Winpower DE20I4, DE65F4, DE45F4, DE30I4, DE90F4 Installation And Operation Manual

ELECTRIC START
DIESEL GENERATORS
INSTALLATION AND OPERATIONS MANUAL with STAMFORD GENERATORS
MODELS: DE20I4 DE30I4 DE45F4 DE65F4 DE90F4
MANUAL KEY START AND DSE3110 ELECTRIC START
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be fol­lowed during installation and maintenance of the generator and batteries.
Read and understand all instructions in the manual before starting and operating the generator set.
USING THIS MANUAL
Congratulations on your choice of a WINPOWER generator set.
You have selected a high-quality, precision-engineered generator
set designed and tested to give you years of satisfactory standby service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem please follow the “Things To Check” near the end of this manual. The warranty listed in this manual describes what you can expect from WINPOWER should you need service assistance in the future.
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINPOWER generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.
MODEL________________________________
SERIAL NUMBER________________________
‘M” Spec. ______________________________
PURCHASE DATE_______________________
DEALER_______________________________
TABLE OF CONTENTS
INTRODUCTION i GUIDE TO PRODUCT SAFETY 1 BASIC INFORMATION 2
Specication Table 2
Description 3 RECEIVING THE GENERATOR 3 Unpacking the unit 3 ENGINE GENERATOR INSTALLATION Installation 4 Engine Generator Set Mounting 5 Fuel Installation 5 Lubrication 6 Coolant 6 Battery Installation 6 Control Panel Wiring Diagram 8 AC Electrical Connection 9 Key Start Panel Layout 10 Manual Key Strt Up 10 DSE3110 Elcectronic Control 11 DSE3110 Start UP 13 DSE3110 Fault Codes 15
TROUBLESHOOTING INFORMATION 16 DC SCHEMATIC - WIRING DIAGRAM MANUAL KEY START
DE20I4 & DE30I4 17 DE45I4 & DE65I4 18
DC SCHEMATIC - WIRING DIAGRAM DSE3110
DE20I4 & DE30I4 DSE 702 19 DE45I4 & DE65I4 DSE 702 20
AC WIRING - THREE PHASE
277/480 Volt 21 120/208 Volt 21 120/240 Volt 22
AC WIRING - SINGLE PHASE
120/240 Volt 22
GENERATOR TESTING RESISTANCES & ENGINE REPLACEMNT PARTS. 23 REMOTE START WIRING 25 12 MONTH WARRANTY 26
PROPER USE AND INSTALLATION
You must be sure your new engine generator set is:
* Properly serviced before starting * Operated in a well ventilated area * Properly exhausted and gases safely dispersed
* Wired by a qualied electrician
* Operated only for its designed purposes * Used only by operators who understand its operation * Properly maintained
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
Read and understand all instructions in the manual before starting and operating the generator set.
This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation,
or re. Please read all safety instructions carefully before
installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
************************************************************
DANGER:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations. ***********************************************************
************************************************************
WARNING:
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ***********************************************************
***********************************************************
CAUTION:
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. ************************************************************
NOTE:
CAUTION is also used on the unit labels and in this manual to indicate a situation that could result in serious damage or destruction of the equipment and possible personal injury.
1. ELECTRIC SHOCK - The output voltage present in this equipment can cause a fatal electric shock. This equipment must be operated by a responsible person.
a. Do not allow anyone to operate the generator without proper instruction. b. Guard against electric shock. c. Avoid contact with live terminals or receptacles. d. Use extreme care if operating this unit in rain or snow. e. Use only three-prong grounded receptacles and extension cords. f. Be sure the unit is properly grounded to an external ground rod driven into the earth.
2. FIRE HAZARD - Diesel fuel presents a hazard of possible
explosion and/or re.
a. Do not smoke or use open ame near the generator
set.
b. Keep a re extinguisher nearby and know its proper use.
Fire extinguishers rated ABC by NFPA are appropriate.
3. DEADLY EXHAUST GAS - Exhaust fumes from any diesel engine contain carbon monoxide, an invisible, odorless and deadly gas that must be mixed with fresh air.
a. Operate only in well ventilated areas. b. Never operate indoors. c. Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms (i.e. through
windows, walls or oors).
4. NOISE HAZARD - Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a. Use hearing protection equipment when working around this equipment for long periods of time. b. Keep your neighbors in mind when permanently install­ ing this equipment.
5. CLEANLINESS - Keep the generator and surrounding area clean.
a. Remove all grease, ice, snow or materials that create slippery conditions around the unit. b. Remove any rags or other material that could create
potential re hazards.
c. Carefully wipe up any fuel or oil spills before starting the unit.
d. Never allow leaves or other ammable material to build
up around the engine exhaust area.
6. SERVICING EQUIPMENT - All service, including the installation or replacement of service parts, should be
performedonlybyaqualiedtechnician.
a. Use only factory approved repair parts. b. Do not work on this equipment when fatigued. c. Never remove the protective guards, cover, or recep­ tacle panels while the engine is running. d. Use extreme caution when working on electrical compo­ nents. High output voltages from this equipment can cause serious injury or death.
e. Always avoid hot mufers, exhaust manifolds, and
engine parts. They all can cause severe burns instantly. f. Installing a generator set is not a “do-it-yourself” project.
Consult a qualied, licensed electrician or contractor.
The installation must comply with all national, state, and local codes. g. Always make sure unit is disabled before placing your hands anywhere near the fan, belts, alternator or water hoses.
4094-00
1
60708-162
TESTING POLICY:
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked.
Rated output of the generators is based on engineering tests of typical units, and is subject to, and limited by, the
temperature,altitude,fuel,andotherconditionsspeciedby
the manufacturer of the applicable engines.
NOTE:
These units come factory set for either key start or manual start. With DSE 3110 controller used in the manual start option it is possible to wire the control for remote start. See page 25 of this manual for wiring instructions. The key start version does not have this option.
SPECIFICATIONS
MODEL DE2014-3 DE20I4-4 DE20I4-17 DE20I4-18
Generator
Wattage 20000 20000 20000 20000
Volts 120/240 120/208 120/240 277/480
Phase single three three three
PF 1.0 .80 .80 .80
AMPs 83.0 69.5 60.2 30.1
Hertz 60 60 60 60
Engine
Model Isuzu 4LE1
Starting System 12 Volt Manual Start
Mufer Standard
Stop System Key/Emergency
Fuel Consumption (full Load) 1.8 Gal/hour
MODEL DE30I4-3 DE30I4-4 DE30I4-17 DE30I4-18
Generator
Wattage 30000 30000 30000 30000
Volts 120/240 120/208 120/240 277/480
Phase single three three three
PF 1.0 .80 .80 .80
AMPs 125 104 90 45
Hertz 60 60 60 60
Engine
Model Isuzu 4LE TurboCharged
Starting System 12 Volt Manual Start
Mufer Standard
Stop System Key/Emergency
Fuel Consumption (full Load) 2.6 Gal/hour
MODEL DE45F4-3 DE45F4-4 DE45F4-17 DE45F4-18
Generator
Wattage 40000 45000 45000 45000
Volts 120/240 120/208 120/240 277/480
Phase single three three three
PF 1.0 .80 .80 .80
AMPs 166 156 135 68
Hertz 60 60 60 60
Engine
Model Iveco N45SM1
Starting System 12 Volt Manual Start
Mufer Standard
Stop System Key/Emergency
Fuel Consumption (full Load) 4.09 Gal/hour
MODEL DE65F4-3 DE65F4-4 DE65F4-17 DE65F4-18
Generator
Wattage 55000 62000 62000 62000
Volts 120/240 120/208 120/240 277/480
Phase single three three three
PF 1.0 .80 .80 .80
AMPs 229 215 186 93
Hertz 60 60 60 60
Engine
Model Iveco N45SM2 TurboCharged
Starting System 12 Volt Manual Start
Mufer Standard
Stop System Key/Emergency
Fuel Consumption (full Load) 4.57 Gal/hour
MODEL DE90F4-3 DE60F4-4 DE90F4-17 DE90F4-18
Generator
Wattage 86000 90000 90000 90000
Volts 120/240 120/208 120/240 277/480
Phase single three three three
PF 1.0 .80 .80 .80
AMPs 358 312 270 135
Hertz 60 60 60 60
Engine
Model Iveco N45TM2 TurboCharged
Starting System 12 Volt Manual Start
Mufer Standard
Stop System Key/Emergency
Fuel Consumption (full Load) 6.94 Gal/hour
60708-162
2
4094-00
INTRODUCTION AND DESCRIPTION
PRODUCT DESCRIPTION:
This engine-generator set is designed for manual key start operation. The engine-generator set is fully tested at the factory prior to shipment to insure proper operation of each individual component as well as the total system’s performance and reliability.
The engine generator set consists of a multi-cylinder, liquid cooled engine nominally operating at 1800 rpm. The generator frequency regulation is maintained by the engine governor to within +/- 1.5
hertz (cps), from no load to rated load for standard mechanical
governors. The generator is a single bearing, direct drive, rotating
eld brushless design. The generator is connected to the engine ywheel via exible drive disks. The Generator Set is skid
mounted with isolation mounts between the engine and base on all units.
NOTICE:
These engine generator sets have only basic engine protections. The Manual Key start panel only provides low oil pressure and high coolant temperature protection, with no voltage or frequency displays. The DSE 3110 electronic start panel displays a basic voltage and frequency reading derived from a line to neutral feed from the generator to the DSE 3110 control. Based on this information it also provides basic over/under speed and voltage protection. Low oil pressure and high water temperature reading/ shutdowns are provided by senders mounted on the engine. No other control options are available on the DE Series Generators, if you application requires additional safety devices or signals consider upgrading to the DR Series Generators by WINPOWER.
A customer supplied 12 Volt battery is required to complete the installation. Battery requirements are listed later under the battery installation section.
These engine generator sets come standard with a manual key start system. This key start system utilities a safety latching relay that shut the unit down if the oil pressure gets low or water temperature gets too high. The safety latching relay must be depressed during cranking. Available as an option is a digital DSE 3110 controller that is also programmed for electric start. The DSE 3110 will electronically display your engine speed, generator voltage, generator frequency, engine running time and your battery level voltage. In addition it monitors your oil pressure, water temperature, over/under speed and overcrank to insure safe trouble free operation. Both systems are discussed later in detail.
GENERATOR SET:
Every WINPOWER Generator Set has its own unique identity
data plate. This data plate identies the complete unit model
number, the system serial number and has links to the individual components that form the generator set in our factory records. Several of the major components also have their own individual identity plates providing additional information to document build data for warranty and replacement parts.
Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference
and for identication whenever requesting eld or factory technical assistance. Primary elds needed for assistance are complete
model number, serial number and especially the M-Spec number.
The M-Spec number (if provided) is recorded in the ‘TYPE NO.’
block on the lower right of the plate.
ENGINE:
This manual covers specic operation of the combined engine
generator set. Refer to engine operating and maintenance
instructions for specic instruction on the care and maintenance
of the engine. Oil and fuel requirements along with maintenance schedules and engine warranty information are provided by the individual engine manufacturers.
** CAUTION **
EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specied in the engine manual.
The engine manufacturer has established an excellent worldwide engine service organization; engine service is available from a nearby authorized dealer or distributor. Go to the WINCO web site for a list of engine dealers. (http://www.wincogen.com/
Engine_Support/ )
The rated power of each engine-generator is limited by the
temperature, altitude and all other ambient conditions specied
by the engine manufacturer. Engine power will decrease 3-1/2% for each 1000 ft. above sea level, and will decrease an additional 1% for each 10 degrees Fahrenheit above 60 degrees Fahrenheit. Units should not be operated in ambient temperature greater than
125 degrees Fahrenheit.
GENERATOR:
WINPOWER Generator Sets use brushless, AVR (Auto-
Voltage Regulator) controlled broad-range generator ends. The
generator converts rotational mechanical energy into electrical energy. These WINPOWER units are equipped with generators
manufactured by Cummins Stamford. Each generator ‘end’ has its
own data tag. A unique serial number is stamped on the data plate
and the data label is afxed to the main frame of the generator on
the left side.
RECEIVING THE GENERATOR
The generator set will generally be shipped by a commercial
‘common freight carrier’. Routing is determined by the bulk, size,
and a means available to unload the generator at the receiving end. WINPOWER recommends units that are shipped by common carrier be delivered to a commercial dock to allow the
Generator Set to be unloaded in a safe, efcient manner and to
minimize handling damage to the unit.
Locate the packing slip on the side of the crate or request it from the truck driver. When receiving the generator take special care in examining it for damage during shipment. Avoid signing for the equipment until a full visual assessment and inventory have been made. Verify that you have received the right equipment and the proper amount by matching up the equipment to the packing list.
4094-00
3
60708-162
UNPACKING INSTRUCTIONS:
When unpacking the generator set, be sure to inspect it carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make note
of the loss or damage on the freight bill, or afx his signature
under the consignee’s memo of the loss or damage. Contact the carrier for claim procedures.
When loss or damage is noted after delivery, segregate the damaged material, and contact the carrier for claim procedures.
“Concealed Damage” is understood to mean damage to the contents of a package which is not in evidence at the time of delivery by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in transit. The title to goods rests with the consignee when generators are shipped fob factory, and only the consignee can
legally le a claim.
***** CAUTION ****
equipment and may be placed on the pad with basic material handling equipment, i.e. a forklift.
CAUTION: - Do not attempt to lift the generator set by the means of the lifting eyes on the engine or generator end.
These lifting points are only for use during the manufacturing process and are designed for lifting of the individual Generator Set component.
*************** ***** WARNING **** ***************
NEVER - attempt to lift the fuel tank while lled with fuel.
Sloshing of the fuel can cause a shift in the balance of the fuel tank, making for a DANGEROUS, unbalanced lifting load. If the generator was shipped on the fuel tank, use the lifting points located on the fuel tank to move the entire Generator Set into place. DO NOT place fuel in the tank prior to lifting.
EQUIPMENT DAMAGE - These units are shipped with oil,
and a 50/50 mix of coolant. Be sure to check all uid
levels before operating. See engine manufacturer’s instruction manual for recommended oil requirements before initial starting.
UNPACKING:
(Not recommended until the unit is on-site)
1. Carefully remove the crate.
2. After inspecting the engine-generator for external physical damage, locate and check the following items packed with the unit.
a. Owner’s operators manual. b. Engine manufacturer’s instruction manual. c. Battery hold-down brackets & hardware. d. Unit components or accessory items shipped loose for on-site installation. e. Optional accessories.
3. Remove main frame hold down bolts.
4. Unit can now be lifted from shipping rails.
INSTALLATION
*************** ***** WARNING **** ***************
PERSONAL INJURY - Before proceeding with the installation, be sure the engine control is in the “stop” position. Before proceeding with the installation, be sure the Generator MLCB (Main Line Circuit Breaker) is in the ‘OFF’ position and the unit starting battery is disconnected.
GENERAL INFORMATION
This series of engine/generator sets are designed and built as open power units, meaning no weather protection has been provided. These unit must be installed inside of an enclosure that will provide proper protection from the elements.
Before beginning the installation process, recheck the voltage, phase and amperage rating of the Generator Set. Be certain it can handle the intended load and are compatible with the intended loads. Plans for installation should be prepared with proper attention to mechanical and electrical engineering detail to assure a satisfactory system installation. The installation must comply with all national, state, and local codes.
LIFTING THE GENERATOR SET
NOTICE - Personal Injury
To prevent injury to persons or equipment, observe the following guidelines when lifting the generator:
Due to the different designs, congurations, options, weights,
site conditions, and available material handling equipment,
specic lifting instructions are not provided for each individual
generator set model. General guidelines provided are applicable to the entire standby generator line. It is the responsibility of the installing party to follow the lifting equipment’s operators manual to prevent injury to personnel and damage to the generator. Smaller Generator Sets may not require use of overhead lifting
60708-162
The information in this manual is offered only as a guide to
nalizing your installation plans.
NOTICE
For full service switching of the entire load, the ATS must be ‘SE’ (Service Entrance) rated or must have a properly rated fusible
disconnect installed before the ATS to protect the contacts.
4
4094-00
ENGINE GENERATOR SET MOUNTING
The unit’s main frame must be bolted solidly to a solid base. The engine-generator is mounted on channels which are attached with special shock mounts to the main frame. This allows the engine-generator free movement without affecting the base or surrounding equipment
*************** ***** WARNING **** ***************
EQUIPMENT DAMAGE - Never mount these engine generator sets to a wooden base/structure. Over time the wood will deteriorate and the unit mountings will come loose. These units must be mounted to a steel or concrete base.
The unit should be mounted to allow for ample working room
around it. A general rule to follow is ve (5) feet of clearance from ammable surfaces. These distances may be reduced for nonammable surfaces but sufcient access must be provided for
servicing the equipment.
VENTILATION REQUIREMENTS
*************** ***** WARNING **** ***************
ENGINE/GENERATOR DAMAGE - It is the installer
responsibility to insure that there is sufcient cooling air
available to prevent the engine and generator from over heating. Damage caused by overheating is not covered by
warranty.
The information in this manual is offered to assist you in providing the proper fuel for your engine. However, this information is only provided to inform you of the engine’s requirements and assist in making you aware of the decisions you must make. In no case should the instructions or information provided be interpreted to
conict with any local, state or national codes. If in doubt, always consult your local re marshal or fuel supplier.
INSTALLING THE FUEL LINE
Engine generator sets are properly adjusted before they leave the factory. Connecting a fuel supply with adequate supply volume is critical to reliable operation. Diesel units with optional base mounted fuel tanks are pre-plumbed to the mechanical fuel pump on the engine.
Open skid mounted Diesel units are often supplied with capped inlet and return lines. The use of a suitable customer supplied
exible fuel lines is essential between the engine and fuel supply
to provide a vibration break between your fuel supply and the engine.
*************** ***** WARNING **** ***************
FIRE DANGER - Connecting rigid fuel line (i.e. steel or copper
line) directly to the inlet fuel lter or fuel pump may cause the fuel line to crack during operation creating a serious re
hazard.
DE45 - DE90 FUEL LINE CONNECTIONS
Providing proper air movement during your installation planning
is absolutely essential, You will need to provide a fresh air inlet as well as a hot air outlet (to the outside of protection housing)
for proper engine performance. These engine generator set are equipped with unit mount radiators and the engine is equipped with a pusher type fan. The hot air from the face of the radiator must be ducted out of the enclosure to insure proper cooling. Failing to do so will allow the hot air to recirculate around the radiator causing the engine to overheat resulting in an engine shutdown. If louvers are used in front of the hot air duct to protect the unit from outside weather, these louvers should be 1 1/2 times as large as the area of the radiator face to prevent back pressure.
In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge. These fresh air inlets should also be 1 1/2 to 2 times large than the radiator face. The extra air inlet area is required to minimize restriction and to provide combustion air for the engine. Do not block fresh air
intakes with other equipment as this will result in insufcient air ow to the engine for cooling. Installing them opposite the hot air discharge will allow a sweeping ow of cooling air across the
engine preventing hot spots.
FUEL INSTALLATION
The fuel supply should be as close to the engine as possible. This will reduce the installation cost of fuel runs and minimize line losses. The diesel fuel supply should be no more than 3 feet below the fuel inlet on the pump. If your fuel supply is lower than three feet you may have to install an additional lift pump to bring the fuel up to the mechanical fuel pump on the engine.
FUEL INLET CONNECTION
FUEL RETURN LINE CONNECTION
4094-00
5
60708-162
DE30 FUEL CONNECTIONS
-35 -30 -25 -20
SAE 10W
SAE 20W
SAE 30
SAE 40
SAE 10W -30
SAE 10W -40
SAE 10W -60
SAE 15W -40
mineral base
SAE 15W -40
semisynthetic base
SAE 20W -60
semisynthetic base
SAE 5W -30
synthetic base
SAE 0W -30
synthetic base
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 °C
°F
-31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Isuzu oil viscosity table
Use API CC or CD
Fiat oil viscosity table
Use API CF or CH4
FUEL INLET CONNECTION
FUEL RETURN LINE CONNECTION
DE20 FUEL CONNECTIONS
FUEL INLET CONNECTION
FUEL RETURN LINE CONNECTION
LUBRICATION
Before starting the engine, check the oil level in the crankcase.
If it is low, rell to the full mark with the proper weight/grade of
oil as recommended by the engine manufacturer’s maintenance instructions. The necessity of using the correct oil, and keeping the crankcase full cannot be over emphasized. Failure to use
the proper oil and keep the crankcase properly lled will cause
excessive engine wear and shorten its useful life.
60708-162
COOLANT
Before starting the engine, check the coolant level in the radiator.
If it is low, rell as specied in the engine manufacturer’s maintenance instructions. The radiator should be lled to about 1 inch below the ller neck. For additional information on engine
coolant requirements see engine manufacturer’s maintenance instructions.
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check to be sure the engine control is in the “stop” position. This should be your last step before initial start-up.
A customer supplied twelve-volt battery is required to complete the installation. Installation of the highest CCA rated battery, within the correct BCI group, will increase cold weather starting performance. BATTERY REQUIREMENTS
MINIMUM Model Voltage BCI Group CCA Rating DR20I4 12 24 650 DE30I4 12 24 650 DE45F4 12 24 650 DE65F4 12 24 650 DE90F4 12 31 900
6
4094-00
************* ***** WARNING ***** *************
EQUIPMENT DAMAGE- All of these units are 12 Volt and they
are all negative ground. Permanent damage will occur if they are connected to a 24 volt system or a positive ground system. If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system.
Installation and servicing of batteries must only be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When installing or replacing batteries, use the proper group/size starting battery. The battery should be a Maintenance Free lead acid design. Deep cycle batteries will not work for this application.
DANGER – Explosive Fire Risk
* Never smoke when near batteries
* Do not cause a ame or spark in the battery area
* Always discharge static electricity from your body before
touching batteries by rst touching a grounded metal surface
SERVICING BATTERIES
Batteries used on these units may, over time, lose water. This is especially true if you are using a trickle charger to maintain your
battery. When relling the battery with water use only distilled
water. Tap water will shorten the service life of the battery.
Never ll the battery above the ll line. Over lling above the upper level line may cause the electrolyte to overow, resulting in
corrosion to the engine or nearby parts. Immediately wash off any spilled electrolyte following the procedure above.
CAUTION – PERSONAL DANGER
CAUTION - NEVER dispose of a battery in a re. The battery is
capable of exploding.
CAUTION -DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic.
These engine generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.
CAUTION – A battery presents a risk of electrical shock and high short circuit current. The following precautions must be observed when working with batteries:
1. Remove watches, rings and other metal objects.
2. Use tools with insulated handles.
3. Check both the battery cable ends and the battery posts to be sure they are free of corrosion.
4. Always connect the battery positive cable rst and then
connect the battery negative cable. When removing the battery cables from the battery reverse the procedure,
disconnect the negative cable rst and then the positive
cable.
5. Be sure all connections are tight and coat the terminals and cable ends with dialectic grease.
NOTE: Always make sure that a new battery is fully charged before installing it on a generator set. Failure to do so can cause damage to the engine control module in the generator set.
All connections must be clean and tight. Check the electrolyte
(uid) in the battery periodically to be sure it is above the plates.
Never allow the battery to remain in a discharged condition.
WARNING – The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following precautions must always be taken:
* Always wear full eye protection and protective clothing * Where electrolyte contacts the skin, wash off immediately with water.
* If electrolyte contacts the eyes, ush thoroughly and
Immediately with water and seek immediate medical attention * Spilled electrolyte is to be washed down with an acid neutral­ izing agent. A common practice is to use a solution of one
pound of bicarbonate of soda (baking soda) to one gallon of
water. The bicarbonate of soda solution is to be added until the evidence of reaction, foaming, has ceased. The resulting
liquid is to be ushed with water and the area dried.
4094-00