Cable Cable Wire/Size O.D. 30TP- 2V Series 30TC- 2V Series*
Type Description (inches) [mm] 40% FILL 40% FILL
THHN / THWN 10 Awg 0.16 4.17 8 66
12 Awg 0.13 3.30 12 106
Cable Cable Wire/Size O.D. 30TP- 2V Series 30TC- 2V Series*
Type Description (inches) [mm] 20% FILL 40% FILL 20% FILL 40% FILL
Unshielded Cat. 5 UTP 0.22 5.59 14 28 18 37 Twisted Pair Cat. 3 UTP 0.19 4.83 19 38 25 50
Telephone 3 Pair 0.15 3.81 30 61 40 79
Coaxial RG59/U 0.24 6.15 12 23 15 31
RG62/U 0.24 6.15 12 23 15 31
RG6/U 0.27 6.86 9 19 12 25 TwinAxial 100 Ohm 0.33 8.38 6 13 8 16 Shielded Type 1 STP 0.39 9.91 4 9 6 12 Twisted Pair Type 2 STP 0.47 11.81 3 6 4 8
Fiber ZipCord 0.11 2.79 56 113 74 14 Fiber Optic Round Fiber 2 Strand 0.18 4.57 21 42 28 55
Round Fiber 4 Strand 0.19 4.83 19 38 25 50
Round Fiber 6 Strand 0.21 5.33 15 31 20 41
Wiremold Electrical Systems conform to and should be properly grounded in compliance with requirements of the current National Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard if improperly installed or used. Wiremold elec­trical products are UL listed, made for interior use in dry locations only and should be installed in conformance with current local and/or the National Electrical Code.
30TC-2V / 30TP-2V Series Tele-Power
®
Poles
INSTALLATION INSTRUCTIONS
The Wiremold Company
60 Woodlawn Street West Hartford, CT 06110 Tel. 1-800-621-0049 Fax 860-232-2062
41573R1 998© 1998 The Wiremold Company
• Grounding: Use ground location when provided or install a suitable ground lug, ring terminal or locknut and ground bushing.
• Mise à la terre: Utiliser l’emplacement de terre prévu ou poser le matériel qui convient: patte de mise à la terre, cosse circulaire à oeil ou écrou de blocage et manchon de terre.
• Conexión a tierra: Use un localizador de tierra cuando se proporcione o instale una orejeta de tierra, anillo terminal o contratuerca y cojinetes de tierra apropiados.
30TP-C
30TP-L
30TC-CVR
30TP-J
(1.59" [40.39mm] dia.)
30TP-A
(1.40" [35.56mm] dia.)
30TP-B
2 3/4"
[69.85mm]
1 17/32"
[38.89mm]
2 3/4"
[69.85mm]
1 17/32"
[38.89mm]
30TP-2V
30TP-2V 30TC-2V*
30TC-2V*
RACEWAY WIRE AND CABLE FILL CAPACITIES FOR TELE-POWER POLES - POWER
RACEWAY WIRE AND CABLE FILL CAPACITIES FOR TELE-POWER POLES - COMMUNICATIONS
* 30TC-2V Series not intended for combining power and communications.
COMMUNICATIONS
POWER
OR
COMMUNICATIONS
P O
W
E R
Page 2
1
2
3a
3b
4 5
6a 6b
7a 7b
8a
8b
9a
9b
10
AC-MFB-022
Loading...