCH DES SCHWIMMKÖRPERS...............37
AUSTAUSCH DER HEBELPACKUNG ....................39
AUSTAUSCH DER VENTILPACKUNG....................40
ENTLÜFTUNG.........................................................40
ERWEITERUNG DER UNTERDRUCKDÜSE..........41
LUFT IN DER KÄLTEANLAGE ................................42
GASBILDUNG IN DER ZULAUFLEITUNG...............42
PARALLELSCHALTUNG VON VERFLÜSSIGERN..42
LUFTGEKÜHLTE VERFLÜSSIGER.........................42
PLATTENVERFLÜSSIGER .....................................43
HD-SAMMELBEHÄLTER.........................................43
EINSATZ VON ÖLKÜHLERN ..................................43
Th. Witt Kältemaschinenfabrik GmbH Lukasstrasse 32, D-52070 Aachen Tel. +49-241-18208-0, Fax. +49-241-18208-49 http://www.TH-WITT.com, [email protected]
W3510-6.01d – 07/2010
8. INSTALLATION .....................................................................35
8.1 PREPARING FOR INSTALLATION ..............................35
8.2 FIXING INSTRUCTIONS ..............................................36
9. COMMISSIONING...................................................................36
9.1 PRIOR TO COMMISSIONING ......................................36
9.2 COMMISSIONING ........................................................37
10. OPERATION ...........................................................................37
11. SERVICE AND MAINTANANCE .............................................37
11.1
11.2
11.3
11.4
11.5
11.6
12. TROUBLE SHOOTING ...........................................................41
12.1
12.2
12.3
12.4
12.5
12.6
12.7
FUNCTIONING CHECK...........................................37
REPLACING THE FLOAT BALL..............................37
REPLACING THE LEVER PACKING.......................39
REPLACEMENT OF THE VALVE PACKING...........40
PURGING................................................................40
ENLARGING THE LOW PRESSURE NOZZLE .......41
AIR IN THE REGRIGERATION SYSTEM................42
GAS FORMATION IN THE LIQUID FEED LINE ......42
PARALLEL OPERATION OF CONDENSERS .........42
AIRCOOLED CONDENSER....................................42
PLATE TYPE CONDENSER....................................43
USE OF HP LIQIUD RECEIVERS ...........................43
USE OF OIL COOLERS ..........................................43
3
Page 4
Hochdruckschwimmer-Regler
High Pressure Float Regulator
Montage- und Betriebsanleitung
1. EINLEITUNG
Bitte lesen Sie die komplette Betriebsanleitung sorgfältig, bevor Sie den Hochdruckschwimmer-Regler auswählen, in Gebrauch nehmen oder Wartungsarbeiten durchfüh­ren.
1.1 VERWENDUNGSZWECK
Der WITT Hochdruckschwimmer-Regler darf ausschließlich in Kälteanlagen eingesetzt werden, um verflüssigtes Kältemittel von der Hochdruckseite auf die Niederdruckseite zu entspan­nen.
1.2 SICHERHEITSBESTIMMUNGEN
1.3 HAFTUNGSAUSSCHLUß
Auch bei bestimmungsgemäßer Verwendung können Gefah­ren für Leib und Leben des Benutzers oder Dritter bzw. Beein­trächtigungen der Maschine und anderer Sachwerte entste­hen.
Übersetzungen werden nach bestem Wissen durchgeführt. Eine irgendwie geartete Haftung für Übersetzungsfehler kön­nen wir nicht übernehmen.
Gegenüber Darstellungen und Angaben dieser Betriebsanlei­tung sind technische Änderungen, die zur Verbesserung des Hochdruckschwimmer-Reglers notwendig werden, vorbehal­ten.
Sämtliche beschriebene Arbeiten an dem Hoch­druckschwimmer-Regler dürfen nur von sachkundi­gem, im Umgang mit Kälteanlagen geschultem Per­sonal durchgeführt werden, das die einschlägigen Vorschriften zur Erstellung und Wartung von Kältean­lagen kennt. Auch die Sicherheitsvorschriften hin­sichtlich des Umgangs mit Kältemittel sind zu beach­ten, insbesondere das Tragen der persönlichen Schutzbekleidung und einer Schutzbrille.
Die auf dem Typenschild und den Zeichnungen an­gegebenen Temperatur- und Druckangaben dürfen auf keinen Fall überschritten werden.
Wenn am Eintritts- und am Austrittsstutzen Absperr­ventile vorgesehen sind, so muss sichergestellt wer­den, dass die Ventile im Betrieb immer voll geöffnet bleiben. Achtung! Dem Inhalt dieser Betriebsanleitung ist unbedingt Folge zu leisten! Abweichender Einsatz schließt eine Haftung und Gewährleistung durch den Hersteller aus!
Die örtlichen Vorschriften für Kälteanlagen und Um­weltauflagen, insbesondere bei der Kältemittel- und Kälteölentsorgung sind einzuhalten.
97/23/EG
1. INTRODUCION
Please read the entire manual careful before select­ing, installing, commissioning or servicing the high­pressure float regulators.
1.1 INTENDED USE
The WITT high-pressure float regulator is intended for the use in refrigerant plants to expand liquid refrigerant from the high pressure to the low-pressure side.
1.2 SAFETY REQUIREMENTS
1.3 MANUFACTURER DISCLAIMER
Even when the float regulator is used for the specified intended purpose it cannot be totally excluded some danger for the life of the user may exist in the installation or system.
Translations are carried out to the best of our knowl­edge. We are unable to accept any liability for translation errors.
We reserve the right to change descriptions, graphs or other statements, which are required due to technical development of the high-pressure float regulators.
HR/HS
Installation- and operating instructions
Any of the following specified procedures must be carried out by trained and knowledgeable personnel experienced in installation and ser­vice of refrigerant plants. All personnel must be familiar with the National legal requirements and safety regulations. All safety regulations and codes of practice concerning the use of refrigerants must be adhered to, with special attention paid to protection clothing and wearing of safety glasses.
Under no circumstances are the stated design temperature- and pressure limitations on the data plate to be exceeded!
When installing inlet and outlet valves please ensure that the valves are fully open during
.
operation.
Important! The contents of this manual must be adhered to. Deviation from the specified conditions will make any claim for liability or warranty void.
All local rules for operation of refrigeration sys­tems and ecological requirements, especially waste treatment of refrigerants and oils must be complied with.
4
Page 5
2. GEWÄHRLEISTUNGSBESTIMMUNGEN
Zur Vermeidung von Unfällen dürfen an den Hochdruck­schwimmer-Reglern weder Veränderungen noch Umbauten vorgenommen werden, die durch die TH. WITT KÄLTEMA­SCHINENFABRIK GMBH nicht ausdrücklich schriftlich ge­nehmigt worden sind. Diese Betriebsanleitung enthält die international genormten SI-Maßeinheiten. Alle Angaben und Hinweise für die Bedienung und Instandhal­tung dieser Hochdruckschwimmer-Regler erfolgen unter Be­rücksichtigung unserer bisherigen Erfahrungen und Erkennt­nissen nach bestem Wissen.
Eine Haftung oder Gewährleistung ist ausgeschlossen, wenn:
• die Hinweise und Anweisungen der Betriebsanleitung nicht beachtet werden,
• die Hochdruckschwimmer-Regler einschließlich zugehöriger Einrichtungen fehlerhaft bedient werden bzw. deren Hand­habung nicht dem vorgeschriebenen Ablauf entspricht,
• die Hochdruckschwimmer-Regler entgegen ihrer Bestim­mung zweckentfremdet genutzt werden,
• Schutzeinrichtungen nicht benutzt oder außer Funktion gesetzt werden,
• Funktionsänderungen jeder Art ohne unsere schriftliche Zustimmung durchgeführt werden,
• die einschlägigen Sicherheitsbestimmungen nicht beachtet werden,
• die Hochdruckschwimmer-Regler unsachgemäß (zeitlich wie auch in der Ausführung) gewartet werden.
• beim Austausch von Teilen bzw. für die Ersatzteilbeschaf­fung nicht die vom Hersteller freigegebenen Originalersatz­teile verwendet werden.
3. TECHNISCHE INFORMATION
2. TERMS
In order to avoid accidents and ensure optimum per­formance, no modifications or conversions may be carried out to the high-pressure float regulator without the explicit written approval by TH.WITT KÄLTE­MASCHINENFABRIK GMBH. These instructions are based on internationally stan­dardised SI units of measurements. All data and information on the operation and mainte­nance of the float regulators are provided based on our extensive experience and to the best of our technical knowledge.
Our liability or warranty is excluded, if:
• The information and instructions in the operating manual are ignored,
• The high-pressure float regulators including accesso- ries are operated incorrectly or are not installed ac­cording to the instructions.
• The high-pressure float regulators are used for pur- pose other than that for which it was designed.
• Safety devices fitted are not used or disconnected
• There have been modifications made to the high
pressure float regulator without the manufacturers written approval
• The safety regulations are not adhered to
• The high-pressure float regulators have not been
maintained or repaired properly (regarding timing and execution)
• Parts that are used during maintenance or service are not the approved genuine TH. WITT spare parts.
OF
WARRENTY
3. TECHNICAL INFORMATION
3.1 TYPENBEZEICHNUNG
Es sind v
HR1 bis HR4 lieferbar. Außerdem bieten wir modular aufge­baute Regler vom Typ HS30 bis HS50, WPHR Schwimmer für Wärmepumpen-Anwendungen sowie HR1BW zur Kondensat­ableitung an.
Die Gehäuse können jeweils mit verschiedenen Schwimmer­kugeln ausgerüstet werden. Es werden N-Kugeln und R­Kugeln für unterschiedliche Kältemittel angeboten.
Die Ausführungen -H, -M, -L unterscheiden sich bzgl. Aus­trittsgeometrien bzw. Hebelübersetzungen.
HR-Regler kommen für Ammoniak-Anwendungen bis ca. 35°C Kondensationstemperatur und bei synthetischen Kälte­mitteln (z.B. HFCKW, FKW, HFO) über den gesamten Tem­peraurbereich zum Einsatz.
HS Regler ermöglichen bei kleiner Baugröße größere Leis­tungen. Auch bei geringer Dichte des Kältemittels (z.B. Am­moniak bei Kondensationstemperaturen > 35°C) sowie bei CO2-Anwendungen bis 40 bar sind HS-Regler die richtige Wahl.
WPHR-Regler wurden für den Einsatz in NH3 Wärmepumpen konstruiert. Sie sind für PS 40 oder PS 65 ausgelegt und enthalten einen druckentlastete Auftriebskörper.
Der HR1BW wurde speziell für die Kondensatableitung bei Heißgasabtauung entwickelt. Aber auch zur Ableitung von Flüssigkeit aus einem Enthitzer, sowie in Kombination mit einem Ölabscheider zur Ölrückführung, hat sich dieser Typ bewährt.
5
ier Baugrößen der Standard-Hochdruckschwimmer-
3.1 DESCRIPTION OF TYPES:
There are four sizes of standard float regulators avail­able: HR1 to HR4. Furthermore we offer modular designed regulators HS30 to HS50, WPHR types for heat-pump applications and a HR1BW for condensate draining.
The float regulator housing may be equipped with different types of float balls. There are type N- and R­ball floats available for different refrigerants.
Executions –H, -M, -L have different liquid orifice outlet dimensions respective varying lever transmissions.
HR-regulators are used for ammonia systems up to condensing temperatures of about 35°C andfor syn­thetic refrigerants (e.g. HCFC, HFC, HFO) over the entire temperature range.
HS-regutaors offer larger capacities at a reduced size of the housing. Also at low densities (e.g. ammonia at condensing temperatures > 35°C) or CO2 applications up to 40 bar, HS types are the right choice.
WPHR- types were designed for the use with NH3 heat pumps. They are rated for PS 40 or PS 65 and include a pressure-released float.
The type HR1 BW is especially designed for the con­densate drainage at hot gas defrost in systems with long hot gas lines. They are also favourable to work in conjunction with desuperheaters or in combination with an oil separator as an oil return.
Page 6
Fig.1a HR 1 – 3 Fig. 1b HR 4
3.2 LIEFERUMFANG
STANDARD LIEFERUMFANG HR
Absperrventile am Eintritt- und Austrittsstutzen bzw. ASTM-Stutzen Schedule40 (bitte angeben) Oben angebrachtes Regelventil zum Entlüften (EE3 bzw. EE6 bei HR4) Unten angebautes Entleerungsventil EA10 GB Nocken G ½” / G ¼” kombiniert für Anschluss eines Si­cherheitsventils (ab HR2) Integrierte Unterdruckdüse Blindkappe am Hebelaustritt Rahmen, nur für den HR4
OPTIONALER LIEFERUMFANG HR
Befestigungskonsolen (lose beigepackt) abweichende Ventilstellung (siehe Kap. 4.5) Unterdruckdüse verschlossen Entlüftungseinrichtung (aufsetzbares Wassergefäß mit Schlauchverbindung zum Entlüftungsventil) Einzelabnahme durch TÜV / andere Prüfgesellschaften Sonderausführungen auf Anfrage
3.2 SCOPE OF DELIVERY
STANDARD SCOPE OF DELIVERY HR
Stop valves at inlet and outlet respective ASTM connec­tions schedule 40 (please specify) Top mounted regulating valve for purging (EE3 resp. EE6 for HR4) Bottom mounted drainage valve EA10GB Combined G ½” / G ¼” threaded connection for safety valve (larger than HR2) Integrated low pressure nozzle Cap for hand lever control mounting frame, only for HR4
OPTIONAL SCOPE OF DELIVERY HR
Support brackets or mounting frame (supplied loose) Alternative valve connection positions (see chapter 4.5) Closed low pressure nozzle Gas purge kit (special water container with hose and connection to the purge valve) Individual inspections of TÜV or other institutions Special non standard executions upon request
Fig 1c HS30 – HS40
STANDARD LIEFERUMFANG HS
DIN- oder ASTM (Schedule 40) Eintrittsstutzen (bitte an­geben) Absperrventil oder ASTM-Stutzen am Austritt (bitte unbe­dingt angeben) Verlängertes Einstellventil EE6 zum Entlüften, oben am Deckel montiert Verlängertes Absperrventil EA10GB zum Entleeren, unten am Deckel montiert Blindkappe am Hebelaustritt Rahmen, nur für HS50
6
Fig. 1d HS50
STANDARD SCOPE OF DELIVERY HS
DIN-or ASTM (Schedule 40) inlet connection (please specify) Stop valve or ASTM connection at the outlet (please specify) Extended purge valve EE6, top mounted in the cover plate Extended stop valve EA10 GB for drainage, bottom mounted in the cover plate Cap for hand lever control Mounting frame, only for HS50
Page 7
OPTIONALER LIEFERUMFANG HS
Unterdruckdüse Entlüftungseinrichtung (aufsetzbares Wassergefäß mit Schlauchverbindung zum Entlüftungsventil) Einzelabnahme durch TÜV bzw. durch andere Prüfgesell­schaften
Fig. 1e WP2HR / WP3HR
OPTIONAL SCOPE OF DELIVERY HS
Low pressure nozzle for HS types Gas purge kit (special water container with hose and connection to the purge valve) Individual inspections of TÜV or other institutions
STANDARD LIEFERUMFANG WPHR
DIN Eintritts- und Austrittsstutzen Oben angebrachtes Regelventil EE3 zum Entlüften Unten angebautes Entleerungsventil EA10 GB Nocken G ½” / G ¼” kombiniert für Anschluss eines Si­cherheitsventils Integrierte Unterdruckdüse Blindkappe am Hebelaustritt
STANDARD LIEFERUMFANG HR1BW
DIN Eintrittsstuten Absperrventil EA10 am Austritt Blindkappe am Hebelaustritt
STANDARD SCOPE OF DELIVERY WPHR
DIN inlet and outlet connection Top mounted regulating valve EE3 for purging Bottom mounted drainage valve EA10GB Combined G ½” / G ¼” threaded connection for safety valve Integrated low pressure nozzle Cap for hand lever control
Fig. 1f HR1BW
STANDARD SCOPE OF DELIVERY HR1BW
DIN inlet connection Stop valve EA10 at the outlet Cap for hand lever control
3.3 ABNAHMEN/BESCHEINIGUNGEN
Hochdruckschwimmer Regler werden als druckhaltende Ausrüstungsteile ausgelegt, gefertigt und mit einer CE­Kennzeichnung gemäß Druckgeräterichtlinie ausgeliefert. Als Grundlage dient das AD-Regelwerk, sowie aktuelle Werkstoffnormen. Außerdem können die Regler mit einer GOST Kennzeich­nung bestellt werden. Eine Bescheinigung, dass die ATEX-Richtlinie nicht auf Hochdruckschwimmer-Regler anwendbar ist, wurde auf Grundlage der Zündgefahrenbewertung erstellt und ist auf Anfrage erhältlich.
7
3.3 INSPECTIONS/CERTIFICATES
High side float regulators are designed and manufac­tured as pressure resistant equipment and will be sup­plied with CE mark according to PED. The evaluation is based on the AD regulation and actual material standards.
The regulators can also be ordered with GOST mark.
A certificate, stating that the ATEX regulation does not apply to high side float regulators, is available upon request. It was based a risk assessment considering potential ignition sources .
Page 8
Falls gewünscht geänderte Ventilstellung gemäß Kapitel
3.4 BESTELLANGABEN
Zur richtigen Auswahl Ihres Hochdruckschwimmer­Reglers benötigen wir folgende Angaben:
• Kältemittel
• Kondensationstemperatur ....[ °C oder °F]
• Verdampfungstemperatur .....[°C oder °F]
• Kälte-/Wärmepumpenleistung ... [kW]
Haben Sie bereits einen Hochdruckschwimmer-Regler ausgewählt, geben Sie bitte folgende Daten an:
• Baugröße: HR 1 bis HR 4, bzw. HS30 bis HS50
• Kältemittel: N- oder R- Kugel bzw bei HS auch SK Kugel
• Ausführung: -L, -M, -H
• Mit / ohne Unterdruckdüse bei HS-Reglern
• WP HR Schwimmer in 40 oder 65 bar
• Erforderliche Abnahmen/Dokumentation
•
4.6
• Sonderausführungen
Bestelltext
z.B. HR3-H mit N-Kugel oder
bei HS Reglern steht die erste Zahl für die Baugröße und die zweite Zahl bedeutet: 1 N-Kugel ohne Unterdruckdüse 2 spezielle SK-Kugel ohne Unterdruckdüse 3 R-Kugel ohne Unterdruckdüse 4 N-Kugel mit Unterdruckdüse 5 spezielle SK-Kugel mit Unterdruckdüse 6 R-Kugel mit Unterdruckdüse z.B. HS34-M (HS-Regler mit N-Kugel, mit Unterdruckdüse und in M-Ausführung)
3.4 ORDERINFORMATION
In order to select the correct high side float regulator for your application we will need the following information
• Refrigerant
• Condensing temperature …. [°C or °F]
• Evaporating temperature....[°C or °F]
• Capacity … [KW]
Please always specify the following technical information when ordering a float regulator:
• Size: HR 1 to HR 4, resp. HS30 to HS50
• Refrigerant: N- or R-ball, resp. for HS also SK-ball
• Execution: –L, -M, -H
• With or without low pressure nozzle for HS-regulators
• WP HR regulators in 40 or 65 bar
• Required standard of inspection and certification
documentation.
• If required alternative valve position, see chapter 4.6
• Any special non standard requirements
Order text
e.g. HR3 with N-float ball or
for HS-regulators the first number indicates the size, wheras the second number has the following meaning:
1 N-float ball, without low pressure nozzle 2 special SK- ball, without low pressure nozzle 3 R- float ball, without low pressure nozzle 4 N-Kugel float ball, with low pressure nozzle 5 special SK- ball, with low pressure nozzle 6 R- float ball, with low pressure nozzle e.g. HS34-M (HS-regulator with N-float ball, with low pressure nozzle and M-execution)
Ersatzteilbestellungen
Die Schiebersteuerung betreffende Ersatzteile können nur als gesamte Steuereinheit geliefert werden, da eine Jus­tierung der Teile erforderlich ist.
Bitte geben Sie Typ, Kältemittel und Baujahr an, wenn Sie eine Steuereinheit bestellen: z.B. HR3 – M, NH3, 05/96
Ordering replacement parts
Replacements parts for the slide valve control are only available as a complete control unit, including the ball float, because all parts need to be adjusted.
Please indicate type, refrigerant and year when order­ing a control unit: e.g. HR3 – M, NH3, 05/96
8
Page 9
3.5 STEUEREINHEIT
3.5 CONTROL UNIT
Artikel-Nr.
Article No.
3591.000232
3591.000233
3591.000234
3591.000235
3591.000236
3591.000237
3591.000238
3591.000239
3591.000240
3591.000245
3591.000246
3591.000242
3591.000243
3591.000247
3591.000248
3591.000249
3591.000254
3591.000255
3591.000251
3591.000252
3591.000256
3591.000257
3591.000258
Typ
Model
HR1-L HR1-M HR1-H
HR1-L HR1-M HR1-H
HR2-L HR2-M HR2-H
HR2 SK-M HR2 SK-H
HR2-M HR2-H
HR3-L HR3-M HR3-H
HR3 SK-M HR3 SK-H
HR3-M HR3-H
HR4-L HR4-M HR4-H
Kugel-Art
Ball-type
1)
N N N
R R R
N N N
SK SK
R R
N N N
SK SK
R R
N N N
Drossel
Orifice
[mm²] [mm] [mm] ~ [mm] ~ [kg]
5 3 2
11
6 4
56 37 19
30 19
56 37
159 108
69 85
69
159 108
333 236 154
Unterdruckdüse ø
Low-press. nozzle
ø
0,7 0,7 0,7
0,7 0,7 0,7
1,5 1,5 1,0
2,0 1,5
1,5 1,0
3,0 3,0 2,0
3,0 2,0
3,0 2,0
6,0 6,0 4,0
Kugel ø
Ball ø
100 100 100
100 100 100
120 120 120
150 150
120 120
150 150 150
200 200
150 150
200 200 200
Länge Hebel
Length Lever
87 87 87
48 87 87
95 87 87
87 87
95 87
148 133 133
133 133
148 133
300 300 300
Gewicht Steuereinheit
Weight Control Unit
0,31 0,31 0,31
0,49 0,51 0,51
0,44 0,44 0,44
0,70 0,70
0,65 0,65
0,90 0,90 0,90
1,75 1,75
1,2 1,2
2,65 2,65 2,65
3591.000262 HR4 SK-H - 146 4,0 230 300 2,5
3591.000259
3591.000260
3591.000261
HR4-L HR4-M HR4-H
R R R
470 333 236
6,0 6,0 4,0
150 150 150
300 300 300
3,36 3,36 3,36
Steuereinheiten komplett bis 05/2009 Control unit complete until 05/2009
Artikel-Nr.
Article No.
3591.713001
3591.713002
3591.713003
3591.713004
3591.713005
3591.713006
3591.713007
3591.713008
3591.713009
3591.713010
3591.713011
3591.713012
3591.713013
3591.713014
3591.713015
3591.713016
3591.813001
3591.813002
3591.813003
Typ
Model
HS31-L HS31-M HS31-H
HS32-L HS32-M HS32-H
HS33-M HS33-H
HS34-L HS34-M HS34-H HS35-L HS35-M HS35-H
HS36-M HS36-H
HS41-L HS41-M HS41-H
Kugel-Art
Ball-type
1)
N N N
SK SK SK
R R
N N
N SK SK SK
R
R
N
N
N
Drossel
Orifice
[mm²] [mm] [mm] ~ [mm] ~ [kg]
56 37 19
52 30 19
56 37
56 37 19 52 30 19
56 37
159 108
69
Unterdruckdüse ø
Low-press. nozzle
ø
ohne
without
ohne
without
ohne
without
mit
with
mit
with
mit
with
ohne
without
Kugel ø
Ball ø
120 120 120
150 150 150
120 120
120 120 120 150 150 150
120 120
150 150 150
Länge Hebel
Length Lever
95 87 87
87 87 87
95 87
95 87 87 87 87 87
95 87
148 133 133
Gewicht Steuereinheit
Weight Control Unit
0,44 0,44 0,44
0,70 0,70 0,70
0,65 0,65
0,44 0,44 0,44 0,70 0,70 0,70
0,65 0,65
0,90 0,90 0,90
9
Page 10
3591.813004
3591.813005
3591.813006
HS42-L HS42-M HS425-H
SK SK SK
140
85 69
ohne
without
200 200 200
133 133 133
1,75 1,75 1,75
3591.813007
3591.813008
3591.813009
3591.813010
3591.813011
3591.813012
3591.813013
3591.813014
3591.813015
3591.813016
HS43-M HS43-H
HS44-L HS44-M HS44-H HS45-L HS45-M HS45-H
HS46-M HS46-H
R R
N N
N SK SK SK
R
R
159 108
159 108
69
140
85 69
159 108
ohne
without
mit
with
mit
with
mit
with
150 150
150 150 150 200 200 200
150 150
148 133
148 133 133 133 133 133
148 133
1,2 1,2
0,90 0,90 0,90 1,75 1,75 1,75
1,2 1,2
Steuereinheiten komplett für HS ab 06/2009 Control unit complete for HS until 05/2009
Artikel-Nr.
Article No.
3591.713021
3591.713022
3591.713023
3591.713024
3591.713025
3591.713026
3591.713027
3591.713028
3591.713029
3591.713030
3591.713031
3591.713032
3591.713033
3591.713034
3591.713035
3591.713036
3591.813021
3591.813022
3591.813023
3591.813024
3591.813025
3591.813026
Typ
Model
HS31-L HS31-M HS31-H
HS32-L HS32-M HS32-H
HS33-M HS33-H
HS34-L HS34-M HS34-H HS35-L HS35-M HS35-H
HS36-M HS36-H
HS41-L HS41-M HS41-H
HS42-L HS42-M HS425-H
Kugel-Art
Ball-type
1)
N
N
N
SK SK SK
R
R
N
N
N SK SK SK
R
R
N
N
N
SK SK SK
Drossel
Orifice
[mm²] [mm] [mm] ~ [mm] ~ [kg]
56 37 19
52 30 19
56 37
56 37 19 52 30 19
56 37
159 108
69
140
85 69
Unterdruckdüse ø
Low-press. nozzle
ø
ohne
without
ohne
without
ohne
without
mit
with
mit
with
mit
with
ohne
without
ohne
without
Kugel ø
Ball ø
120 120 120
150 150 150
120 120
120 120 120 150 150 150
120 120
150 150 150
200 200 200
Länge Hebel
Length Lever
95 87 87
87 87 87
95 87
95 87 87 87 87 87
95 87
148 133 133
133 133 133
Gewicht Steuereinheit
Weight Control Unit
0,44 0,44 0,44
0,70 0,70 0,70
0,65 0,65
0,44 0,44 0,44 0,70 0,70 0,70
0,65 0,65
0,90 0,90 0,90
1,75 1,75 1,75
3591.813027
3591.813028
3591.813029
3591.813030
3591.813031
3591.813032
3591.813033
3591.813034
3591.813035
3591.813036
HS43-M HS43-H
HS44-L HS44-M HS44-H HS45-L HS45-M HS45-H
HS46-M HS46-H
R
R
N
N
N SK SK SK
R
R
159 108
159 108
69
140
85 69
159 108
ohne
without
mit
with
mit
with
mit
with
150 150
150 150 150 200 200 200
150 150
148 133
148 133 133 133 133 133
148 133
1,2 1,2
0,90 0,90 0,90 1,75 1,75 1,75
1,2 1,2
3591.000256
3591.000257
3591.000258
3591.000259
3591.000260
3591.000261
HS51/54-L HS51/54-M HS51/54-H
HS53/56-L HS53/56-M HS53/56-H
N
N
N
R
R
R
333 236 154
470 333 236
ohne / optional
without / optional
ohne / optional
without / optional
200 200 200
200 200 200
300 300 300
300 300 300
2,65 2,65 2,65
3,36 3,36 3,36
10
Page 11
Artikel-Nr.
Article No.
3591.000244
3591.000253
3591.000270
3591.000232
3591.000233
3591.000234
3591.000235
3591.000236
3591.000237
1)
Kugel Art:
Typ
Model
WP2 HR WP3 HR WP3HR-65bar HR1 BW-L HR1 BW-M HR1 BW-H
HR1 BW-L HR1 BW-M HR1 BW-H
Kugel-Art
Ball-type
1)
WP WP WP
N N N
R R R
Drossel
Orifice
Unterdruckdüse ø
Low-press. nozzle ø
Kugel ø
Ball ø
Länge Hebel
Length Lever
Gewicht Steuereinheit
Weight Control Unit
[mm²] [mm] [mm] ~ [mm] ~ [kg]
11 46 46
5 3 2
11
6 4
1,8 3,0 3,0
-
-
-
-
-
-
1)
float ball type:
150 200 200 100 100 100
100 100 100
87 133 133
87
87
87
48
87
87
0,38 1,01 1,03 0,31 0,31 0,31
0,49 0,51 0,51
N für Kältemittel mit geringer Dichte ρ < 1000 kg/m³ N for refrigerants with low density ρ < 1000 kg/m³ z.B. NH3 (R717), Propan (R290), Öl e.g. NH3 (R717), Propan (R290), oil
R für Kältemittel mit einer Dichte ρ > 1000 kg/m³ R for refrigerants with density ρ > 1000 kg/m³ z.B. R22, R507, R134a, R404a e.g. R22, R507, R134a, R404a
SK für Kältemittel mit erhöhter Kondensationstemperatur SK for refrigerants with higher condensing temperature
WP für Einsatz in Wärmepumpen WP for heat pump applications
4. TECHNISCHE DATEN
4.
TECHNICAL
DATA
4.1 MATERIALIEN
Gehäusemantel: P 265 GH (St 35.8) Flansch: P 265 GH Klöpperböden: P 265 GH Schrauben: A2-70 Dichtung: Centellen Schutzkappe: Al Stopfbuchse: Al Stopfbuchspackung: Ne Hebel/Knebel: St Anstrich: W9.1 + W9.2 W9.1 + W9.2 = 2k Epoxydharz nach DIN ISO 12944/5, RAL 7001
4.2 DRUCK/TEMPERATUR BEREICHE HR, HS50 und HR1BW Hochdruckschwimmer-Regler
Max. zul. Druck PS: 25 bar zwischen +75 / -10°C,
18,75 bar zwischen -10 /-60°C
Prüfdruck Pt: 37 bar Öldruck
HS30 und HS40 Hochdruckschwimmer-Regler
Max. zul. Druck PS: 40 bar zwischen +75 / -10°C, 30 bar zwischen –10 / -60°C Prüfdruck Pt: 59 bar Öldruck
WP Hochdruckschwimmer-Regler
40 bar Ausführung
Max. zul. Druck PS: 40 bar zwischen +90 / -10°C, 30 bar zwischen –10 / -60°C Prüfdruck Pt: 59 bar Öldruck
WP Hochdruckschwimmer-Regler
65 bar Ausführung
Max. zul. Druck P
: 65 bar zwischen +100 / -10°C,
S
49 bar zwischen –10 / -60°C Prüfdruck Pt: 100 bar Öldruck
4.1 MATERIALS
Housing: P 265 GH (St 35.8) Flange: P 265 GH End caps: P 265 GH Bolts: A2-70 Gaskets: Centellen Cap: Al Gland: Al Packing: Ne Lever: St Painting system: W9.1 + W9.2 W9.1 + W9.2 = 2 k epoxy finish according to DIN ISO 12944/5, RAL 7001
4.2 PRESSURE/TEMPERATURE RANGE
HR, HS50 and HR1BW type high side float regulators
Max. allow. Pressure PS: 25 bar between +75 / -10 °C,
18.75 bar between –10 /-60 °C
Test Pressure: 37 bar oil pressure
HS30 and HS40 type high side float regulators
Max. allow. Pressure PS: 40 bar between +75 / -10 °C, 30 bar between –10 / -60°C Test pressure Pt: 59 bar oil pressure
WP type high side float regulators
40 bar execution
Max. allow. Pressure PS: 40 bar between +90 / -10 °C, 30 bar between –10 / -60°C Test pressure Pt: 59 bar oil pressure
WP type high side float regulators
65 bar execution
Max. allow. Pressure P
: 65 bar between +100 / -10 °C,
S
49 bar between –10 / -60°C Test pressure Pt: 100 bar oil pressure
11
Page 12
Steuereinheit,
41; 42; 43; 44; 2x45; 6x46, 2x 47
Befestigungskonsole
Entlüftungsvorric
Nur für NH
Dichtungssatz
1x31, 1x32, 6x33 2x34,1x35, 2x36
4.3 ÜBERBLICK 4.3 OVERVIEW
Hochdruckschwimmer-Regler Modelle
HR
Float Regulator Models
Fig. 2a HR1 – HR3
Fig. 2b HR4
Komplette HR-Austausch Baugruppen
Complete HR replacement assemblies
mit Teilen:
htung
mit Teilen 91; 92; 93
3
,
mit Teilen:
Control unit,
41; 42; 43; 44; 2x45; 6x46, 2x 47
Brackets Vent Device,
ammonia with parts 91; 92; 93
Set of gaskets
1x31, 1x32, 6x33, 2x34, 1x35, 2x36
12
with parts:
O
nly for
with parts:
Part
HR1 / HR1
No.
40
BW
Kap.3.4
chap. 3.4
HR2 /
WP2 HR
Kap.3.4 chap. 3.4
HR3 /
WP3 HR
Kap.3.4 chap. 3.4
HR4 /
HS50
Kap.3.4 chap. 3.4
HS30 HS40
Kap.3.4 chap. 3.4
70 3911.000010 3911.000010 3911.000010 ----- --- --­90
E30 3591.000363 3591.000364 3591.000365 3591.000366
3591.000346
bis/until 05/2009
3591.000395
ab/from 06/2009
3591.000401
Kap.3.4 chap. 3.4
bis/until 05/2009
3591.000396
ab/from 06/2009
3591.000402
Page 13
4.4 Overview
4.4 Überblick Schnittzeichnungen HS
Sectional drawings
Fig. 2c HS30 – HS40
Fig. 2c HS30 – HS40
13
Fig. 2d HS50
Page 14
Overview
4.4 Überblick Schnittzeichnungen WPHR / HR1BW
4.4
Sectional drawings
Fig. 2e WP2HR / WP3HR
14
Fig. 2f HR1BW
Page 15
A
n
zahl
A
n
zahl
Teileliste
Spezielle Ersatzteilwünsche nur nach Rücksprache mit dem Lieferanten!
Special parts only upon request!
No. Gehäuse Deckel Eingangsventil/Ausgangsventil Entlüftungsventil Ablaßventil 6kt - Schraube 6kt – Schraube für 65bar Ausführung 6kt - Schraube 6kt - Mutter Anschweißmutter Zylinderschraube mit Innen-6kt. (WP 2-3 HR) Zylinderschraube mit Innen-6kt. Flachdichtung Dichtung - Düseneinsatz Stopfbuchspackung zu 12 Stopfbuchspackung zu 13 Stopfbuchspackung zu 50 Flachdichtung zu 13 + 14 + 12 HR 1 BW Dichtung Düsenhalter Kugel Kugelarm Steuerschieber Düseneinsatz Bolzen Scheibe Splint Düsenhalter ( WP 2-3 HR ) Aufnahme-Platte ( WP 2-3 HR ) Drehachse Drehachse für WP 65bar Spannstift zu 50 Grundring Exzenter Spannstift zu 53 Flachkopfschraube / Bolzen ( HR 4 ) Zugstange / Druckstab Zugstange / Druckstab - WP HR Führungsbügel Unterdruckförderer Spannstift zu HR 1 BW Hebelstütze WP - HR Kupplungsstück WP - HR Stellring WP - HR Spannstift/Gewindestift WP - HR + HR 4 Schutzkappe zu 12 Schutzkappe zu 13 + 14 + 12 HR 1BW + 50 Stopfbuchse zu 12 Stopfbuchse zu 50 Blindkappe Überwurfmutter zu 12 HR 1 BW Schweißnippel zu 12 HR 1 BW Rahmenfuß Entlüftungsbehälter Schlauch komplett Schaftschraube
Teil Abmessung
main housing cover plate inlet valve vent valve drain valve cover plate hexagon screw cover plate hexagon screw for 65 bar hexagon head cap screw haxagon nut nut insert hexagon socket screw hexagon socket screw cover plate gasket gasket behind orifice house packing for 12 packing for 13 packing for 50 gasket for valve cap for 13+14+12 HR1BW gasket at orifice ball ball lever slide valve orifice block pin washer solit pin mount at orifice mounting plate spindle Spindle for WP 65bar locking pin for 50 base ring excenter for hand operation locking pin for 53 pan head screw/bolt tow/pressure bar tow/pressure bar guide bracket low pressure nozzle locking pin for HR 1 BW column for WP-HR
clutch .... for WP - HR
collet WP -HR locking pin/grub screw for WP - HR+HR 4 spindle cap for 12 spindle cap for 13+14+12 HR 1BW + 50 gland for 12 gland for 50 blind cap cap nut for 12 HR 1 BW welded-in stub frame, galvanized vent container hose threaded pin
Part Dimension
10 Typ 1 1 ----------------- Typ 2 1 ----------------- Typ 3 1 ----------------- Typ 4 1 ----------------­11 Typ 1 1 ----------------- Typ 2 1 ----------------- Typ 3 1 ----------------- Typ 4 1 ----------------­12 EA 20 1 ----------------- EA 32 1 ----------------- EA 50 1 ----------------- EA 80 1 ----------------­13 EE 3 GB 1 ----------------- EE 3 GB 1 ----------------- EE 3 GB 1 ----------------- EE 6 GB 1 ----------------­14 EA 10 GB 1 ----------------- EA 10 GB 1 ----------------- EA 10 GB 1 ----------------- EA 10 GB 1 ----------------­21 M16x40 6 5111.CLA3B3 M16x40 8 5111.CLA3B3 M16x50 12 5111.CLA3BD M16 x 50 12 5111.CLA3BD
21 M20x70 16 5111.CLC2BX 22a ------------ -- ----------------- ------------ -- ----------------- ------------ -- ----------------- M12 x 35 4 5111.CH81AY 22b ------------ -- ----------------- ------------ -- ----------------- ------------ -- ----------------- M12 4 5151.AH8100
23 M 10 1 ----------------- M 10 1 ----------------- M 10 1 ----------------- --------------- -- -----------------
24 ------------ -- ----------------- M8x30 2 ----------------- M8x30 2 ----------------- ------------ -- -----------------
25 M8x20 2 5112.BC61AJ M8x20 2 5112.BC61AJ M8x20 2 5112.BC61AJ M6x20 2 5112.BC51AJ
31 125/145x2 1 5632.1DGE0K 180/200x2 1 5632.1EZFJK 260/280x2 1 5632.1H7HRK 260/280x2 1 5632.1H7HRK
32 18/50x2 1 5632.1AHBDK 18/50x2 1 5632.1AHBDK 26x60x2 1 5632.1APBNK 43/74x2 1 5632.1B6C1K
33 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 12x4 3 5642.ABAX02 19x4 3 5642.ABBL01
34 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01
35 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 12x4 3 5642.ABAX02
36 10/18x2 1 5632.1A9AHK 10/18x2 1 5632.1A9AHK 10/18x2 1 5632.1A9AHK 10/18x2 1 5632.1A9AHK
37 ------------ -- ----------------- ø 45x2 1 ----------------- ø 60x2 1 ----------------- ------------ -- -----------------
41 ø 100 1 ----------------- ø 120 1 ----------------- ø 150 1 ----------------- ø 200 1 -----------------
42 Typ 1 1 ----------------- Typ 2 1 ----------------- Typ 3 1 ----------------- Typ 4 1 -----------------
43 34x15x12,5 1 ----------------- 34x15x12,5 1 ----------------- 40x25x12.5 1 ----------------- 60x40x20,5 1 -----------------
44 50x35x18 1 ----------------- 50x35x18 1 ----------------- 60x44x26 1 ----------------- 85x44x65 1 -----------------
45 ø 4x25 2 ----------------- ø 4x25 2 ----------------- ø 4x35 2 ----------------- ø 4x35x22 2 -----------------
46 A 4,3 6 ----------------- A 4,3 6 ----------------- A 4,3 6 ----------------- A 4,3 6 -----------------
47 ø 1x15 2 ----------------- ø 1x15 2 ----------------- ø 1x15 2 ----------------- ø 1x15 2 -----------------
48 ------------ -- ----------------- Typ 1 1 ----------------- Typ 2 1 ----------------- ------------ -- -----------------
49 ------------ -- ----------------- ø 45x19 1 ----------------- ø 60x19 1 ----------------- ------------ -- -----------------
50 ø 8x115 1 3591.000123 ø 8x135 1 3591.000124 ø 8x135 1 3591.000124 ø 14x200 1 3591.000125
50 ø 8x200 1 3591.000120
51 ø 3x10 1 5723.AA0301 ø 3x10 1 5723.AA0301 ø 3x10 1 5723.AA0301 --------------- -- -----------------
52 ø 13x8x2 1 6438.000004 ø 13x8x2 1 6438.000004 ø 13x8x2 1 6438.000004 --------------- -- -----------------
53 ø 25x15 1 3591.000115 ø 35x15 1 3591.000116 ø 35x15 1 3591.000116 ø 40x16 1 3591.000117
54 ø 3x30 1 5723.AA0302 ø 3x30 1 5723.AA0302 ø 3x30 1 5723.AA0302 ø 3x30 1 5723.AA0302
55 M4 x 5 1 5117.AB30A4 M4 x 5 1 5117.AB30A4 M4 x 5 1 5117.AB30A4 ø 4x25x22 1 5724.A00401
56 ø 3x60 1 3591.000095 ø 3x94 1 3591.000096 ø 3x121 1 3591.000097 ø 8x1x235 1 3591.000100
56 ------------ -- ----------------- ø 3x94 1 3591.000096 ø 3x118 1 3591.000093 --------------- -- -----------------
57 ------------ -- ----------------- 67,5x50x15 1 ----------------- 65,5x60x15 1 ----------------- --------------- -- -----------------
58 ø 6x1x107 1 ----------------- ø 6x1x156 1 ----------------- ø 6x1x230 1 ----------------- ø 6x1x360 1 -----------------
59 ø 3x30 1 ----------------- ----------------- -- ----------------- ----------------- -- ----------------- --------------- -- -----------------
60 ------------ -- ----------------- Typ 1 1 3591.000111 Typ 2 1 3591.000112 ------------ -- -----------------
61 ------------ -- ----------------- ø 50x30 1 3591.000118 ø 50x30 1 3591.000118 ------------ -- -----------------
62 ------------ -- ----------------- ø 8/16x15 1 3591.000126 ø 8/16x15 1 3591.000126 ø 14/40x16 1 3591.000127
63 ------------ -- ----------------- ø 3x30 1 5723.AA0302 ø 3x30 1 5723.AA0302 M6x12 1 5121.CD50AB
71 SW 27 2 6436.AAP270 SW 27 2 6436.AAP270 SW 27 2 6436.AAP270 SW 46 2 6436.AAP460
72 SW 27 2 6436.AAP270 SW 27 2 6436.AAP270 SW 27 2 6436.AAP270 SW 27 2 6436.AAP270
73 SW 12 1 6438.000006 SW 12 1 6438.000006 SW 17 1 6438.000002 SW 22 1 6438.000003
74 SW 12 1 6438.000001 SW 12 1 6438.000001 SW 12 1 6438.000001 SW 17 1 6438.000002
75 G 1/2 2 6436.ABDD00 G 1/2 2 6436.ABDD00 G 1/2 2 6436.ABDD00 G 1/2 2 6436.ABDD00
76 SW 27 1 6436.ACDD00 ------------ -- ----------------- ------------ -- ----------------- ------------ -- -----------------
77 6/13 1 6424.AH0001 ------------ -- ----------------- ------------ -- ----------------- ------------ -- -----------------
81 ------------ -- ----------------- ----------------- -- ----------------- ----------------- -- ----------------- 600x495 2 -----------------
91 ------------ 1 ----------------- ------------ 1 ----------------- ------------ 1 ----------------- ------------ 1 -----------------
92 ------------ 1 ----------------- ------------ 1 ----------------- ------------ 1 ----------------- ------------ 1 -----------------
93 M 10x65 1 ----------------- M 10x65 1 ----------------- M 10x65 1 ----------------- M 10x65 1 -----------------
HR 1 / HR 1 BW HR 2 HR 3 HR 4
WP 2 HR WP 3 HR
Artikelnr. Abmessung Artikelnr. Abmessung Artikelnr. Abmessung
Part - No. Dimension Part - No. Dimension Part - No. Dimension
Anzahl
quantity
quantity
quantity
Parts-List
Artikelnr.
Part - No.
Anzahl
quantity
15
Page 16
Teileliste
A
n
zahl
A
n
zahl
A
n
zahl
Spezielle Ersatzteilwünsche nur nach Rücksprache mit dem Lieferanten!
Special parts only upon request!
No. Gehäuse Deckel Eingangsventil Entlüftungsventil Ablaßventil 6kt - Schraube 6kt - Schraube 6kt - Mutter Zylinderschraube mit Innen-6kt. Zylinderschraube mit Innen-6kt. (Sonderkugel) Zylinderschraube mit Innen-6kt. Flachdichtung Dichtung - Düseneinsatz Stopfbuchspackung zu 12 Stopfbuchspackung zu 13 + 14 Stopfbuchspackung zu 50 Flachdichtung zu 13 + 14 Dichtung Düsenhalter Kugel Kugelarm Steuerschieber Düseneinsatz Bolzen Scheibe Splint Düsenhalter Aufnahme-Platte
Drehachse Spannstift zu 50
Exzenter Spannstift zu 53 Flachkopfschraube / Bolzen ( HR 4 ) Zugstange / Druckstab Zugstange / Druckstab - HR SK
Führungsbügel Unterdruckförderer Hebelstütze Kupplungsstück Kupplungsstück
Spannstift/Gewindestift HS 50 Schutzkappe zu 12 Schutzkappe zu 13 + 14 + 50 Stopfbuchse zu 12 Stopfbuchse zu 50 Blindkappe
Rahmenfuß Entlüftungsbehälter Schlauch komplett Schaftschraube
Teil Abmessung Artikelnr. Abmessung Artikelnr. Abmessung Artikelnr. part
main housing cover plate outlet valve vent valve drain valve cover plate hexagon screw hexagon head cap screw haxagon nut hexagon socket screw hexagon socket screw hexagon socket screw cover plate gasket gasket behind orifice house packing for 12 packing for 13 + 14 packing for 50 gasket for valve cap for 13+14 gasket at orifice ball ball lever slide valve orifice block pin washer solit pin mount at orifice mounting plate
stem for hand operation locking pin for 50
excenter for hand operation locking pin for 53 pan head screw/bolt tow/pressure bar tow/pressure bar
guide bracket low pressure nozzle column
clutch ....
clutch ....
locking pin/grub screw for HS 50 spindle cap for 12 spindle cap for 13+14 + 50 gland for 12 gland for 50 blind cap
frame, galvanized vent container hose threaded pin
10 Typ 3 1 ----.------ Typ 4 1 ----.------ Typ 5 1 ----.------
11 Typ 3 1 ----.------ Typ 4 1 ----.------ Typ 5 1 ----.------
12 EA 50 1 ----.------ EA 80 1 ----.------ EA 80 1 ----.------
13 EE 6 GB/L 1 ----.------ EE 6 GB/L 1 ----.------ EE 6 GB 1 ----.------
14 EA 10 GB/L 1 ----.------ EA 10 GB/L 1 ----.------ EA 10 GB 1 ----.------
21 M16x60 12 5111.CLA3BN M16x70 12 5111.CLA3BX M16x50 12 5111.CLA3BD 22a ---------- -- ----.------ ---------- -- ----.------ M12x35 4 5111.CH81AY 22b ---------- -- ----.------ ---------- -- ----.------ M12 4 5151.AH8100 24a M8x30 2 5112.BC61AT M8x45 2 5112.BC61B8 ---------- -- ----.-----­24b M8x45 2 5112.BC61B8 M8x65 2 5112.BC61BS ---------- -- ----.------
25 M8x20 2 5112.BC61AJ M8x20 2 5112.BC61AJ M6x20 2 5112.BC51AJ
31 206/225x2 1 5632.1FPG8K 311/330x2 1 5632.1IMJ5K 260/280x2 2 5632.1H7HRK
32 18/50x2 1 5632.1AHBDK 26/50x2 1 5632.1APBNK 43/74x2 1 5632.1B6C1K
33 12x4 3 5642.ABAX02 19x4 3 5642.ABBL01 19x4 3 5642.ABBL01
34 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01
35 8/14x8 1 5643.ABAP01 8/14x8 1 5643.ABAP01 12x4 3 5642.ABAX02
36 10/18x2 1 5632.1A9AHK 10/18x2 1 5632.1A9AHK 10/18x2 1 5632.1A9AHK
37 45x2 1-2 ----.------ 60x2 1-2 ----.------ ---------- -- ----.------
41 ø120/ø150 1 ----.------ ø150/ø200 1 ----.------ ø200 1 ----.------
42 Typ 2 1 ----.------ Typ 3 1 ----.------ Typ 4 1 ----.------
43 34x15x12.5 1 ----.------ 40x25x12.5 1 ----.------ 60x40x20.5 1 ----.------
44 50x35x18 1 ----.------ 60x44x26 1 ----.------ 75x85x44 1 ----.------
45 ø4x25 2 ----.------ ø4x35 2 ----.------ ø4x35x22 2 ----.------
46 A 4,3 6 ----.------ A 4,3 6 ----.------ A 4,3 6 ----.------
47 ø1x15 2 ----.------ ø1x15 2 ----.------ ø1x15 2 ----.------
48 Typ 1 1 ----.------ Typ 2 1 ----.------ Typ 3 1 ----.------
49 ø60x19 1 ----.------ ø88x25 1 ----.------ ---------- -- ----.------
50 ø 8x185 1 3591.045010 ø 8x185 1 3591.045010 ø 14x200 1 3591.000125
51 ø 3x10 1 5723.AA0301 ø 3x10 1 5723.AA0301 ---------- -- ----.------
53 76-5/10 1 3591.043008 76-5/10 1 3591.043008 ø 40x16 1 3591.000117
54 ---------- -- ----.------ ---------- -- ----.------ ø 3x30 1 5723.AA0302
55 M4x5 1 5117.AB30A4 M4x5 1 5117.AB30A4 ø 4x25x22 1 5724.A00401
56
56
57 67.5x50x15 1 ----.------ 65.5x60x15 1 ----.------ ---------- - ----.------
58 ø 6x1x136 1 ----.------ ø 6x1x230 1 ----.------ ø 6x1x360 1 ----.------
60 HS 3 1 3591.042005 HS 4 1 3591.042006 ---------- 1 ----.-----­61a ø 14 1 2441.001001 ø 14 1 2441.001001 ---------- -- ----.-----­61b ø 8 1 2441.001002 ø 8 1 2441.001002 ---------- -- ----.------
63 ---------- -- ----.------ ---------- -- ----.------ M 6x12 1 5121.CD50AB
71 SW 27 1 6436.AAP270 SW 46 1 6436.AAP460 SW 46 1 6436.AAP460
72 SW 27 3 6436.AAP270 SW 27 3 6436.AAP270 SW 27 3 6436.AAP270
73 SW 17 1 6438.000002 SW 17 1 6438.000002 SW 22 1 6438.000003
74 SW 12 1 6438.000001 SW 12 1 6438.000001 SW 17 1 6438.000002
75 G 1/2" 2 6436.ABDD00 G 1/2" 2 6436.ABDD00 G 1/2" 2 6436.ABDD00
81 ---------- -- ----.------ ---------- -- ----.------ 600x495 2 ----.------
91 ---------- 1 ----.------ ---------- 1 ----.------ ---------- 1 ----.------
92 ---------- 1 ----.------ ---------- 1 ----.------ ---------- 1 ----.------
93 M 10 1 ----.------ M 10 1 ----.------ M 10 1 ----.------
HS 30 HS 40 HS 50
Dimension Part - No. Dimension Part - No. Dimension Part - No.
ø 3x__ 1 ----.------ ø 3x__ 1 ----.------ ø 8x1x235 1 3591.000100 ø 3x__ 1 ----.------ ø 3x__ 1 ----.------ ø 8x1x235 1 3591.000100
quantity
quantity
Parts-List
quantity
16
Page 17
4.4 ABMESSUNGEN Fig. 3a
HR 1 - 3
4.4 DIMENSIONS
Ausführung mit Ventilen Execution with valves
Ausführung ohne Ventile, Schedule 40 Stutzen Execution without valves, Schedule 40 connections
HR1 46 53 90 160 200 139 440 425 265 200 65 390 26,9x2,3 26,9x2,9 13 HR2 50 71,5 105 160 250 194 480 445 285 200 90 450 42,4x2,6 42,4x3,6 23 HR3 90 95 115 160 345 273 640 555 395 260 135 530 60,3x2,9 60,3x4,0 54
HR1 1.81 2.09 3.54 6.3 7.87 5.47 17.32 16.73 10.43 7.87 2.56 15.35 1.06x0.09 1.06x0.11 28.6 HR2 1.97 2.81 4.13 6.3 9.84 7.64 18.90 17.52 11.22 7.87 3.54 17.72 1.67x0.10 1.67x0.14 50.7 HR3 3.54 3.74 4.53 6.3 13.58 10.75 25.20 21.85 15.55 10.24 5.31 20.87 2.37x0.11 2.37x0.16 119
17
a1
mm
a1
inch
a2
mm
a2
inch
e1
mm
e1
inch
e2
mm
e2
inch
d1
mm
d1
inch
d2
mm
d2
inch
l1
mm
l1
inch
l2
mm
l2
inch
l3
mm
l3
inch
h1
mm
h1
inch
h2
mm h mm
h2
inch h inch
d x s
mmxmm
d x s
inch
d x s1
mmxmm
d x s1
inch
Gewicht
Weight
kg
Gewicht
Weight
lb
Page 18
4.4 Abmessungen HR 4
Fig. 3b
4.4 Dimensions
HR4 mit Absperrventilen am Eintritt und Austritt HR4 with stop-valves at inlet and outlet
HR4 mit Schedule 40 Anschluss-stutzen HR4 with Schedule 40 connections
18
Page 19
4.4 Abmessungen
Fig. 3c
HS 30 -40
4.4 Dimensions
HS30 /HS40 mit Austrittsventil HS30 /HS40 with outlet stop-valve
HS30 /HS40 mit Schedule 40 Anschlüssen HS30 /HS40 with Schedule 40 connections
a1
a2
a3
d1
mm
mm
mm
mm
HS30 90 255 180 290 219,1 114,3x3,6 60,3x2,9 115 555 510 655 460 155 127 49 HS40 147 355 262 400 323,9 168,3x4,5 88,9x5,6 155 750 685 775 585 194 154 107
d2
mm
d3xs
mmxmm
d4xs
mmxmm
e1
mm h mm
h1
mm
l1
mm
l2
mm
l3
mm
l4
mm
Gewicht
Weight
kg
HS30 3.7 10.04 7,08 11.42 8.63 4.5x0.24 2.37x0.16 4.53 21.8 20.08 25.79 18.11 6.10 5,00 108,02 HS40 5.79 14 10,31 15.75 12.75 6.63x0.28 2.71x0.22 6.1 29.52 26.97 30.51 23.03 7.68 6.06 235,89
a1
inch
a2
inch
a3
inch
d1
inch
d2
inch
d3xs1
inch
d4xs2
inch
e1
inch h inch
h1
inch
l1
inch
l2
inch
l3
inch
l4
inch
Gewicht
Weight
lb
19
Page 20
4.4 Abmessungen
Fig. 3d
HS 50
4.4 Dimensions
HS50 mit Austrittsventil HS50 with stop-valve at the outlet
HS50 mit Schedule 40 Anschluss-Stutzen HS50 with Schedule 40 connections
20
Page 21
WP3HR
-
65bar
4.4 Abmessungen WPHR / HR1BW
4.4 Dimensions
Fig. 3e WP2HR / WP3HR
a1
mm
a2
mm
b
mm
e
mm
d1
mm
d2
mm
l1
mm
h
mm
dxs
mmxmm
Gewicht
Weight
kg
WP2HR 200 100 275 230 250 194 475 460 42,4x2,6 26 WP3HR 270 140 375 275 345 273 640 545 60,3x2,9 61
270 150 375 275 355 273 650 545 60,3x2,9 68
a1
inch
a2
inch
b
inch
e
inch
d1
inch
d2
inch
l1
inch
h
inch
dxs
inchxinch
Gewicht
Weight
lb
WP2HR 7.87 3.94 10.83 9.06 9.84 7.64 18.7 18.11 1.67x0.1 57.32 WP3HR 10.63 5.51 14.76 10.83 13.58 10.75 25.2 21.46 2.37x0.11 134.48
WP3HR-
65bar
10.63 5.90 14.76 10.83 13.98 10.75 25.6 21.46 2.37x0.11 150,00
Fig. 3f HR1BW
21
Page 22
4.5 GEÄNDERTE VENTILSTELLUNGEN
Fig. 4a
HR 1 - 3
4.5 MODIFIED VALVE POSITIONS
22
Page 23
4
.5 geänderte Ventilstellungen
Fig. 4b
4.5 Modified Valve Positions
HR 4
23
Page 24
5. FUNKTIONSBESCHREIBUNG
Der Hochdruckschwimmer-Regler entspannt alles auf der Hochdruckseite anfallende Kältemittel auf die Nie­derdruckseite, ohne jedoch Gas durchzulassen. Durch diese einfache mechanische Methode wird eine äußerst energiesparende Betriebsweise ohne elektrische Rege­lung ermöglicht.
5.1 FUNKTION INNERHALB DER ANLAGE
5.1.1 Einstufige Anlage
Das Prinzip der Hochdruckschwimmer-Regelung für eine einstufige Anlage ist in Fig. 5 dargestellt.
5. DESCRIPTION OF OPERATION
The high-pressure float regulator expands all liquid refriger­ant condensed on the high-pressure side of the system to the low-pressure, but prevents any gas from flowing through the regulator. This simple mechanical operation enables a very energy efficient operation, eliminating the need for complicated electrical controls.
5.1 OPERATION WITHIN THE PLANT
5.1.1 Single stage plant design
The principle of a float regulation for a single stage plant is shown in fig. 5.
Prinzip einer einstufigen Anlage Im Verflüssiger anfallendes flüssiges Kältemittel gelangt
in den Schwimmer und wird dort bei konstanter Enthal­pie zur Niederdruckseite entspannt. Durch die Entspannung im Austritt des Hochdruck­schwimmer-Reglers befindet sich hinter dem Hoch­druckschwimmer-Regler ein Flüssigkeits-/Gasgemisch, das zum Abscheider strömt. Vom Abscheider aus kann das Gas wieder dem Verdich­ter, bzw. die Flüssigkeit den Verdampfern zugeführt werden. Die Kondensattemperatur kann sich den äußeren Gege­benheiten entsprechend optimal anpassen, wodurch eine sehr energiesparende Betriebsweise gewährleistet wird. Eine Unterkühlung der Flüssigkeit ist normalerwei­se ausgeschlossen.
5.1.2 Zweistufige Anlage
Das Prinzip für eine zweistufige Anlage stellt die folgen­de Abbildung, Fig. 6, dar.
Fig. 5
Principle of a single stage plant Any refrigerant liquid condensate that forms in the con-
denser will flow to the float regulator and will be expanded to the low-pressure side at constant enthalpy.
As a result of the liquid expansion there is a mixture of flash gas and liquid refrigerant in the liquid line from the regulator to the surge drum.
The resulting flash gas will be drawn from the surge drum by the compressor while the liquid feed to the surge drum will be distributed to the low side evaporators.
The condensing temperature varies according to the ambi­ent temperature conditions, allowing an energy-saving op­eration.
Sub cooling of the liquid is not possible at normal operating conditions.
5.1.2 Two-stage plant design
The principle of a two-stage plant with float regulation is shown in fig. 6.
Prinzip einer zweistufigen Anlage
24
Fig. 6
Principle of a two stage plant
Page 25
Auch hier ist ein Hochdruckschwimmer-Regler zwischen Verflüssiger und Abscheider montiert, der das Kondensat auf den Mitteldruck entspannt. Ein zweiter Regler wird verwendet, um das Kältemittel zur Niederdruckseite zu entspannen. Zweistufige Kälteanlagen mit Hochdruck­schwimmer-Regelung haben einen verbesserten Wir­kungsgrad und vermeiden hohe Endtemperaturen der Verdichtung
Da der zwischen MD- und ND-Seite montierte Hochdruckschwimmer-Regler das Kältemittel aus dem MD-Behälter bis zu seinem Abgriffspunkt zur ND-Seite ableitet, ist der ND-Behälter so auszu­führen, dass die komplette schwankende Kälte­mittelmenge aufgenommen werden kann (ND­Seite und Überschuss der MD-Seite!).
The system uses a float regulator between condenser
and surge drum, this expands the liquid refrigerant to the
intermediate pressure. A second regulator is used to
expand the liquid refrigerant further to the low-pressure
side of the system.
Two stage refrigeration systems with float regulation
have an improved efficiency and avoid very high gas
temperatures for second stage compression.
As all the liquid from the condenser and inter­mediate vessel up to the connection to the second float regulator is passed to the surge drum on the low pressure side, this has to be designed to accommodate the full amount of fluctuating refrigerant charge (low pressure side and excess of the intermediate side.
5.1.3 Abtauen von Verdampfergruppen
Bei gängigen Abtauzeiten der Verdampfer (ca. 30 min) reicht für die Auslegung des Hochdruckschwimmer­Reglers eine 1,5 - 2 fache Leistung der gleichzeitig abtau­enden Verdampfer aus. Sollten kürzere Abtauzeiten erfor­derlich sein, muss die Leistung auf das 3 – 4-fache der gleichzeitig abtauenden Verdampfer erhöht werden.
Die konventionelle Methode Verdampfer abzutauen ist in nachfolgender Zeichnung 7a beschrieben. Sie bietet sich an, wenn Verdampfer mit großen Leistungen eingesetzt werden.
Dabei wird pro Verdampfer ein Hochdruckschwimmer­Regler vorgesehen, der das Kondensat in die Saugleitung zurückführt. Eine Standard-Unterdruckdüse reicht in der Regel aus, um ein Gaspolster zu verhindern.
Ein hinter dem Regler montiertes Rückschlagventil verhin­dert ein Rückströmen von Kältemittel, wenn einzelne Ver­dampfer abgetaut werden.
Diese Funktion kann auch von einem automatisch betätig­baren Ventil bzw. Kugelhahn übernommen werden.
Wenn der Druck im Normalbetrieb den Öffnungsdruck des Rückschlagventils übersteigt (z.B. bei Einsatz von Ver­dampferdruckreglern), sollte auf jeden Fall ein automati­sches Ventil/Kugelhahn eingesetzt werden.
5.1.3 Hot Gas Defrosting of evaporators
For common defrost periods (ca. 30 min) the high side
float regulator has to be sized for 1,5 - 2 times the ca-
pacity of the evaporators that are defrosted at the same
time. If shorter defrost periods are required the capacity
has to be increased up to 3 – 4 times the capacity of the
evaporators that are defrosted at the same time.
The conventional method of defrosting evaporators is
shown in fig. 7a. This method is used particularly for
evaporators with large capacities.
There is one high side float regulator for each evaporator
that drains condensate in the common pump return line.
A standard low pressure nozzle is normally sufficient to
avoid a gas buffer in the regulator housing.
A check valve that is mounted behind the regulator will
prevent a backflow of refrigerant when other evaporators
are defrosted.
For this function you may also use an automatic oper-
ated valve or ball valve.
If the pressure during the normal refrigeration cycle can
exceed the pressure that will open the check valve (e.g.
when using back pressure regulators) you should always
select an automatic operated valve instead of a check
valve!
Konventionelle Anordnung
Fig. 7a
Conventional defrost installtion
25
Page 26
Für die schnelle Kondensatableitung beim Abtauen von Verdampfergruppen hat sich die nachfolgende, kosten­günstige Anordnung nach Fig. 7b bewährt.
ca. 2%
For fast condensate drainage of evaporators the following cost-effective arrangement, according to fig. 7b, has worked well.
Anordnung der Verdampfergruppen
Fig. 7b
Bei der Einbindung der Verdampfer ist darauf zu achten, dass die Heißgasleitung mit etwa 1-2% Gefälle zum HR1 BW verlegt wird (siehe Fig. 7b ). Der HR1BW leitet das Kondensat der Heißgasleitung ab und verhindert so ein schlagartiges Verdampfen von Rest­Flüssigkeit beim Einsetzten der Heißgansabtauung.
Am Ende der Kondensatleitung soll ein Hochdruck­schwimmer-Regler mit verschlossener Unterdruckdüse montiert werden. Wenn das Magnetventil nach Beendigung der Heißgasab­tauung geschlossen wird verhindert das eingeschlossene Gaspolster, das Flüssigkeit im normalen Betrieb durch den Regler gedrückt werden kann.
Ein Überströmventil in einer Bypassleitung zwischen Kon­densat- und Saugleitung dient der Absicherung der Kon­densatleitung, falls der Druck unzulässig ansteigt.
5.1.4 HR1BW zur Ölrückführung
Alternativ kann der HR 1 BW auch für eine Ölrückführung eingesetzt werden. Hierzu wird der Regler an der tiefsten Stelle des Ölabscheiders montiert. Das sich ansammelnde Öl wird dann automatisch zum Verdichter zurückgeführt ohne Gas durchzulassen.
Da der HR1BW Öl ständig zum Verdichter zurückführt, entfällt die Ölvorlage, d.h. es kann weniger Öl eingefüllt werden! Nach Stillstandzeiten kann das Magnetventil in der Ver­bindung zurück zum Verdichter schon nach wenigen Minu­ten wieder geöffnet werden, da eventuell im Ölabscheider kondensiertes Kältemittel sofort im Betrieb verdampft.
Installation of evaporator groups
When installing the hot gas line use a gradient of app. 1 – 2% to the HR1BW according to fig. 7b. The HR1BW will drain any condensate that is formed in the hot gas line so that a sudden evaporation / slug of liquid is avoided when the hot gas cycle starts.
At the end of the condensate drain line there should be a high-pressure float regulator with closed low-pressure nozzle When the solenoid valve closes upon finishing of the hot gas cycle, the enclosed gas buffer will prevent that any liquid refrigerant is pushed through the regulator during normal operation
Excessive pressure between the liquid condensate and the pump return line should be avoided by use of a by­pass line with an overflow valve.
5.1.4 HR1BW for oil return
Alternatively the HR1BW can be used for an oil return. Therefore the HR1BW should be placed at the lowest spot of the oil separator.
Any oil that accumulates will automatically be returned to the compressor without any gas passing through.
Since oil is permanently returned by the HR1BW the oil charge can be reduced.
After stand-still the solenoid valve in the line between HR1BW and compressor can be opened only after a few minutes, because any refrigerant that may have con­densed will immediately evaporate during operation.
26
Page 27
5.1.5 Selbstheilungseffekt
Auf HD-seitige Sammler sollte grundsätzlich verzichtet wer­den:
Bei zu klein ausgelegtem Regler tritt ein Rückstau des Kälte­mittels ein. Dieser Rückstau bewirkt, dass sich die wirksame Verflüssigerfläche verkleinert und der Kondensationsdruck solange ansteigt, bis der Regler in der Lage ist, das anfallen­de Kondensat abzuführen. Mit zwischengeschalteten Samm­lern kann diese günstige Eigenschaft nicht genutzt werden, da zunächst der Sammler gefüllt wird, bevor sich Kältemittel im Kondensator zurückstauen kann!
Achtung: Durch die Verlagerung des Kältemittels zur HD-Seite (erkennbar an einer messbaren Unterkühlung des Konden­sats) kann der Minimalstandsalarm auf der ND-Seite ausge­löst werden.
Wird die maximal zulässige Druckdifferenz überschrit­ten, z.B. bei hohen Kondensationstemperaturen, kann der Auslassmechanismus des Reglers blockiert wer­den!
5.1.5 Recovery Effect
The installation of a HP-receiver must generally be avoided.
When the float regulator is selected too small, refriger­ant will back-up into the condenser. This back up has the result that the effective condenser surface will be decreased and the condensing pressure will raise until the float regulator is again capable to release the accu­mulated condensate. With a high-pressure receiver installed in between the two components this very help­ful characteristic cannot be used, since the receiver will be filled first before any condensate will build up in the condenser.
Caution: If too much liquid migrates to the high-pressure side (this can be checked by sensing the sub cooling of condensate) the llow-evel alarm of the LP surge drum may be activated.
If the maximum allowable differential pressure is exceeded, e.g. at high condensate temperatures, the outlet mechanism of the regulator may be­come blocked!
5.2 SCHWIMMER-REGELUNG
Das in das Hochdruckschwimmer-Regler Gehäuse eintreten­de Kondensat bewirkt dort, dass der Schwimmkörper angeho­ben wird. Über eine Hebelübersetzung wird ein Schieber betä­tigt, der einen entsprechenden Anteil der Drosselöffnung frei­gibt und das Kondensat zum Abscheider ablässt. Weil der Schwimmkörper Reibungskräfte überwinden muss, findet ein schrittweises Verstellen der Öffnung statt.
Wenn der Flüssigkeitsstand im Schwimmer fällt wird der Schieber über die Öffnung bewegt und verschließt so den Auslaß. Wenn die Schwimmerkugel unten angelangt sorgen die geläppten Oberflächen von Schieber und Auslaß für einen dichten Abschluss. Der Auftrieb des Schwimmkörpers ist ab­hängig von Durchmesser und Gewicht der Kugel und von der Dichte der abzuleitenden Flüssigkeit.
Für Kältemittel mit geringer Dichte sind die SK-Kugeln bei den HS Reglern vorgesehen.
Beim WP HR sind die Schwimmerkugeln unten offen. Durch Gasansammlung innerhalb der Kugel schwimmt diese auf und gibt die Drosselöffnung frei. Aus diesem Grund dürfen die Hochdruckschwimmer-Regler WP HR nicht unterhalb des
Verflüssigers angeordnet werden.
5.3 FUNKTION DER UNTERDRUCKDÜSE
5.2 FLOAT REGULATION
Liquid condensate flows into the regulator housing lifting the float ball. This movement is transmitted to the moving part of a slide valve block, which in turn proportionally exposes the mating seat orifice releasing condensate to the surge drum. Since the float has to overcome friction, there is a pro­gressive exposure of the orifice area. .
As the liquid level drops, the slide block moves back over the orifice closing the outlet. When the float ball is down at its lowest position the pre­cisely machined surfaces of slide block and orifice area will seal tightly. Movement of the float depends on the diameter and weight of the ball as well as the density of the liquid refrigerant
For refrigerants with low density we have alternative SK­balls to be integrated in the HS type regulators.
With the WP HR the ball float is open at the bottom. Due to gas formation within the ball it will move upwards, ex­posing a part of the orifice area. This is why high­pressure float regulator WP HR are not to be mounted
underneath the condenser.
5.3 FUNCTION OF THE LOW PRESSURE NOZZLE
To enable any liquid condensate to flow to the regulator
Damit anfallendes Kondensat selbstständig dem Regler zu­fließen kann, wäre es eigentlich erforderlich den Regler unter­halb des Verflüssigers anzuordnen. Um eine Anordnung auch oberhalb des Verflüssigers zu ermöglichen, sind mit Ausnah­me des HR1BW, alle HR und WPHR Hochdruckschwimmer­Regler mit einer internen Unterdruckdüse ausgestattet. Bei HS-Reglern ist die Unterdrückdüse optional erhältlich.
Die Unterdruckdüse verbindet den Gasraum des Gehäuses mit dem Austrittsstutzen. Aufgrund der Druckdifferenz zwi­schen Hochdruck- und Niederdruckseite wird Gas aus dem Gehäuse zur Niederdruckseite angesaugt und im Gehäuse entsteht ein leichter Unterdruck.
27
by gravity, it would be necessary to arrange the regulator underneath the condenser. To permit an installation with the regulator above the condenser, all HR and WP HR float regulators, with the exception of the HR1BW, are equipped with an internal low-pressure. HS-regulators may also be ordered with low-pressure nozzle (optional). This low pressure nozzle connects the gas space in the housing with the outlet connection. Due to the pressure difference between high and low pressure side, the gas is drawn to the low-pressure side resulting in a slight under pressure in the housing.
Page 28
Dadurch können Gase, die sich aufgrund von Druckverlusten bilden, bis zu 3 m Höhenunterschied und bis zu 30 m horizon­tale Distanz, zum Kondensator abgeführt werden.
Außerdem wird gewährleistet, dass auch ein geringer Teil Flashgas, das sich in den Zulaufleitungen bzw. während eines Anlagenstillstands bildet, über die Unterdruckdüse abgeführt werden kann.
Es ist keine zusätzliche Entgasungsleitung erforderlich!
Bei Anlagenstillstand erfolgt ein langsamer Druckausgleich, so dass sich die gesamte Kältemittelfüllung zur kältesten Stelle verlagern kann. (Im Winter kann dies der Verflüssiger sein.)
Wenn dieser Druckausgleich nicht erwünscht ist, muss der Regler ohne bzw. mit verschlossener Unterdruckdüse bestellt werden!
Die werksseitige Bemessung der Unterdruckdüse ist so aus­gelegt, dass der durch Gas-bypass theoretische ermittelte Leistungsverlust im Bereich unterhalb 1% der Nennleistung verbleibt.
This effect allows that gases are drawn off that form over a vertical distance from the condenser of up to 3 m and a horizontal distance of up to 30 m.
In addition this allows the small amount of flash gas, which can form in the liquid feed line or during plant standstill to be bled away.
There is no additional purging line required!
During standstill of the plant system the pressure will slowly equalize allowing the entire refrigerant charge to transfer to the coldest part of the system. (During winter­time this can be the condenser).
If it is not desired that the pressure equalize, the regula­tor must be ordered without respective with closed low­pressure nozzle.
Factory selection of the low-pressure nozzle is made in such a way that the theoretically calculated loss of ca­pacity due to gas by-pass is less than 1% of the nominal capacity.
5.3.1 Anlagen mit verschlossener Unterdruckdüse
Bei HR-Reglern kann die vorhandene Unterdruckdüse bei Bedarf verschlossen werden. Standard HS Schwimmer kön­nen ohne Unterdruckdüse bestellt werden (Ausführung ge­mäß Fig. 8b).
Wenn der Druckausgleich im Stillstand der Kälteanlage nicht erwünscht ist, z.B. in Verbindung mit der Ölkühlung von Am­moniak-Schraubenverdichtern, muss der HR Regler mit ver­schlossener Unterdruckdüse bestellt werden, siehe Fig. 8a. (Bei einer solchen Sonderbestellung wird der Hochdruck­schwimmer-Regler mit einem Aufkleber „verschlossene Un­terdruckdüse“ ausgeliefert.
Verbindung zur optionalen Unterdruckdüse geschlossen. Connection to the optional low pressure nozzle is closed.
5.3.1 Plant with closed low pressure nozzle
HR-float have always an integrated low pressure nozzle that can be closed if necessary. Standard HS regulator can be ordered without low pressure nozzle (execution of the HS according to fig. 8b).
When the pressure equalization during standstill of the refrigeration plant is not desired, e.g. in connection with oil coolers of ammonia screw compressors, the HR regu­lator must be ordered with closed low-pressure nozzle, see fig. 8a. (These special orders will be delivered with an identifying label “closed low pressure nozzle”).
Fig.8a HR Regler mit verschlossener Unterdruckdüse HR regulator with closed low pressure nozzle
Fig.8b HS Regler ohne Unterdruckdüse HS regulator without low pressure nozzle
28
Page 29
den
5.3.2 HS-Regler ohne Unterdruckdüse
Die HS Regler Modelle HS31 – HS33, HS41 – HS43 sowie HS51 und HS53 werden ohne Unterdruckdüse ausgeliefert.
Wenn HS Regler unmittelbar unter dem Verflüssiger mon­tiert werden, kann auf die Unterdruckdüse verzichtet wer Eventuell entstehende Gasblasen können über die großzü­gig bemessene Verbindungsleitung zum Verflüssiger auf­steigen und werden dort verflüssigt.
Fig. 9a
Die Verbindungsleitung zu HS-Reglern ohne Unter­druckdüse sollte großzügig bemessen sein (gleiche Dimension wie der Anschluß am Reglergehäuse). Außerdem sollte die Leitung so kurz wie möglich auf direktem Weg und ohne Widerstände verlegt werden. Zusätzliche Bögen, Reduzierungen oder Armaturen sollten vermieden werden. Eine Gasblase soll unge­hindert zum Verflüssiger aufsteigen können
Fig. 9b
5.3.2 HS regulators without low pressure nozzle
HS regulator models HS31 – HS33, HS41 – HS43 as well as HS51 and HS53 are delivered without low pressure nozzle.
When the HS regulator is mounted as close as possible underneath the condenser, there is no need for a low pressure nozzle. Any gas bubbles can raise back to the condenser through a generously sized connection be­tween regulator housing and condenser, where they will be condensed.
Fig. 9c
When using HS regulatos without low pressure nozzle it should be sonsidered that the connection to the condenser should have the same dimension as the top connection of the regulator housing.
The line should be as short as possible avoiding resistances caused by elbows, reducers or valves. A gas bubble should be able to raise back to the condenser.
5.3.3 Anlagen mit Ölkühlern
In Fig. 10 ist das Prinzip einer Anlage mit Ölkühler darge­stellt. Die Entgasung des Reglergehäuses wird über eine externe Entgasungsleitung vorgenommen.
5.3.3 Installations with oil coolers
Fig. 10 shows the principle installation of a plant with oil cooler. Purging of the regulator housing has to be carried out with an external vent line.
Fig 10a Fig. 10b
Prinzip einer Anlage mit Ölkühlern
Principle installation with oil coolers
29
Page 30
Am Einstellventil, das oben am Reglergehäuse angebracht ist, wird eine Steuerleitung mit Magnetventil zur Nieder­druckseite verlegt. (Die Größe der Steuerleitung sollte gleich der Anschlussgröße des Einstellventils sein.) Das Magnet­ventil bleibt bei Stillstand der Anlage geschlossen und ver­hindert den Druckausgleich.
Beim Einsatz von kältemittelgekühlten Ölkühlern ist darauf zu achten, dass immer eine ausreichende Vorlage zum Ölkühler vorhanden ist. Der Hochdrucksammler muss des­halb oberhalb des Ölkühlers angebracht sein.
Die in Fig. 10 dargestellten Höhen h1 und h2 müssen aus­reichend bemessen sein. In der Praxis hat sich gezeigt, dass diese häufig zu gering gewählt werden: die Höhe h1 reicht dann nicht aus, um Druckschwankungen auszuglei­chen bzw. die Höhe h2 reicht nicht aus um den Druckverlust in der Leitung zu kompensieren.
A separate set of controls is to be fitted from the top purge connection. After the EE3/EE6 regulating valve a solenoid valve has to be installed in the line returning to the low-pressure drum. (The line size should be the same as the regulating valve). The solenoid valve has to be closed during plant standstill preventing equalisation of the system pressure.
When used with refrigerant cooled oil coolers care must be taken to ensure that a sufficient liquid refrigerant feed to the oil cooler is maintained at all times. The high­pressure receiver must therefore be positioned above the oil cooler.
Heights h1 and h2 shown in fig. 10 have to be correctly sized. It has been observed in practice that these heights are insufficient. Height h1 was not large enough to balance any pressure fluctuations and height h2 did not exceed the pressure drop in the liquid line.
6. PLANUNGSHINWEISE
6.1 ALLGEMEINES
Die hochdruckseitige Regelung erfüllt innerhalb der Anlage die Aufgabe der Drosselung durch Kondensatableitung. Sie ist deshalb besonders geeignet bei Anlagen mit Zentralab­scheidern- oder Verdampfern mit energiesparender Be­triebsweise. Aufgrund der rein mechanischen Betriebsweise ist die Kondensatableitung jederzeit ohne zusätzlichen Re­gelaufwand gewährleistet.
Im Gegensatz zur Niederdruckschwimmer-Regelung befin­det sich die schwankende Kältemittelmenge im Zentralab­scheider.
6.2 AUSWAHLKRITERIEN
Für die Auslegung von WITT Hochdruckschwimmer-Regler verweisen wir auf unser Auslegungsprogramm, dass Sie auf unserer Website www.th-witt.com runterladen können und auf unseren Katalog: „Hochdruckschwimmer-Regler für Käl­teanlagen und Wärmepumpen“.
WITT Hochdruckschwimmer-Regler sind durch folgende Eigenschaften charakterisiert:
• Unabhängig von einer minimalen Druckdifferenz
• Unabhängig von einer minimalen Leistung
• Der max. Massenstrom ist abhängig von der Druckdiffe-
renz und der Abmessungen von Gehäuse bzw. Stutzen
• Die maximal zulässige Druckdifferenz ist abhängig von der spezifischen Dichte des Kondensats
6.3 ANORDNUNG
6.3.1 Allgemeines
Aufgrund der Unterdruckdüse kann der Hochdruckschwim­mer-Regler auch über dem Verflüssiger angeordnet werden. Max. 3m Höhenunterschied und 30 m horizontaler Abstand zwischen Regler und Verflüssiger können berücksichtigt werden. Dies trifft nicht auf den HR1BW (sowie HS Regler ohne Unterdruckdüse) zu, der nicht oberhalb des Verfüssi­gers montiert werden darf und auf WP HR, die nicht unter­halb des Verflüssigers montiert werden dürfen. Der WPHR muss 1 – 3 m oberhalb des Veflüssigers angeordnet wer­den, damit aufsteigende Gase den Auftrieb der Schwimmer­kugel unterstützen.
6. HINTS FOR PLANNING
6.1 GENERAL
High-pressure regulation within a plant is achieved by expanding condensed refrigerant liquid. This is particu­larly favourable with plants that have a central surge drum or with evaporators operating very energy efficient. Simple mechanical operation gives a high degree of reli­ability, maintaining the liquid condensate drainage at all­time without further regulating effort.
In contrast to low-pressure regulators the entire fluctuat­ing refrigerant charge is located in the central surge drum.
6.2 SELECTION CRITERIA
For selection of WITT high-pressure float regulators please refer to our selection program that can be downloaded from our website www.th-witt.com and our brochure float regulators for refrigeration plants and heat pumps.
WITT high pressure float regulators are characterised by the following design features:
• Independent from a minimum pressure difference
• Independent from a minimum capacity
• The maximum flow is dependent on the pressure
difference and the dimensions of housing respective connections
• The maximum allowable pressure difference is de- pendent on the specific weight of the liquid refriger­ant
6.3 LOCATION
6.3.1 General
Due to the low-pressure nozzle design, the high-pressure regulator can be positioned above the level of the con­denser. A max. vertical distance of 3 m and a horizontal distance between regulator and condenser of up to 30 m are possible. These dimensions are not valid for the HR1BW (and HS regulators without low pressure nozzle), which cannot be installed above the condenser and the model WP HR that must not be installed below the condenser. The WPHR must be mounted 1 – 3 m above the condenser so that rising gases support the lifting of the float ball.
30
Page 31
Arrangement of the high pressure float regulator
Anordnung des Hochdruckschwimmer-Reglers
Der Regler kann in der Nähe des Niederdruckteils der Kälte­anlage angeordnet werden, sodass die zu isolierende Einspritz-Leitung kurz bemessen werden kann. Allerdings ist darauf zu achten, dass die Flüssigkeit in der Zulaufleitung auf ihrem Weg vom Verflüssiger (Mitteldruckbehälter) zum Hochdruckschwimmer-Regler einem möglichst geringen Druckabfall und Wärmeeinfall ausgesetzt wird.
6.3.2 Parallelschaltung von Verflüssigern
Die Parallelschaltung von mehreren Verflüssigern an eine gemeinsame Sammelleitung sollte auf jeden Fall vermieden werden! Es ist empfehlenswert, hinter jeden Verflüssiger einen separaten Hochdruck­schwimmer-Regler zu montieren.
Sollte eine Parallelschaltung von Verflüssigern mit gemein­samer Sammelleitung dennoch gewählt werden, so ist dar­auf zu achten, dass nur gleiche Verflüssiger parallel ge­schaltet werden und eine symmetrische Anordnung gewählt wird. Dadurch wird gewährleistet, dass die Druckverluste sowohl in den Verflüssigern als auch in den Leitungen zum Sammler gleich sind.
Beim Einsatz verschiedener Verflüssigertypen oder bei un­symmetrische Verschaltung der Verflüssiger bedingen die unterschiedlichen Betriebszustände, dass Kondensat in ei­nem Verflüssiger rückstauen kann, während der andere bereits Gas durchlässt.
Die Höhe H vom Verflüssigerauslass zur Oberkante des HD­Sammlers, gemäß Abb. 12a bzw. 12b, wird vom Verflüssi­gerhersteller angegeben. In der Regel wird eine Mindesthö­he H gemäß Fig. 12 empfohlen.
In der Praxis hat sich gezeigt, dass diese Höhe mit­unter nicht ausreicht, die Schwankungen zu kompen­sieren! Speziell bei größeren Druckdifferenzen ist daher die Höhe H entsprechend zu vergrößern.
Die Leitungen vom Verflüssiger sollten mit einem Bogen von unten and die Sammelleitung angeschlossen werden. Wenn kein Sammler eingesetzt wird, muss die Sammelleitung aus­reichend dimensioniert werden um immer eine ausreichende Vorlage bereitzustellen.
Wird ein Hochdrucksammler eingesetzt, ist die Sammellei­tung von unten an den Hochdrucksammler anzuschließen, damit die Sammelleitung immer mit Flüssigkeit gefüllt ist, bzw. sich die Fallleitungen entsprechend füllen können.
Eine Entgasungsleitung von der Sammelleitung bzw. dem Sammler sollte möglichst entsprechend Fig. 12 angeschlos­sen werden
Fig. 11
The regulator can be positioned and installed near to the low-pressure side of the refrigerant plant, so the length of cold piping that requires insulation can be kept to a mini­mum. Note: It is important that the liquid refrigerant feed pipe work should not be exposed to high ambient tempera­tures or excessive pressure drop.
6.3.2 Parallel arrangement of condensers
Parallel installation of condensers with a common liquid receiver should be avoided under all circum­stances. It is recommended to install a separate high­pressure float regulator behind each condenser.
If the parallel arrangement of condensers with a common collector has to be selected, special care must be taken that only equally sized models of condensers are installed in parallel and that they are arranged symmetrically. This is to ensure the pressure drop in the condensers and in the lines to the common liquid receiver are approxi­mately the same.
When different condenser types are installed or an asym­metric arrangement is made the different operating condi­tions will result in a back up of liquid refrigerant in one of the condensers while letting by-pass of discharge gas through the others.
The height H from the condenser outlet to the top of the HP collector according to fig. 12a respective 12b, will be indicated in the manual of the condenser manufacturer. It is commonly recommended you use a minimum height H as indicated in fig. 12.
It has been observed in practice that this height is sometimes not sufficient to compensate for the fluctuations in liquid level. Particulatly with higher pressure differences the height H has to be in­creased.
The lines from the condenser shall be connected with an elbow from the bottom to the common collector line. The common collector line should be seized generously to make sure there is always sufficient liquid to feed the high side float regulator.
When a main liquid header is used the connection of the common collector line should done from the bottom to en­sure the header and drain legs from each condenser circuit are always full of refrigerant.
A purging line of the common collector line respective main header should be executed according to fig. 12.
31
Page 32
Fig. 12a
Fig. 12b
Ausführung bei parallel geschalteten Verflüssigern
Application with parallel condensers
6.3.3 Parallelschaltung der Regler
Eine Parallelschaltung der Hochdruckschwimmer-Regler ist besonders günstig, wenn die Anlage in Teillast oder im unte­ren Leistungsbereich betrieben wird.
Bei einer Parallelschaltung sollten die Regler gemäß nach­folgender Abbildung übereinander angeordnet werden. Um den Leistungsverlust durch mehrere Unterdruckdüsen zu vermeiden, ist es empfehlenswert die Unterdruckdüse des oberen Reglers zu verschließen und deren Funktion durch ein Magnetventil zu ersetzen.
6.3.3 Parallel Installation of float regulator
Parallel installation of float regulators is particularly favour­able in case of part load or low capacity operation.
For parallel arrangement install the regulators according to the schematic below. To avoid a loss of efficiency with multiple low-pressure nozzles, it is advisable to close the low-pressure nozzle of the top mounted regulator and to replace it with an external purging line with solenoid valve control.
Parallele Anordnung der Regler
32
Fig. 13
Parallel installation of float regulators
Page 33
C A B
6.4 ZULAUFLEITUNG
6.4.1 Allgemein
Die Zulaufleitung ist so zu bemessen, dass die Geschwin­digkeit des Kondensats unter 1 m/s bleibt. Dies ist gewähr­leistet, wenn die Rohrleitung den gleichen Durchmesser wie der Anschlussstutzen am WITT-Eintrittsventil hat. Dadurch wird verhindert, dass sich aufgrund von Reibungs­verlusten zu viel Gas in der Zulaufleitung bildet.
6.4.2 Anschluss an Hochdruckbehälter
Wenn die Zulaufleitung an einen Druckbehälter angeschlos­sen werden soll, z.B. einen Sammler, einen Vorlagebehälter oder an einen Zwischenkühler, so ist gemäß nachfolgender Darstellung (Fig. 14a) zu verhindern, dass Gas angesaugt wird.
Auf keinen Fall darf die Zulaufleitung unisoliert durch warme Räume geführt werden, oder neben warmen Maschinen montiert sein, noch direkter Sonnenbestrahlung ausgesetzt werden.
Einbauten wie Filter oder Trockner dürfen auf kei­nen Fall vorgesehen werden!
6.4 LIQUID FEED LINE
6.4.1 General
The liquid feed line shall be sized so that the velocity of the liquid refrigerant does not exceed 1 m/s. This will be achieved when piping has the same diameter as the con­nection at the WITT inlet valve. By maintaining this velocity you will ensure that flash gas is kept to a minimum.
6.4.2 Connection to a HP receiver
Under no circumstances shall the liquid feed line be installed uninsolated when piped through warm areas, beside machines, or exposed to direct sunlight.
Internal filters or dryers are not permitted in the liquid feed line!
When the liquid feed line has to be connected to a pres­sure vessel, e.g. receiver, feed vessel or an intermediate cooler, the installation shall follow the schematic below to prevent any HP gas becoming entrained in the liquid line (see fig. 14a).
Richtiger Anschluss an einen Druckbehälter
Die beiden folgenden Anordnungen sollen nicht gewählt werden, da in Fig. 14b D aufgrund einer Strudelbildung Gas mitgerissen wird und auch die Anordnung gemäß Fig. 14b E Gas ansaugt.
Falscher Anschluss an den HD-Behälter
D
Fig. 14a
Fig. 14b
Proper connection to a HP vessel
The following two connection arrangements must not to be used, as in fig. 14b D gas will be entrained due to vortex­ing and in fig 14b E the entrained gas will be drawn into the liquid..
E
False connection to a high pressure vessel
33
Page 34
Schematic of the siphon connecting to a plate condenser
6.4.3 Automatische Ventile in der Zulaufleitung
6.4.3 Automatic valves in the liquid feed line
Automatische Ventile sind in der Zulaufleitung grundsätzlich zu vermeiden. Sollten diese dennoch benötigt werden, emp­fehlen sich z.B. elektrisch oder pneumatisch betriebene Ku­gelhähne. Differenzdruckabhängige Ventile (z.B. Pilotventile) sind we­gen fehlender Druckdifferenz zwischen Verflüssiger und Regler ungeeignet.
6.4.4 Anschluss an Plattenverflüssiger
Wenn kein HS-Regler ohne Unterdruckdüse verwendet wer­den kann (z.B. wenn der Regler nicht unter dem Verflüssiger angeordnet werden kann), ist folgendes zu beachten:
Besonders bei Plattenwärmetauschern, die nur eine geringe Kältemittelfüllung haben, ist darauf zu ach­ten, dass kein Gas zu dem Regler gelangen kann.
Da der interne Druckverlust in den Kanälen des Platten­verflüssigers häufig schwankt, ist auf einen ausreichend dimensionierten Siphon zu achten.
The use of automatic valves in the liquid feed line should generally be avoided. If they are absolutely necessary, it is recommended to use e.g. electrically or pneumatically operated full bore ball valves. Any valves depending on a pressure difference (e.g. pilot valves) are unsuitable because of the lack of pressure difference between condenser and float regulator.
6.4.4 Connection to plate condensers
When HS regulators without low pressure nozzle cannot be used (e.g. the regulator cannot be placed underneath the condenser), consideration should be given to the following:
Particularly attention has to be paid to applica­tions with plate-type condensers, which use a low refrigerant charge. Care has to be taken to avoid
any gas is flowing to the regulator. As the internal pressure difference within the plate chan­nels fluctuates a sufficiently laid-out siphon (duck neck) drain connection has to be used.
Gestaltung des Siphons bei Anschluss an einen Plattenapparat
6.5 EINSPRITZLEITUNG
Hinter dem Hochdruckschwimmer-Regler befindet sich ein Gemisch aus Gas und Flüssigkeit. Die Leitung ist mit einer Gasgeschwindigkeit von 15 – 25 m/s auszulegen. Die Eintrittsgeschwindigkeit in den Abscheider sollte bei durchschnittlich 10 – 15 m/s liegen.
In der Praxis hat es sich bewährt, die Einspritzlei­tung 1 - 2 Nennweiten größer als die Zulaufleitung zu wählen.
Die Länge der Einspritzleitung ist nicht kritisch, sie ist je­doch aufgrund der notwendigen Isolierung recht teuer.
Die Druckdifferenz zwischen HD und ND-Seite sollte mög­lichst größer als 1 bar sein um Druckverluste in der Ein­spritzleitung kompensieren zu können. (Nachfolgende Gleichung erläutert dies näher.)
Fig.
15
6.5 LOW PRESSURE LINE FROM THE REGULATOR
After the regulator there is a mixture of gas and liquid re­frigerant in the LP line. This line should be sized so that the gas velocity of the liquid is 15 – 25 m/s. The inlet-velocity into the surge drum shall not exceed an average of 10 – 15 m/s.
It is our experience and proven practice to size the low-pressure line from the regulator 1 – 2 seizes larger than the liquid feed line to the regulator.
The length of the low-pressure line is not critical, but due to the insulation required it can be expensive.
The pressure difference between HP and LP side shall be more than 1 bar to compensate for the pressure drop in the low-pressure line. (The following equation explains this further)
34
Page 35
Die Druckdifferenz am Hochdruckschwimmer-Regler be­rechnet sich aus:
∆pHR = (pc – p0) ± ∆p
wobei ∆p
in der Regel vernachlässigt werden können,
Verluste
stat.Zulauf
- ∆p
Verluste
solange sich keine reine Flüssigkeitssäule in der Einspritz­leitung befindet, da
∆p
Verluste
= ± ∆p
stat.ND-Ltg
- ∆p
Reibungsverluste
(Die Gleichungen beziehen sich ausschließlich auf das Kondensat)
Um Flüssigkeitsschläge in Einspritzleitungen zu verhin­dern, sollte sie nicht in größeren vertikalen Strecken ver­legt werden. Kann dies nicht vermieden werden sollten alle ca. 5 – 8 m Flüssigkeitsfallen vorgesehen werden.
Der Anschluss der Einspritzleitung an den Abscheider sollte so angeordnet werden, dass keine Flüssigkeit vom Verdichter angesaugt werden kann, siehe dazu auch Fig. 5 und Fig. 6.
7. TRANSPORT UND LAGERUNG
Alle Öffnungen (Stutzen, etc.) sind mit gelben Kunststoff­Schutzkappen versehen, die den Eintrag von Wasser, Schmutzpartikeln, etc. verhindern.
Zum Feststellen der Schwimmerkugel während des Trans­ports ist die Hebelstellung (bzw. Bohrung im Hebel) im Anlie­ferzustand nach oben weisend (Transportsicherung).
The pressure difference at the high pressure float regula­tor is calculated per:
∆
pHR = (pc – p0) ± ∆p
whereas ∆p
losses
stat.supply
can normally be neglected, as long as
- ∆p
losses
there is no liquid in the injection line, because of the fol­lowing equation:
∆
p
= ± ∆p
losses
stat.LP-Line
- ∆p
friction
(These equations are only for liquid refrigerant!)
To prevent liquid hammer in the low-pressure line, it should not be installed with a large vertical riser. If this cannot be avoided, there shall be a liquid ”U” trap every 5 – 8 m.
The connection of the low-pressure line to the surge drum shall be arranged to avoid any danger of liquid being entrained in the dry suction line to the compressor (see fig. 5 and fig. 6).
7. TRANSPORT AND STORAGE
All connections are protected with yellow plastic caps to prevent any dirt, debris or water contaminates the regula­tor.
For safe transportation during delivery the float ball is locked in position by turning the lever upwards (lever, re­spective the hole in the lever is facing upwards).
Die Lagerung sollte trocken und vor Schmutz geschützt er­folgen.
8. MONTAGE
Montagearbeiten an den Hochdruckschwimmer­Reglern sind grundsätzlich nur von sachkundigem Personal durchzuführen!
8.1 MONTAGEVORBEREITUNG
Vor Montage des Hochdruckschwimmer-Reglers sind fol­gende Maßnahmen zu ergreifen:
• HR auspacken und auf Transportschäden und Vollstän­digkeit der Lieferung überprüfen. Im Falle einer Be­schädigung ist der Lieferant umgehend zu informieren.
• Vergleichen Sie die Informationen auf dem Typenschild mit den Anforderungen bzw. der Bestellung: ist Typ und Kältemittel korrekt, ist die Unterdruckdüse ver­schlossen, falls dies bestellt wurde, etc.
• Plastikschutzkappen oder andere Versiegelungen sind erst unmittelbar vor Montage zu entfernen.
• Kontrollieren Sie ob die Rohrleitungsanschlüsse zu den Regleranschlüssen passen.
• Es ist sicher zu stellen das die Rohrleitungen frei von Verunreinigungen sind
Hochdruckschwimmer-Regler werden im Werk einer Druckprüfung mit Mineralkältemaschinenöl unterzogen. Wenn die Regler in einer Anlage ein­gesetzt werden, in der die Verunreinigung mit Mi­neralöl unzulässig sind, z. B. bei Verwendung von Esteröl, muss der Regler zuvor mit einem Lösungs­mittel ausreichend gespült werden.
Storage shall be dry and protected from any dirt or debris.
8. INSTALLATION
Any work on float regulators must be carried out by trained and knowledgeable personnel experi­enced in installation and service of refrigeration systems.
8.1 PREPARING FOR INSTALLATION
Before the float regulator can be installed the following functions should be carried out
• Unpack the float regulator and check for damages during shipping and the correct scope of equipment supplied. In case of any damages inform your supplier immediately.
• Check the information provided on the nameplate with your order requirements, respective order confirma­tion: is type and refrigerant correct, is the low­pressure nozzle closed, if ordered, etc.
• Remove plastic caps or other sealing immediately prior to (and not before) installation of the regulator.
• Check whether the regulator pipe connections match the piping connections required.
• The piping system is to be clean and free of any mois- ture.
The HR float regulator has undergone a pressure test with mineral refrigerant machine oil in the factory. If the regulator will be used in systems where contamination with mineral oil is not al­lowed, i.e. in cases with ester oil in the system, the residual oil must be removed adequately and cleaned by use of solvents.
35
Page 36
leert und mit
The refrigeration system must be pressure tested, have
completed a successful vacuum test and be charged with
Turn the lever in automatic position (hole in the lever
8.2 MONTAGEANLEITUNG
8.2 FIXING INSTRUCTIONS
Richten Sie den Hochdruckschwimmer-Regler in waage­rechter Lage aus, so dass das Typenschild lesbar ist.
Sehen Sie ausreichend Platz vor, so dass der Schwimmerkörper ggf. ausgebaut werden kann und die Ventile zugänglich sind.
Auf keinen Fall darf am Schwimmergehäuse ge­schweißt werden, da sonst die Bescheinigung sowie die Herrestellergarantie ihre Gültigkeit verlieren!
Beim Anschweißen der Rohrleitungen an die dafür vorgesehenen Stutzen ist auf spannungsfreie Mon­tage zu achten!
Berücksichtigen Sie, dass sich die Rohrleitungen beim Her­unterkühlen entsprechend verkürzen!
Die angeschweißten WITT-Ventile sollten beim Anschwei­ßen halb geöffnet sein und mit einem feuchten Tuch gekühlt werden.
Beim Anschweißen an die Stutzen des WP HR , HR4 und HS bzw. an ohne Ventile ausgelieferten Stutzen, ist darauf zu achten, dass der O-Ring am Austritt nicht beschädigt wird.
Die HR-Schwimmer, ab Größe HR2 sind mit einem Nocken für Sicherheitsventile vorgesehen.
Align the float regulator in a horizontal position, so that the nameplate can be read.
Provide sufficient space, so that the internal float ball can be exchanged and the valves are accessi­ble.
Under no circumstances should any attachments be welded to the float regulator housing. Such welding will make the certificates and manufactur­ers warranty void.
Make sure the installtion is stress free when welding the float regulator to the pipework.
It is important to consider the stress in the pipe work dur­ing system temperature pull down.
WITT valves should be half open and cooled with a wet cloth during welding.
When welding to the connections of the WP HR, HR4, HS or to the connections without valves, make sure the heat of welding will not damage the O-ring at the outlet.
All HR-regulators, above size HR 2 the housing is equipped with a safety valve connection.
Drehen Sie den Hebel für die Schwimmerarretierung nach Abschluss der Montagearbeiten nach unten. Das Loch im Hebel müssen nach unten zeigen für „Automatikbetrieb“.
9. INBETRIEBNAHME
9.1 VORBEREITUNG DER INBETRIEBNAHME
Die Kälteanlage muss druckgeprüft, vakuument Kältemittel gefüllt sein.
Die Steuereinheit darf bei der Druckprüfung nicht dem Prüfdruck ausgesetzt werden. Daher ist der Hochdruckschwimmer Regler nicht in der Druckprü­fung einzubinden (er wurde bereits im Werk einer Dichtigkeits- und Druckprüfung unterzogen). Sollte eine Druckprüfung mit dem Regler erforderlich sein, muss die Steuereinheit für die Dauer der Druckprü­fung demontiert werden.
Die Ein- und Austrittsventile müssen voll geöffnet sein. Stellen Sie sicher, dass sich der Hebel in „Automatik­Position“ befindet (d.h.. Bohrung im Hebel zeigt nach un­ten). Verschliessen sie die Ventilspindeln mit den dazugehören­den Kappen.
9. COMMISSIONING
9.1 PRIOR TO COMMISSIONING
When the installation is complete, turn the lever downwards to unlock the transportation-securing device of the float. The hole in the lever shall point downwards for “automatic operation”.
refrigerant.
It is not permitted the control unit is exposed to the high test pressure. Therefore the high side pressure regulator should be excluded from the pressure testing on site (it has already undergone a leak- and pressure test at the manufacturer). If it is necessary to include the regulator in thepressure test, the con­trol unit must be removed during the duration of the pressure test.
The inlet- and outlet valves must be fully open
pointing downwards).
Protect the valve spindle with the supplied cap.
36
Page 37
9.2 INBETRIEBNAHME
9.2 COMMISSIONING
Stellen Sie sicher, dass aus der Anlage sämtliche Fremdga­se entfernt wurden. Es ist ratsam die Anlage bei der Inbe­triebnahme noch einmal gründlich zu entlüften. (Siehe dazu auch „Entlüften“ im Kap. 11.5).
Prüfen Sie ob die Kondensationstemperatur stabil bleibt oder stetig ansteigt. (Wenn letzteres zutrifft muss noch ein­mall entlüftet werden.) Wenn das Kondensat, das vom Verflüssiger kommt, unter­kühlt ist, befinden sich voraussichtlich Luft oder andere nicht kondensierbare Gase im System.
Überprüfen Sie beim Einsatz von wassergekühlten oder Verdunstungsverflüssigern, dass die Temperatur nach dem Druckausgleich nicht unter den Gefrierpunkt sinkt (Einfrier­gefahr).
10. BETRIEB
Der Hochdruckschwimmer-Regler arbeitet völlig selbststän­dig und bedarf keiner weiteren Bedienung.
11.
WARTUNG UND INSTANDHALTUNG
Der eingebaute Schieber unterliegt kaum Verschleiß und die kontinuierliche Selbstreinigung der Schiebersteuerung macht Wartungsarbeiten normalerweise überflüssig.
Ensure that all non-condensable gases are removed from the system. It is recommended to purge the system thor­oughly during start up. (Please refer to “Purging” in Chap­ter 11.5).
Check that the condensing temperature is stable or in­creasing slowly (if you observe it is increasing, the installa­tion must be purged again). If the liquid refrigerant draining from the condenser is sub cooled, there is too much air or non-condensable gases in the system.
When the plant stops check that the water-cooled respec­tive evaporative condenser temperature after system pres­sure equalisation cannot drop below freezing point (dan­ger of freeze-up!). .
10. OPERATION
The high-pressure regulator operates automatically and does not require further attention.
11. SERVICE
The low friction slide block offers low wear and continuous self-cleaning of the orifice area, which normally requires no further maintenance.
AND
MAINTANANCE
Vor dem Öffnen des Hochdruckschwimmer-Reglers ist die­ser vom Kältemittel zu entleeren.
Wenn Wartungsarbeiten am Hochdruckschwimmer­Regler HR durchgeführt werden sollen, muss das Gehäuse drucklos sein und das Kältemittel vollstän­dig abgesaugt sein, bevor die Verschraubungen ge­löst werden!
Beim Öffnen der Regler kann es zu einer plötzlichen Verdampfung von eingeschlossenem Kältemittel kommen! Deshalb unbedingt Schutzkleidung tragen! Entfernen Sie auf keinen Fall alle Schrauben, wenn noch Kältemittel oder Druck vorhanden ist.
Beim Zusammenbau des Reglers ist auf Vorhandensein aller Dichtungen und deren Unversehrtheit zu achten. Es wird empfohlen die Dichtungen nach jedem Öffnen auszu­wechseln!
Ist die Demontage von Sicherheitseinrichtungen beim Rüs­ten, Warten und Instandsetzen erforderlich, haben unmittel­bar nach Abschluss der Arbeiten die Remontage und Über­prüfung der Sicherheitseinrichtungen zu erfolgen!
11.1 FUNKTIONSKONTROLLE
Alle Regler haben einen von außen zu betätigenden Hebel, der ein Anheben der Schwimmerkugel ermöglicht. Dadurch kann der Regler bewusst geöffnet werden, um dessen Funk­tion zu überprüfen.
11.2 AUSTAUSCH DES SCHWIMMKÖRPERS
Beachten Sie beim Ausbau unbedingt die lokalen Unfall Verhütungs-Vorschriften. Beachten Sie insbesondere fol­gendes:
• Prüfen Sie Fluchtmöglichkeiten, um im Notfall schnell die Gefahrenstelle verlassen zu können.
• Sorgen Sie aus Sicherheitsgründen für Hilfe bei der
37
Before opening the high side float regulator any refrigerant need to taken out.
When the high-pressure float regulator HR is to be
11.1 FUNCTIONING CHECK
11.2 REPLACING THE FLOAT BALL
maintained, the housing must be completely de­pressurised and all the refrigerant entirely removed, before loosening any screws and opening up!
During opening up a sudden boiling of residue re­frigerant may occur. Therefore wear the required safety clothing! Do not remove all the screws until you are sure no residue refrigerant or pressure exists.
Upon re-assembly take care that all gaskets are in place and in good condition. It is recommended to replace all gasket each time the float regulator has been opened.
If you have to disassemble any safety devices for mainte­nance or repair make sure that on completion the re­assembly and proper functions are checked.
All float regulators are provided with a lever that can be operated externally to lift the float. The regulator can be opened or closed that way to check that it is functioning correctly.
Follow all national and local safety requirements and codes of practice when removing the float. Please take particular care of the following:
• Check the plant room layout and exit doors so you can evacuate the area quickly in case of an emer­gency.
Page 38
Demontage des Reglers.
Schrauben Sie Zylinderschrauben M 8 x 20, Pos. 25,
• Sorgen Sie für geeignete Schutzkleidung, mindestens für eine Sicherheitsbrille und Handschuhe und bei Ver­wendung von NH3 für eine griffbereite Gasmaske.
Gehen Sie beim Austausch wie folgt vor :
• Schließen Sie das Eintrittsventil
• Arretieren Sie den Schwimmkörper, indem Sie den
Hebel nach oben drehen
• Warten Sie bis sich das Kältemittel zur ND-Seite ent­spannt hat
• Schließen Sie nun auch das Austrittsventil
• Lassen Sie verbleibendes Kältemittel und Öl vorsichtig
über das untere Ablassventil EA 10 GB ab
• Falls erforderlich, Spülen Sie das Gehäuse mit Stick­stoff
• Seek assistance to handle and remove the float
• Wear the correct protective safety clothing, as a mini-
mum use safety goggles and gloves, in case of NH
have a safety gas mask within easy reach When exchanging the float please carry out the following steps :
• Close the inlet valve
• Lock the float by turning the lever upwards
• Wait until all refrigerant is released to the low pressure
side
• Now close the outlet valve
• Drain any remaining refrigerant and oil carefully
through the bottom mounted drain valve EA 10 GB
• If necessary purge the regulator housing with nitrogen
3
Fig. 16 a Fig. 16 b
HR1 – HR3 (Siehe hierzu auch Fig. 16a und 16b)
• Entfernen Sie bei den Typen HR1 bis HR 3 das Ge­häuse
• Drehen Sie die Schraube M 4 x 5, Pos.55 heraus
•
aus dem Gehäusedeckel heraus
• Entfernen Sie Führungsbügel, Pos. 57 und Zugstan­ge, Pos. 56
• Tauschen Sie die komplette Steuereinheit aus
• Ersetzen Sie Flachdichtung, Pos. 32
• Montieren Sie Führungsbügel Pos. 57, Zugstange
Pos. 56 und befestigen Sie die Steuereinheit mit den Zylinderschrauben Pos. 25.
• Befestigen Sie Zugstange Pos. 56 mit Schraube, Pos. 55, im Exzenter, Pos. 53
• Auf losen Sitz der Zugstange im Führungsbügel achten!
• Montieren Sie das Reglergehäuse wieder, nachdem die Deckeldichtung, Pos. 31, erneuert wurde.
Verfahren Sie dann gemäß Kap. 9
HR1 – HR3 (refer to Fig. 16a and 16b):
• For access remove the housing of types HR 1 to HR 3,
• Remove screw M 4 x 5, Pos 55,
• Unscrew the cylindrical screws M 8 x 20, Pos. 52, out
of the cover
• Remove guide bracket, Pos. 57 and tow bar, Pos. 56
• Exchange the entire control unit
• Replace the gasket, Pos. 32
• Re-assemble guide bracket, Pos. 57, tow bar, Pos. 56
and fix the control unit with the cylindrical screws Pos. 25
• Secure the tow bar, Pos. 56 with screw, Pos. 55 in the excenter, Pos. 53
• Pay attention to the tow bar, it should be seated loosely in the guide bracket
• Always re-install the regulator housing using a new cover gasket, Pos. 31.
Proceed according to chapter 9 for commissioning and start-up.
38
Page 39
log Pos. 25 aus Fig. 16b) kann die Steuereinheit
w
Dabei wird der Hebel für die Funktionskontrolle aus
ving screws,
HR4 und HS50 (siehe dazu Schnittzeichnung 2b und 2d)
• Um den Deckel-Flansch, Pos. 11, abnehmen zu können muss zunächst die Schutzkappe, Pos. 72 sowie die Stopfbuchse, Pos 74, des Hebels entfernt werden.
• Schrauben M16x50, Pos 21 entfernen und den De­ckel-Flansch abnehmen
• Durch Lösen der beiden Innensechskant-Schrauben (ana entfernt und ausgetauscht werden.
• Tauschen Sie beim Zusammenbau die Dichtung der Steuereinheit (analog Pos. 32 aus Fig. 16b) sowie die Deckeldichtung, Pos. 31 aus.
Verfahren Sie gemäß Kap. 9.
HR4 and HS50 (see also sectional drawings 2b and 2d)
• In order to take the cover flange, pos. 11 off, you need to first remove the protective cap, pos. 72 and unscre the gland, pos. 74 of the lever.
• Remove the cover plate hexagon screws, pos. 21 and take the cover off
• Remove the two hexagon socket screw (similar to pos. 25 of fig. 16b) and you can take the entire control unit out and exchange it.
• Always replace the gasket of the control unit (similar pos. 32 of fig, 16b) und the cover-gasket during re­assemby.
Proceed per chapter 9.
Fig. 16 c Fig. 16 d
HS30 – HS40/ WPHR (siehe Fig. 2c, 2e sowie 16 c, 16
HS30 – HS40/ WPHR (see fig. 2c, 2e and fig. 16c, 16d)
d)
• Entfernen Sie den Deckelflansch, Pos. 11, indem Sie die Schrauben Pos 21 entfernen.
• der Kupplung gelöst
• Durch Entfernen der Zylinderschrauben, Pos. 25 kann die komplette Steuereinheit entfernt und aus­getauscht werden.
• Ersetzten Sie die Dichtungen der Steuereinheit, Pos. 37 sowie des Deckel-Flanschs, Pos 31 beim Zusammenbau des Reglers
Verfahren Sie gemäß Kap. 9
11.3 AUSTAUSCH DER HEBELPACKUNG
Zum Austauschen der Packung sollte das Regler­gehäuse grundsätzlich drucklos gemacht werden
• Take the cover flange, pos 11, off by remo pos 21.
• When removing the cover flange, the lever will be re- moved from the coupling
• Remove the two hexagon socket screwsM, pos. 25 and you ran remove and exchange the entire control unit
• Always replace the gasket of the control unit, pos. 37 and the gasket of the cover flange, pos. 31 when re­assembling the regulator
Proceed per chapter 9
11.3 REPLACING THE LEVER PACKING
Please make sure the regulator housing is depres­surised before replacing the packing.
39
Page 40
Die Packung kann ausgetauscht werden ohne das Reg-
Dazu wird nach Entfernen der Schutzkappe, Pos.
72, die Stopfbuchse Pos. 74 herausgedreht und die
EE6 HR4, HS50
lergehäuse zu öffnen.
•
Packung Pos. 35 gewechselt.
• Danach die Stopfbuchse Pos. 74 wieder ein­schrauben und auf Dichtheit prüfen.
You can replace the lever packing without opening the regulator housing.
• After removal of the protective cap, pos. 72, unscrew the gland, Pos. 74 and replace the packing Pos. 35.
• Re-assemble the gland, Pos. 74 and check for leak- ages
11.4 AUSTAUSCH DER VENTILPACKUNG
Die Ventile dichten rückwärts, d.h. im voll geöffneten Zustand können die Packungen ausgewechselt werden. Dennoch ist es empfehlenswert das Reglergehäuse zu­vor drucklos zu machen (siehe 11.2). Der Austausch der Packung am Hebel darf nur wie oben beschrieben vorgenommen werden!
11.5 ENTLÜFTUNG
Luft oder andere nicht kondensierbare Gase können sich sehr schädlich auf die gesamte Anlage und insbesonde­re den Hochdruckschwimmer-Regler auswirken. Nahezu alle Probleme können darauf zurückgeführt werden. Eine gute Entlüftung ist daher wichtig.
Wenn die Anlage häufig entlüftet werden muss oder das Eindringen von Luft nicht vermieden werden kann, z.B. wenn Gleitringdichtungen von Verdichtern im Vacuum laufen, ist eine automatische Entlüftungseinrichtung sehr zu empfehlen!
Das nachfolgend (Fig. 17) dargestellte WITT-Zubehör (kann optional bestellt werden) wird zur Entlüftung ge­nutzt. Es besteht aus einem Wasserbehälter, der auf den Regler aufgesetzt werden kann und einem Schlauch mit ½“ Gewindeanschluss.
Schrauben Sie den Gewindestift Pos. 93 an der dafür vorgesehenen Stelle ein (beim HS sowie HR 4 im Flansch). Setzen Sie den Wasserbehälter Pos. 91 auf und befestigen Sie den Schlauch Pos.9 2 an dem Entlüf­tungsventil EE3/EE6. Nachdem das Gefäß mit Wasser gefüllt wurde, kann das Einstellventil EE3/EE6 vorsichtig geöffnet werden.
11.4 REPLACEMENT OF THE VALVE PACKING
The valves can be back seated which means the stem packing can be replaced in a fully open position. It is still recommended that you depressurise the regulator housing before carrying out this work (see 11.2) The replacement of the lever packing has to be carried out as decribed above (11.3).
11.5 PURGING
Air or any other non-condensable gases can harm the entire refrigeration plant, particularly the high-pressure float regulator. Most of the difficulties experienced are caused by this particular problem. Efficient purging is therefore very important.
When purging is necessary regularly or air intake cannot be excluded, e.g. shaft seals of compressors are operating in vacuum, an automatic purger is highly recommended.
The following sketch (fig. 17) shows the optional WITT gas purge equipment designed to be used for correct purging. The equipment consists of a special water container that can be positioned on the float and a hose with ½” threaded connection.
Screw in the threaded pin, Pos.93, at the intended location (at the HS and HR4 in the flange). Place the water con­tainer, Pos. 91 on the pin and connect the hose, Pos. 92, to the purge valve EE3/EE6 at the top. After the container has been filled with water you can carefully open the regu­lating valve EE3/EE6.
Entlüftungseinrichtung für HR / HS
Solange Luftblasen bzw. nichtkondensierbare Ga­se aufsteigen, befindet sich noch Luft in der Anla­ge.
Achtung: Ammoniak ist in Wasser sehr gut löslich und erzeugt keine Blasen.
40
Fig. 17
EE3 HR1-HR3, HS30-HS40
Optional purge device HR / HS
As long as air or non-condensable gas bubbles continue to rise to the surface the housing is being purged. Attention:Ammonia is very good soluble in water and creates no bubbles.
Page 41
Die Entlüftung ist auf jedenfalls vorsichtig vorzunehmen, da das Wasser während des unter Umständen länger dauern­den Vorgangs verdampfen kann und dann Ammoniak aus­treten kann. Wenn der Regler an einer frostgefährdeten Stelle montiert ist, könnte das Wasser einfrieren.
Purging must be carried out carefully as the water may over a period of time evaporate allowing ammonia to atmosphere also. The regulator should only be fitted with this air purger in a frost-free location to avoid the water freezing.
Die Entlüftung darf nur unter Aufsicht erfolgen!
Im Anschluss ist das Wasser z.B. mit Lackmuspapier zu prüfen und ggf. zu neutralisieren, bevor es in die Kanalisati­on eingeleitet werden darf
11.6 ERWEITERUNG DER UNTERDRUCKDÜSE
Die Bohrung der Unterdruckdüse ist werkseitig so bemes­sen, dass der durch den Gas-Bypass theoretisch ermittelte Leistungsverlust unter 1% der Nennleistung bleibt. Bei übli­cher Leitungsdimensionierung sollten die Gase, die sich auf einer Entfernungen bis zu 30 m und Höhenunterschiede von bis zu 3 m bilden, abgeführt werden.
Bei erhöhtem Gasanfall ist es möglich, die Unterdruckdüse etwas zu erweitern, indem die Öffnung schrittweise aufge­bohrt wird.
Zuvor sollten Sie sicherstellen, dass die Anlage ausreichend entlüftet wurde!
Der Leistungsverlust der Anlage erhöht sich durch das Aufbohren der Unterdruckdüse.
Das Gehäuse wie zuvor beschrieben entleeren und drucklos machen, bevor die Schrauben gelöst warden Nach Abnahme des Deckels/Gehäuses kann die Funktion des Reglers gut beobachtet und geprüft werden.
11.6 ENLARGING THE LOW PRESSURE NOZZLE
Purging should only be carried out under supervi­sion!
Upon completion of purging, the water should be checked and neutralized if required before safe disposal.
The hole of the low pressure nozzle is delivered from the work shop in such a way that the theoretical calculated value of the capacity loss due to the gas-bypass is less than 1% of the nominal capacity. With common design of the piping system any gases that may form over a dis­tance of up to 30 m and height differences of up to 3 m shall be drawn off. When increased gas formation occurs it is possible to increase the low-pressure nozzle orifice size by drilling it out step by step.
Before carrying out this modification please make sure the plant has correctly been purged!
The efficiency of the plant will fall the more the low-pressure nozzle orifice is increased.
The housing should be drained and purged as described before, before any srews are loosened. Upon taking the cover/housing off, the function of the regulator can be observed and checked.
Die Bohrung am oberen Ende des Röhrchens stellt die eigentliche Unterdruckdüse dar. Bei HR1-3 Reglern ist das Röhrchen am Deckel befestigt, beim HR4, WPHR und den HS-Reglern kann das Röhrchen aus der Verschraubung gelöst werden. Es empfiehlt sich die Bohrung bei Bedarf schrittweise zu vergrößern.
Wenn der Hochdruckschwimmer-Regler häufig im Teillast­bereich eingesetzt wird, kann es sinnvoll sein, die Unter­druckdüse zu verkleinern.
12. FEHLERSUCHE
Trotz des einfachen mechanischen Prinzips der Hochdruck­schwimmer-Regelung kommt es bei ausgeführten Anlagen gelegentlich zu Problemen.
Erfahrungen haben gezeigt, dass in den meisten Fällen eine zu große Gasmenge im Reglergehäuse das Ansteigen des Flüssigkeitsniveaus behindert und deshalb die Schwimmer­kugel nicht aufschwimmen kann.
Ein Schauglas mit kommunizierenden Verbindungen zum Entlüftungs-/Ablassventil, vorübergehend montiert, kann Aufschluss über den Füllstand im Reglergehäuse geben.
Die häufigsten Fehlerursachen sind im folgenden näher er­läutert:
The hole (orifice) on the top of the small tube works as a low pressure nozzle. For HR1 – 3 the small tube is connected to the cover, with HR4, WPHR and HS-regulators you disassemble the tube from the screw connection. It is recommended to increase the hole step by step.
If the high-pressure float regulator is operated mainly under part load conditions, it is possible to restrict the low-pressure nozzle orifice diameter.
12. TROUBLE SHOOTING
Although the float regulation is a simple mechanical de­sign in some cases problems occur in refrigeration plants.
Our long term experience has shown that in nearly all cases an increased amount of flash gas in the housing will have the effect of lowering the liquid level making it difficult for the ball to rise
A temporary side glass with branch connections at the inlet-/outlet valves can be used to check the liquid level within the regulator housing.
The most common reasons for installation problems are explained in the following chapters:
41
Page 42
to be realised as mentioned earlier the installed height H
12.1 LUFT IN DER KÄLTEANLAGE
Bei großem verdampferseitigem Inhalt der Kälteanlage wird oft eine Restmenge an Luft unterschätzt, die trotz des Eva­kuierens vor der Inbetriebnahme in der Anlage verbleibt. Bei NH
gelangt die Luft zwangsläufig in das Schwimmergehäu-
3
se und kann hier die Unterdruckdüse überfordern.
Eine Entlüftung, wie in Kap. 11.5 beschrieben, schafft in den meisten Problemfällen Abhilfe.
12.2 GASBILDUNG IN DER ZULAUFLEITUNG
Es kann verschiedene Gründe für dieses Problem geben:
• eine knappe Leitungsdimensionierung,
• das Vorhandensein von Einbauten wie z.B. Filtern,
• eine ungewöhnlich hohe Platzierung des HR über
dem Verflüssigerausgang oder
• eine unisolierte Leitungsführung in heißer Umge- bung.
All dies kann dazu führen, dass ein zu großer Dampfanteil in der Zulaufleitung gebildet wird, der die Unterdruckdüse überfordert.
Wenn die oben genannten Ursachen nicht beseitigt werden können, ist es möglich, die Unterdruckdüse durch schrittwei­ses Aufbohren so zu erweitern, dass die Dampfmenge abge­führt werden kann (siehe Kap. 11.6).
12.3 PARALLELSCHALTUNG VON VERFLÜSSIGERN
ei der Parallelschaltung von Verflüssigern in eine gemein­same Sammelleitung wird häufig beobachtet, dass unter­schiedliche Strömungswiderstände der Verflüssiger zu einer Gasbildung in der Leitung zum Hochdruckschwimmer­Regler führt. Die Temperaturen am Austritt der einzelnen Verflüssiger sind zu überprüfen. Wenn eine Unterkühlung des Konden­sats in einem Verflüssiger festgestellt werden kann, dann staut sich Kondensat im Verflüssiger zurück. Die Anlage arbeitet dann instabil und beeinträchtigt so die Funktion des Hochdruckschwimmer-Reglers.
Eine Flüssigkeitssäule am Austritt der Verflüssiger gemäß Kap. 6.3.2 soll die unterschiedlichen Druckverluste ausglei­chen. Wie bereits erwähnt, sind die eingeplanten Höhen in manchen Fällen nicht ausreichend und müssen ggf. ent­sprechend vergrößert werden.
Sind die oben genannten Maßnahmen nicht durchführbar oder nicht erfolgreich, so muss für jeden Verflüssiger ein separater Hochdruckschwimmer-Regler vorgesehen wer­den.
12.1 AIR IN THE REGRIGERATION SYSTEM
With plants where large internal volumes exist on the evaporator side there are often quantities of remaining air and non-condensable gases in the system that are often underestimated. When using NH3 the air will auto­matically collect in the float regulator housing. This vol­ume of gas will exceed than capability of the low­pressure nozzle.
Purging according to chapter 11.5 will resolve the prob­lem in most cases.
12.2 GAS FORMATION IN THE LIQUID FEED LINE
There are several causes of this problem:
• The liquid feed line has been sized too small
• There are internal filters, etc,
• The regulator is positioned too high above the
condenser
• The liquid supply line is installed uninsulated in warm plant room environment
All these will contribute to an unacceptable level of flash gas in the liquid feed line, causing the low-pressure noz­zle to become overloaded.
If the above-mentioned conditions cannot be changed it is possible to increase the low-pressure nozzle orifice diameter so the gas can be released (see chapter 11.6).
12.3 PARALLEL OPERATION OF CONDENSERS
With parallel installation of condensers in a common feed line to the float regulator it has often be observed that the different line pressure drops causes flash gas formation in the feed line to the high-pressure float regulator.
Check the temperatures at each condenser outlet. If you observe sub cooling of the liquid refrigerant at one of the condenser outlets this will indicate that liquid is backing up inside the condenser. The entire plant is then operating in an unstable condition effecting the proper functioning of the high-pressure float regulator.
With the pipe work layout using a liquid head in the down leg of each condenser circuit according to chap. 6.3.2 the different pressure drops can be compensated. But it has
in some cases will not sufficient and should be increased accordingly. If the above-mentioned modifications cannot be achieved or do not have the desired effect, each condenser must be equipped with its own separate high-pressure float regulator.
12.4 LUFTGEKÜHLTE VERFLÜSSIGER
Der oben beschriebene Effekt tritt auch bei luftgekühlten Verflüssigern auf, wenn die einzelnen Rohrreihen nicht gleichmäßig beaufschlagt werden, weil z.B. eine Seite von der Sonne angewärmt wird oder die Rohrleitungen unter­schiedliche Druckverluste aufweisen.
Durch Drosseln am Eingang jeder Rohrreihe lassen sich die unterschiedlichen Druckverluste ausgleichen.
42
12.4 AIRCOOLED CONDENSER
The above flash gas formation can occur with air-cooled condenser installations. Where separate banks of tube rows are loaded differently, , e.g. if sunshine warms up part of one side or if the tube banks have different pres­sure drops.
By regulating each pipe row the different pressure drops can be compensated for.
Page 43
12.5 PLATTENVERFLÜSSIGER
Bei Plattenverflüssigern besteht die Verbindung zwischen Eintritt und Austritt aus dünnen Kanälen, die häufig unter­schiedlich belastet sind. Ein ausreichend dimensionierter Siphon ist hier besonders wichtig. (Siehe Kap.6.4.4)
12.6 HD-SAMMELBEHÄLTER
Die Einbindung eines HD-Sammlers verhindert den er­wünschten Selbstheilungseffekt, der in Kap. 5.1.5 beschrie­ben wird.
12.7 EINSATZ VON ÖLKÜHLERN
Beim Einsatz von Hochdruckschwimmer-Reglern mit ver­schlossener Unterdruckdüse in Verbindung mit kältemittel­gekühlten Ölkühlern ist besonders darauf zu achten, dass immer eine ausreichende Flüssigkeitsvorlage im HD­Sammler zur Verfügung steht. Der Hochdruckbehälter sollte so bemessen sein, dass ca. 5 min der Ölkühler mit Flüssig­keit aus der Vorlage versorgt werden kann, bevor Konden­sat von den Verflüssigern nachfließt. Achtung: Bei Anlauf der Verdichter kann die Flüssigkeits­vorlage sehr schnell absinken.
Beim Einbinden des Reglers gemäß 10b ist speziell darauf zu achten, dass kein Gas in den Regler gelangen kann (sie­he dazu Kap. 6.4.2) Häufig kommt es beim Anlaufen der Verdichter zu einem Kältemittelmangel, d.h. dem Hochdruckschwimmer-Regler fließt kein Kältemittel zu. Es wird ein Blockieren des Schwimmkörpers unterstellt, da sich der Regler abkühlt und mitunter die Leitung zum Magnetventil bereifen kann. Ein Bereifen der Magnetventilleitung ist jedoch kein Indiz dafür, dass das Schwimmergehäuse mit Flüssigkeit gefüllt ist. Durch Drosselung des Kältemittelzuflusses zum Ölkühler kann ggf. eine ausreichende Vorlage im HD-Sammler er­reicht werden.
12.5 PLATE TYPE CONDENSER
For plate in shell type condensers with thin channels that are loaded unequally from an internal hot gas con­nection between inlet a properly sized siphon is ex­tremely important (see chapter 6.4.4)
12.6 USE OF HP LIQIUD RECEIVERS
The use of a high-pressure receiver in the feed line will slow down or stop the self-recovery effect that is ex­plained in chapter 5.1.5.
12.7 USE OF OIL COOLERS
When high-pressure float regulators with closed low­pressure nozzles are used in systems with refrigerant cooled oil coolers you must ensure that there is always sufficient liquid refrigerant in the HP receiver. The high-pressure receiver should be sufficiently sized so that the oil cooler can be supplied with refrigerant for at least 5 min., before refrigerant is returned from the condensers. Caution: Be aware under certain start-up conditions of the system the surge drum can rapidly empty of refriger­ant. When the regulator is installed per fig. 10b particular care should be taken that no gas can enter the regulator (see therefore chapter 6.4.2) It has been observed during start-up there is a lack of refrigerant liquid feed to the high-pressure float regulator. When a blockage of the float ball is suspected, i.e. as the regulator is cold and the line to the solenoid valve is be­coming frosted. Note: A frosted line to the solenoid valve does not nec­essarily indicate that the housing is filled with refrigerant. By throttling the refrigerant flow to the oil coolers with regulating valves it may be possible to achieve the re­quired feed from the HP receiver.
43
Page 44
Regulator does not open
Nr.
1
2
3
4
5
6
44
Erscheinung
Regler öffnet nicht im Automatikbetrieb
Regler schließt nicht
Verflüssigungsdruck zu hoch ohne Rück­stau
Zu hoher Verflüssi­gungsdruck durch Rückstau
Stark schwankender Druck auf der ND­Seite
Minimalstandalarm auf der ND-Seite
STÖRUNGSANALYSE:
Ursachen und Behebung
- Zu viel Luft im System
- Zu klein dimensionierter Regler?
- Eintritts-/Austrittventil verschlossen?
- Zu große Druckdifferenz?
- Unterdruckdüse zu klein oder blockiert?
- Feuchtigkeit im System, Unterdruckdüse zugefro-
ren?
- Schieberersteuerung z.B. durch Ablagerung oder Korrosion blockiert
- Schwimmerkugel defekt
- falsche Schwimmerkugel (ggf. austauschen)
- Transportsicherung des Hebels (Knebel bzw. Loch
im Hebel muss nach unten weisen)
- Schiebersteuerung verschlissen (ggf. austauschen)
- Öffnung der Unterdruckdüse zu groß (oder bei
Anschluss einer Magnetventilleitung nicht ver­schlossen worden)
- fehlende Wärmeabfuhr am Verflüssiger
- zu klein dimensionierter Verflüssiger
- zu große Kälteleistung im Anfahrzustand
- Luft in der Anlage (siehe Kap 12.1)
- Dampfbildung in der Zulaufleitung (siehe Kap. 12.2)
- Verflüssiger parallel angeordnet (siehe Kap. 12.3)
- Einsatz von Plattenverflüssiger siehe Kap. 12.5)
- Mangelhafte Ölkühlerfunktion (siehe Kap. 12.7)
- Zu große Widerstände in der Zulaufleitung (siehe
Kap. 6.4)
- Zu großer Höhenunterschied vor dem Regler (ggf.
Unterdruckdüse vergrößern)
- zu geringe Kältemittelfüllung
- hohe Reibkräfte an der Schiebersteuerung (Innen-
teile auf Ablagerungen bzw. Korrosion prüfen)
- Regler wurde überdimensioniert
- siehe Pkt. 4
- Verflüssiger im Winter mit Kältemittel gefüllt (ein-
zelne oder alle Verflüssiger absperren)
- Zu geringe Kältemittelfüllung
Symptom
during automatic opera­tion
Regulator does not close
Condensing pressure is too high without back-up
Too high condensing pressure because of back-up
Heavy fluctuating pres­sure on the LP side
Minimum level alarm on the LP side
TROUBLE SHOOTING
Possible Causes
- Too much air in the system
- Too small selected regulator?
- Closed inlet-/outlet valve?
- Too high pressure difference?
- Low-pressure nozzle too small or blocked?
- Moisture in the system, now pressure nozzle frozen?
- Slide regulation is blocked, e.g. with debris or due to
corrosion
- Float ball is damaged
- False float ball (can be exchanged)
- Transport safety device blocks the float ball (hole in
the lever shall face down)
- Slide block is worn (can be exchanged)
- Opening of the low pressure nozzle is too big (or:
when connecting a solenoid valve line the low pres­sure nozzle is not closed)
- Condenser does not transfer any heat
- Too small condenser
- Capacity is too large during start-up
- Air in the system (see chap. 12)
- Gas in the supply line (see chap. 12.2)
- Parallel condensers (see chap. 12.3)
- Use of plate type condenser (see chap. 12.5)
- False connection of oil coolers (see chap. 12.7)
- Resistance in the supply line is too high (see chap.
6.4)
- The vertical distance is too high (the low pressure nozzle can be enlarged)
- Too low refrigerant charge
- High friction at the slide block (look for any debris or
corrosion)
- Float regulator is too big
- See point 4
- Condenser is backed up with refrigerant (isolate one
or more condensers)
- Too low refrigerant charge
:
Page 45
45
Page 46
TH.WITT Kältemaschinenfabrik GmbH
Lukasstraße 32 •52070 Aachen, Germany Tel. +49 (0)241 1 8208 - 0 Fax +49 (0)2 41 1 82 08- 49 [email protected]
W3510-6.01 c–4.0702
www.th-witt.com
Loading...