WIREMOLD®
Poke-Thru Abandonment
No: 1001759R2 – 1116
Catalog Number(s) • Numéro(s) de Catalogue • Número(s) de Catálogo:
AP-FITTC, FITPLUG-C, FITPLUG-T, and RCAPFFTC
Abandonment Options:
FIT Abandoned with Poke-Thru Stem in Floor – Use AP-FITTC
FIT Abandoned with Poke-Thru Stem Removed – Use FITPLUG-C or FITPLUG-T
RC91GHBTC, RC92GHBTC – Use RCAPFFTC
RC9FFTC – Use RCAPFFTC
Country of Origin • Pays d'origine • País de origen:
Made in US • Fabriqué aux États-Unis • Hecho en US
IMPORTANT:
Please read all instructions before
beginning installation
Legrand electrical systems conform to and
should be properly grounded in compliance with
requirements of the current National Electrical
Code or codes administered by local authorities.
All electrical products may present a possible
shock or fire hazard if improperly installed
or used. Legrand electrical products may
bear the mark of a Nationally Recognized
Testing Laboratory and should be installed
in conformance with current local and/or the
National Electrical Code.
IMPORTANT :
Veuillez lire l'ensemble des
instructions avant de commencer
l'installation.
Les systèmes électriques Legrand sont
conformes au Code National de l'électricité
(National Electrical Code) ou aux codes
locaux en vigueur et doivent être mis à la terre
conformément à ces codes.
Tous les produits électriques peuvent présenter
un risque d'électrocution ou d'incendie s'ils ne
sont pas installés ou utilisés correctement. Les
produits électriques Legrand peuvent porter la
marque d'un laboratoire reconnu et doivent être
installés conformément au Code national de
l'électricité et/ou aux codes locaux en vigueur.
Installation Instructions • Notice d’Installation• Instrucciones de Instalación
IMPORTANTE:
Lea todas las instrucciones antes
de comenzar la instalación.
Los sistemas eléctricos Legrand cumplen con
los requisitos del Código Eléctrico Nacional
(National Electrical Code, NEC) actual o con los
códigos impuestos por las autoridades locales y
deben conectarse a tierra consecuentemente.
Todos los productos eléctricos pueden presentar
un riesgo de descarga o incendio si se los
instala o utiliza incorrectamente. Los productos
eléctricos Legrand pueden llevar la marca de
un laboratorio de pruebas reconocido a nivel
nacional y se deben instalar conforme al código
local en vigencia o al Código Eléctrico Nacional.
Abandonment plates are required to maintain the fire rating of the floor assembly whenever a
poke-thru fitting is abandoned or removed from the floor. The abandonment plates in these
instructions are shown in the UL Fire Resistance Directory.
FIT Abandoned with Poke-Thru Stem in Floor: (Use AP-FITTC)
Disconnect electrical service from service fitting.
1

2
Remove side screws and top of 200 or 241 Service
Head. Remove receptacles and communication
modules. Remove cables.
3
4
Remove two anchoring screws and base of service
head.
Attach abandonment plate with two #8-32 screws.
200 Series
241 Series
5
Completed installation.
2

FIT Abandoned with Poke-Thru Stem Removed: (Use FITPLUG-C or FITPLUG-T)
Disconnect electrical service from service fitting.
1
Remove side screws and top of 200 or 241 Service Head.
Remove receptacles and communication modules.
Remove cables.
2
3
4
Remove two anchoring screws and base of service head.
200 Series
241 Series
Pull poke-thru device body through floor from below.
Pull Down
3

5
A. Align FITPLUG-C or FITPLUG-T with opening in
surface.
B. For Carpet: Push plug down into hole until round
plate seats against concrete.
For Tile: Push plug down into hole until rectangular
plate seats against tile surface.
Complete installation on tile or carpet.
Step A
Step B
6
Tile
Carpet
Glue Carpet Over
Abandonment Fitting
4

RC91GHBTC and RC92GHBTC: (Use RCAPFFTC)
Disconnect electrical service from service fitting.
1
NOTE: Includes 291 and 292 Pedestal Service Fitting.
Remove side screws and top of service head. Remove
receptacles and communication modules. Remove cables.
2
3
4
Remove four anchoring screws and base of service head.
Cut 6 1/2" [165mm] diameter hole in carpet that is
concentric with the cored hole.
NOTE: Use template provided on last page of instruction sheet.
5

5
6
Attach abandonment plate with the four #6-32 screws
provided.
Completed installation
RC9FF: (Use RCAPFFTC)
Disconnect electrical service from service fitting.
1
Remove cables. Remove lid, eight anchoring screws,
hex housing, and trim ring.
2
Lid
Hex Housing
Trim Ring
6

3
4
Attach abandonment plate with the four #6-32
screws provided.
Completed installation.
7

Template for 6 1/2" [165mm] Cutout Required for RC91GHB/RC92GHB Abandonment Installation:
Carpet/Tile Cutout
6 1/2" [165mm]
6 1/2"
[165mm]
CAUTION: When printing copies of this template, please be sure template is scaled
correctly and is the correct size once it is printed.
No: 1001759R2 1116
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
860.233.6251
1.877.BY.LEGRAND
www.legrand.us
www.legrand.ca