Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.
Evolution™Series
Floor Boxes
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 010 387R1 – Updated February 2012
Products Covered: EFB6S, EFB8S, EFB10S, EFB6S-OG, EFB8S-OG, EFB10S-OG
CAUTION: Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
NOTE: For use on bare (polished) concrete or terrazzo floors. EFB610-CTR is required.
IMPORTANT: Please read all instructions
before beginning.
EVOLUTION SERIES FLOOR BOX COMPONENTS
(EFB10S Shown)
End Cap
Cable Guide
Box
Filler Plate
Toggle Clamp
Tunnel
D
ivider
Back Plate
Device Bracket
Concrete Leveling Legs
KO Plates
INSTALLATION INSTRUCTIONS –
For Use in a Concrete Pour Application
Step 1Position box in accordance with job site floor plan
and/or engineering blue print. Use the dimensions given
in the following table as a reference for positioning.
FLOOR BOX SIZEWIDTHBOX
(Min.)HEIGHT
8-10 Gang Box –13"6"
(EFB8S, EFB10S, EFB8S-OG, EFB10S-OG)[330mm][152mm]
Step 4Each device module is supplied with ground leads
and positionable dividers to segregate services.
Attach devices to Mounting Brackets using
fasteners provided with devices, and re-attach
Back Plate to Modules using the screws provided.
ivider
D
ack
B
late
P
Mounting
Bracket
Ground Screw
Step 6If the top of the floor box cover is to be flush with
the finished concrete floor, install the
concrete/terrazzo ring before the concrete pour.
(See installation instructions included with
concrete terrazzo ring kit.) If the finished floor
surface is to be terrazzo, install the trim ring after
the concrete pour.
Step 5Level box as required and anchor box to decking. To
level use 3/8-16 threaded rod cut to length as needed
and secure with hex nuts . (Threaded rod & nuts not
included). Holes for threaded rod are provided in
each end of the leveling legs attached to the bottom
of box. Be sure to set height of the top of the box to
be flush with the finished level of the concrete pour.
NOTE: There is no provision for post
pour box height adjustment.
Step 7Pour concrete flush with the top of floor box
protective cover.
WARNING: Pour concrete to within no more than 1/16"
[1.6mm] above box protective cover. Pours
of 1/4" [6.4mm] or more over box cover will
make it difficult to break out the cover and
cause excessive concrete spalling around
the edges of the box.
3
Page 4
Step 8After the concrete has cured, locate box and
lear away any concrete from cover as needed.
c
Remove cover from box, device mounting
brackets from device modules, and clean out
any debris from inside of box.
Step 9If the finished floor is to be terrazzo, remove the
rotective cover from the box, and install the
p
concrete/terrazzo trim ring kit. See instruction
sheet included with trim ring kit.
Step 10 Pull wires as specified, and terminate to
appropriate devices (not included).
NOTE: Make sure that each device is properly
grounded in accordance with the National
Electrical Code and any local code that
may apply.
Step 11 10 Gang Box – Accepts only EFB10 Series Faceplates
8 Gang Box – Accepts standard size device plates
(2 3/4" x 4 1/2" [70mm x 114mm])
6 Gang Box – Accepts standard size device plates
(2 3/4" x 4 1/2" [70mm x 114mm])
NOTE: Various faceplates are available to accommodate
a wide range of devices, colors and styles.
(Sold separately.)
NOTE: EFB10 Series Plates only work with
EFB10S Series Floor Boxes
8 Gang Plate layout10 Gang Plate layout
Step 12 Formed wire retainers are mounted to the inside
of the box to help route card and cables exiting
the box. Retainers can be removed by loosening
the attachments screws.
NOTE: Evolution Series Floor
Boxes and Covers are
UL/cUL Listed for use
with raised floors, wood
floors, bare concrete,
concrete terrazzo, tile
and carpet or wood
covered concrete floors.
Step 13 Complete installation by attaching an Evolution
Series Floor Box Cover (Sold separately) following
the installation instructions supplied with the cover.
4
Page 5
INSTALLATION INSTRUCTIONS – For Use in a Wood or Raised Floor Application
APPLICATIONS: These units are for wood floor and access floor construction with:
• 1 1/2" [38mm] subflooring with carpet padding or
• 1 1/2" [38mm] subflooring with 1/4" [6.4mm] underlayment or and tile or linoleum
floor covering. These requirements represent the maximum floor thickness to ensure
enough cross section is available for the box to lock into the subflooring.
Step 1Position box in accordance with job site floor
plan and/or engineering blue print. Mark and cut
hole in wood floor or raised floor panel based on
the dimensions given in the following table.
Step 2Remove protective cover and device modules from
box and lower box into hole cut in floor.
1 9/16"
1
294mm]
[
15 3/8"
[391mm]
Step 3At front and back sides of box are adjustable toggle clamps that are used to
secure box to floor. Clamps are positioned to allow for up to 1 1/2" thick
floors. Tighten clamps so that box is held securely to floor.
Adjustable Toggle
Clamp Screw
NOTE: Modules are removable to facilitate
easier connection of services. Box
only needs to be removed during
adds, moves and changes.
Toggle Clamp
5
Page 6
Step 4If cabling is to be run in the direction of the long side
of the box, remove tunnel components. Remove
required KOs from box sides and attach cable fittings
Not included) to box.
(
A. It will be necessary to remove the end panels from
both the tunnel and the device module to allow
access to the module or to be able to pass wires
through the box. Module and tunnel end panels are
easily disassembled by removing their respective
ounting screws. Remove tunnel divider by cutting
m
off dividers at the score line with a hacksaw as
shown below.
emove End Cap for access
R
nto the module.
i
Device Plate
Mounting Screws
Remove Tunnel Divider shown
to pass cables from one
Module to the next.
Step 5Each device module is supplied with ground leads
and positionable dividers to segregate services.
Attach devices to Mounting Brackets using fasteners
provided with devices, and re-attach Back Plate to
Modules using the screws provided.
Divider
Back
Plate
Mounting
Bracket
Ground Screw
Step 6 10 Gang Box – Accepts only EFB10 Series Faceplates
8 Gang Box – Accepts standard size device plates
(2 3/4" x 4 1/2" [70mm x 114mm])
6 Gang Box – Accepts standard size device plates
(2 3/4" x 4 1/2" [70mm x 114mm])
8 Gang Plate layout10 Gang Plate layout
NOTE: Various faceplates are available to accommodate a wide
range of devices, colors and styles. (Sold separately.)
NOTE: EFB10 Series Plates only work with
EFB10S Series Floor Boxes
6
Page 7
Step 7Attach cable as specified and terminate to
appropriate devices (Not included).
Step 7a Re-install module into box.
Step 8Formed wire retainers are mounted to the inside of
the box to help route card and cables exiting the box.
Retainers can be removed by loosening the
attachments screws.
Step 10 Complete installation by attaching an Evolution
Series Floor Box Cover (Sold separately) following
the installation instructions supplied with the cover.
Step 9Re-attach protective cover until ready to install
finish cover.
7
Page 8
tep 11 In a raised floor application, if it is necessary to reposition floor box after box has been wired, (If
S
MC or flex cabling has been used), it is possible to detach device modules and filler plate from
box and pass the module out through the back side of the box without disconnecting wiring.
Be sure to re-use all fasteners when re-assembling box after repositioning.
NOTE: Be sure to turn off power services before working on floor box.
11A: Remove cover assembly
11B: Remove Tunnel
11C: Remove gasket plates11D: Pass module through back of floor box
NOTE: Services do not need to be disconnected
in order to move modules.
Step 12 For factory wired EFB6S, EFB8S and EFB10S with Walkerflex®Modular Wiring devices, follow steps 1 through 11.
CAUTION: Do not make or break connections while circuits are energized.