Wiremold 881RC4ATC, 881RC4ARTTC Installation Manual

Page 1
Poke-Thru Abandonment
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 003 615 – October 2003
Walker® electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
IMPORTANT: Please read all instructions
before beginning.
Products Covered: 881RC4ATC, 881RC4ARTTC
Step 1 Determine Floor Covering Thickness.
For Floor Covering less than 3/8" [10mm] thick (carpet or tile): Cut top of box off flush
with concrete surface.
For Floor Covering greater than 3/8" [10mm] thick but less than 3/4" [19mm] (carpet or tile): Allow equivalent portion of
box (floor covering thickness minus 3/8" [10mm] to extend above concrete surface.
For use with no Floor Covering or floor covering greater than 3/4" [19mm] thick (carpet or tile): Consult factory.
Step 3 Install floor covering.
Cut circular opening concentric with exposed floor box opening. Use template on back page.
Cat. No. 881RC4ATC, 881RC4ARTTC requires a 7" [178 mm] opening.
Step 2 Remove top.
Power Conduit
(center)
Communication
Conduit (outer)
Discard upper portion
of floor box.
Cut floor covering 7" [178 mm] for 881RC4ATC, 881RC4ARTTC.
Page 2
2
Step 4 Determine box height to calculate barrier score line.
Determine the letter of the highest uncut section
remaining in the box sidewall after the upper section is cut away. If any portion of the box extends above the highest graduation mark, make calculations based on the letter that appears below it.
Step 5 Cut divider at required score line.
See cross-reference chart at right.
Step 6 Separate barrier.
Step 7 Insert upper portion of barrier
in floor box adjacent to outer (communication) conduit.
CAUTION: A portion of a letter may be visible in a partial
section. Ignore letters in incomplete sections. Note the example shown.
Saw Cut
“G” Section
EXAMPLE: The box is actually
cut in “G” section; however, “F” is the highest uncut sec­tion. Cut barrier to length based on “F” section directions.
EXAMPLE: “F” cut in box
requires divider to be cut on “A” score line.
BARRIER HEIGHT CROSS
REFERENCE CHART
BOX LETTER CUT DIVIDER
(section between AT THIS LETTER
Graduations)
M (not cut) H
LG
KF
JE
ID
HC
GB
FA
E
D
C
B
A
Do not use in concrete pours less than 4" [102mm].
Example shown
Discard lower portion
Actual distance between top of box (after removing excess top) and top of divider is 2-3/8" [60 mm]. If uncertain where to cut divider for regions between letters (through horizontal bar), Cut divider to measure a minimum of 2-3/8" below floor level. Can be slightly less if thick floor covering is used.
Page 3
3
Orient cover assembly so this side overlaps floor box barrier
Circuit “A”
Alignment Key
Channel
Communications raceway
(outer)
Step 8 Power Activation
Cat. No. 881RC4 This activation is pre-wired. Connect receptacle leads to circuit conductors with wire nuts or other approved methods.
Wire according to required configuration. See schematic below. If circuit is connected to an isolated ground, apply IG icon on receptacle slide as shown.
Step 9 Insert cover assembly into floor box
opening. No glue required.
Orient alignment keys to adapter with channels in floor box and push downward. Cover assembly is secured in place with ratchet fingers.
Step 10 Pull communication cable through
opening in bottom of activation then through cover as shown.
Power raceway (center)
Circuit “B”
NOTE: The orange triangle shall only be placed on devices that
are wired for isolated ground. See NEC 250-146(d).
CAUTION: Receptacle mounting means not grounded. Grounding
wire connection required. For isolated ground wiring, connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d).
CAUTION: Opening on side of adapter must be positioned directly
over the divided side of the floor box. This will allow the divider and adapter to overlap, maintaining passage of communication wiring and separation of services.
CONVENTIONAL WIRING SCHEMATIC ISOLATED GROUND WIRING SCHEMATIC ISOLATED GROUND WIRING SCHEMATIC
CIRCUIT A CIRCUIT B
BLACK or HOT BLACK BLACK or HOT BLACK BLACK or HOT RED
From branch circuit from receptacle From branch circuit from activation receptacle From branch circuit from activation receptacle
WHITE or NEUTRAL WHITE WHITE or NEUTRAL WHITE WHITE or NEUTRAL WHITE w/ BLUE STRIPE
From branch circuit from receptacle From branch circuit from activation receptacle From branch circuit from activation receptacle
GREEN or GROUND GREEN ISOLATED GROUND GREEN ISOLATED GROUND GREEN w/YELLOW STRIPE
From branch circuit from receptacle From branch circuit from activation receptacle From branch circuit from activation receptacle
System Ground
GREEN GREEN or GROUND GREEN or GROUND
equipment ground From branch circuit GREEN (jumper wire) From branch circuit GREEN (jumper wire) from receptacle System Ground equipment ground from activation System Ground equipment ground from activation
Electrical Connections
WARNING: Ground wire from activation body must be connected to SYSTEM GROUND.
Page 4
4
Step 11 Remove slide cover to access
communication raceway.
Ortronics TracJack Installation
(TracJack Modules not included, sold separately.)
Step 12 COMMUNICATION CIRCUIT CONNECTIONS
Wire communication devices per instructions provided with product. Mount in poke thru per illustrations shown below. Communication inserts may be mounted either flush or recessed. Some inserts, such as fiber optic, must be mounted recessed in order for slides to close properly.
NOTE: GASKET AND GASKET SUPPORT
MUST BE REMOVED BEFORE WIRING DATA CONNECTIONS
NOTE: To maintain UL Fire Classification, all communication modules or blank inserts (factory or customer supplied) must be UL Listed Communication
Circuit Accessories, and must fit securely in the supplied communication bracket or housing with no visible openings between the modules and
bracket/ housing. Supplied foam plugs must be used when passing cables through the communication openings.
CAUTION: De-energize circuit if activated.
Gasket
Gasket
Support
Ortronics Series II Installation
(Series II Modular Inserts not included, sold separately.)
Combination
Both Recessed
Both Flush
Recessed/ Flush
Both Recessed Both Flush Recessed/ Flush
Page 5
5
Pass & Seymour Network Wiring
(2 Cat 5e inserts provided with catalog number 881RC4ATC.)
Both Recessed
Both Flush
Recessed/ Flush
NOTE: To accommodate both Keystone and Avaya jacks, four communication inserts are provided with every unit (two dual port Keystone inserts,
2A-U2KEY-BK, and two dual port Avaya inserts, 2A-U2ATT-BK). Two Activate Dual Category 5 (2A245-B5-BK) inserts are also included. Whichever option is not installed can be discarded.
Step 13 Insert blanking plugs or neoprene foam blocks in
unused communication ports.
Step 14 Place gasket support plate
on poke-thru inserting the four posts through holes on receptacle brackets.
Step 17 Installation complete.
Step 15 Align gasket over receptacles
and press bead into flange channel.
Step 16 Attach slide cover with
(2) #6-32 screws.
CAUTION: Empty communication ports must be closed off with foam
blocks or Trac Jack blanks to maintain Fire Classification.
Communication inserts may be mounted either flush or recessed. Some inserts, such as fiber optic, must be mounted recessed in order for slides to close properly. Instructions for mounting communication inserts are on the following page.
TracJack Blank
(supplied)
foam block
(supplied)
Ortronics TracJack
Bezel
Comm Jack
(sold separately)
Pass & Seymour
Keystone Bezel
TracJack
(sold separately)
Page 6
4
WIRE FILL CAPACITY CHART
LETTER CUT AVAILABLE VOLUME
(below DIVIDER of ENCLOSURE
complete at this VOLUME INDICATED when used with EXTERIOR HEIGHT
uncut LETTER
2
by FLOOR BOX
1
ACTIVATION & of BOX (In.)
graduation) DIVIDER
Cu. Inches [ML] Cu. Inches [ML] Max. Min.
M (not cut) H 76.5 1254.0 39.5 647.0 6 7/16 6 7/16
LG72.0 1180.0 35.9 588.0 6 7/16 6 1/16
KF67.5 1106.0 32.3 529.0 6 1/16 5 3/4
JE63.0 1032.0 28.7 470.0 5 3/4 5 3/8
ID58.5 959.0 25.1 411.0 5 3/8 5
HC54.0 885.0 21.5 352.0 5 4 11/16
GB49.5 811.0 17.9 293.0 4 11/16 4 5/16
FA45.0 737.0 13.4 220.0 4 5/16 3 15/16
E 3 15/16 3 5/8
D 3 5/8 3 1/4
C 3 1/4 3
B 32 9/16
A 2 9/16 2 3/16
Cat. No. 881 RATCHET PRO FLOOR BOX
when used with 881RC4ATC, 881RC4ARTTC COVERS
DO NOT USE IN CONCRETE POURS
LESS THAN 4 INCHES*
* Caution: Installation must comply with NEC & local code
conductor volume requirements. Available volume for a dual service installation at 4 inches (102 mm) is 13.4 cu. in. (220 ml). Minimum height of box should be based on necessary wire fill requirements.
1. To calculate box fill capacity, use the displacement of the largest uncut section remaining.
2. The distance between the box cover to the top of the divider is 2-3/8" [60mm]. If uncertain which score line to use to cut the divider, measure a minimum of 2-3/8" below floor level to the top of the divider. This measurement can be slightly less if a thick floor covering is used.
Floor Level
Divider
Box Cover
Available volume of enclosure when used with activation and divider. See Chart above.
2 3/8"
[60mm]
Page 7
5
Carpet/Tile Cut-Out Template
6 1/2"
[165mm]
7" [178mm] Template for 881CTC, 881RC4ATC, and 881RC4ARTTC
6 1/2" [165mm] Template for 897CTC and 897CFFTC
CAUTION: When printing copies of this template, please
be sure template is scaled correctly and is the correct size once it is printed.
Page 8
© Copyright 2003 The Wiremold Company All Rights Reserved
The Wiremold Company
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251 Canada: 850 Gartshore Street • Fergus, Ontario N1M 2W8 1-800-741-7957 • FAX 519-843-5980
1 003 615 1003
Loading...