Wiremold 2600-10, 1542D, 2642D, 2100B, 2186A Installation Instructions

...
Page 1
UNSHIELDED SHIELDED
TWISTED PAIR TELEPHONE TWISTED
TYPE 24 AWG, 4-PAIR 24 AWG, NO. OF PAIRS COAXIAL
TWINAXIAL
PAIR FIBER OPTIC
TWO STRAND (DUPLEX)
CAT. 5 CAT. 3 2 3 4 25
RG58/U RG59/U RG62/U RG6/U
MULTIMODE, 62.5/125µm O.D. inches 0.220 0.190 0.140 0.150 0.190 0.410 0.195 0.242 0.242 0.270 0.330 0.390 0.465 0.245 0.190 O.D. [mm] [5.6] [4.8] [3.6] [3.8] [4.8] [10.4] [5.0] [6.1] [6.1] [6.9] [8.4] [9.9] [11.8] [6.2] [4.8] 40% fill 2 3 6 5 3 0 3 2 2 1 1 0 0 2 3
1500 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
1500, 2600, 2100 Two-Piece Metal Raceway
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 41404R3 – Updated September 2003
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local and/or the National Electrical Code.
TYPE AWG,
THHN/THWN 8 10 12 14
O.D. inches 0.216 0.164 0.130 0.111 O.D. [mm] 5.5 4.2 3.3 2.8 40% fill 2 4 6 9
1500 RACEWAY WIRE FILL CAPACITIES FOR POWER
UNSHIELDED SHIELDED
TWISTED PAIR TELEPHONE TWISTED
TYPE 24 AWG, 4-PAIR 24 AWG, NO. OF PAIRS COAXIAL
TWINAXIAL
PAIR FIBER OPTIC
TWO STRAND (DUPLEX)
CAT. 5 CAT. 3 2 3 4 25
RG58/U RG59/U RG62/U RG6/U
MULTIMODE, 62.5/125µm O.D. inches 0.220 0.190 0.140 0.150 0.190 0.410 0.195 0.242 0.242 0.270 0.330 0.390 0.465 0.245 0.190 O.D. [mm] [5.6] [4.8] [3.6] [3.8] [4.8] [10.4] [5.0] [6.1] [6.1] [6.9] [8.4] [9.9] [11.8] [6.2] [4.8] 40% fill 7 10 18 16 10 2 9 6 6 5 3 2 1 6 10
2600 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
TYPE AWG,
THHN/THWN 8 10 12 14
O.D. inches 0.216 0.164 0.130 0.111 O.D. [mm] 5.5 4.2 3.3 2.8 40% fill 8 13 21 29
2600 RACEWAY WIRE FILL CAPACITIES FOR POWER
UNSHIELDED SHIELDED
TWISTED PAIR TELEPHONE TWISTED
TYPE 24 AWG, 4-PAIR 24 AWG, NO. OF PAIRS COAXIAL
TWINAXIAL
PAIR FIBER OPTIC
TWO STRAND (DUPLEX)
CAT. 5 CAT. 3 2 3 4 25
RG58/U RG59/U RG62/U RG6/U
MULTIMODE, 62.5/125µm O.D. inches 0.220 0.190 0.140 0.150 0.190 0.410 0.195 0.242 0.242 0.270 0.330 0.390 0.465 0.245 0.190 O.D. [mm] [5.6] [4.8] [3.6] [3.8] [4.8] [10.4] [5.0] [6.1] [6.1] [6.9] [8.4] [9.9] [11.8] [6.2] [4.8] 40% fill 8 11 21 19 11 2 11 7 7 5 3 2 1 7 11
2100 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
TYPE AWG, WITHOUT DEVICES
WITH DEVICES (2127G RECEPTACLE)
THHN/THWN 8 10 12 14 8 10 12 14
O.D. inches 0.216 0.164 0.130 0.111 0.216 0.164 0.130 0.111 O.D. [mm] 5.5 4.2 3.3 2.8 5.5 4.2 3.3 2.8 40% fill 2 4 6 9 0 3 5 7
2100 RACEWAY WIRE FILL CAPACITIES FOR POWER
Page 2
2100B
2100C
1500R
2186A
1500-10 2600-10 1542D 2642D
8 3/16"
[208mm]
• Use No. 8 (5/16", [7.9mm] head size) flat head fastener or equivalent to mount base to surface.
• Utiliser une attache à tête plate de calibre 8 (tête de 7.9mm, 5/16" po.) ou une fixation équivalente pour assujettir le tube guide-fils et les raccords à la surface de montage.
• Use un sujetador de cabeza plana No. 8 (tamaño de cabeza: 7.9mm, 5/16" de pulgada) o su equivalente para unir la canalita y los accesorios a la superficie de montaje.
•Grounding: Use ground location when provided or install a suitable ground lug, ring terminal or locknut and ground bushing.
• Mise à la terre: Utiliser l’emplacement de terre prévu ou poser le matériel qui convient: patte de mise à la terre, cosse circulaire à oeil ou écrou de blocage et manchon de terre.
• Conexión a tierra: Use un localizador de tierra cuando se proporcione o instale una orejeta de tierra, anillo terminal o contratuerca y cojinetes de tierra apropiados.
The Wiremold Company
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6251 Canada: 850 Gartshore Street • Fergus, Ontario N1M 2W8 1-800-741-7957 • FAX 519-843-5980
41404R3 – Updated September 2003
© Copyright 2003 The Wiremold Company All Rights Reserved