Wine Guardian WG 175 User Manual

Wine Cellar Cooling Systems
Installation, Operation and Maintenance Guide
Models: WG 40, WG 75, WG 100, WG 175
50Hz
Manufactured by:
Wine Guardian division of Air Innovations, Inc. Syracuse, NY
www.wineguardian.com www.airinnovations.com
Wine Guardian reserves the right, without notice, to make changes to this document at our sole
discretion. Please visit our web site for the most current version of the Wine Guardian Manual and
other literature. Wine Guardian is a registered Trademark (76/551,126) of Air Innovations, Inc.
Edition 11/2011
Table of Contents
Directory of Terms ....................................................................................................................... 2
Receiving, Inspecting and Unpacking the Wine Guardian Unit .......................................... 3
Receiving and Inspecting the Unit .............................................................................................................................. 3
Review the Packing Slip to verify: ....................................................................................................................... 3
Check the unit for: ....................................................................................................................................................... 3
General Description ............................................................................................................. 4
Standard Specifications ....................................................................................................................................................... 5
The Wine Guardian Unit Contains .............................................................................................................. 5
Accessories and Optional Equipment ................................................................................................................... 6
Heating Coils ........................................................................................................................................................................... 6
Water Cooled Option ........................................................................................................................................... 6
Duct Collars and Flexible Ducts .......................................................................................................................... 6
Extended Compressor Warranty ......................................................................................................................... 6
Low Ambient Option ...................................................................................................................................................... 6
Condensate Pump ........................................................................................................................................................ 6
Humidifier and Humidistat .................................................................................................................................... 6
Overview of the Wine Guardian Unit ................................................................................................................... 7
Overview Illustration of the Wine Guardian Unit ........................................................................................... 8
Refrigeration Illustration - Vapor Compression System ............................................................................... 8
Wiring Diagram WG40 ................................................................................................................................. 9
Wiring Diagram WG75 ................................................................................................................................ 10
Wiring Diagram WG100 .............................................................................................................................. 11
Wiring Diagram WG175 ....................................................................................................................... 12
Dimensional Data ................................................................................................................................. 13
Safety ......................................................................................................................................14
Safety Message Conventions ................................................................................................................................... 14
Danger .................................................................................................................................................. 14
Warning ............................................................................................................................................... 14
Caution ............................................................................................................................................... 14
Lockout/Tag out Procedure ...................................................................................................................................... 15
Safety Considerations ....................................................................................................................................... 15
Safety Hazards .................................................................................................................................................................. 16
Electrical Hazards ....................................................................................................................................... 15
Electrical Shock Hazards ........................................................................................................................... 15
Hot Parts Hazards ...................................................................................................................................... 15
Moving Parts Hazards ........................................................................................................................................ 16
Equipment Safety Interlocks .............................................................................................................................. 16
Main Power Switch ........................................................................................................................................................... 16
Installation ................................................................................................................. 18
Pre-installation Test........................................................................................................................................................... 18
Air Flow Illustration ...................................................................................................................................... 18
Planning the Installation .......................................................................................................................................... 20
Addressing Items in the Planning Process ................................................................................................ 20
Performing a Pre-installation Check .................................................................................................... 20
Locating the Unit ........................................................................................................................................................ 20
Grilles ................................................................................................................................................................................... 21
Reducing Noise from the Unit ............................................................................................................................ 21
Installing the Unit Outdoors .......................................................................................................................................21
Mounting the Unit ............................................................................................................................................................... 22
Floor Mounting ............................................................................................................................................................ 22
Wall Mounting ............................................................................................................................................................. 22
Ceiling Mounting ........................................................................................................................................................ 22
Installing the Condensate Drain Connection ....................................................................... 22
Installing the Drain Line .............................................................................................................................................23
Priming the Drain Trap ...................................................................................................................................................... 23
Wiring the Unit for Power .............................................................................................................. 24
Serial Plate .................................................................................................................................................................................... 24
Installing the Thermostat and Communication Cable ........................................................ 25
Mounting the Remote Interface Controller ................................................................................................. 25
Installation of the Wine Guardian Remote Sensor ............................................................ 27
Mounting the remote sensor
Joining Communication Cable ................................................................................................................................................................................... 29
Changing Jumper Positions ............................................................................................................................... 29
Standard Controller Functions .................................................................................................................... 30
Alarm Codes ............................................................................................................................................................... 34
........................................................................................................................................... 27
Installing the Ductwork ............................................................................................................ 35
Location of Supply and Return Grilles ...................................................................................................................... 35
General Duct Recommendation ...................................................................................................................................... 36
Not Using Ductwork ........................................................................................................................................................... 36
Using Ductwork ................................................................................................................................................................. 36
Typical Mounting Arrangements ................................................................................................. 37
Remote Mount on Floor .............................................................................................................................................37
Ceiling Mounts .................................................................................................................................................................. 37
Outside Mounts .................................................................................................................................................................. 37
Duct Adapter Sizes ................................................................................................................... 38
Ducting Options .................................................................................................................. 38
Single Duct Installation ..............................................................................................................................................38
Dual Duct Installation ................................................................................................................................................38
Inspection and Start-up Checklists ...................................................................................... 39
Receiving and Inspecting .........................................................................................................................................39
Handling and Installing .............................................................................................................................................39
Starting-up the Unit .................................................................................................................................................................... 39
Starting-up and Operating the Wine Guardian .................................................................... 40
Turn on the Unit ........................................................................................................................................................40
Testing the Fan .........................................................................................................................................................40
Running the Unit .......................................................................................................................................................40
Cycling the Unit .................................................................................................................................................................. 41
Setting the Thermostat ...................................................................................................................................... 41
Regulating the Wine Cellar Temperature .................................................................................................................41
Changing the Air Flow Direction ..............................................................................................................................41
Maintenance............................................................................................................................... 42
General ...................................................................................................................................................... 42
Cleaning the Filters ................................................................................................................................................... 43
Cleaning the Condensate Drain System .................................................................................................................. 43
Cleaning the Humidifier ............................................................................................................................................. 43
Heating Coil Option .................................................................................................................................................. 43
Low Ambient Option .......................................................................................................................................................... 44
Maintenance Schedule .................................................................................................................................................... 44
Monthly ............................................................................................................................................................... 44
Yearly .......................................................................................................................................................................... 44
Troubleshooting ........................................................................................................................ 45
Typical Start-up Problems ........................................................................................................................................ 45
Unit Does Not Start-up ............................................................................................................................................. 45
Power Switch Light is off .................................................................................................................................... 45
Power Switch Light is on and the Thermostat Light is off .......................................................................... 45
Power Switch Light is on and the Thermostat Light is on ......................................................................... 45
Unit is Operating and Blows Evaporator Air, but the Supply Air is Not Colder than the Return Air from the
Cellar .......................................................................................................................................................... 46
Problems Controlling Cellar Temperature ................................................................................................................ 46
Cellar Temperature is Too Low (Below 11°C) When Unit is Running .................................................. 46
Cellar Temperature is Too Cold (Below 11°C) When Unit is not Running ............................................... 46
Cellar Temperature is Too High, but Supply Air is Cold ............................................................................. 47
Problems Controlling Cellar Humidity ................................................................................................................ 47
Humidity Too Low or Supply Air is Too Cold, Without Optional Humidifier .............................................. 47
Humidity Too Low and Without Optional Humidifier .................................................................................. 47
Humidity Too Low and With Optional Humidifier ........................................................................................ 47
Humidity Too High When Unit is Running But Not Cooling ...................................................................... 47
Humidity Too High When Unit is Not Running ................................................................................................. 48
Humidity Too High When Unit is Running and Cooling ............................................................................ 48
Other Miscellaneous Problems ........................................................................................................................ 48
Unit operates but the Power Switch light is not ON .................................................................................... 48
Unit is leaking water ............................................................................................................................................ 48
Unit is Running Properly, but the Sound of Unit is Objectionable ......................................................... 48
High Pressure Switch has Shut the Unit Down ................................................................................................. 49
Instructions to Reset High Pressure Switch ..................................................................................................... 49
Advanced Troubleshooting ............................................................................................................... 50
Evaporator Coil is Freezing ....................................................................................................................................... 50
High Pressure Switch Keeps Opening Even After Checking for Obstructions and Dirty Filters/Coils ......... 50
Unit Cycles On and Off More than 8 times/hr. ................................................................................................. 50
High Pitched or Loud Rubbing Noise, Clanking or Vibration ............................................................................. 50
Replacing the Blowers ...................................................................................................................................................... 50
Warranty Procedure ................................................................................................................. 51
Directory of Terms
2
Ambient Air – The surrounding area outside the cellar such as a room, basement, garage or outdoors.
CACLS – Cubic litres per second. A unit of measurement for the amount of air handled by the fan.
Condensate / Condensation – The water formed out of the air when it is cooled below a certain temperature
(called dew point). Often referred to as “sweating” on pipes and cold surfaces. This water collects at the bottom of the evaporator or cooling coil and drains out of the unit through the drain line.
Condenser (Heat Rejection) Section / Coil – The Condenser Section uses the compressor, condenser coil and fan to remove heat from the refrigerant to the ambient air outside the wine cellar. The word condenser refers to the condensation of the refrigerant from gas to liquid phase.
CE– Certificate of European conformity Exhaust Air – The air leaving the evaporator or condenser section of the Wine Guardian unit.
Evaporator (Cooling) Section / Coil – The Evaporator Section uses the cooling coil and the fan to remove
heat from the air inside the wine cellar to the refrigerant, cooling the air and condensing moisture out of the air. The word evaporator refers to the evaporation of the refrigerant from liquid to gas phase in the coil. The Evaporator Section is connected to or inside the wine cellar.
Flexible Duct – Round ducts with steel reinforced plastic liners, a layer of insulation and an outer plastic layer used to convey the air from the unit to the cellar or ambient space.
Grille or Diffuser – Inlet or outlet plates to direct the airflow or protect the inside of the unit. Heat Gain / Loss – The amount of cooling or heating expressed in watts transferred between the wine
cellar and the ambient space. The Wine Guardian must offset this load.
Inlet Air – The air entering the evaporator and condenser sections of the Wine Guardian unit. NEC– National Electrical Code
Recovery – The amount of cooling the unit does to return the cellar to its set point temperature after some new load is introduced, such as people or new cases of warm wine entering the cellar.
Return Air - The air leaving the cellar and returning to the inlet of the evaporator coil. SP – Static pressure. Unit of measurement (mm of water or pascals of water column) of the pressure of the air
handled by the fan.
Set Point – The desired temperature or humidity set on the thermostat or humidistat.
Supply Air - The air entering the cellar from the discharge of the evaporator coil.
Receiving, Inspecting and Unpacking the
3
Wine Guardian Unit
Receiving and Inspecting the Unit
NOTE
Wine Guardian units are factory assembled and tested prior to shipment.
Wine Guardian units are shipped in individual cardboard boxes.
Lift at the designated handhold locations only or fully support from underneath. A
shipment may include one or more boxes containing accessories.
Before opening the container, inspect the packing crates or boxes for obvious signs of
damage or mishandling.
Write any discrepancy or visual damage on the bill of lading before signing. Inspect all equipment for any sign of damage caused during transit. Report all visual or concealed damage to the carrier and file a claim immediately. Thoroughly inspect the contents for any visible damage or loose parts.
IMPORTANT
If this procedure is not followed, the shipping company may reject the claim and the consignee may suffer the loss. Do not return the shipment to the factory.
Review the Packing Slip to Verify:
Model number Factory installed options Unit accessories
If any items listed on the packing slip do not match your order information, contact the place of purchase immediately.
Check the unit for:
An electrical power cord A thermostat with communications cable plugged into side of unit A drain line coming out of the unit
General Description
4
View the Overview Illustration on page 8 for details. The Wine Guardian cooling unit is a professional grade American manufactured, self-contained
climate control unit designed specifically for the storage of wine at cellar temperatures. It is designed for easy installation and operation. Wine Guardian uses digital electronic controls and environmentally friendly R-134a refrigerant.
All Wine Guardian 50Hz units carry the CE mark. Each unit is furnished with a sealed, CE­approved power cord and plug.
The Wine Guardian unit is completely self-contained and includes either an integral air or water cooled condenser. The unit is functionally divided into two sections, the evaporator or cooling section and the condenser or heat rejection section. Each section contains a coil to add or remove heat and a fan to move the air through the coil and into or out of the cellar or adjacent space. The Wine Guardian unit is designed to be used as a remote mounted unit with external ductwork connections.
Air from the cellar first enters a filter to remove any airborne dust particles and then enters the cooling coil. Air passes through the cooling coil and is cooled by the refrigerant inside the coil. This causes any excess humidity in the air to condense and be captured in the drain pan and piped outside the unit. Air then enters the fan where it is pressurized and discharged out of the unit. Optional heating coils are located between the cooling coil and the fan. These coils heat the air to prevent low temperatures in the cellar. The thermostat, located in the cellar, turns on the cooling or heating as needed to maintain its set point. It does not allow the cooling and heating to be on at the same time.
The compressor and condenser sections are activated whenever the unit is cooling. The condenser fan draws air from the surrounding or ambient space either directly or through a duct. The air is first drawn through a filter to remove any airborne dust particles to keep the coil clean. Then the air flows through the condenser coil where it absorbs heat from the refrigerant in the coil. The air is finally discharged out of the unit by the condenser fan.
The water-cooled Wine Guardian system requires cooling water to be piped to the unit for proper operation. The cooling water absorbs the refrigerant heat through the unit’s water-cooled condenser coil. Warm water is then directed out of the unit back to the cooling water system or to a drain.
IMPORTANT
The air exhaust from the condenser fan is hot and will be 15 to 18 degrees C above the entering temperature. This may cause overheating problems in the summer months, especially with high humidity. Exhaust the hot air to the outside. In the winter, this heated air can help to heat the surrounding space.
Standard Specifications
5
IMPORTANT
Design and specifications are subject to change without notice
The Wine Guardian Unit Contains
A thermal expansion valve to control the flow of refrigerant into the evaporator coil A filter dryer to keep the refrigerant clean and free of contaminant A sight glass to observe the level of refrigerant An automatic low pressure switch on the discharge to protect the compressor form high
pressures
The unit uses only environmentally friendly refrigerant F-134a A built-in condensate drain trap. No external trap is required.
The Wine Guardian meets or exceeds its rated capacities for total watts and cubic litres per second at design cellar conditions and external static pressures. Both the evaporator and condenser fans are capable of rated CFM against the external static pressure imposed by recommended ductwork. Both fans are motorized impeller plug fans, statically and dynamically balanced, and use permanently lubricated direct drive motors requiring no maintenance.
All exterior framing of the Wine Guardian is powder coated 1.6mm gauge aluminum to prevent rust and corrosion. All coils are copper tubes with aluminum fins. The unit uses an external drain to remove excess moisture and not reintroduce it into the cellar or ambient space. Removable, multiple access doors are provided to facilitate cleaning and maintenance, duct connections, and access to components and wiring.
Both the evaporator and the condenser coils have pre-filters on the inlet to prevent dust and dirt from fouling the coils, thereby reducing capacity. Each unit has at least three discharge outlets on both the evaporator and the condenser coils to facilitate custom installations. Water-cooled units have copper straight tube connections for both cooling water inlet and outlet.
Each unit is provided with a pre-wired and tested electronic digital thermostat for remote mounting in the cellar. The thermostat has multiple control functions for the fans, cooling and heating. It has a fully automatic mode to switch between heating and cooling.
Compressors are rotary, self-lubricating, permanently sealed, hermetic reciprocating type compres­sors, with internal overload protection and capacitor start with a minimum of one-year manufacturer’s warranty and an optional five-year warranty. Compressors are mounted on rubber-in-shear isolators to reduce noise and vibration.
Electric power is supplied by a single factory furnished cord and plug. All external controls are digital and proprietary to Wine Guardian products. Only approved communication cable and Wine Guardian controllers are suitable for proper system operation.
6
Accessories and Optional Equipment
Heating Coils
An optional heating coil is built-in and requires no additional power source. The electric heating option is factory installed and includes primary and secondary over-temperature protection devices per UL and NEC.
Water Cooled Option
A water cooled option is available that uses a tube-in-tube heat exchanger in place of the condenser coil and fan. Waste heat from the refrigerant is transferred to the water. A two-way control valve is used to regulate the flow of water to maintain head pressure.
Duct Collars and Flexible Ducts
Ducting for the Wine Guardian is sold in kits by size for each unit. Each kit contains two adapter collars, one 7.62 meter length of round flexible duct and two straps. The number of duct kits needed depends on the layout. The size of the kit depends on the model Wine Guardian selected. Follow installation instructions carefully. Poorly or incorrectly installed ducts can degrade the performance of your unit dramatically.
Extended Compressor Warranty
The Wine Guardian uses only the best commercially available compressors on the market. However, since the compressor is the single most expensive component in the unit, it is recommended that you purchase the extended warranty option.
Low Ambient Option
A factory installed Low Ambient option is available which makes the Wine Guardian capable of exposure to low ambient temperatures. This feature controls the condenser fan operation based on head pressure and heats the oil reservoir. The Low Ambient Option (LAO) is recommended whenever the condenser section is exposed to air temperatures below 50°C. This can occur if the unit is placed in a garage or under an outdoor canopy or if the unit is located inside a heated space but the condenser air is ducted in from the outside.
Condensate Pump
An optional Wine Guardian automatic condensate pump is available outside. It requires a separate 220/240 volt electrical outlet.
Humidifier and Humidistat
Another popular option for the Wine Guardian is a humidifier. It comes with a sheet metal adapter box and a pre-wired humidistat. The humidifier is available for field installation and can be retrofitted onto an existing unit. Each humidifier is furnished with an electronic digital humidistat to control the humidity in the cellar. The humidifier mounts directly onto the Wine Guardian unit and uses the common drain. The humidifier requires a water supply and no additional external power.
CAREFULLY FOLLOW THE INSTALLATIONS INSTRUCTIONS INCLUDED WITH THE HUMIDIFIER. REFER TO THE IN-
STRUCTIONS CONTAINED IN THE BOX FOR THE HUMIDISTAT.
CAUTION
to pump the water to a sink or
Overview of the Wine Guardian Unit
7
Refer to illustrations on page 8
Cabinet
for corrosion protection and an attractive, maintenance free appearance. Areas in contact with cold temperatures are lined with insulation to prevent condensation.
The cabinet and access doors are constructed of aluminum with a powder coated finish
Condensing Section
permanently lubricated, motorized impeller blower. This section also contains the compressor and the electrical controls. If the water cooled option is purchased, a heat exchanger is used in place of the condenser coil and blower.
Evaporator Section
same as above. The large evaporator coil face area eliminates condensate carry-over, reduces air pressure drop and optimizes heat transfer. A drain pan is located directly below the coil to capture condensate and is fabricated from aluminum to prevent rust and corrosion. The electric heating coil, if ordered, is factory installed between the evaporator coil and the blower, and is complete with contactor(s) and limit controls.
Electrical Controls
accessible through the condenser section. Wires are numbered and color coded to match the wiring diagrams.
Factory Tested
performance.
Filters
protect the coils from dust and dirt. These filters are washable and reusable.
– Nominal 25mm thick filters are provided on both the evaporator and condenser inlets to
Ambient air is circulated through the condenser section by a direct drive,
Cellar air is circulated through the evaporator section by another blower the
Most of the electrical components and controls are located in a separate area
All Wine Guardian units are factory run-tested and checked for operational
Humidity Option
onto the Wine Guardian without any additional electrical power wiring. It automatically adds moisture into the cellar by the evaporation of water over a distribution pad. A cellar mounted digital electronic humidistat automatically controls the amount of moisture added.
Internal Drain Trap
prevent air from being drawn back through the drain tube. This allows the drain pan to drain freely. No external trap is required.
Refrigerant Circuit
external equalizer, sight glass with moisture indicator, a filter dryer, an automatic low pressure switch, and a manual reset high pressure switch. For the low ambient option, an automatic pressure switch controls the operation of the condenser blower and a heating element is added to the compressor oil reservoir. See Refrigeration Illustration on next page.
Supply/return grilles
the evaporator and condenser sections. One grille is provided on an outlet. These are readily interchangeable with access doors to control and direct the airflow. These grilles may be used in the room on the end of the ducts in ducted systems.
The optional humidifier comes fully assembled and tested for field installation
-
Water condensate from the evaporator coil fills the trap and forms a seal to
– The factory charged circuit includes a thermal expansion valve with an
Powder-coated steel single direction grilles are provided for the inlets to
Overview Illustration of the Wine Guardian Unit
8
Refrigeration Illustration - Vapor Compression System
Wiring Diagram Model WG 40
9
Wiring Diagram Model WG 75
10
Wiring Diagram Model WG100
11
11
Wiring Diagram WG 175
12
Wine Guardian
Wine Guardian Dimensional Data
Model Number
WG4
WG75
WG100
WG175
Dimensions - Nominal - add 9.5mm for each grille
A - Width
mm
356
559
559
559
B - Height
mm
356
356
356
457
C - Length
mm
889
991
991
1092
D – Cond. discharge location
mm
540
591
591
660
E – Evap. discharge location
mm
137
137
137
137
F - Inlet opening width
mm
267
470
470
479
G - Drain outlet location
mm
502
552
552
619
H - Discharge opening width
mm
63
254
254
295
I - Inlet opening Height
mm
202
282
282
381
J - Location to wall
mm
368
419
419
457
Weight
kg
36.3
56.7
65.8
88.4
Refrigerant Charge – 134A
g
539
737
964
1417
13
Safety
F
DANGER
14
Before installing or maintaining the Wine Guardian Unit do the following:
1) Read these instructions.
2) Keep these instructions.
3) Heed all warnings.
4) Follow all instructions.
IMPORTANT
The equipment described in this manual uses electricity. When using
this equipment, be sure to follow the safety procedures outlined in the
Wine Guardian Manual.
Safety Message Conventions
Safety messages contained in this manual, DANGER, WARNING, and CAUTION are bold and highlighted in red for quick identification.
Danger
A Danger message indicates an imminently hazardous situation which, if not avoided, results in death or serious injury. Messages identified by the word DANGER are used sparingly and only for those situations presenting the most serious hazards.
IGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets.
Before opening panels turn off all power.
Use the Lockout/Tagout procedure.
Warning
A Warning message indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Following is a typical example of a Warning message as it could appear in the manual
WARNING
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Modification to the equipment may cause injury.
:
Caution
A Caution message indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
Following is a typical example of a Caution message as it could appear in the manual:
CAUTION
15
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard.
Read all of the installation instructions before installing the Wine Guardian unit.
Lockout/Tagout Procedure
1) Turn off the power switch (indicator light should be off)
2) Unplug the unit from the electrical outlet and cover the outlet to prevent accidently plugging in the unit.
Safety Considerations
The equipment covered by this manual is designed for safe and reliable operation when installed and operated within its designed specifications. To avoid personal injury or damage to equipment or property when installing or operating this equipment, it is essential that qualified, experienced personnel perform these functions using good judgment and safe practices. See the following cautionary statements.
Installation and maintenance of this equipment is to be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment.
Safety Hazards
Exposure to safety hazards is limited to maintenance personnel working in and around the unit. When performing maintenance, always use the Lockout/Tagout procedure, which is described in this chapter. Observe the maintenance safety guideline in the Wine Guardian Manual.
Electrical Hazards
Working on the equipment may involve exposure to dangerously high voltage. Make sure you are aware of the level of electrical hazard when working on the system. Observe all electrical warning labels on the unit.
Electrical Shock Hazards
All power must be disconnected prior to installation and servicing this equipment. More than one source of power may be present. Disconnect all power sources to avoid electrocution or shock injuries
.
Hot Parts Hazards
Electric Resistance heating elements must be disconnected prior to servicing. Electric Heaters may start automatically, disconnect all power and control circuits prior to servicing the unit to avoid burns.
18
Moving Parts Hazards
WARNINGS
16
The Motor and Blower must be disconnected prior to opening access panels. The motor can start automatically. Disconnect all power and control circuits prior to servicing to avoid serious injuries or possible dismemberment.
The fans are free-wheeling after the power is disconnected. Allow the fans to stop completely before servicing the unit to avoid cuts or dismemberment.
Rotating Fan Blades are present in the Wine Guardian unit. Sticking a hand into an exposed fan while under power could result in serious injury. Be sure to use the Lockout/Tagout procedure when working in this area or remove the power cord.
Equipment Safety Interlocks
There are no electrical safety lockouts installed within the unit. The power cord attached to the control box must be disconnected from the power sources prior to working on any part of the electrical system.
Main Power Switch
The main power switch is located on the side of the Wine Guardian unit. (See Overview Illustration on page 8) It shuts off the power to the unit.
Energy Type Electrical
Hazard ................................ Electrocution, electrical burns and shock
Magnitude .................................. 230 volts AC 1 phase, 50 cycles
Control Method ................. Disconnect power cord and On/Off Switch
Never reach into a unit while the fan is running.
Never open an access door to a fan while the fan is running.
Disconnect the power cord switch before working on the unit. The unit may have
more than one power source to disconnect.
Avoid risk of fire or electric shock. Do not expose the unit to rain or moisture.
Check weights to be sure that the rigging equipment can support and move the Wine
Guardian unit safely. Note any specific rigging and installation instructions located in the Installation section of the Wine Guardian Manual.
DANGER
All supports for the unit must be capable of safely supporting the equipment’s weight
and any additional live or dead loads encountered.
17
All supports for the unit must be designed to meet applicable local codes and
ordinances.
Do not remove access panels until fan impellers have completely stopped.
Pressure developed by moving impellers can cause excessive force against the access panels.
Fan impellers continue to turn (free-wheel) after the power is shut
off
.
CAUTION
Clean only with a dry cloth.
Never pressurize equipment above specified test pressure. See Wine Guardian
Specification Sheet
Do not use the Wine Guardian near water.
Do not block any supply or return air register or duct. Install in accordance
with the instructions in the Wine Guardian Manual. Do not defeat the safety purpose of the polarized or grounding type plug. A polarized plug has two blades with one wider than the other. A grounding type plug has two blades and a third grounding prong. The wide blade or the third prong is provided for your safety. If the provided plug does not fit into your outlet, consult an electrician for replacement of the obsolete outlet.
Protect the power cord from being walked on or pinched, particularly at the
outlet plugs, convenience receptacles, and the point where it exits the unit.
Only use attachments/accessories specified by the manufacturer.
Always operate this equipment from a 230 VAC, 1 phase 50Hz power sources
only.
Always ground the outlet to provide adequate protection against voltage surges
and built-up static charges
Refer all servicing to qualified service personnel. Servicing is required when
the unit has been damaged in any way. such as:
The power supply cord or plug is damagedLiquid has been spilled or objects have fallen into the unitThe unit has been exposed to rain or moistureThe unit does not operate4 normallyThe unit has been dropped
Installation
CAUTION
18
SHARP EDGES
RISK OF SERIOUS INJURY
Sharp edges are present inside the Wine Guardian system.
Pre-installation Test
Test the system before installing it to check for non-visible shipping damage.
To test the system:
Set the system on the floor or a sturdy level surface.Plug in the system.Press the on/off switch, control illuminates. This indicates the system has power.The built in timer prevents short cycling and keeps the system from turning
on right away. The system comes on and runs as long as the temperature of the space is above the thermostat set point. After several minutes, cold air comes out of the system from the evaporator section side and hot air comes from the condenser section. Listen for any unusual noise or vibration.
Air Flow Illustration
WARNING
19
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Modification to the equipment may cause injury or damage to the equipment
.
DANGER
This equipment is heavy. Place the unit on the floor or on a level and stable
surface that can support the full weight of the unit.
Do not modify the equipment, it may cause damage to the equipment and will
void the warranty.
Never place anything on top of the unit. Never block or cover any of the openings or outlets to the unit. Never allow anything to rest on or roll over the power cord. Never place the unit where the power cord is subject to wear or abuse. Do not use extension cords. Never overload wall outlets. Do not remove or open any cover unless the unit is turned off and the power
cord is plugged in.
Use only dedicated power outlet boxes of the correct capacity and configuration
for the unit model.
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard. Read all of
the installation instructions before installing the Wine Guardian unit
Planning the Installation
20
Addressing Items in the Planning Process
Where to locate the unit? Should it be built into the wall or mounted remote and
ducted into the cellar?
How to mount the unit?Decide where to locate the supply and return grilles in the room to achieve the
temperature gradient and circulation preferred.
Locate the electrical power outlet close to the unit, in cellar or out. Do not use
an extension cord!
Does the condenser heat exhaust need to be ducted away? Where to locate the thermostat?Where to run the drain line?Are all the parts here to complete the installation?
Performing a Pre-installation Check
Check for the proper installation of the electrical plug configuration.Check for the properly sized breaker.Is the cellar built with adequate insulation and vapor barriers?
Are ducts installed above the ceiling or in accessible places properly sized before
being covered?
Is enough space available around the unit for service and repair?
Locating the Unit
Wine Guardian units are typically installed indoors located near the cellar to minimize the duct runs. Each unit is provided with one entering or return air inlet and three possible supply air outlets for each of the evaporator and condenser sections. A maximum cumulative total length for both supply and return ducts (including bends) of 7.5 meters is recommended. If longer runs are needed use more than one supply opening to reduce the airflow in each duct by 1/2. See
Recommended Flexible Ductwork Sizing Chart on page 30.
Provide a 1 meter clearance around the unit for removal of grilles or ductwork, access to filters and unit maintenance. If the humidifier is used, provide access space in front of it for service.
Grilles
21
Each of the inlets and one evaporator outlet and one condenser outlet come from the factory with grilles over the openings. The grilles are removable. Remove the necessary grilles for installing ductwork between the unit and the cellar. If desired, use the grilles as wall grilles inside the cellar. The return air, or inlet, to the unit must connect to the return air outlet from the cellar. Any of the three supply air outlets on the unit can be used for the ductwork to the supply grille inside the cellar. The factory installed outlet grille can be relocated to any of the other two openings. The procedures below apply to both the evaporator and the condenser sections. In most cases, no ducts are installed on the condenser section because the unit is located in a mechanical or storage type space. If exhaust heat is undesirable use the grilles to install ductwork to move the heat outdoors or to another space. Also, use ductwork to direct condenser air noise away from occupants.
Reducing Noise from the Unit
Consider noise when locating the unit close to the cellar or an adjacent occupied space. A piece of 25 or 50mm dense rubber or Styrofoam with foil face in between the unit and the wall absorbs and reduces the noise from the unit. For air noise use better grilles or block the noise with a solid piece of wood or Styrofoam. Sound usually travels as a line of sight. Sound is reduced when it turns a corner, such as, passing through a bend in ductwork. If the unit is supported from a wall or joist, using a rubber pad under the unit will reduce vibration transmission.
Installing the Unit Outdoors
The Wine Guardian is NOT designed nor approved for direct outdoor installation. If it is located outdoors, it MUST be protected with a rain-proofed enclosure.
Mount it above the ground on a solid, waterproof base to protect the unit from
ground water.
Do not locate it where grass clippings or leaves can blow into the unit.
Keep the area around the unit clean and free of debris.
Protect from damage when the unit is located in a garage or unheated shed. In both
cases, the unit MUST have the low ambient controls built into the unit.
Double insulating ducts with exterior grade insulation is recommended to keep the ducts
dry and effective. Wine Guardian suggests installing one sized flexible duct inside the next larger size duct where ductwork is exposed.
Allow enough space at both ends of the unit to remove the grilles or ductwork and
allow access to the filters.
CAUTION
22
Mounting the Unit
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Check supporting structure for load bearing capacity to support the Wine Guardian.
All supports must be designed to meet applicable local codes and ordinances.
If in doubt, consult a qualified architect, engineer or contractor.
Note
Review the mounting illustrations on pages 32 and 33 before mounting the unit.
Floor Mounting
Mount the Wine Guardian on the floor but elevate it on frame with a plywood surface to keep it away from water. Allow adequate space for the external drain.
Wall Mounting
If the unit is mounted through the wall, adequately support it on both sides of the wall. Use floor or knee braces to transfer the load of the unit to the floor or wall.
Ceiling Mounting
Construct a structurally sound, level platform to place the unit on when hanging it from the ceiling joists. The Wine Guardian is NOT designed to be suspended from the top of the unit. Place the unit on a platform to ensure that the unit is supported on all for corners. Leave ad­equate space on the top of the unit to remove the access doors for service.
In all cases the unit must be level to within +/- 6mm end-to-end and +/- 3mm side-to-side for proper operation. Locate the unit as close to the wine cellar as possible to reduce the length of the duct runs. If possible, use short and straight ducting on all ductwork. The addition of 6mm thick rubber pads helps prevent the transmission of vibration and noise.
Installing the Condensate Drain Connection
The Wine Guardian unit provides dehumidification for the inside of the wine cellar. It cools the air down to the dew point corresponding to the temperature set point of the thermostat. If the vapor barrier of the wine cellar is poorly constructed or excess moisture is in the basement, the unit has to remove excessive amounts of moisture from the wine cellar. The moisture appears in the condensate drain of the unit.
Note
If moisture becomes excessive, install a room type dehumidifier to dehumidify the basement
so as to not overload your Wine Guardian.
Installing the Drain Line
23
The drain line must extend from the unit to an external drain or disposal site. Do not use drain tubing any smaller than 12mm inside dimension on the unit.
Splice the drain extension onto the drain outlet with a sort piece of 12mm copper tubing and secure with claps.
If no drain is available, use a bucket. Do not extend the drain below the rim of the bucket. Empty the bucket periodically.
The Guardian Unit is provided with a built-in drain trap. The drain trap creates a water seal to prevent air from backing up into the drain pan and causing the drain pan to overflow. Do not create secondary traps in the external drainline.
Allow enough height for the drain line to function properly. If draining into a nearby sink, the unit must be elevated higher than the rim of the sink in order for the water to drain by gravity. Install with a 10mm per linear meter. Do not tie the condensate drain line directly into the sanitary sewer system. See Accessories and Optional Equipment section for information about the Condensate Pump.
Priming the Drain Trap
The internal drain trap primes itself automatically once the unit has run for a period of time and after the unit cycles off. This is confirmed by water dripping from the drain.
Wiring the Unit for Power
DANGER
24
23
Electrical 240/1/50 Electric Heat Amps (Opt.) 4.4 Locked Rotor Amps 18.5 Humidifier Amps (opt.) 0.3 Compressor RLA 2.4 Crankcase Htr. Amps (opt.) 0.4 Condenser Fan Amps 0.7 Min. Circuit Amps (w/o opt.) 4.4 Evaporator Fan Amps 0.7 Refrigerant R-134-A Condensate Heater N/A System Charge 1lb. 3oz.
Total Unit Amps (w/o opt.) 3.8 Test Pressure 275psi
00 1 315-452-7400 * Fax: 00 1 315-452-7420
Model No. WG40
Serial No.
Air Innovations, 7000 Performance Drive, North Syracuse, New York 13212
ELECTRICAL SHOCK HAZARD
RISK OF SERIOUS INJURY OR DEATH
The electrical outlet and wiring installation must meet the national and local
building codes.
DO:
Match the electrical outlet to the plug provided on the Wine Guardian.
Provide dedicated circuit and wiring for the system.
Match the wiring and breaker size to the rated load as shown on the serial
DO NOT:
 
plate and in this guide. See sample serial plate illustration on the following page.
DO NOT MODIFY THE PLUGS IN ANY WAY! Do not use extension cords.
Installing the Thermostat and
IMPORTANT
Wine Guardian units are supplied with 15 meters of Cat 3, 6-wire twisted pair
communication cable with RJ-11 connectors. Failure to use this type of communication
cable WILL cause product damage and WILL void any equipment warranty.
Installation instructions should be followed CAREFULLY as improper splicing and/or
joining of twisted pair cables can ca use equipment failure .
1. Disconnect the communication cable from the side of
the Wine Guardian unit and the Remote Interface Controller.
a) Install the communication cable within the wall and/or ceiling structure of the wine cellar to the desired controller mounting location.
b) Mount the remote interface controller on a solid surface away from doors, corners, air outlets, drafts or heat generating equipment. Do not mount the Remote Interface Controller directly on an outside wall or wall adjacent to a boiler room.
25
Communication Cable
The Wine Guardian Remote Interface Controller is a combination temperature and humidity controller with single stage cooling, heating and humidifier control. Each Wine Guardian unit is supplied with a Remote Interface Controller and 15 meters feet of communication cable. It is wired at the factory for testing prior to shipment.
In most applications the Remote Interface
Controller will be mounted within the wine cellar. The remote interface controller can also be mounted directly outside of the wine cellar or in any other room of the home or building. When mounted outside of the wine cellar, a remote sensor kit must be purchased and installed within the wine cellar. See below for remote sensor installation details.
Mounting the Remote Interface Controller
2. Remove the back plate of the controller and mark the
mounting points at the desired location. (Fig. 2)
a) Mark the location of the communication cable connection as this area will require sufficient clearance for instance, a 3.8cm hole in the wall for flush mounting of the back plate. (Fig. 3)
3. Drill two (2) .32cm holes and insert anchors (provided)
within the mounting surface. Anchors may not be required if securing to a wall stud or racking system.
4. Plug in the communication cable to the back of the
Remote Interface Controller backing plate. (Fig.4)
a) Attach backing plate to wall using the two screws
provided with the system. (Fig.5)
5. Re-install plastic face plate on to backing plate.
6. Re-attach the communication cable to the side of the
Wine Guardian cooling unit. (Fig.6)
26
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Installation of the Wine Guardian Remote Sensor
1. Disconnect the communication cable from the side of
the Wine Guardian unit and the remote sensor. Install the communication cable within the wall and/or ceiling structure of the wine cellar to the desired controller mounting location.
2. Mount the Remote Sensor on a solid surface away from
doors, corners, air outlets, drafts or heat generating equipment. Do not mount the Remote Sensor directly on an outside wall or wall adjacent to a boiler room. Use a piece of foam insulation behind the sensor to insulate it from a hot or cold surface. The recommended height is
1.2 to 1.5 meters above the finished floor.
3. Remove the sensor cover plate by removing the two
allen head screws at the top of the cover using the allen head wrench provided in the kit.(Fig.2) Mark the mounting points at the desired location within the wine cellar. Also mark the location of the communication cable connection as this area will require sufficient clearance, for instance 3.8cm hole in the wall for flush mounting of the sensor plate.
Fig.2
Important A splitter device has been supplied within the Remote Sensor kit. The splitter device must be mounted at the WG unit as shown. DO NOT mount the splitter device at the back of the Remote Interface Controller or to the back of the Remote Sensor as this WILL cause component or system damage.
27
The Remote Sensor is a combination temperature and humidity sensor only. It is designed to be mounted within the wine cellar and can be used in combination with the Remote Interface Controller or up to three additional Remote Sensors to read and control multiple areas within the wine cellar.
Mounting the remote sensor
Fig.1
4. Drill two (2) .32cm holes and insert anchors (provided) within the mounting surface. Anchors may not be required if securing to a wall stud or racking system. (Fig.3)
5. Plug in the communication cable to the back of the Remote Sensor and attach to the wall using the two screws provided in the kit. (Fig.4)
6. Plug the Remote Sensor cables into the splitter device at the WG unit along with the communication cable for the Remote Interface Controller. (Fig.5)
If using multiple Remote Sensors in one wine room continue to mount the remaining sensors before installation of the sensor cover plates. When multiple sensors are used the sensor jumper position must be adjusted in order for proper averaging of temperature and humidity readings. See page 27 for jumper set up.
Fig.3
Fig 4
Fi
Fig.5
Fig 6
28
Joining Communicati
Joining Communication Cable
If using multiple Remote Temperature/Humidity sensors in your application, refer to the photos showing the need to change the jumper locations internal to the control board on each remote sensor (up to 3 maximum).
For the control to average all of the sensors utilized (if more than one), the jumper must be in different positions on the pins.
As you can see, there are three pin settings. To access the jumper:
1. Remove the two-set screws holding on the plastic cover. This procedure allows the control to go to each remote sensor in sequence to average. Failure to perform this procedure will result in the system reading only one sensor and not the average of multiple sensors.
NOTE: If multiple sensors control the WG unit, change factory default in configuration setting 10 to “averaging.” You will need access code from Air Innovations service to use in configuration 8 to reach configuration 10.
Jumper position 1
Jumper position 2
Jumper position 3
Important
Wine Guardian cooling systems are supplied with 15 meters of 6 wire, Cat 3 twisted pair communication cable with RJ11 type connectors. Caution must be taken when connecting two lengths of communication cable (splicing) to ensure uniform wire color before and after splice. An RJ11 Modular 6 wire STRAIGHT THROUGH type coupler is the ONLY coupler approved for splicing Wine Guardian twisted pair communication cable.
29
Changing Jumper Positions (Averaging readings from Remote Sensor)
How to:
Turn system on/off
Press the On/Off button once. Note: There
is a five (5) second time delay before the system turns on or turns off.
Change Temperature
Press the “Up” arrow once. The display will
show the existing temperature set point.
Press the up or down arrow buttons to adjust
the temperature to the desired set point.
Change Humidity
Press the “Up Arrow” once. This display
will show the existing temperature set point.
Press the “Mode” button once to display the
Humidity setpoint.
Press the “Up or “Down arrows to adjust
the humidity to the desired set point. Note – a Wine Guardian humidifier must be installed and setting six (6) set to “1 or “2” before the controller will let you change percent humidity.
.
Change Mode -­Cooling/Heating/Auto
Press the “Mode” button once to display the
“Set” function at the bottom of screen. The
existing mode will display next to the word “Set” at the bottom of the screen.
Press the mode button again to scroll
through settings for “Cool” (cooling only), “Heat” (heating only) or “Heat Cool”
(Auto).
STANDARD CONTROLLER FUNCTIONS
Humidity
Temperature
Alarm Indication Area
Mode Area
Up Button
Down Button
Mode button (right side)
On/Off (left side)
30
Settings – Press and hold the “Mode” button for five (5) seconds to access the following
Deg F or Deg C
Setting 1
Press the “Down” arrow to change temperature
from Deg F to Deg C.
Press the “Up” arrow to change temperature from
Deg C to Deg F.
Low temperature alarm set point
Setting 2
Press “Mode” button to advance to Setting 2. Press the “Up or “Down arrow buttons to adjust
to the desired set point. Factory default is 10 Deg. C..
High temperature alarm set point
Setting 3
Press “Mode” button to advance to Setting 3. Press the “Up” or “Down arrow buttons to adjust
to the desired set point. Factory default is 18 Deg C.
Low humidity alarm set point
Setting 4
Press “Mode” button to advance to Setting 4. Press the “Up” or “Down arrow buttons to adjust
to the desired set point. Factory default is 5%.
High humidity alarm set point
Setting 5
Press “Mode” button to advance to Setting 5. Press the up or down arrow buttons to adjust to the
desired set point. Factory default is 95%.
Add or remove humidifier
Setting 6
Press “Mode” button to advance to Setting 6. Press the up or down arrow buttons to adjust to the
desired set point. Factory default is zero (0).
Zero (0) = No humidifier One (1) = Stand-alone remote mounted humidifier Two (2) = Integral Wine Guardian mounted humidifier
Fan AUTO or ON
Setting 7
Press “Mode” button to advance to Setting 7. Press the “Up or “Down arrow buttons to adjust
number to the desired set point. Factory default is zero (0).
Zero (0) = Auto – fan only turns on when there is a call for cooling or heating One (1) = Fan On – fan remains on continuously
31
settings.
Advanced Settings--
Special access required. Contact Wine Guardian Service Department for access code
Setting 8
Press “Mode” button to advance to Setting 8. Press the up or down arrow buttons to adjust
number to the access code. Press “Mode” button to continue onto setting 9 through 19.
Compressor anti-short cycling time
Setting 9
Press “Mode” button to advance to Setting 9. Press the “Up” or “Down arrow buttons to adjust
to the desired time in one (1) minute increments. Maximum is 10 minutes, minimum is 0 minutes.
Compressor anti-short cycling time is the amount of allowable time between compressor stop and restart. Rapid start/stop of compressors can cause premature failure. Factory default is 5 minutes.
WINE GUARDIAN DOES NOT RECOMMEND SETTINGS LOWER THAN FACTORY DEFAULT.
Set up remote sensor or thermostat
Setting 10
Press “Mode” button to advance to Setting 10. Press the “Up or “Down arrow buttons to adjust
to the desired setting.
rS = Remote sensor rI = Remote interface LI= Local interface – Through-the-wall unit only A = Averaging – Jumper position within sensors must be adjusted. See page 27.
Room sensor calibration
Setting 15
Press “Mode” button to advance to Setting 15. Press the “Up or “Down buttons to adjust to the
desired set point. Maximum setting is +2°C, minimum setting is -2°C. Factory default is zero (0). Sensor calibration set point changes the actual display reading (temperature only) by the value of this setting.
Example: Sensor reading = 13 Deg C Setting 15 set to +2 Display reading = 15 Deg C
32
Differential temperature adjustment
Setting 16
Press “Mode” button to advance to Setting 16. Press the “Up or “Down buttons to adjust to the
desired set point.
This setting changes the system/compressor. Turn on temperature above set point. Factory default is set to 1°C. Example: Sensor reading = 13°C Setting 16 set to +1°C System/compressor turns on at 14 Deg. C.
Deadband setting
Setting 17
Press “Mode” button to advance to Setting 17. Press the “Up or “Down buttons to adjust to the
desired set point.
This setting is the minimal allowable temperature difference between heating and cooling set points. Maximum is 3°C, minimum is 1°C. Factory default is set to 1°C
Test mode setting
Setting 18
Press “Mode” button to advance to Setting 7. Press the “Up” or “Down buttons to adjust to the
desired set point. When set to one (1) the controller will automatically turn on all outputs with the exception of electric heat. Factory default is zero (0).
Zero (0) = Off
One (1) = On
System Selection
Setting 19
DO NOT CHANGE
33
Alarm Codes
High temperature alarm
Press the “Up or “Down arrow once to change screen from alarm to normal Temperature and
Humidity indication. “Hi Temp” will remain on
screen until temperature falls below the High Temperature Alarm set point (Setting 3).
Low temperature alarm
Press the “Up or “Down arrow once to change screen from alarm to normal Temperature and
Humidity indication. “Lo Temp” will remain on
screen until temperature rises above the Low Temperature Alarm set point (Setting 2).
High humidity alarm
Press the “Up or “Down arrow once to change screen from alarm to normal Temperature and
Humidity indication. “Hi Hum” will remain on screen
until humidity falls below the High Humidity Alarm set point (Setting 5).
Low humidity alarm
Press the “Up or “Down arrow once to change screen from alarm to normal Temperature and Humidity indication. “Lo Hum” will remain on screen until humidity rises above the Low Humidity Alarm set point (Setting 4).
Open Fault
Press the “Up or “Down arrow once to change screen from alarm to normal Temperature and Humidity indication.
THIS ALARM FORCES THE SYSTEM TO SHUT DOWN. “Alarm” will remain on screen until
the High Pressure reset switch has been reset. See the trouble shooting guide page 47 for “Instructions to Reset High Pressure Switch”
34
Installing the Ductwork
Model Inlet Outlet
Single Double
WG40 200 200 200 150
WG75 250 200 250 150
WG100 250 250 250 200
WG175 300 300 300 300
Condenser (heat rejection) Coil
Recommended Insulated Flexible ductwork Sizing Chart
Inlet (Return Air)
Outlet (supply air)
Single
200
250
Double
150
150
200
250
250
300
Evaporator (cooling) Coil
Notes: 1. The above references izes are internal diameter in mm.
2. If a single supply is used out of the unit but then splits into two (2) ducts, the above size
recommended for double is used after the split.
35
Use ductwork to connect the unit to the supply and return outlets in the wine cellar. Use only insulated ductwork to minimize cooling loses, prevent sweating, and to reduce noise.
Use ductwork on the condenser section to redirect or absorb sound, to bring in outside air to the unit inlet, and/or to exhaust the hot air out of the ambient space.
NOTE
Do not exceed a total of 7.5 meters for each length of ductwork run.
CAUTION
RISK OF DAMAGE TO EQUIPMENT
Avoid crimping the flexible ducts. This chokes down the inside area and reduces the airflow
causing the unit to operate erratically.
Be sure all ducts and surface in contact with the airflow are insulated
and have a vapor barrier on the outside surface.
Location of Supply and Return Grilles
Locate the supply and return grilles inside the cellar to create an airflow pattern that maximizes air circulation in the room. Avoid short circulating of the air.
Do Not:
Install the return air grilles directly on the floor as the grilles will collect dust from the
floor.
Locate the supply or return air grille where it is blocked by bottles, boxes or cases.
Locate the supply air grille where it blows directly on the thermostat.
Relocating a grille on the Wine Guardian
1) Remove the fasteners from the grille.
2) Remove the fasteners from the access door panel to be replaced by the grille.
3) Relocate the outlet grille to its new location and secure in place using its fasteners.
4) Replace the access door panel where grille was located.
28
Uninsulated ducts and surfaces cause bare exposed metal surfaces to sweat,
36
further degradation of the insulation and a loss of equipment cooling capacity.
General Duct Recommendation
 Support the flexible duct often to prevent sags or bends.  Stretch the duct to make for a smoother interior for less air resistance. For a 90 degree bend, insert a metal elbow inside the flexible duct to avoid crimping. Do not squeeze or reduce the inside diameter of the ducts. This restricts the
airflow.
Use short and straight ductwork. Review the configuration schematic on the Overview Sketch on page 8 for
information about which panels are available for duct connections and service.
Remove the panels or grilles from the openings to connect the ductwork. Check that all the fan blades move freely. Check for loose foreign objects in any of the air paths. Connect the round flexible ducts to the Wine Guardian using the duct collars
provided with the duct accessory kit.
Pull the outer plastic wrapping and insulation away from the end of the duct to
expose the reinforced inside duct liner.
Use tie straps of clamp around the inside liner to fasten the duct collar.
Do not clamp around the outside insulation. It compresses and loosens over time.
Secure the duct collar to the unit using the screws provided. Be careful not to damage
or bend the gasket.
Not Using Ductwork
The supply and return grilles stay on the unit if no ductwork is used.
The supply and exhaust grilles may be relocated to any of three openings. (Refer to the manufacturers installation instructions located in the box of flexible ductwork).
Using Ductwork
Cold Air to/from Wine Cellar
Remove supply air grille or access door panels to install ductwork between the Wine Guardian unit and the cellar.
Connect the supply air ductwork from the cellar to the supply air inlet at the Wine Guardian unit.
Connect the return air ductwork from the cellar to the return air inlet at the Wine Guardian unit.
Warm Air to/from Condenser
Connect ductwork on the condenser to direct heat and the air noise away from occupants.
Connect ductwork to another space within the basement, a building or to the outdoors if the heat being exhausted is undesirable.
33
Typical Mounting Arrangements
Remote Mount on Floor
Condenser inlet and exhaust – to outside
Ceiling Mounts
Through-Wall ceiling mount with dual supply
Outside Mounts
Outside Remote Mount
The following illustrations are suggested mounting arrangements. These illustrations are not intended to be complete and detailed installation drawings. For questions or help regarding installation, call customer service at or 00 1 315-452-7400 fax 00 1 315-452-7420 or email (info@wineguardian.com) a sketch of the proposed area where the unit is to be installed.
Duct Adapter Sizes
UNIT SIZE
LOCATION
ROUND
OPENING SIZE
FLANGE SIZE
DUCT SIZE
WIDTH
HEIGHT
WIDTH
HEIGHT
1/4
INLET
202
267
283
295
346
1/4
OUTLET
202
203
283
244
346
1/2 & 1
INLET
252
346
283
549
346
1/2 & 1
OUTLET
253
254
283
295
346
1
DUAL OUTLET
202
254
283
295
346
2
INLET
303
479
381
549
448
2
OUTLET
303
295
381
346
448
2
DUAL OUTLET
252
295
381
346
448
38
Ducting Options
Single Outlet Duct Installation
Dual Outlet Duct Installation
Inspection and Start-up Checklists
39
Receiving and Inspecting
Unit received undamaged
Unit received complete as ordered including accessories
Handling and Installing
Unit mounted on solid level surface
Sufficient space allowed for access to unit and accessories Proper electrical service
provided
Hot water provided to humidifier
Drain lines and trap installed properly
Ductwork, fittings and grilles installed properly
Al
l cold duct surfaces insulated
Low ambient control included if freezing condition present No obstructions to air
flow to condenser
Starting-up the Unit
General visual inspection looks good All wiring connections checked
All ducts, grilles and panels in place
Start unit
Check ducts and connections for air leaks
Balance air distribution
Confirm condenser airflow is unrestricted
Verify cooling and heating operation
Check for excessive noise or vibration
CAUTION
Rick of personal injury.
Starting-up and Operating the Wine Guardian
40
Now that the installation is complete, it’s time to start the unit up. Check to make sure all ductwork
and electrical connections are secure. Replace all panels which were removed during installation. Check that all of the openings in the unit
are covered with a blank panel, a ductwork connection or a grille.
Cover all openings of the unit to prevent a hand or finger from access inside
the unit.
Turn on the Unit
Plug in the unit. Turn-on the rocker switch on the side of the unit. The rocker switch lights up to indicate power to the unit. The unit may not come on right away due to the timer built into the circuiting to prevent short-cycling.
Testing the Fan
(Configuration Setting 7)
Factory default is AUTO FAN operation. You change into setting 7 to change from “AUTO” to “ON.
ON means the fan runs continuously and indicates that the power is on and the control circuit is energized and operating.
AUTO means the fan runs only when the thermostat is calling for cooling, heating, or the optional humidistat is calling for humidification.
Running the Unit
Check unit to confirm the compressor is running, such as the hum of the compressor
or cool air leaving the unit.
Check for any unusual noise or vibration, such as clanking or rubbing
.
Initially, the unit may run continuously for several hours, up to a day or more, while it lowers the cellar temperature. Once the unit reaches the set point temperature, it shuts off and starts to cycle on and off as it continues to lower the bottle temperature to the set point. The cellar air reaches set point before the bottles. If the cellar temperature started at 24°C, the supply air temperature discharged from the unit will probably be 8°C to 11°C colder. As the cellar temperature decrease to 13°C, the supply temperature differential decreases 6 to 7°C colder.
NOTE
The remote interface controller will show a “Hi Temp” fault until the wine cellar temperature
falls below 18°C. See page 32 for Hi Temp Alarm details.
Cycling the Unit
41
The fans continue to free-wheel for several minutes when the unit cycles off. This is normal.
If the unit is furnished with a low ambient control, the condenser fan also cycles on and off during cooling. This maintains the head pressure on the compressor under low ambient conditions, and is normal. The bottom of the compressor stays warm even when the unit is off to keep the lubricating oil warm and separated from the refrigerant.
Setting the Thermostat
Normal settings are between 12 and 14°C. If the optional heating coil is furnished, enter a separate temperature setting to maintain the lower setting. To prevent the unit from short cycling, the setting between heating and cooling cannot be closer than 2°C.
Regulating the Wine Cellar Temperature
Wine cellars have a natural temperature gradient of approximately 3°C between floor and ceiling. To increase or decrease the temperature in various zones, change the air flow patterns.
To keep the entire wine cellar at the same temperature, set the thermostat to run the supply fan continuously and not just when the cooling is operating. Set Fan switch to ON instead of AUTO.
NOTE
To monitor the Cellar Temperature, place thermometers in various locations in the
cellar to monitor the temperature zones. Change the temperature in various zones by
shifting the air flow patterns.
Changing the Air Flow Direction
The grilles furnished with Wine Guardian are single directional. Rotate the grilles to change the direction of the air flow.
When using multiple supply ductwork balance the air flow between the ductwork. If too much air flows though one duct but not enough air flows from the other duct, install a damper or other restriction into the duct with too much air. That will force more air to flow out the other duct.
Maintenance
WARNING
DANGER
CAUTION
CAUTION
42
General
BEFORE PERFORMING MAINTENANCE ON THE UNIT, READ AND UNDERSTAND THE SAFETY
INFORMATION CONTAINED WITHIN THE SAFETY CHAPTER OF THE WINE GUARDIAN
MANUAL.
HIGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets. Turn off all power. Use the Lockout/
Tagout procedure before opening panels.
SHARP EDGES
RISK OF SEROUS INJURY
Sharp edges are present on the fan wheels, housing, fins and coils.
Maintenance on Wine Guardian units requires working with high voltage and
sheet metal with possible sharp edges. Only qualified personnel should
perform maintenance. Some tasks require knowledge of mechanical and
electrical methods. Make sure you are familiar with all hazards, general safety
related procedures, and safety labels on the unit.
EXPOSURE TO MICROBIAL GROWTH (MOLD) CAN CAUSE SERIOUS HEALTH PROBLEMS
Standing water in drain pans promote microbial growth (mold) that cause unpleasant odors and serious health-related indoor air quality problems. If mold is found, remove it immediately and sanitize that portion of the unit.
The Wine Guardian is designed for minimum maintenance. The refrigerant system is hermetically­sealed and requires no maintenance. The fans are permanently lubricated and require no maintenance. Some maintenance to the unit may be required due to dust or dirt in the air stream.
Cleaning the Filters
43
The evaporator and condenser coils are provided with reusable, washable air filters. The filters protect the coils from becoming coated or plugged by dust. Frequency of cleaning the filters is based on the amount of dust or dirt generated in the cellar or basement.
1. Remove the grille or duct collar on the inlet end of the unit.
2. Remove the filter covering the face the coil.
3. Wash it under warm water.
4. Shake off excess water.
5. Inspect and clean the face of the coil.
CAUTION
SHARP EDGESRISK OF SERIOUS INJURY
Sharp edges are present on the fins and coils.
6. Reinstall the filter.
7. Replace the grille or duct collar.
Cleaning the Condensate Drain System
The condensate drain system traps dust and dirt. Clean the drain system once a year.
1. Shut off the rocker switch and unplug the unit.
2. Remove the grille or duct on the evaporator inlet.
3. Remove the filter and inspect the drain pan under the coil.
4. If drain pan appears soiled, pour some hot water mixed with liquid bleach (diluted solution) along the length of the pan to flush the dirt down the drain tube.
5. Continue this treatment until the drain appears clean and free of dirt.
6. Reinstall filter and grille or duct collar.
7. Plug in the unit and restart.
Cleaning the Humidifier (optional)
If the unit was furnished with a humidifier it requires periodic maintenance. Follow the instructions in the humidifier guide.
Heating Coil Option
The heating coil is located between the evaporator coil and blower inside the transition duct. It contains the heating element and high temperature limit switches. The heating coil is wired to work in conjunction with the thermostat. Since the thermostat prevents the heating and cooling circuits from being energized at the same time, no additional power wiring is needed. We do recommend using the AUTO mode on the thermostat so it can switch from heating to cooling automatically. If using either the heat or cool only mode, the thermostat will not switch automatically.
No additional maintenance is required for the heating coil. To test the heating coil operation,
44
set the thermostat on HEAT and set the temperature above the cellar temperature. The supply air temperature should rise above the return air temperature by an amount shown in the specifications.
Low Ambient Option
The purpose of the Low Ambient Option is to protect the compressor and refrigerant system. It has two distinct components, a crankcase heater to keep the oil in the compressor warm and prevent slugging on system start-up and a head pressure control to cycle the condenser fan on and off automatically to maintain system head pressure.
To confirm that the system is working, feel the bottom of the heater when the compressor unit has cycled off. When the unit starts, the condenser fan does not start at the same time as the compressor. The condenser fan starts after the head pressure has built up. As the unit is running the condenser fan cycles off and on while it holds the head pressure within a fixed range. The amount of cycling (frequency and duration) depends on the air temperature. The colder the air, the more frequent the cycling and with a longer duration.
Maintenance Schedule
Monthly
(or quarterly depending on experience with individual cellar)
Check filter and drain trap – clean if needed. Check for noise or vibration.
Check for short-cycling of the unit – a turning on and off of the compressor unit
more than either (8) times/hour.
Yearly
(in addition to monthly)
Replace filters if worn or plugged beyond cleaning. Check evaporator and condenser coils for dirt – use a vacuum with a brush
attachment to clean the coils.
Clean condensate pan under the evaporator coil by flushing. Be careful to keep the
drain pans clear of any and all debris.
Inspect cabinet for corrosion or rusting – clean and paint. Inspect for dirt buildup on or inside the unit. Clean unit by vacuuming or wiping it
down.
Check for loose insulation, fasteners, gaskets or connections. Check the wiring connections and integrity or cords. Examine ducts for any cracks or breach. Check fan and solenoid on humidifier. Replace humidifier pad (if used).
Troubleshooting
Typical Start-up Problems
Possible Cause
Loose, improper or defective thermostat or humidistat cable
Solution
Check power, and thermostat or humidistat cable
Incorrect thermostat or humidistat (optional) settings.
Check the thermostat and optional humidistat setup for the application.
Changed settings on the thermostat
A common problem is not waiting long enough for the internal timers to complete their timed delay.
Power Switch Light is Off
Possible Cause Solution
Switch not on Turn on switch No power to outlet Check circuit breaker and wiring Unit not plugged in Plug in the unit
Power Switch Light is On and the Thermostat Light is Off Possible Cause Solution
No power to thermostat Check Main Control Board for L.E.D. indication
Check wiring for loose, broken or frayed connections
Check wiring for proper splicing Remote Interface Controller may be faulty
Power Switch Light is On and the Thermostat Light is On
Possible Cause Solution
Thermostat is not set up properly Check thermostat set up in the guide. Press fan ON switch to check evaporator fan only
45
WARNING
BEFORE PROCEEDING, READ AND UNDERSTAND THE SAFETY INFORMATION CONTAINED IN
THE SAFETY SECTION OF THE WINE GUARDIAN MANUAL.
IMPORTANT
This section is intended as a diagnostic aid only. For detailed repair or parts replacement
procedures, contact a qualified service company. Check the following table for some solutions
before calling a service technician.
Unit Does Not Start-up
Unit is Operating and Blows Evaporator Air, but the Supply Air is
Possible Cause Solution
Thermostat not set up properly Check thermostat setup in the manufacture’s
thermostat guide
Compressor not operating High pressure switch open (button up) (see
below)
Condenser airflow is blocked Remove blockage
Clean filter and coil (if needed)
Head Pressure (HP) switch is open Reset HP switch See reset instructions on
page 49
Cellar Temperature too cold (below 11°C) when unit is running
Possible Cause Solution
Thermostat set too low on cooling Reset thermostat to higher cooling temperature
Heating coil (optional) not operating Check for temperature rise across coil Thermostat set too low on heating Reset thermostat to higher heating
temperature
Thermostat not controlling temperature Thermostat mounted in bad location
Cellar Temperature is too cold (below 11°C) when unit is not running
Possible Cause Solution
Too much heat loss to adjacent spaces Increase insulation around the ductwork Check and clean filter and coil Coil frozen – shut off unit for two hours
Cellar loads are too high Install additional insulation Replace with larger sized unit
Problems Controlling Cellar Temperature
Problems are occurring even though the unit seems to be fully operational – evaporator fan blows air into the cellar and compressor and condenser fan runs.
46
Not Colder Than the Return Air from the Cellar
Problems Controlling Cellar Humidity
Humidity too low or supply air is too cold, without optional humidifier
Possible Cause Solution
Not enough evaporator airflow Remove blockage in supply or return ductwork Check and clean filter and coil Coil frozen – shut off unit for two hours
Defective Thermal Expansion Valve If under warranty call for service If not under warranty call a refrigeration Temperature set too cold technician Raise temperature set point at thermostat
Humidity too low, without optional humidifier
Possible Cause Solution
No moisture being added to cellar Add Wine Guardian humidifier or a room humidifier
Humidity too low with optional humidifier
Possible Cause Solution
Humidifier not operating Check wiring for loose, broken or frayed connections Check humidistat set up Check for water flow & solenoid valve operation
Humidifier operating Check for water being hot Check drip pad – replace if scaled No vapor barrier around cellar
Humidity too high when unit is running but not cooling
Possible Cause Solution
Compressor not operating Check and reset high limit switch Clear blockage of condenser airflow
Ambient temperature is too high Reduce temperature or draw condenser air from another space
47
Humidity too high when the unit is not running
Possible Cause Solution
Unit needs to run to dehumidify Run unit. Seal openings around doors (gasket and
sweep)
Humidity too high when unit is running and cooling
Possible Cause Solution
Too much moisture in cellar Poor vapor barrier installation
Humidifier malfunction refer to the humidifier instructions.
Add dehumidifier to surrounding space
Unit operates but the power switch light is not ON
Possible Cause Solution
Bulb is burned out Replace bulb
Unit is leaking water
Possible Cause Solution
Piping from unit to drain is trapped Re-pipe to remove external traps Trap plugged Clean trap
Condensate pan plugged Remove blockage and clean Unit not level Level with shims
48
Other Miscellaneous Problems
Unit is running properly , but the sound of the uni t is obj ectionable
Possible Cause Solution
Noise is from airflow Redirect airflow
Add baffles
Add insulated ductwork
Noise is from unit Add sound baffle between unit and occupied space
High Pressure Switch has Shut the Unit Down
49
Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system. This switch shuts the compressor and condenser down if the head pressure in the system is too high. It is intended to protect the compressor. Restricted airflow through the condenser is the most common reason for the pressure to become too high. This can be caused by dust covering the filter or an obstruction blocking the airflow in the duct or grille
.
Possible Cause Solution
Head Pressure in unit is too high because Remove the obstruction in the duct or grille or an obstruction is restricting air flow clean the filter. Then restart the unit after
resetting the using the high pressure switch.
Instructions to Reset High Pressure Switch
Remove the access panel, grille or duct collar at the condenser opening labeled “High
Press. Manual Reset Switch ----- “Remove panel or grille to access”
Locate the high pressure switch near the compressor (a cylindrical device piped into the
refrigeration system with two wires a red button on the top).
Push in the button until it locks into position.Push the rocker switch to restart the unit.
Advanced Troubleshooting
Evaporator Coil is Freezing
Possible Cause Solution
Charge too low Check sight glass
Check for leaks Add refrigerant
TXV malfunctioning Repair or replace
High Pressure Switch Keeps Tripping Even After Checking for Obstructions and Dirty Filters/Coils
Possible Cause Solution
Condenser fan not operating Repair or replace Defective switch Replace
Unit Cycles on and off more than 8 times/hr
Possible Cause Solution
Thermostat malfunctioning Check the thermostat guide for
thermostat information
Low suction pressure Check low pressure switch
Check pressure and adjust superheat
High Pitched or Loud Rubbing Noise , Clanking or Vibration
Possible Cause Solution
Fans loose or malfunctioning Repair or replace Excessive compressor vibration Replace
TXV malfunctioning Repair or replace
Replacing the Blowers
When replacing the fan or motor, replace the fan and motor as a unit. Do
not remove the motor from the impeller wheel.
IMPORTANT
THIS SECTION IS INTENDED FOR QUALIFIED REFRIGERATION SERVICE TECHNICIANS ONLY.
THE TECHNICIAN SHOULD REPEAT ALL OF THE PREVIOUS TROUBLESHOOTING STEPS
BEFORE
TAKING ACTION ON THESE MORE TECHNICAL SOLUTIONS.
Appendix
51
Warranty Procedure
The Wine Guardian unit serial number is noted on all packing lists and bills of lading and, along with the shipping date, is kept on file at Wine Guardian for warranty purposes. All
correspondence regarding warranty must include the model number and serial number of the unit involved. Note that the warranty is null and void if the serial number on the unit or
compressor is altered, removed or defaced. All inquires or correspondence regarding warranty should be handled in accordance with the “Warranty” and directed to:
Wine Guardian
7000 Performance Drive
North Syracuse, New York 13212 USA
Attn: Service Department
001 315 452-7400 Phone
001 315 452-7420 Fax
This procedure includes but is not limited to:
Obtaining authorization from Wine Guardian prior to incurring any charges for repair or
replacement under warranty.
Returning prepaid within 30 days any and all defective parts.

Loading...