Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Legrand/Wiremold electrical
products may bear the mark of a Nationally Recognized Testing
Laboratory (NRTL) and should be installed in conformance with current
local and/or the National Electrical Code.
Poke-Thru
Plates & Plugs
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 002 048 R4 – Updated January 2012
Products Covered – Abandonment Plates:RC7APTC, RC9APTC, AMD8APTC, AV3APTC, RC4APTC, RC3APTC
NOTE: Abandonment plates and plugs are required to maintain the fire rating of the floor assembly whenever a poke-thru fitting is
abandoned. The abandonment plates and plugs shown in these instructions are in the UL Fire Resistance Directory.
Abandonment
IMPORTANT: Please read all instructions
before beginning.
Abandonment Plugs: ABPLUG3, ABPLUG4, ABPLUG6 and ABPLUG8.
ABANDONMENT INSTRUCTIONS – For use when the poke-thru unit is left in the floor.
Covers the following series of devices: RC7, RC9, RC9AMD, RC4, RC3, AV3 and AMD8
Step 1 Existing poke-thru unit. Step 2 Remove two screws in slide
NOTE: RC3 Series shown in example. RC4, RC7, and
RC9 Series abandonment installations follow
the same steps.
CAUTION: RC3, RC4, RC7, and RC9 Series must be
abandoned with receptacles installed.
holder. Remove slide holder
and attached doors.
IMPORTANT: The internal gasket,
duplex receptacle,
and communication
modules must not
be removed to
maintain UL Listing
and Classification.
Step 3 Attach abandonment plate
with two screws provided.
CAUTION: Do not over tighten
cover mounting screws.
Step 4 Complete installation.

ABANDONMENT INSTRUCTIONS – for use when the poke-thru unit is removed from the floor.
Covers all 3", 4", 6" and 8" poke-thru devices
Step 1 Locate poke-thru unit or core hole
Step 2a For ABPLUG3 & ABPLUG4:
that needs to be sealed with an
abandonment plug.
Step 2b For ABPLUG6 & ABPLUG8: Remove cover
assembly from Poke-Thru by removing two
(2) 8-32 screws and lifting cover off.
Remove slide holder assembly
and the internal gasket.
Disconnect power and
communications devices and
remove flange.
Step 3b For ABPLUG6 & ABPLUG8: Remove poke-thru
unit from floor by bending tabs inward and
pulling unit up.
Step 3a For ABPLUG3 & ABPLUG4:
Remove poke-thru unit from hole.
Step 4 Push in proper abandonment plug.
For 3" core hole, use ABPLUG3
For 4" core hole, use ABPLUG4
For 6" core hole, use ABPLUG6
For 8" core hole, use ABPLUG8
Step 5 Installation complete.