Products Covered: AV3STC, 4FFATC, 4FFCTC CAUTION DO NOT operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the
surface finish of the product. Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
4" Furniture Feed Poke-Thru Device
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 004 301 – January 2005
Walker® electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Walker electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
24" [610mm] Min Center – Center
7"
[178mm]
CAUTION: Be certain to drill hole at least 4" [102mm] from any wall or
pillar to leave enough room for Poke-Thru cover assembly.
CAUTION: For tile installations up to a maximum of
3/4" [19.1mm] thick.
NOTE: For tile thickness greater than 3/4" [19.1mm]
consult factory.
IMPORTANT: Please read all instructions
before beginning.
CAUTION: Spacing is limited to 2 feet on center and no
more than one hole per each 65 sq. ft. [6 sq. m] of floor area in each span.
Step 2 Remove 7" dia. [178mm] section from carpet
or tile. Use template provided.
Step 1 Layout and locate position of hole(s).
Step 3 Core drill hole.
CAUTION: Poke-Thru cannot be rotated in
hole after inserted into floor.
4" [102mm] Diameter Core Drill 4 1/16" [103mm] Actual Diameter
Push Down
#6-32 x 3/8" PHMS
three (3) required
Step 4 Stem Assembly:
Catalog No. AV3STC Insert stem into hole.
Step 5 Cover Assembly:
Catalog No. 4FFCTC. Remove disposable plate and replace with carpet/tile flange. Install with three (3) #6-32 x 3/8" [9.5mm] PHMS.
Page 2
2
Push
Down
Step 6 Complete assembly: Catalog No. 4FFTATC
Step 7 With the assembly installed, remove the
screw plugs and install conduit fittings as necessary. Attach conduit to adapter.
CAUTION: Poke-Thru cannot be rotated in
hole after inserted into floor.
Step 8 Pull cables and complete installation.
1 1/4" Trade Size Flexible
EMT. Not required
For Communication
Conduit Fitting.
3/4" Trade Size Flexible EMT. Must Be Attached
To Power Conduit Fitting.
Page 3
The 4FFTC Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards to the following conditions:
The AV3STC poke-thru stem with the 4FFCTC service head fitting, the 4FFATC factory assembled poke-thru device are for use with 1, 1-1/2, and 2 hr rated unprotected reinforced concrete floors and 1, 1-1/2 or 2 hr rated floors employing unprotected steel floor units and concrete topping (D900-Series Designs), or concrete floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the poke-thru fittings).
The assembled poke-thru stem and service fitting will not reduce the ratings of the floor assembly when the thickness and type of concrete(required for the specific rating) are within the specified limits and the fittings are installed as specified:
1. – Spacing – Minimum of 2' [610mm] OC and not more than one unit per 65 sq ft [6 sq. m] of floor area in each span.
2. – Concrete – Minimum thickness of structural concrete topping of 2 1/4 in. [57mm] over metal deck or a minimum
3 in. thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.
3. – Installation – Mounted in a 4 in. diameter core-drilled hole in concrete per installation instructions accompanying the fittings or abandonment fittings. For use with power circuits, date and/or telephone cables as tabulated below:
The “TC” suffix letters indicate that device may be installed on tile or carpet covered concrete floors. The “LJB” suffix letters
indicate units supplied without a junction box. (A) Maximum number of No. 12 AWG Type THHN conductors in power compartment of Poke-Thru fitting. (B) Maximum number of 22 AWG conductors in low-voltage compartment of Poke-Thru fitting (4 pair cables have
8 conductors). When conductors larger than No. 22 AWG are used, the aggregate cross-sectional area of the copper conductors shall not exceed the aggregate cross-sectional area of the 22 AWG conductors permitted in the low-voltage compartment.
FLOOR COVERINGS: The poke-thru device is fire rated for carpet or wood covered floors, tile floor coverings up to 3/4" [19.1 mm] maximum thickness, and linoleum floor coverings up to a maximum 1/8" [3.2 mm] thickness. For other floor coverings not listed above, consult factory.
Size Solid
#24 .00032 sq. in. [.20645mm2] #22 .00050 sq. in. [.32258mm2] #14 .00323 sq. in. [2.08386mm2] #12 .00512 sq. in. [3.30321mm2] #10 .00815 sq. in. [5.25805mm2] # 8 .01296 sq. in. [8.36127mm2]
COPPER CROSS SECTIONAL AREA
OF COMMONLY USED CONDUCTORS
NOTE: Use above values for solid or stranded conductors.
3
4FFATC Series 16 (.08192 sq in.) [52.861mm2] 144
(.072 sq. in.) [46.452mm2]
AV3STC Series 4FFCTC Series 16 (.08192 sq in.) [52.861mm
2
] 144
(.072 sq. in.) [46.452mm
2
]
POKE-THRU SERVICE POWER COMMUNICATION
FITTING TYPE FITTING TYPE CONDUCTORS (A) CONDUCTORS (B)
Page 4
The Wiremold Company
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251 Canada: 850 Gartshore Street • Fergus, Ontario N1M 2W8 1-800-741-7957 • FAX 519-843-5980
1 004 301 0105
© Copyright 2005 The Wiremold Company All Rights Reserved
Carpet Cutout
7" [178mm]
Core Hole
4 1/16" [103mm]
CAUTION: When printing copies of
this template please be sure template is scaled correctly and is the correct size once it is printed.
Carpet Cutout Template