Main Power Switch ....................................................................................................................................... 15
Pre-installation Test ...................................................................................................................................... 17
Air Flow Illustration ....................................................................................................................................... 17
Planning the Installation .............................................................................................................................. 19
Mounting the Unit ......................................................................................................................................... 21
Installing the Condensate Drain Connection ............................................................................................. 22
Installing the Drain Line ................................................................................................................................ 22
Priming the Drain Trap ................................................................................................................................. 22
Wiring the Unit for Power ..................................................................................................... 23
Inspection and Start-up Checklists ........................................................................................ 38
Starting-up and Operating the Wine Guardian ...................................................................... 39
Turn on the Unit ............................................................................................................................................. 39
Testing the Fan .............................................................................................................................................. 39
Cycling the Unit .............................................................................................................................................. 40
Setting the Thermostat ................................................................................................................................. 40
Regulating the Wine Cellar Temperature .................................................................................................. 40
Changing the Air Flow Direction .................................................................................................................. 40
Cleaning the Filters ........................................................................................................................................ 42
Cleaning the Condensate Drain System ..................................................................................................... 42
Cleaning the Humidifier (optional).............................................................................................................. 42
Ambient Air – The surrounding area outside the cellar such as a room, basement, garage or outdoors.
CACLS – Cubic litres per second. A unit of measurement for the amount of air handled by the fan.
Condensate / Condensation – The water formed out of the air when it is cooled below a certain temperature
(called dew point). Often referred to as “sweating” on pipes and cold surfaces. This water collects at the bottom
of the evaporator or cooling coil and drains out of the unit through the drain line.
Condenser (Heat Rejection) Section / Coil – The Condenser Section uses the compressor, condenser coil and
fan to remove heat from the refrigerant to the ambient air outside the wine cellar. The word condenser refers to
the condensation of the refrigerant from gas to liquid phase.
CE– Certificate of European conformity
Exhaust Air – The air leaving the evaporator or condenser section of the Wine Guardian unit.
Evaporator (Cooling) Section / Coil – The Evaporator Section uses the cooling coil and the fan to remove
heat from the air inside the wine cellar to the refrigerant, cooling the air and condensing moisture out of the
air. The word evaporator refers to the evaporation of the refrigerant from liquid to gas phase in the coil. The
Evaporator Section is connected to or inside the wine cellar.
Flexible Duct – Round ducts with steel reinforced plastic liners, a layer of insulation and an outer plastic
layer used to convey the air from the unit to the cellar or ambient space.
Grille or Diffuser – Inlet or outlet plates to direct the airflow or protect the inside of the unit.
Heat Gain / Loss – The amount of cooling or heating expressed in watts transferred between the wine
cellar and the ambient space. The Wine Guardian must offset this load.
Inlet Air – The air entering the evaporator and condenser sections of the Wine Guardian unit.
NEC– National Electrical Code
Recovery – The amount of cooling the unit does to return the cellar to its set point temperature after some
new load is introduced, such as people or new cases of warm wine entering the cellar.
Return Air - The air leaving the cellar and returning to the inlet of the evaporator coil.
SP – Static pressure. Unit of measurement (mm of water or pascals of water column) of the pressure of the air
handled by the fan.
Set Point – The desired temperature or humidity set on the thermostat or humidistat.
Supply Air - The air entering the cellar from the discharge of the evaporator coil.
2
Receiving, Inspecting and Unpacking the
Wine Guardian Unit
Receiving and Inspecting the Unit
NOTE
Wine Guardian units are factory assembled and tested prior to shipment.
Wine Guardian units are shipped in individual cardboard boxes.
Lift at the designated handhold locations only or fully support from underneath. A
shipment may include one or more boxes containing accessories.
Before opening the container, inspect the packing crates or boxes for obvious signs of
damage or mishandling.
Write any discrepancy or visual damage on the bill of lading before signing.
Inspect all equipment for any sign of damage caused during transit.
Report all visual or concealed damage to the carrier and file a claim immediately.
Thoroughly inspect the contents for any visible damage or loose parts.
IMPORTANT
If this procedure is not followed, the shipping company may reject the claim
and the consignee may suffer the loss. Do not return the shipment to the
factory.
Review the Packing Slip to Verify:
Model number
Factory installed options
Unit accessories
If any items listed on the packing slip do not match your order information, contact the place of
purchase immediately.
Check the unit for:
An electrical power cord
A thermostat with communications cable plugged into side of unit
A drain line coming out of the unit
3
General Description
View the Overview Illustration on page 8 for details.
The Wine Guardian cooling unit is a professional grade American manufactured, self-contained
climate control unit designed specifically for the storage of wine at cellar temperatures. It is
designed for easy installation and operation. Wine Guardian uses digital electronic controls and
environmentally friendly R-134a refrigerant.
All Wine Guardian 50Hz units carry the CE mark. Each unit is furnished with a sealed, CEapproved power cord and plug.
The Wine Guardian unit is completely self-contained and includes an integral air or water cooled
condenser. The unit is functionally divided into two sections, the evaporator or cooling section and
the condenser or heat rejection section. Each section contains a coil to add or remove heat and a fan
to move the air through the coil and into or out of the cellar or adjacent space. The Wine Guardian
unit is designed to be used either as a free-blowing, through- the-wall unit, or as a remote mount
unit with external ductwork connections.
Air from the cellar first enters a filter to remove any airborne dust particles and then enters the
cooling coil. Air passes through the cooling coil and is cooled by the refrigerant inside the coil.
This causes any excess humidity in the air to condense and be captured in the drain pan and piped
outside the unit. Air then enters the fan where it is pressurized and discharged out of the unit.
Optional heating coils are located between the cooling coil and the fan. These coils heat the air to
prevent low temperatures in the cellar. The thermostat, located in the cellar, turns on the cooling
or heating as needed to maintain its set point. It does not allow the cooling and heating to be on at
the same time.
The compressor and condenser sections are activated whenever the unit is cooling. The condenser
fan draws air from the surrounding or ambient space either directly or through a duct. The air is
first drawn through a filter to remove any airborne dust particles to keep the coil clean. Then the
air flows through the condenser coil where it absorbs heat from the refrigerant in the coil. The air
is finally discharged out of the unit by the condenser fan.
The water-cooled Wine Guardian system requires cooling water to be piped to the unit for proper
operation. The cooling water absorbs the refrigerant heat through the unit’s water-cooled
condenser coil. Warm water is then directed out of the unit back to the cooling water system or
to a drain.
IMPORTANT
The air exhaust from the condenser fan is hot and will be 15 to 18 degrees C above
the entering temperature. This may cause overheating problems in the summer
months, especially with high humidity. Exhaust the hot air to the outside. In the
winter, this heated air can help to heat the surrounding space.
4
Standard Specifications
IMPORTANT
Design and specifications are subject to change without notice
The Wine Guardian Unit Contains
A thermal expansion valve to control the flow of refrigerant into the evaporator coil
A filter dryer to keep the refrigerant clean and free of contaminant
A sight glass to observe the level of refrigerant
An automatic low pressure switch on the discharge to protect the compressor form high
pressures
The unit uses only environmentally friendly refrigerant F-134a
A built-in condensate drain trap. No external trap is required.
The Wine Guardian meets or exceeds its rated capacities for total watts and cubic litres per second at
design cellar conditions and external static pressures. Both the evaporator and condenser fans are
capable of rated CFM against the external static pressure imposed by recommended ductwork. Both
fans are motorized impeller plug fans, statically and dynamically balanced, and use permanently
lubricated direct drive motors requiring no maintenance.
All exterior framing of the Wine Guardian is powder coated 1.6mm gauge aluminum to prevent rust
and corrosion. All coils are copper tubes with aluminum fins. The unit uses an external drain to
remove excess moisture and not reintroduce it into the cellar or ambient space. Removable, multiple
access doors are provided to facilitate cleaning and maintenance, duct connections, and access to
components and wiring.
Both the evaporator and the condenser coils have pre-filters on the inlet to prevent dust and dirt from
fouling the coils, thereby reducing capacity. Each unit has at least three discharge outlets on both the
evaporator and the condenser coils to facilitate custom installations.
Each unit is provided with a pre-wired and tested electronic digital thermostat for remote mounting in
the cellar. The thermostat has multiple control functions for the fans, cooling and heating. It has a
fully automatic mode to switch between heating and cooling.
Compressors are rotary, self-lubricating, permanently sealed, hermetic reciprocating type compressors, with internal overload protection and capacitor start with a minimum of one-year manufacturer’s
warranty and an optional five-year warranty. Compressors are mounted on rubber-in-shear isolators to
reduce noise and vibration.
Electric power is supplied by a single factory furnished cord and plug. All external controls are
digital and proprietary to Wine Guardian products. Only approved communication cable and Wine
Guardian controllers are suitable for proper system operation.
5
Accessories and Optional Equipment
Heating Coils
An optional heating coil is built-in and requires no additional power source. The electric heating
option is factory installed and includes primary and secondary over-temperature protection devices
per UL and NEC.
Water Cooled Option
A water cooled option is available that uses a tube-in-tube heat exchanger in place of the condenser
coil and fan. Waste heat from the refrigerant is transferred to the water. A control valve is used to
regulate the flow of water to maintain head pressure.
Duct Collars and Flexible Ducts
Ducting for the Wine Guardian is sold in kits by size for each unit. Each kit contains two adapter
collars, one 7.3 metre length of round flexible duct and two straps. The number of duct kits needed
depends on the layout. The size of the kit depends on the model Wine Guardian selected. Follow
installation instructions carefully. Poorly or incorrectly installed ducts can degrade the performance
of your unit dramatically.
Extended Compressor Warranty
The Wine Guardian uses only the best commercially available compressors on the market. However,
since the compressor is the single most expensive component in the unit, it is recommended that you
purchase the extended warranty option.
Low Ambient Option
A factory installed Low Ambient option is available which makes the Wine Guardian capable of
exposure to low ambient temperatures. This feature controls the condenser fan operation based on
head pressure and heats the oil reservoir. The Low Ambient Option (LAO) is recommended
whenever the condenser section is exposed to air temperatures below 50°C. This can occur if the
unit is placed in a garage or under an outdoor canopy or if the unit is located inside a heated space
but the condenser air is ducted in from the outside.
Condensate Pump
An optional Wine Guardian automatic condensate pump is available
outside. It requires a separate 220/240 volt electrical outlet.
to pump the water to a sink or
Humidifier and Humidistat
Another popular option for the Wine Guardian is a humidifier. It comes with a sheet metal adapter
box and a pre-wired humidistat. The humidifier is available for field installation and can be
retrofitted onto an existing unit. Each humidifier is furnished with an electronic digital humidistat
to control the humidity in the cellar. The humidifier mounts directly onto the Wine Guardian unit
and uses the common drain. The humidifier requires a HOT water supply and no additional
external power.
CAREFULLY FOLLOW THE INSTALLATIONS INSTRUCTIONS INCLUDED WITH THE HUMIDIFIER. REFER TO THE
INSTRUCTIONS CONTAINED IN THE BOX FOR THE HUMIDISTAT.
CAUTION
6
Overview of the Wine Guardian Unit
Refer to illustrations on page 8
Cabinet
for corrosion protection and an attractive, maintenance free appearance. Areas in contact with cold
temperatures are lined with insulation to prevent condensation.
–
The cabinet and access doors are constructed of aluminum with a powder coated finish
Condensing Section
–
Ambient air is circulated through the condenser section by a direct drive,
permanently lubricated, motorized impeller blower. This section also contains the compressor and
the electrical controls. If the water cooled option is purchased, a heat exchanger is used in place of
the condenser coil and blower.
Evaporator Section
–
Cellar air is circulated through the evaporator section by another blower the
same as above. The large evaporator coil face area eliminates condensate carry-over, reduces air
pressure drop and optimizes heat transfer. A drain pan is located directly below the coil to capture
condensate and is fabricated from aluminum to prevent rust and corrosion. The electric heating coil,
if ordered, is factory installed between the evaporator coil and the blower, and is complete with
contactor(s) and limit controls.
Electrical Controls
–
Most of the electrical components and controls are located in a separate area
accessible through the condenser section. Wires are numbered and color coded to match the wiring
diagrams.
Factory Tested
–
All Wine Guardian units are factory run-tested and checked for operational
performance.
Filters
– Nominal 25mm thick filters are provided on both the evaporator and condenser inlets to
protect the coils from dust and dirt. These filters are washable and reusable.
Humidity Option
–
The optional humidifier comes fully assembled and tested for field installation
onto the Wine Guardian without any additional electrical power wiring. It automatically adds
moisture into the cellar by the evaporation of water over a distribution pad. A cellar mounted digital
electronic humidistat automatically controls the amount of moisture added.
Internal Drain Trap
-
Water condensate from the evaporator coil fills the trap and forms a seal to
prevent air from being drawn back through the drain tube. This allows the drain pan to drain freely.
No external trap is required.
Refrigerant Circuit
– The factory charged circuit includes a thermal expansion valve with an
external equalizer, sight glass with moisture indicator, a filter dryer, an automatic low pressure
switch, and a manual reset high pressure switch. For the low ambient option, an automatic pressure
switch controls the operation of the condenser blower and a heating element is added to the
compressor oil reservoir. See Refrigeration Illustration on next page.
Supply/return grilles
–
Powder-coated steel single direction grilles are provided for the inlets to
the evaporator and condenser sections. One grille is provided on an outlet. These are readily
interchangeable with access doors to control and direct the airflow. These grilles may be used in the
room on the end of the ducts in ducted systems.
7
Overview Illustration of the Wine Guardian Unit
Refrigeration Illustration - Vapor Compression System
8
WiringDiagram Model WG40
Wiring Diagram Model WG 75
9
10
Wiring Diagram Model WG100
10
Wiring Diagram WG 175
11
Wine Guardian Dimensional Data
Model Number
WG40
WG75
WG100
WG175
Dimensions - Nominal - add 9.5mm for each grille
A - Width
mm
356
559
559
559
B - Height
mm
356
356
356
457
C - Length
mm
838
838
838
1270
D – Cond. discharge location
mm
540
591
591
660
E – Evap. discharge location
mm
137
137
137
137
F - Inlet opening width
mm
267
470
470
479
G - Drain outlet location
mm
502
552
552
619
H - Discharge opening width
mm
63
254
254
295
I - Inlet opening Height
mm
202
282
282
381
J - Location to wall
mm
368
419
419
457
Weight
kg
36.3
56.7
65.8
88.4
Refrigerant Charge – 134A
g
539
737
964
1417
Wine Guardian
12
Safety
DANGER
Before installing or maintaining the Wine Guardian Unit do the following:
1) Read these instructions.
2) Keep these instructions.
3) Heed all warnings.
4) Follow all instructions.
IMPORTANT
The equipment described in this manual uses electricity. When using
this equipment, be sure to follow the safety procedures outlined in the
Wine Guardian Manual.
Safety Message Conventions
Safety messages contained in this manual, DANGER, WARNING, and CAUTION are bold and
highlighted in red for quick identification.
Danger
A Danger message indicates an imminently hazardous situation which, if not avoided, results in
death or serious injury. Messages identified by the word DANGER are used sparingly and only
for those situations presenting the most serious hazards.
Following is a typical example of a Danger message as it could appear in the manual
HIGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets.
Before opening panels turn off all power.
Use the Lockout/Tagout procedure .
Warning
A Warning message indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.
Following is a typical example of a Warning message as it could appear in the manual
WARNING
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Modification to the equipment may cause injury.
:
13
CAUTION
Caution
A Caution message indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It may also be used to alert against unsafe practices.
Following is a typical example of a Caution message as it could appear in the manual:
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard.
Read all of the installation instructions before installing the Wine Guardian unit.
Lockout/Tagout Procedure
1) Turn off the power switch (indicator light should be off)
2) Unplug the unit from the electrical outlet and cover the outlet to prevent
accidently plugging in the unit.
Safety Considerations
The equipment covered by this manual is designed for safe and reliable operation when
installed and operated within its designed specifications. To avoid personal injury or damage
to equipment or property when installing or operating this equipment, it is essential that
qualified, experienced personnel perform these functions using good judgment and safe
practices. See the following cautionary statements.
Installation and maintenance of this equipment is to be performed only by qualified
personnel who are familiar with local codes and regulations, and are experienced with this
type of equipment.
Safety Hazards
Exposure to safety hazards is limited to maintenance personnel working in and around the
unit. When performing maintenance, always use the Lockout/Tagout procedure, which is
described in this chapter. Observe the maintenance safety guideline in the Wine Guardian
Manual.
Electrical Hazards
Working on the equipment may involve exposure to dangerously high voltage. Make sure you
are aware of the level of electrical hazard when working on the system. Observe all electrical
warning labels on the unit.
14
Electrical Shock Hazards
All power must be disconnected prior to installation and servicing this equipment. More than
one source of power may be present. Disconnect all power sources to avoid electrocution or
shock injuries
.
Hot Parts Hazards
Electric Resistance heating elements must be disconnected prior to servicing. Electric Heaters
may start automatically, disconnect all power and control circuits prior to servicing the unit to
avoid burns.
Moving Parts Hazards
The Motor and Blower must be disconnected prior to opening access panels. The motor can
start automatically. Disconnect all power and control circuits prior to servicing to avoid
serious injuries or possible dismemberment.
The fans are free-wheeling after the power is disconnected. Allow the fans to stop completely before servicing the unit to avoid cuts or dismemberment.
Rotating Fan Blades are present in the Wine Guardian unit. Sticking a hand into an exposed
fan while under power could result in serious injury. Be sure to use the Lockout/Tagout
procedure when working in this area or remove the power cord.
Equipment Safety Interlocks
There are no electrical safety lockouts installed within the unit. The power cord attached to the
control box must be disconnected from the power sources prior to working on any part of the
electrical system.
Main Power Switch
The main power switch is located on the side of the Wine Guardian unit. (See Overview
Illustration on page 8) It shuts off the power to the unit.
Energy Type Electrical
Hazard ............................... Electrocution, electrical burns and shock
Magnitude 230 volts AC 1 phase, 50 cycles
Control Method .................. Disconnect power cord and On/Off Switch
Never reach into a unit while the fan is running.
Never open an access door to a fan while the fan is running.
DANGER
Disconnect the power cord switch before working on the unit. The unit may have more than one
power source to disconnect.
Avoid risk of fire or electric shock. Do not expose the unit to rain or moisture.
15
WARNINGS
Check weights to be sure that the rigging equipment can support and move the Wine Guardian
unit safely. Note any specific rigging and installation instructions located in the Installation section
of the Wine Guardian Manual.
All supports for the unit mustbe capable of safely supporting the equipment’s weight and any
additional live or dead loads encountered.
All supports for the unit must be designed to meet applicable local codes and
ordinances.
Do not remove access panels until fan impellers have completely stopped. Pressure
developed by moving impellers can cause excessive force against the access panels.
Fan impellers continue to turn (free-wheel) after the power is shut
off
Clean only with a dry cloth.
Never pressurize equipment above specified test pressure. See Wine Guardian
CAUTION
Specification Sheet
Do not use the Wine Guardian near water.
Do not block any supply or return air register or duct. Install in accordance with the
instructions in the Wine Guardian Manual. Do not defeat the safety purpose of the polarized
or grounding type plug. A polarized plug has two blades with one wider than the other. A
grounding type plug has two blades and a third grounding prong. The wide blade or the
third prong is provided for your safety. If the provided plug does not fit into your outlet,
consult an electrician for replacement of the obsolete outlet.
Protect the power cord from being walked on or pinched, particularly at the outlet plugs,
convenience receptacles, and the point where it exits the unit.
Only use attachments/accessories specified by the manufacturer.
Always operate this equipment from a 230 VAC, 1 phase 50Hz power sources only.
Always ground the outlet to provide adequate protection against voltage surges and built-
up static charges
Refer all servicing to qualified service personnel. Servicing is required when the unit has
been damaged in any way. such as:
The power supply cord or plug is damaged
Liquid has been spilled or objects have fallen into the unit
The unit has been exposed to rain or moisture
The unit does not operate4 normally
The unit has been dropped
16
Installation
CAUTION
SHARP EDGES
RISK OF SERIOUS INJURY
Sharp edges are present inside the Wine Guardian system.
Pre-installation Test
Test the system before installing it to check for non-visible shipping damage.
To test the system:
Set the system on the floor or a sturdy level surface.
Plug in the system.
Press the on/off switch, control illuminates. This indicates the system has
power.
The built in timer prevents short cycling and keeps the system from
turning on right away. The system comes on and runs as long as the
temperature of the space is above the thermostat set point. After several
minutes, cold air comes out of the system from the evaporator section side
and hot air comes from the condenser section. Listen for any unusual noise
or vibration.
Air Flow Illustration
WARNING
17
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Modification to the equipment may cause injury or damage to the
equipment
.
DANGER
This equipment is heavy. Place the unit on the floor or on a level and
stable surface that can support the full weight of the unit.
Do not modify the equipment, it may cause damage to the equipment and
will void the warranty.
Never place anything on top of the unit.
Never block or cover any of the openings or outlets to the unit.
Never allow anything to rest on or roll over the power cord.
Never place the unit where the power cord is subject to wear or abuse.
Do not use extension cords.
Never overload wall outlets.
Do not remove or open any cover unless the unit is turned off and the
power cord is plugged in.
Use only dedicated power outlet boxes of the correct capacity and
configuration for the unit model.
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard. Read
all of the installation instructions before installing the Wine Guardian unit
18
Planning the Installation
Addressing Items in the Planning Process
Where to locate the unit? Should it be built into the wall or mounted remote
and ducted into the cellar?
How to mount the unit?
Decide where to locate the supply and return grilles in the room to achieve
the temperature gradient and circulation preferred.
Locate the electrical power outlet close to the unit, in cellar or out. Do not
use an extension cord!
Does the condenser heat exhaust need to be ducted away?
Where to locate the thermostat?
Where to run the drain line?
Are all the parts here to complete the installation?
Performing a Pre-installation Check
Check for the proper installation of the electrical plug configuration.
Check for the properly sized breaker.
Is the cellar built with adequate insulation and vapor barriers?
Are ducts installed above the ceiling or in accessible places properly sized
before being covered?
Is enough space available around the unit for service and repair?
Locating the Unit
Wine Guardian units are typically installed indoors located near the cellar to minimize the
duct runs. Each unit is provided with one entering or return air inlet and three possible supply
air outlets for each of the evaporator and condenser sections. A maximum cumulative total
length for both supply and return ducts (including bends) of 7.5 metres is recommended. If
longer runs are needed use more than one supply opening to reduce the airflow in each duct
by 1/2. See Recommended Flexible Ductwork Sizing Chart on page 30.
Provide a 1 metre clearance around the unit for removal of grilles or ductwork, access to
filters and unit maintenance. If the humidifier is used, provide access space in front of it for
service.
19
Grilles
Each of the inlets and one evaporator outlet and one condenser outlet come from the factory
with grilles over the openings. The grilles are removable. Remove the necessary grilles for
installing ductwork between the unit and the cellar. If desired, use the grilles as wall grilles
inside the cellar. The return air, or inlet, to the unit must connect to the return air outlet from
the cellar. Any of the three supply air outlets on the unit can be used for the ductwork to the
supply grille inside the cellar. The factory installed outlet grille can be relocated to any of the
other two openings. The procedures below apply to both the evaporator and the condenser
sections. In most cases, no ducts are installed on the condenser section because the unit is
located in a mechanical or storage type space. If exhaust heat is undesirable use the grilles to
install ductwork to move the heat outdoors or to another space. Also, use ductwork to direct
condenser air noise away from occupants.
Reducing Noise from the Unit
Consider noise when locating the unit close to the cellar or an adjacent occupied space. A
piece of 25 or 50mm dense rubber or Styrofoam with foil face in between the unit and the
wall absorbs and reduces the noise from the unit. For air noise use better grilles or block the
noise with a solid piece of wood or Styrofoam. Sound usually travels as a line of sight. Sound
is reduced when it turns a corner, such as, passing through a bend in ductwork. If the unit is
supported from a wall or joist, using a rubber pad under the unit will reduce vibration
transmission.
Installing the Unit Outdoors
The Wine Guardian is NOT designed nor approved for direct outdoor installation. If it is
located outdoors, it MUST be protected with a rain-proofed enclosure.
Mount it above the ground on a solid, waterproof base to protect the unit from
ground water.
Do not locate it where grass clippings or leaves can blow into the unit.
Keep the area around the unit clean and free of debris.
Protect from damage when the unit is located in a garage or unheated shed. In both
cases, the unit MUST have the low ambient controls built into the unit.
Double insulating ducts with exterior grade insulation is recommended to keep the
ducts dry and effective. Wine Guardian suggests installing one sized flexible duct
inside the next larger size duct where ductwork is exposed.
Allow enough space at both ends of the unit to remove the grilles or ductwork and
allow access to the filters.
20
Mounting the Unit
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Check supporting structure for load bearing capacity to support the Wine Guardian.
All supports must be designed to meet applicable local codes and ordinances.
If in doubt, consult a qualified architect, engineer or contractor.
Note
Review the mounting illustrations on pages 32 and 33 before mounting the unit.
Floor Mounting
Mount the Wine Guardian on the floor but elevate it on frame with a plywood surface to
keep it away from water. Allow adequate space for the external drain.
Wall Mounting
If the unit is mounted through the wall, adequately support it on both sides of the wall. Use
floor or knee braces to transfer the load of the unit to the floor or wall.
Ceiling Mounting
Construct a structurally sound, level platform to place the unit on when hanging it from the
ceiling joists. The Wine Guardian is NOT designed to be suspended from the top of the unit.
Place the unit on a platform to ensure that the unit is supported on all for corners. Leave adequate space on the top of the unit to remove the access doors for service.
In all cases the unit must be level to within +/- 6mm end-to-end and +/- 3mm side-to-side
for proper operation. Locate the unit as close to the wine cellar as possible to reduce the
length of the duct runs. If possible, use short and straight ducting on all ductwork. The
addition of 6mm thick rubber pads helps prevent the transmission of vibration and noise.
21
Installing the Condensate Drain Connection
The Wine Guardian unit provides dehumidification for the inside of the wine cellar. It cools
the air down to the dew point corresponding to the temperature set point of the thermostat. If
the vapor barrier of the wine cellar is poorly constructed or excess moisture is in the
basement, the unit has to remove excessive amounts of moisture from the wine cellar. The
moisture appears in the condensate drain of the unit.
Note
If moisture becomes excessive, install a room type dehumidifier to dehumidify the basement
so as to not overload your Wine Guardian.
Installing the Drain Line
The drain line must extend from the unit to an external drain or disposal site.
Do not use drain tubing any smaller than 12mm inside dimension on the unit.
Splice the drain extension onto the drain outlet with a sort piece of 12mm
copper tubing and secure with claps.
If not drain is available, use a bucket. Do not extend the drain below the rim of
the bucket. Empty the bucket periodically.
The Guardian Unit is provided with a built-in drain trap. The drain trap creates a water seal to
prevent air from backing up into the drain pan and causing the drain pan to overflow. Do not
create secondary traps in the external drainline.
Allow enough height for the drain line to function properly. If draining into a nearby sink, the
unit must be elevated higher than the rim of the sink in order for the water to drain by gravity.
Install with a 10mm per linear metre. Do not tie the condensate drain line directly into the
sanitary sewer system. See Accessories and Optional Equipment section for information about
the Condensate Pump.
Priming the Drain Trap
The internal drain trap primes itself automatically once the unit has run for a period of time
and after the unit cycles off. This is confirmed by water dripping from the drain.
Air Innovations, 7000 Performance Drive, North Syracuse, New York 13212
Wiring the Unit for Power
ELECTRICAL SHOCK HAZARD
RISK OF SERIOUS INJURY OR DEATH
The electrical outlet and wiring installation must meet the national and local
building codes.
DO:
Match the electrical outlet to the plug provided on the Wine Guardian.
Provide dedicated circuit and wiring for the system.
Match the wiring and breaker size to the rated load as shown on the serial
plate and in this guide. See sample serialplate illustration on the following
page.
DO NOT:
DO NOT MODIFY THE PLUGS IN ANY WAY!
Do not use extension cords.
23
Installing the Thermostat and
Communication Cable
The Wine Guardian Remote Interface
Controller is a combination temperature and
humidity controller with single stage cooling, heating
and humidifier control. Each Wine Guardian unit is
supplied with a Remote Interface Controller and 15
meters feet of communication cable. It is wired at
the factory for testing prior to shipment.
In most applications the Remote Interface
Controller will be mounted within the wine
cellar. The remote interface controller can also be
mounted directly outside of the wine cellar or in
any other room of the home or building. When mounted outside of the wine cellar, a remote sensor
kit must be purchased and installed within the wine cellar. See below for remote sensor installation
details.
IMPORTANT
Wine Guardian units are supplied with 15 meters of Cat 3, 6-wire twisted pair
communication cable with RJ-11 connectors. Failure to use this type of communication
cable WILL cause product damage and WILL void any equipment warranty.
Installation instructions should be followed CAREFULLY as improper splicing and/or
joining of twisted pair cables can cause equipment failure.
Mounting the Remote Interface Controller
1
. Disconnect the communication cable from the side of
the Wine Guardian unit and the Remote Interface
Controller.
a) Install the communication cable within the wall
and/or ceiling structure of the wine cellar to the
desired controller mounting location.
b) Mount the remote interface controller on a solid
surface away from doors, corners, air outlets, drafts or
heat generating equipment. Do not mount the Remote
Interface Controller directly on an outside wall or wall
adjacent to a boiler room.
24
Fig. 6
Fig. 2
Fig. 3
Fig. 4
Fig. 5
2. Remove the back plate of the controller and mark the
mounting points at the desired location. (Fig. 2)
a) Mark the location of the communication
cable connection as this area will require
sufficient clearance for instance, a 3.8cm hole in the
wall for flush mounting of the back plate. (Fig. 3)
3. Drill two (2) .32cm holes and insert anchors (provided)
within the mounting surface. Anchors may not be
required if securing to a wall stud or racking system.
4. Plug in the communication cable to the back of the
Remote Interface Controller backing plate. (Fig.4)
a) Attach backing plate to wall using the two screws
provided with the system. (Fig.5)
5. Re-install plastic face plate on to backing plate.
6. Re-attach the communication cable to the side of the
Wine Guardian cooling unit. (Fig.6)
25
The Remote Sensor is a combination temperature and
humidity sensor only. It is designed to be mounted within the
wine cellar and can be used in combination with the Remote
Interface Controller or up to three additional Remote Sensors
to read and control multiple areas within the wine cellar.
*** The remote sensor is now only available in black ****
Fig.2
Fig.1
Installation of the Wine Guardian Remote Sensor
Mounting the remote sensor
1. Disconnect the communication cable from the side of
the Wine Guardian unit and the remote sensor. Install
the communication cable within the wall and/or ceiling
structure of the wine cellar to the desired controller
mounting location.
A splitter device has been supplied within the Remote Sensor
kit. The splitter device must be mounted at the WG unit as
shown. DO NOT mount the splitter device at the back of the
Remote Interface Controller or to the back of the Remote
Sensor as this WILL cause component or system damage.
2. Mount the Remote Sensor on a solid surface away from
doors, corners, air outlets, drafts or heat generating
equipment. Do not mount the Remote Sensor directly on an
outside wall or wall adjacent to a boiler room. Use a piece of
foam insulation behind the sensor to insulate it from a hot or
cold surface. The recommended height is 1.2 to 1.5 meters
above the finished floor.
3.
Remove the sensor cover plate by removing the two allen
head screws at the top of the cover using the allen head
wrench provided in the kit.(Fig.2) Mark the mounting
points at the desired location within the wine cellar. Also
mark the location of the communication cable connection
as this area will require sufficient clearance, for instance
3.8cm hole in the wall for flush mounting of the sensor
plate
Important
.
26
Fig.3
Fig 4
Fi
Fig 6
Fig.5
4. Drill two (2) .32cm holes and insert anchors
(provided) within the mounting surface. Anchors
may not be required if securing to a wall stud or
racking system. (Fig.3)
5. Plug in the communication cable to the back of
the Remote Sensor and attach to the wall using
the two screws provided in the kit. (Fig.4)
6. Plug the Remote Sensor cables into the splitter
device at the WG unit along with the
communication cable for the Remote Interface
Controller. (Fig.5)
If using multiple Remote Sensors in one wine room
continue to mount the remaining sensors before
installation of the sensor cover plates. When multiple
sensors are used the sensor jumper position must be
adjusted in order for proper averaging of temperature
and humidity readings. See page 27 for jumper set up
.
*** The remote sensor is now only available in black
****
27
28
Joining Communication Cable
Important
Wine Guardian cooling systems are supplied with 15 meters of 6 wire, Cat 3 twisted pair
communication cable with RJ11 type connectors. Caution must be taken when connecting
two lengths of communication cable (splicing) to ensure uniform wire color before and
after splice. An RJ11 Modular 6 wire STRAIGHT THROUGH type coupler is the
ONLY coupler approved for splicing Wine Guardian twisted pair communication cable.
Jumper position 1
Jumper position 2
If using multiple Remote Temperature/Humidity sensors in
your application, refer to the photos showing the need to
change the jumper locations internal to the control board on
each remote sensor (up to 3 maximum).
For the control to average all of the sensors utilized (if
more than one), the jumper must be in different positions on
the pins.
As you can see, there are three pin settings. To access the
jumper:
1. Remove the two-set screws holding on the plastic cover.
This procedure allows the control to go to each remote
sensor in sequence to average. Failure to perform this
procedure will result in the system reading only one
sensor and not the average of multiple sensors.
NOTE: If multiple sensors control the WG unit,
change factory default in configuration setting 10 to
“averaging.” You will need access code from Air
Innovations service to use in configuration 8 to reach
configuration 10
Changing Jumper Positions
(Averaging readings from Remote Sensor)
How to:
Turn system on/off
Press the “On/Off” button once. Note:
There is a five (5) minute time delay before
the system turns on or turns off.
Change temperature
Press the “Up” arrow once. The display will
show the existing temperature setpoint.
Press the “up or down” arrow buttons to
adjust the temperature to the desired
setpoint.
Change humidity
Press the “Up” arrow once. This display will
show the existing temperature setpoint.
Press the “Mode” button once to display
the “Humidity” setpoint.
Press the “Up” or “Down” arrows to adjust
the humidity to the desired set point. Note
– a Wine Guardian humidifier must be
installed and Setting 6 set to “1” or “2”
before the controller will let you change
percent humidity.
Humidity
Temperature
"Heat" symbol
Settings Area
Up Button
Down Button
Settings button (right side)
On/Off (left side)
"Cool" symbol
Standard Controller Functions
29
Deg F or Deg C
Setting 1
Press the “Down” arrow to change temperature
from Deg F to Deg C.
Press the “Up” arrow to change temperature
from Deg C to Deg F.
Low temperature alarm
setpoint
Setting 2
Press “Mode” button to advance to Setting 2.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default is
50 Deg.F (10 Deg C).
High temperature alarm
setpoint
Setting 3
Press “Mode” button to advance to Setting 3.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default is
65 Deg F (18 Deg C).
Low humidity alarm set
point
Setting 4
Press “Mode” button to advance to Setting 4.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default is
5%.
High humidity alarm
setpoint
Setting 5
Press “Mode” button to advance to Setting 5.
Press the up or down arrow buttons to adjust to
the desired setpoint. Factory default is 95%.
Add or remove
humidifier
Setting 6
Press “Mode” button to advance to Setting 6.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setpoint. Factory default is
zero (0).
Zero (0) = No humidifier
One (1) = Integral Wine Guardian mounted
humidifier
Two (2) = Stand-alone remote mounted
humidifier
Fan AUTO or ON
Setting 7
Press “Mode” button to advance to Setting 7.
Press the “Up” or “Down” arrow buttons to
adjust number to the desired set point. Factory
default is zero (0).
Zero (0) = Auto – fan only turns on when there is
a call for cooling or heating
One (1) = Fan On – fan remains on continuously
Settings – Press and hold the “Settings” button for five (5) seconds to access the
following settings.
Settings –Press andholdthe“Mode” buttonforfive (5)seconds to access the following settings.
30
Advanced Settings-Special access required.
Contact Wine Guardian
Service Department for
access code
Setting 8
Press “Mode” button to advance to Setting 8.
Press the up or down arrow buttons to adjust
number to the access code. Press “Mode”
button to continue onto setting 9 through 19.
Compressor anti-short
cycling time
Setting 9
Press “Mode” button to advance to Setting 9.
Press the “Up” or “Down” arrow buttons to
adjust to the desired time in one (1) minute
increments. Maximum is 10 minutes, minimum is
0 minutes.
Compressor anti-short cycling time is the amount of
allowable time between compressor stop and
restart. Rapid start/stop of compressors can cause
premature failure. Factory default is 5 minutes.
WINE GUARDIAN DOES NOT RECOMMEND
SETTINGS LOWER THAN FACTORY DEFAULT.
Set up remote sensor
or thermostat
Setting 10
Press “Mode” button to advance to Setting 10.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit only
A = Averaging – Jumper position within sensors
must be adjusted. See page 28.
Room sensor calibration
Setting 15
Press “Mode” button to advance to Setting 15.
Press the “Up” or “Down” buttons to adjust to
the desired set point. Maximum setting is +2°C,
minimum setting is -2°C. Factory default is zero
(0). Sensor calibration set point changes the
actual display reading (temperature only) by the
value of this setting.
Example: Sensor reading = 13 Deg C
Setting 15 set to +2
Display reading = 15 Deg C
31
Differential temperature
adjustment
Setting 16
Press “Mode” button to advance to Setting 16.
Press the “Up” or “Down” buttons to adjust to the
desired set point.
This setting changes the system/compressor. Turn on
temperature above set point. Factory default is set to
1°C.
Example: Sensor reading = 13°C
Setting 16 set to +1°C
System/compressor turns on at 14 Deg. C.
Deadband setting
Setting 17
Press “Mode” button to advance to Setting 17.
Press the “Up” or “Down” buttons to adjust to the
desired set point.
This setting is the minimal allowable temperature
difference between heating and cooling set points.
Maximum is 3°C, minimum is 1°C. Factory default is
set to 1°C
Test mode setting
Setting 18
Press “Mode” button to advance to Setting 7.
Press the “Up” or “Down” buttons to adjust to the
desired set point. When set to one (1) the
controller will automatically turn on all outputs
with the exception of electric heat. Factory default
is zero (0).
Zero (0) = Off
One (1) = On
System Selection
Setting 19
DO NOT CHANGE
32
High temperature
alarm
Flashing temperature
number
Press the “Up” or “Down” arrow once to change
screen from alarm to normal Temperature and
Humidity indication. “Flashing temperature
number”
Along with flashing (!) symbol will remain on screen
until temperature falls below the High Temperature
Alarm set point (Setting 3).
Low temperature
alarm
Flashing temperature
number
Press the “Up” or “Down” arrow once to change
screen from alarm to normal Temperature and
Humidity indication. “Flashing temperature
number” Along with flashing (!) symbol will remain
on screen until temperature rises above the Low
Temperature Alarm set point (Setting 2).
High humidity alarm
Flashing humidity
number
Press the “Up” or “Down” arrow once to change
screen from alarm to normal Temperature and
Humidity indication. “Flashing humidity number”
Along with flashing (!) symbol will remain on screen
until humidity falls below the High Humidity Alarm
set point (Setting 5).
Low humidity alarm
Flashing humidity
number
Press the “Up” or “Down” arrow once to change
screen from alarm to normal Temperature and
Humidity indication. “Flashing humidity number”
Along with flashing (!) symbol will remain on screen
until humidity rises above the Low Humidity Alarm
set point (Setting 4).
Open Fault
!1= High pressure
Switch fault
Press the “Up” or “Down” arrow once to change
screen from alarm to normal Temperature and
Humidity indication.
THIS ALARM FORCES THE SYSTEM TO SHUT DOWN.
“!1” will remain on screen until the High Pressure
reset switch has been reset. See the trouble
shooting guide page 55 for “Instructions to
Notes: 1. The above references izes are internal diameter in mm.
2. If a single supply is used out of the unit but then splits into two (2) ducts, the above size
recommended for double is used after the split.
Installing the Ductwork
Use ductwork to connect the unit to the supply and return outlets in the wine cellar. Use only insulated
ductwork to minimize cooling loses, prevent sweating, and to reduce noise.
Use ductwork on the condenser section to redirect or absorb sound, to bring in outside air to the unit
inlet, and/or to exhaust the hot air out of the ambient space.
NOTE
Do not exceed a total of 7.5 metres for each length of ductwork run
.
CAUTION
RISK OF DAMAGE TO EQUIPMENT
Avoid crimping the flexible ducts. This chokes down the inside area and reduces the airflow
causing the unit to operate erratically.
Be sure all ducts and surface in contact with the airflow are insulated
and have a vapor barrier on the outside surface.
Location of Supply and Return Grilles
Locate the supply and return grilles inside the cellar to create an airflow pattern that maximizes
air circulation in the room. Avoid short circulating of the air.
Do Not:
Install the return air grilles directly on the floor as the grilles will collect dust
from the floor.
Locate the supply or return air grille where it is blocked by bottles, boxes or
cases.
Locate the supply air grille where it blows directly on the thermostat.
Relocating a grille on the Wine Guardian
1) Remove the fasteners from the grille.
2) Remove the fasteners from the access door panel to be replaced by the grille.
3) Relocate the outlet grille to its new location and secure in place using its fasteners.
4)
Replace the access door panel where grille was located
34
Uninsulated ducts and surfaces cause bare exposed metal surfaces to sweat,
further degradation of the insulation and a loss of equipment cooling capacity.
General Duct Recommendation
Support the flexible duct often to prevent sags or bends.
Stretch the duct to make for a smoother interior for less air resistance.
For a 90 degree bend, insert a metal elbow inside the flexible duct to avoid crimping.
Do not squeeze or reduce the inside diameter of the ducts. This restricts the
airflow.
Use short and straight ductwork.
Review the configuration schematic on the Overview Sketch on page 8 for
information about which panels are available for duct connections and service.
Remove the panels or grilles from the openings to connect the ductwork.
Check that all the fan blades move freely.
Check for loose foreign objects in any of the air paths.
Connect the round flexible ducts to the Wine Guardian using the duct collars
provided with the duct accessory kit.
Pull the outer plastic wrapping and insulation away from the end of the duct to
expose the reinforced inside duct liner.
Use tie straps of clamp around the inside liner to fasten the duct collar.
Do not clamp around the outside insulation. It compresses and loosens over time.
Secure the duct collar to the unit using the screws provided. Be careful not to damage
or bend the gasket.
Not Using Ductwork
The supply and return grilles stay on the unit if no ductwork is used.
The supply and exhaust grilles may be relocated to any of three openings. (Refer to the
manufacturers installation instructions located in the box of flexible ductwork).
Using Ductwork
Cold Air to/from Wine Cellar
Remove supply air grille or access door panels to install ductwork between the Wine Guardian
unit and the cellar.
Connect the supply air ductwork form the cellar to the supply air inlet at the Wine Guardian unit.
Connect the return air ductwork from the cellar to the return air inlet at the Wine Guardian unit.
Warm Air to/from Condenser
Connect ductwork on the condenser to direct heat and the air noise away from occupants.
Connect ductwork to another space within the basement, a building or to the outdoors if the heat
being exhausted is undesirable.
35
33
Remote Mount on Floor
Condenser inlet and
exhaust – to outside
Ceiling Mounts
Through-Wall ceiling mount with
dual supply
Outside Mounts
Outside Remote Mount
Typical Mounting Arrangements
The following illustrations are suggested mounting arrangements. These illustrations are not intended to
be complete and detailed installation drawings. For questions or help regarding installation, call customer
service at or 00 1 315-452-7434, fax 00 1 315-452-7420 or email (info@wineguardian.com) a
sketch of the proposed area where the unit is to be installed.
36
UNIT SIZE
LOCATION
ROUND
OPENING SIZE
FLANGE SIZE
DUCT SIZE
WIDTH
HEIGHT
WIDTH
HEIGHT
1/4
INLET
202
267
283
295
346
1/4
OUTLET
202
203
283
244
346
1/2 & 1
INLET
252
346
283
549
346
1/2 & 1
OUTLET
253
254
283
295
346
1
DUAL OUTLET
202
254
283
295
346
2
INLET
303
479
381
549
448
2
OUTLET
303
295
381
346
448
2
DUAL OUTLET
252
295
381
346
448
Duct Adapter Sizes
Ducting Options
Single Outlet Duct Installation
Dual Outlet Duct Installation
37
Inspection and Start-up Checklists
Receiving and Inspecting
Unit received undamaged
Unit received complete as ordered including accessories
Handling and Installing
Unit mounted on solid level surface
Sufficient space allowed for access to unit and accessories Proper electrical service
provided
Hot water provided to humidifier
Drain lines and trap installed properly
Ductwork, fittings and grilles installed properly
Al
l cold duct surfaces insulated
Low ambient control included if freezing condition present No obstructions to air
flow to condenser
Starting-up the Unit
General visual inspection looks good All wiring connections checked
All ducts, grilles and panels in place
Start unit
Check ducts and connections for air leaks
Balance air distribution
Confirm condenser airflow is unrestricted
Verify cooling and heating operation
Check for excessive noise or vibration
38
CAUTION
Rick of personal injury.
Starting-up and Operating the Wine Guardian
Now that the installation is complete, it’s time to start the unit up. Check to make sure all ductwork
and electrical connections are secure.
Replace all panels which were removed during installation. Check that all of the openings in the unit
are covered with a blank panel, a ductwork connection or a grille.
Cover all openings of the unit to prevent a hand or finger from access inside
the unit.
Turn on the Unit
Plug in the unit. Turn-on the rocker switch on the side of the unit. The rocker switch lights up to
indicate power to the unit. The unit may not come on right away due to the timer built into the
circuiting to prevent short-cycling.
Testing the Fan
(Configuration Setting 7)
Factory default is AUTO FAN operation. You change into setting 7 to change from “AUTO” to “ON.
ON means the fan runs continuously and indicates that the power is on and the
control circuit is energized and operating.
AUTO means the fan runs only when the thermostat is calling for cooling, heating,
or the optional humidistat is calling for humidification.
Running the Unit
√Check unit to confirm the compressor is running, such as the hum of the compressor
or cool air leaving the unit.
√ Check for any unusual noise or vibration, such as clanking or rubbing
.
Initially, the unit may run continuously for several hours, up to a day or more, while it lowers the
cellar temperature. Once the unit reaches the set point temperature, it shuts off and starts to cycle on
and off as it continues to lower the bottle temperature to the set point. The cellar air reaches set point
before the bottles. If the cellar temperature started at 24°C, the supply air temperature discharged
from the unit will probably be 8°C to 11°C colder. As the cellar temperature decrease to 13°C, the
supply temperature differential decreases 6 to 7°C colder.
The remote interface controller will show a"Hi Temp" fault until the wine cellar
temperature falls below 18°C. See page 30 for Hi Temp Alarm details.
Note
39
Cycling the Unit
The fans continue to free-wheel for several minutes when the unit cycles off. This is normal.
If the unit is furnished with a low ambient control, the condenser fan also cycles on and off during
cooling. This maintains the head pressure on the compressor under low ambient conditions, and is
normal. The bottom of the compressor stays warm even when the unit is off to keep the lubricating oil
warm and separated from the refrigerant.
Setting the Thermostat
Normal settings are between 12 and 14°C. If the optional heating coil is furnished, enter a separate
temperature setting to maintain the lower setting. To prevent the unit from short cycling, the setting
between heating and cooling cannot be closer than 2°C.
Regulating the Wine Cellar Temperature
Wine cellars have a natural temperature gradient of approximately 3°C between floor and ceiling. To
increase or decrease the temperature in various zones, change the air flow patterns.
To keep the entire wine cellar at the same temperature, set the thermostat to run the supply fan
continuously and not just when the cooling is operating. Set Fan switch to ON instead of AUTO.
NOTE
To monitor the Cellar Temperature, place thermometers in various locations in the
cellar to monitor the temperature zones. Change the temperature in various zones by
shifting the air flow patterns.
Changing the Air Flow Direction
The grilles furnished with Wine Guardian are single directional. Rotate the grilles to change the
direction of the air flow.
When using multiple supply ductwork balance the air flow between the ductwork. If too much air
flows though one duct but not enough air flows from the other duct, install a damper or other
restriction into the duct with too much air. That will force more air to flow out the other duct.
40
WARNING
DANGER
CAUTION
CAUTION
Maintenance
General
BEFORE PERFORMING MAINTENANCE ON THE UNIT, READ AND UNDERSTAND THE SAFETY
INFORMATION CONTAINED WITHIN THE SAFETY CHAPTER OF THE WINE GUARDIAN
MANUAL.
HIGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets. Turn off all power. Use the Lockout/
Tagout procedure before opening panels.
SHARP EDGES
RISK OF SEROUS INJURY
Sharp edges are present on the fan wheels, housing, fins and coils.
Maintenance on Wine Guardian units requires working with high voltage and
sheet metal with possible sharp edges. Only qualified personnel should
perform maintenance. Some tasks require knowledge of mechanical and
electrical methods. Make sure you are familiar with all hazards, general safety
related procedures, and safety labels on the unit.
EXPOSURE TO MICROBIAL GROWTH (MOLD) CAN CAUSE SERIOUS HEALTH PROBLEMS
Standing water in drain pans promote microbial growth (mold) that cause
unpleasant odors and serious health-related indoor air quality problems. If
mold is found, remove it immediately and sanitize that portion of the unit.
The Wine Guardian is designed for minimum maintenance. The refrigerant system is hermeticallysealed and requires no maintenance. The fans are permanently lubricated and require no
maintenance. Some maintenance to the unit may be required due to dust or dirt in the air stream.
41
Cleaning the Filters
The evaporator and condenser coils are provided with reusable, washable air filters. The
filters protect the coils from becoming coated or plugged by dust. Frequency of cleaning the
filters is based on the amount of dust or dirt generated in the cellar or basement.
1. Remove the grille or duct collar on the inlet end of the unit.
2. Remove the filter covering the face the coil.
3. Wash it under warm water.
4. Shake off excess water.
5. Inspect and clean the face of the coil.
CAUTION
SHARP EDGESRISK OF SERIOUS INJURY
Sharp edges are present on the fins and coils.
6. Reinstall the filter.
7. Replace the grille or duct collar.
Cleaning the Condensate Drain System
The condensate drain system traps dust and dirt. Clean the drain system once a year.
1. Shut off the rocker switch and unplug the unit.
2. Remove the grille or duct on the evaporator inlet.
3. Remove the filter and inspect the drain pan under the coil.
4. If drain pan appears soiled, pour some hot water mixed with liquid bleach (diluted
solution) along the length of the pan to flush the dirt down the drain tube.
5. Continue this treatment until the drain appears clean and free of dirt.
6. Reinstall filter and grille or duct collar.
7. Plug in the unit and restart.
Cleaning the Humidifier (optional)
If the unit was furnished with a humidifier it requires periodic maintenance. Follow the
instructions in the humidifier guide.
Heating Coil Option
The heating coil is located between the evaporator coil and blower inside the transition duct. It
contains the heating element and high temperature limit switches. The heating coil is wired to
work in conjunction with the thermostat. Since the thermostat prevents the heating and
cooling circuits from being energized at the same time, no additional power wiring is needed.
We do recommend using the AUTO mode on the thermostat so it can switch from heating to
cooling automatically. If using either the heat or cool only mode, the thermostat will not
switch automatically.
42
No additional maintenance is required for the heating coil. To test the heating coil operation,
set the thermostat on HEAT and set the temperature above the cellar temperature. The supply
air temperature should rise above the return air temperature by an amount shown in the
specifications.
Low Ambient Option
The purpose of the Low Ambient Option is to protect the compressor and refrigerant system.
It has two distinct components, a crankcase heater to keep the oil in the compressor warm and
prevent slugging on system start-up and a head pressure control to cycle the condenser fan on
and off automatically to maintain system head pressure.
To confirm that the system is working, feel the bottom of the heater when the compressor unit
has cycled off. When the unit starts, the condenser fan does not start at the same time as the
compressor. The condenser fan starts after the head pressure has built up. As the unit is
running the condenser fan cycles off and on while it holds the head pressure within a fixed
range. The amount of cycling (frequency and duration) depends on the air temperature. The
colder the air, the more frequent the cycling and with a longer duration.
Maintenance Schedule
Monthly
(or quarterly depending on experience with individual cellar)
Check filter and drain trap – clean if needed.
Check for noise or vibration.
Check for short-cycling of the unit – a turning on and off of the compressor unit
more than either (8) times/hour.
Yearly
(in addition to monthly)
Replace filters if worn or plugged beyond cleaning.
Check evaporator and condenser coils for dirt – use a vacuum with a brush
attachment to clean the coils.
Clean condensate pan under the evaporator coil by flushing. Be careful to keep the
drain pans clear of any and all debris.
Inspect cabinet for corrosion or rusting – clean and paint.
Inspect for dirt buildup on or inside the unit. Clean unit by vacuuming or wiping it
down.
Check for loose insulation, fasteners, gaskets or connections.
Check the wiring connections and integrity or cords.
Examine ducts for any cracks or breach.
Check fan and solenoid on humidifier.
Replace humidifier pad (if used).
43
Typical Start-up Problems
Possible Cause
Loose, improper or defective
thermostat or humidistat cable
Solution
Check power, and thermostat
or humidistat cable
Incorrect thermostat or
humidistat (optional) settings.
Check the thermostat and optional
humidistat setup for the application. Read the
thermostat troubleshoot guideline in the
Thermostat Installation and Operating
Instructions.
Changed settings on the thermostat
A common problem is not waiting long
enough for the internal timers to complete
their timed delay. These timers can be
manually overridden. Follow the
Power Switch Light is Off
Possible Cause Solution
Switch not on Turn on switch
No power to outlet Check circuit breaker and wiring
Unit not plugged in Plug in the unit
Power Switch Light is On and the Thermostat Light is Off
Possible Cause Solution
No power to thermostat Check wiring for loose, broken or frayed
connections
Check transformer for 24v output to
Troubleshooting
WARNING
BEFORE PROCEEDING, READ AND UNDERSTAND THE SAFETY INFORMATION CONTAINED IN
THE SAFETY SECTION OF THE WINE GUARDIAN MANUAL.
IMPORTANT
This section is intended as a diagnostic aid only. For detailed repair or parts replacement
procedures, contact a qualified service company. Check the following table for some solutions
before calling a service technician.
Unit Does Not Start-up
44
Power Switch Light is On and the Thermostat Light is On
Possible Cause Solution
Thermostat is not set up properly Check thermostat set up in the guide.
Press fan ON switch to check evaporator
fan only
Possible Cause Solution
Thermostat not set up properly Check thermostat setup in the manufacture’s
thermostat guide
Compressor not operating High pressure switch open (button up) (see
below)
Condenser airflow is blocked Remove blockage
Clean filter and coil (if needed)
High Pressure (HP) switch is open Reset HP switch See reset instructions on
page 50
Cellar Temperature too cold (below 11°C) when unit is running
Possible Cause Solution
Thermostat set too low on cooling Reset thermostat to higher cooling
temperature
Heating coil (optional) not operating Check for temperature rise across coil
Thermostat set too low on heating Reset thermostat to higher heating
temperature
Thermostat not controlling temperature Wiring integrity compromised (shorted),
replace wiring
Cellar Temperature is too cold (below 11°C) when unit is not running
Possible Cause Solution
Too much heat loss to adjacent spaces Increase insulation around the ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours
Cellar loads are too high Install additional insulation
Replace with larger sized unit
Problems Controlling Cellar Temperature
Problems are occurring even though the unit seems to be fully operational –
evaporator fan blows air into the cellar and compressor and condenser fan runs.
Unit is Operating and Blows Evaporator Air, but the Supply Air is Not
Colder Than the Return Air from the Cellar
45
Problems Controlling Cellar Humidity
Humidity too low or supply air is too cold, without optional humidifier
Possible Cause Solution
Not enough evaporator airflow Remove blockage in supply or return
ductwork
Check and clean filter and coil
Coil frozen – shut off unit for two hours
Defective Thermal Expansion Valve If under warranty call for service
If not under warranty call a refrigeration
technician
Humidity too low, without optional humidifier
Possible Cause Solution
No moisture being added to cellar Add Wine Guardian humidifier or a room
humidifier
Humidity too low with optional humidifier
Possible Cause Solution
Humidifier not operating Check wiring for loose, broken or frayed
connections
Check humidistat set up
Check for water flow & solenoid valve
operation
Check damper operation
Humidifier operating Check for water being hot
Check drip pad – replace if scaled
No vapor barrier around cellar
Humidity too high when unit is running but not cooling
Possible Cause Solution
Compressor not operating Check and reset high limit switch
Clear blockage of condenser airflow
Ambient temperature is too high Reduce temperature or draw condenser air
from another space
39
46
Humidity too high when the unit is not running
Possible Cause Solution
Unit needs to run to dehumidify Run unit. Seal openings around doors (gasket and
sweep)
Humidity too high when unit is running and cooling
Possible Cause Solution
Too much moisture in cellar Poor vapor barrier installation
Humidifier malfunction refer to
the humidifier instructions.
Add dehumidifier to surrounding space
Unit operates but the power switch light is not ON
Possible Cause Solution
Unit is leaking water
Possible Cause Solution
Trap plugged Clean trap
Condensate pan plugged Remove blockage and clean
Unit not level Level with shims
Other Miscellaneous Problems
Unit is running properly, but the sound of the unit is objectionable
Possible Cause Solution
Noise is from airflow Redirect airflow
Add baffles
Add insulated ductwork
Noise is from unit Add sound baffle between unit and occupied
space
47
High Pressure Switch has Shut the Unit Down
Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system. This
switch shuts the compressor and condenser down if the head pressure in the system is too high. It is
intended to protect the compressor. Restricted airflow through the condenser is the most common
reason for the pressure to become too high. This can be caused by dust covering the filter or an
obstruction blocking the airflow in the duct or grille
.
Possible Cause Solution
Head Pressure in unit is too high because Remove the obstruction in the duct or grille or
an obstruction is restricting air flow clean the filter. Then restart the unit after
resetting the using the high pressure switch.
Instructions to Reset High Pressure Switch
Remove the access panel, grille or duct collar at the condenser opening labeled “High
Press. Manual Reset Switch ----- “Remove panel or grille to access”
Locate the high pressure switch near the compressor (a cylindrical device piped into the
refrigeration system with two wires a red button on the top).
Push in the button until it locks into position.
Push the rocker switch to restart the unit.
48
Evaporator Coil is Freezing
Possible Cause Solution
Charge too low Check sight glass
Check for leaks
Add refrigerant
TXV malfunctioning Repair or replace
High Pressure Switch Keeps Tripping Even After Checking for
Obstructions and Dirty Filters/Coils
Possible Cause Solution
Condenser fan not operating Repair or replace
Defective switch Replace
Unit Cycles on and off more than 8 times/hr
Possible Cause Solution
Thermostat malfunctioning Check the thermostat guide for
thermostat information
Low suction pressure Check low pressure switch
Check pressure and adjust superheat
High Pitched or Loud Rubbing Noise , Clanking or Vibration
Possible Cause Solution
Fans loose or malfunctioning Repair or replace
Excessive compressor vibration Replace
TXV malfunctioning Repair or replace
Replacing the Blowers
When replacing the fan or motor, replace the fan and motor as a unit. Do
not remove the motor from the impeller wheel.
Advanced Troubleshooting
IMPORTANT
THIS SECTION IS INTENDED FOR QUALIFIED REFRIGERATION SERVICE TECHNICIANS ONLY.
THE TECHNICIAN SHOULD REPEAT ALL OF THE PREVIOUS TROUBLESHOOTING STEPS
BEFORE TAKING ACTION ON THESE MORE TECHNICAL SOLUTIONS
.
49
Appendix
Warranty Procedure
The Wine Guardian unit serial number is noted on all packing lists and bills of lading and, along
with the shipping date, is kept on file at Wine Guardian for warranty purposes. All
correspondence regarding warranty must include the model number and serial number of
the unit involved. Note that the warranty is null and void if the serial number on the unit or
compressor is altered, removed or defaced. All inquires or correspondence regarding warranty
should be handled in accordance with the “Warranty” and directed to:
Wine Guardian
7000 Performance Drive
North Syracuse, New York 13212 USA
Attn: Service Department
001 315 452-7400 Phone
001 315 452-7420 Fax
This procedure includes but is not limited to:
Obtaining authorization from Wine Guardian prior to incurring any charges for repair or
replacement under warranty.
Returning prepaid within 30 days any and all defective parts.
50