Wiremold ZA277Y Installation Manual

Page 1
ZONESENTINEL® SERIES
AC Panel Transient Voltage Surge Suppressors
Installation
Instructions
& User Manual
Page 2
INTRODUCTION
This document explains how to install the ZoneSentinel® Series of AC Panel Surge Protective Devices.
INSTALLATION INSTRUCTIONS
Warning: Terminals marked L1, L2, L3, N, GND (where relevant)
must be connected respectively to phase(s) neutral and ground. Failure to comply may result in danger or damage. See correspond­ing diagrams for proper connections.
INSTALLATION DESCRIPTION
ZoneSentinel® units are connected in parallel (or in “shunt” across)
the supply to be protected. The connecting cable does not carry the supply current, only the current associated with suppressing the transient overvoltage.
MOUNTING
The units should be mounted as close as possible to the panel to be protected. See Connecting Lead lenghts on page 4. Conduit, prefer­ably metallic, is to be installed from the suppressor to the panel. Drill holes in the ZoneSentinel® enclosure only in the designated areas as shown in recommended cable dressing illustrations (page
5). Mount the unit in the appropriate location using the mounting holes provided on the enclosure.
2
Page 3
OVERCURRENT PROTECTION
The ZoneSentinel® can be installed on electrical services without overcurrent protection if the available SCCR is 100k AIC or less. If the SCCR is greater than 100k AIC, coordinated overcurrent protection (30-60A) must be installed.
FLUSH MOUNT
The fl ush mount ZoneSentinel® is installed into a suitably sized hole in the wall. Remove the four snap-in screw covers and remove the cover, temporarily disconnect the cover ground wire. Choose a location such that the recessed part of the ZoneSentinel® enclosure can be fi xed to a wall stud or suitable upper or lower support. Be sure that the ZoneSen- tinel® enclosure is fl ush with the wall. Follow the standard instructions for location and connecting leads. Reconnect the cover ground wire and install the cover plate. Replace the four snap-in screw covers.
INCORRECT INSTALLATION WILL IMPAIR THE EFFEC­TIVENESS OF THE AC PANEL PROTECTORS. Particularly
important is the length of the connecting leads (page 4).
Page 4
CONNECTING LEADS
Connect the suppressor as shown in the installation diagram. Refer to page 5 for recommended cable dressing. Connect the terminals within the suppressor to the load side of 30A breakers within the panel.
RECOMMENDED WIRE GAUGE
Minimum of 10 AWG Maximum of 4 AWG ( for ease of dressing)
LENGTH OF CONNECTING LEADS
The longer the connecting leads between the ZoneSentinel® and power panel, the higher the residual transient voltage.
RECOMMENDED MAXIMUM: 19” (500mm) IDEALLY: 10” (250mm)
Each 10” (250mm) increase in cable length; increases clamping voltage by 25V per 1000A surge current discharged.
• BIND THE PHASE NEUTRAL AND GROUND CONDUCTORS TIGHTLY, OVER THE ENTIRE RUN FROM THE SUPPRESSOR TO THE SERVICE PANEL.
• ALWAYS USE THE SHORTEST LENGTH OF CONNECTING CABLE POSSIBLE.
4
Page 5
RECOMMENDED CABLE DRESSING
DIMENSIONS
5
Page 6
STATUS INDICATORS
The ZoneSentinel® units have comprehensive, continuous visual status monitoring present on each module.
Power/Protection
Indicator
Status Full Reduced No No Power to High N-G
Indicated Protection (Standby) Protection Protector Voltage* Present Protection
LED Green Red Red Green Red & Green Indicator LED Lit LED Lit LED Lit LED Out LED Lit
REMOTE INDICATORS
A remote indication of the reduced protection state is available as a nor ­mally open or normally closed dry contact.
Pluggable Connector
Customer
supplied wires
Common
Normally Closed
Normally Open
End view of ZoneSentinel Module
*WARNING:
OF HIGH NEUTRAL TO GROUND VOLTAGE
On certain models, if both Red and Green lights are on, consult a qualifi ed electrical contractor to check the integrity of the building wiring.
6 3
Page 7
ZONESENTINEL
and Schematic Connection Diagrams
120/240V SPLIT PHASE 3W
®
Confi guration
ZONESENTINEL
and Schematic Connection Diagrams
120/208V THREE PHASE 4W WYE 240/415V THREE PHASE 4W WYE 277/480V THREE PHASE 4W WYE 220/380V THREE PHASE 4W WYE
®
Confi guration
7
Page 8
MAINTENANCE
At intervals not exceeding two months, check:
1. Status indication lights
2. Conditions of connecting cables and terminals
Module Replacement
WARNING: Before opening the access panel, ensure
that the AC supply has been disconnected.
Unplug the remote contact connector at the top of the module. Remove the mounting nuts at the top and bottom of the module. The protection module can now be removed.
WARNING: Replace the defective module with a module
having the same model numbers.
Installation of the replacement module is the reverse of the above procedure. Final step, check that all cable connections are secure and nuts are tightened. Do not overtighten.
NOTE: No customer serviceable parts inside. Opening module WILL void Warranty
The Wiremold Company
In US:
60 Woodlawn Street, West Hartford, CT 06110 800-621-0049 FAX 860-232-2062 Outside U.S.: 860-232-6251
In Canada:
Patented No. 5, 311, 393
850 Gartshore Street, Fergus, Ontario N1M 2W8 (519) 834-4332 FAX (519) 843-5980
Loading...