PLUGMOLD PLUS™NM2000
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 41080R4 – Updated June 2003
Lay out Raceway path. Determine feed method and location
from figures A, B, and C below.
1
Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.
All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are
UL Listed to U.S. and Canadian safety standards,made for interior
use only, and should be installed in conformance with current local
and/or the National Electrical Code.
Wire Size No. of Wires
THHN/THWN O.D. @ 40% Fill
Power Wiring 10 AWG 0.153 15
Without Devices 12 AWG 0.122 31
14 AWG 0.105 45
Power Wiring 10 AWG 0.153 —
With Plugmold Devices 12 AWG 0.122 8*
14 AWG 0.105 8*
*Includes the four conductors of the wiring harness.
NM2051H
Fig. A* – Back Feed
* This method is not recommended if splice area is less
than 4". See Figure B or C for feeding this condition.
Measure and cut raceway base and cover.
See commmon fittings dimensions below.
2
1 3/4"
[45mm]
NM2010A
Fig. B – End Feed
1 5/8" [41mm]
from edge of wall
1" [25mm]
from edge
of wall
1 1/16"
[27mm]
Fig. C – Feed from Existing Wall Box
Install raceway and fittings bases
using No. 8 flathead screws.
3
Wiring Method – Refer to Instructions (A thru E) according to your application.
Field Wired Raceway – NM2000 Series:
A
Install wire in raceway and install wire clips as needed.
A1
A2
Install blank
end fittings with
No. 8 flathead
screws where
needed. Slide
raceway cover
into end fitting.
Base
NM2010B
NM2000WC
Snap on raceway and fitting covers.
A3

Wired Cover Sections:
B
Connect receptacle harness to feedpoint
B1
using approved methods.
Snap cover/harness assembly onto
B2
base and snap on any fitting covers.
For additional circuits, use bypass area shown below.
B3
End View
Bypass
Areas
Snapicoil – NM2000SC Series:
D
Lay out Snapicoil harness so that receptacles are
D1
not located over feed point or at corners. Connect
harness to feed point.
C
C1
NOTE: This device features an internal protection that will disconnect
Snap receptacles into
D2
NM2000 cover.
Wired Cover Sections with Receptacle
Surge Protection – NM20SGB Series:
Install wired cover system as above.
To remove, back out screw
and unplug. To replace, push
in plug and install screw.
the surge protective component at the end of its life but will
maintain power to the load – now unprotected. If this situation
is undesirable for the application, follow manufacturer’s
instructions for replacing this device.
Snap wired cover section
D3
onto base and snap on
any fitting covers.
NM2027SP
Relocatable Power Tap – NM20C:
E
Install mounting clip using
E1
flat head screws.
NM2003
Snap unit into
E2
mounting clips.
© Copyright 2003 The Wiremold Company All Rights Reserved
Plug cordset into wall outlet.