Window Master WSC 310, WSC 320 Installation Instructions Manual

Page 1
UK
  +44 (0) 1536 614 070
Other markets
  +45 4567 0300
WSC 3xx iinstall 1711-Firmware v126 - UK ©WindowMaster 2015, 2017 ®WindowMaster is a registred trademark used under the license by WindowMaster International A/S WindowMaster International A/S, Skelstedet 13, DK-2950 Vedbæk
WSC 310 & WSC 320
Plus versions
Installation instruction
CompactSmoke™
(Version 1711 – from firmware version 1.26 (main card) &
from version 1.06 (motor line card))
Save this installation instruction to the end user
Page 2
2
1 Safety information ........................................................................................................................................................ 4
1.1 Safety ................................................................................................................................................................ 4
1.2 230V AC ............................................................................................................................................................ 4
1.3 Back-up batteries .............................................................................................................................................. 4
1.4 Application ......................................................................................................................................................... 4
1.5 Cable routing and electrical connection ............................................................................................................. 4
2 Structure of the smoke panel ...................................................................................................................................... 5
3 Variants of panels ........................................................................................................................................................ 6
3.1 CompactSmoke™ Plus versions ....................................................................................................................... 7
3.2 Max numbers of actuators per motor line and panel
............................................................................................. 7
4 Accessories and spare parts ...................................................................................................................................... 8
5 Technical data .............................................................................................................................................................. 9
6 Mounting ..................................................................................................................................................................... 11
7 Installation .................................................................................................................................................................. 11
7.1 Cable routing ....................................................................................................................................................11
7.2 Cables into housing ..........................................................................................................................................11
7.3 Connection of safety earth wire and 230V AC ..................................................................................................11
7.4 Installation of the break glass unit, ventilation keypad and smoke detector .....................................................11
7.5 Assembly instructions .......................................................................................................................................12
8 Cable dimensioning ................................................................................................................................................... 12
8.1 Maintaining the cable functions ........................................................................................................................12
8.2 Max. cable Length ............................................................................................................................................12
8.2.1 Formula for the calculation of the maximum actuator cable length ............................................................. 12
8.2.2 Max cable length – ±24V standard actuators .............................................................................................. 13
8.2.3 Max cable length – actuators with MotorLink® ............................................................................................. 13
9 Cable plan for connection to WSC 310 / 320 Plus version ..................................................................................... 15
10 Description of cards and mains connection ............................................................................................................ 16
10.1 WSC 310 mains connection and power supply unit (WCA 3P1) ......................................................................16
10.2 WSC 320 mains connection and power supply unit (WCA 3P2) ......................................................................16
10.3 Connections between cards .............................................................................................................................17
10.4 Main control card WCA 3SP – Plus Version .....................................................................................................17
10.5 Motor line card – WCA 3M8 .............................................................................................................................28
10.6 Keypad card – WCA 3KI ..................................................................................................................................29
10.7 Fieldbus cards ..................................................................................................................................................29
11 Cable monitoring of actuators .................................................................................................................................. 30
11.1 Usage of non-WindowMaster actuators ...........................................................................................................30
12 Back-up batteries ....................................................................................................................................................... 30
13 Touch screen .............................................................................................................................................................. 31
13.1 Icons .................................................................................................................................................................31
13.2 Rotation of the touch screen ............................................................................................................................32
14 Configuration – main menu ....................................................................................................................................... 32
14.1 Motor lines – motor groups – smoke zones ......................................................................................................32
14.1.1 Examples with motor lines / motor groups / smoke zones ........................................................................... 32
14.2 Motor line .........................................................................................................................................................33
14.2.1 Motor line - numbering ................................................................................................................................ 33
14.2.2 Motor line - configuration ............................................................................................................................. 33
14.2.3 Colour code - motor line .............................................................................................................................. 35
14.3 Motor group ......................................................................................................................................................35
14.3.1 Motor group - configuration ......................................................................................................................... 35
14.3.2 Colour code – motor group .......................................................................................................................... 35
14.4 Break glass unit ................................................................................................................................................35
14.4.1 Break glass unit – configuration .................................................................................................................. 35
14.4.2 Colour code – break glass unit .................................................................................................................... 37
14.5 Smoke zone .....................................................................................................................................................37
14.6 Local input ........................................................................................................................................................38
14.6.1 Numbering of local inputs ............................................................................................................................ 38
14.6.2 Local input - configuration ........................................................................................................................... 39
14.6.3 Usage of wind/rain sensors - WLA 33x ...................................................................................................... 40
14.7 Local output ......................................................................................................................................................41
14.7.1 Numbering of local output ........................................................................................................................... 42
14.7.2 Local output - configuration ......................................................................................................................... 42
14.8 Weather station type ........................................................................................................................................43
14.9 Sequence control .............................................................................................................................................44
14.10 Magnetic clamp (magnetic door retainer) .........................................................................................................44
14.11 Master / Slave connection of smoke zones ......................................................................................................45
14.12 Network ............................................................................................................................................................47
14.14 Log in ...............................................................................................................................................................48
14.15 Configuration files on USB ...............................................................................................................................49
14.16 System .............................................................................................................................................................49
14.16.1 Service timer ............................................................................................................................................... 50
Page 3
3
14.17 Fieldbus (KNX and BACnet) .............................................................................................................................51
14.17.1 KNX configuration ....................................................................................................................................... 51
14.17.2 BACnet configuration .................................................................................................................................. 52
15 Status – main menu ................................................................................................................................................... 52
16 Manual operation – main menu ................................................................................................................................. 52
17 Configuration missing – main menu ........................................................................................................................ 53
18 Hardware error – main menu ..................................................................................................................................... 53
18.1 Error on the Power supply ................................................................................................................................53
18.1.1 Blown battery fuse – 20A fast ...................................................................................................................... 54
19 View all details – main menu ..................................................................................................................................... 54
20 Remote control of CompactSmoke™ ....................................................................................................................... 54
21 Commissioning and test run ..................................................................................................................................... 55
21.1 The control ventilation panel is completely installed, without the operating voltage applied .............................55
21.2 With mains voltage, without accumulator .........................................................................................................55
21.3 With mains voltage, with accumulator ..............................................................................................................56
21.4 Ventilation keypad ............................................................................................................................................56
21.5 Break glass unit WSK 50x ................................................................................................................................56
21.6 Smoke detectors ..............................................................................................................................................56
21.7 Emergency power supply test ..........................................................................................................................56
21.8 Wind/rain detector ............................................................................................................................................56
22 Maintenance ............................................................................................................................................................... 56
22.1 Maintenance agreements .................................................................................................................................57
22.2 Replacement cards ..........................................................................................................................................57
22.2.1 Replacement of 3M8 and 3KI cards ............................................................................................................ 57
22.2.2 Replacement of 3SP card ........................................................................................................................... 57
23 Declaration of Conformity and Declaration of Perfomance.................................................................................... 57
Page 4
4
1 Safety information
1.1 Safety
Only allow correspondingly trained, qualified and skilled personnel to carry out installation work. Reliable operation and the avoidance of damage and hazards are only guaranteed if installation and settings are carried out
carefully in accordance with these instructions. There may be personal danger by electrically operated windows:
- the forces occurring in the automatic mode can be such that parts of the body could get crushed
- when opened, actuators (spindles) could protrude into the room For this reason, measures have to be taken prior to starting up the actuators, which exclude the danger of injury.
For safety reasons we recommend to install opening restrictors on bottom-hung windows. In the event that windows are subjected to rain and/or high wind loads, we recommend connecting a wind/rain sensor to the
smoke ventilation panel for the automatically closing of the windows. The smoke ventilation panel is to be located in a safe place, protected from the effects of fire and smoke.
The smoke ventilation panel is to be surface mounted. The smoke ventilation panel has two energy suppliers: 230V AC and back-up batteries. The manufacturer does not assume any liability for possible damage resulting from inappropriate use.
1.2 230V AC
230V AC can cause death, severe injury or considerable damage to assets. The connection of the smoke ventilation panel is reserved for qualified personnel. Disconnect all poles of the panel from the supply voltage prior to opening, installation or assembling. Installation and use according to the national regulations.
1.3 Back-up batteries
Back-up batteries 2 batteries per panel can cause severe injury or considerable damage to assets. The connection of the smoke ventilation panel is reserved for qualified personnel. Disconnect all poles of the panel from the back-up batteries prior to installation or assembling. Ensure that the mains cable can be switched via an external or customer-supplied two-pole switch element or a switch element controlling all poles – see section 7.1 “Cable routing”. Installation and use according to the National regulations. Dispose of used batteries according to the National regulation.
CAUTION RISK OF EXPLOSION IF BATTERIES ARE REPLACED BY AN INCORRECT TYPE.
1.4 Application
The smoke ventilation panel is exclusively designed for the automatic opening and closing of smoke extraction systems, windows, flaps or doors. Always check that your system meets the valid national regulations. Pay particular attention to the opening cross section, the opening time and opening speed. The cable cross sections depend on the cable length and current consumption (amperage).
1.5 Cable routing and electrical connection
Fuse the 230VAC power supply cable separately on site. Cable routing and connection - adhere to national regulations. Establish the cable types, if necessary, with the local approval bodies or the fire protection authority. Do not conceal flexible cables. Junction box must be accessible for maintenance purposes. Disconnect all poles of the mains voltage and the back-up batteries prior to starting maintenance work or making changes to the system. Secure the system to prevent unintentional switching on again. Route all low voltage cables (24VDC) separate from the power current cables. Design cable types, lengths and cross sections in accordance with the technical information. Cable specifications is a guide only, the overall responsibility resides with the electrical contractor on site. Installation must be in accordance with the national electrical regulations.
Page 5
5
2 Structure of the smoke panel
Sizes & Versions
The WSC 310 and WSC 320 smoke ventilation panels are available in two different versions namely a Standard and a Plus version. This installation instruction only deals with the Plus versions. Please see separate installation instruction for the Standard versions of WSC 310 and WSC 320.
Cards
Each panel contains a power supply unit (SMPS), either a WCA 3P1 or a WCA 3P2 for the 10A or 20A version respectively. Aside from the power supply unit the Plus version also includes a main control card type WCA 3SP, which includes a touch screen for easy configuration of the panel. Motor line and input cards, as well as fiedbus cards, can be added to the panel depending on requirements.
Selection of cards
The Main control card type WCA 3SP allows connections of 2 motor lines and 2 keypads. If more than 2 motor lines or 2 keypads are required, the necessary cards can be added. Cards:
- WCA 3M8 motor line card, allows additional 8 motor lines.
- WCA 3KI input card, allows additional 10 keypads (requires WCA 3M8).
A fieldbus card must be added, if communication via KNX or BACnet is required. Fieldbus cards:
- WCA 3FK fieldbus card, fieldbus interface for KNX
- WCA 3FM fieldbus card, fieldbus interface for BACnet / MSTP
- WCA 3FB fieldbus card, fieldbus key for BACnet IP
Installation of cards may only be done when there is no power on the panel (no battery or power on). Motor line and input cards are ordered together with the panel and mounted to the panel from the factory side, whereas the fieldbus cards are delivered as individual products and are to be mounted by the customer – see separate installation manual for mounting of fieldbus card.
The item no. of the panel specifies the type and mounting of the cards - see "Variants of panels" for more information
Motor groups and motor lines
A motor group consists of one or more motor lines and all the motor lines are operated simultaneously. The motor lines on both the main control card (WCA 3SP) and the motor line card (WCA 3M8) can all be configured for either a
±24V standard actuators or MotorLink® actuators. A motor group can contain motor lines with both ±24V standard actuators and MotorLink® actuators, whereas a motorline only can have ±24V standard or MotorLink® actuators connected.
Adding panels
The smoke ventilation installation can be expanded by adding more panels and creating a master/slave connection among them. The master/slave connection is done directly on the WSA 3SP card. On the master panel the break glass inputs are used and on the slave panel the X11 input is used. The total cable length between 2 panels must not exceed 200m.
Break glass unit
Break glass unit type WSK 50x are to be used together with WSC 310/320. The units are configured and assigned to smoke zones via the touch screen on the main control card WCA 3SP.
Page 6
6
Inputs
Cabling
The WSC 3xx CompactSmoke™ uses bus technology and the overall cabling for break glass units, smoke detectors and keypads is significantly reduced compared to other types of smoke panels.
The main control card has 1 input for a smoke detector, 2 inputs for break glass units (where up to 10 break glass units can be connected) and 2 inputs for ventilation keypads (no max number of keypads).
Smoke detectors are either connected to the smoke detector input or to a break glass unit (type WSK 501 / 502).
The number of smoke zones and motor groups can be configured as required.
- max 2 smoke zones and 2 motor groups for a panel without motor line card.
- max 10 smoke zones and 10 motor groups for a panel with motor line card
System example with WSC 320
Smoke ventilation panel (20A) motor line and keypad card configured in 2 smoke zones.
The keypads and smoke detector units are cabled directly to the break glass units in the smoke zones, which means that the need for cabling in the building is significantly reduced.
A wind/rain sensor is connected to close the windows during comfort ventilation in case of high wind and/or rain.
The smoke ventilation panel is connected to the Fire Alarm System via the WCA 3SP card.
3 Variants of panels
Item composing
WSC 3
xx x xx
xx x 1
1 = Product version number
E = EN 12101-10
Input card* 02 = No input card 12 = Input card (10 additional keypad inputs)
Motor line card 02 = No motor line card 10 = Motor line card (8 additional lines)
Panel version S = Standard P = Plus
Panel size 10 = 10A 20 = 20A
Compact smoke series 3
* Input card for keypads requires card for motor lines
Page 7
7
3.1 CompactSmoke™ Plus versions
Number of motor lines and other functions
Cards
Item number
Examples with WSC 310
Plus version 2 motor lines 2 keypads / inputs
No cards
WSC 310 P 0202 E1
Example with WSC 320
Plus version 2 motor lines 2 keypads / inputs
No cards
WSC 320 P 0202 E1
Plus version 10 motor lines 12 keypads / inputs
1 x WCA 3M8 1 x WCA 3KI
WSC 320 P 1012 E1
3.2 Max numbers of actuators per motor line and panel
The table shows the maximum number of actuators, which can be connected per motor line and panel depending on the type of the actuator, panel and connected card. The total power consumption of all the connected actuators must not exceed 10A for WSC 310 and 20A for WSC 320.
Actuator type
Per Motor line
Per 10A panel
Per 20A panel
± 24V
actuators
MotorLink®
actuators
± 24V
actuators
MotorLink®
actuators
± 24V
actuators
MotorLink® actuators
2 motor lines
2 motor lines
10 motor lines
WMS 306-1
10 4 10 8 20 8 20
WMS 306-2
10 2 10 4 20 4 20
WMS 306-3
9 3 9 6 18 6 18
WMS 306-4
8 4 8 8 20 8 20
WMS 309-1
10 4 10 8 20 8 20
WMS 309-2
10 2 10 4 20 4 20
WMS 309-3
9 3 9 6 18 6 18
WMS 309-4
8 4 8 8 20 8 20
WMS 409 xxxx 01
5 0 5 0 10 0 0
WMS 409-1
5 4 5 4 10 8 10
WMS 409-2
4 2 4 4 8 4 10
WMS 409-3
3 3 3 3 9 6 9
WMS 409-4
4 4 4 4 8 8 8
WMS 515 2 0 2 0 4 0
0
WMU 836-1
10 4 10 8 20 8 20
WMU 836-2
10 2 10 4 20 4 20
WMU 836-3
9 3 9 6 18 6 18
WMU 836-4
8 4 8 8 20 8 20
WMU 861-1
6 4 6 6 12 8 12
WMU 861-2
6 2 6 4 12 4 12
WMU 861-3
6 3 6 6 12 6 12
WMU 861-4
4 4 4 4 12 8 12
WMU 842 / 862 / 882-1
4 4 4 4 8 8 8
WMU 842 / 862 / 882-2
4 2 4 4 8 4 8
WMU 842 / 862 / 882-3
3 3 3 3 6 6 6
WMU 842 / 862 / 882-4
4 4 4 4 8 8 9
WMU 863 / 883-1
3 3 3 3 6 6 6
WMU 863 / 883-2
2 2 2 2 6 4 4
WMU 863 / 883-3
3 3 3 3 6 6 6
WMU 863 / 883-4
0 0 0 0 4 4 4
Page 8
8
Per Motor line
Per 10A panel
Per 20A panel
± 24V
actuators
MotorLink®
actuators
± 24V
actuators
MotorLink®
actuators
± 24V
actuators
MotorLink® actuators
2 motor lines
2 motor lines
10 motor lines
WMU 864 / 884-1
2 2 2 2 4 4 4
WMU 864 / 884-2
2 2 2 2 4 4 4
WMU 864 / 884-3
0 0 0 0 3 3 3
WMU 864 / 884-4
0 0 0 0 4 4 4
WMU 885 / 895-1
2 2 2 2 4 4 4
WMU 885 / 895-2
2 2 2 2 4 4 4
WMU 885 / 895-3
0 0 0 0 3 3 3
WMU 885 / 895-4
0 0 0 0 4 4 4
WMX 503 / 504 / 523 / 526-1
20 4 20 8 40 8 40
WMX 503 / 504 / 523 / 526-2
20 2 20 4 40 4 20
WMX 503 / 504 / 523 / 526-3
18 3 18 6 39 6 30
WMX 503 / 504 / 523 / 526-4
20 4 20 8 40 8 40
WMX 803 / 804 / 823 / 826-1
10 4 10 8 20 8 20
WMX 803 / 804 / 823 / 826-2
10 2 10 4 20 4 20
WMX 803 / 804 / 823 / 826-3
9 3 9 6 18 6 18
WMX 803 / 804 / 823 / 826-4
8 4 8 8 20 8 20
WML 820/825
10 0 10 0 20 0 0
WML 860-1
10 4 10 8 20 8 20
WML 860-2
10 2 10 4 20 4 20
WML 860-3
9 3 9 6 18 6 18
WML 860-4
8 4 8 8 20 8 20
WMB 801/802*
max. 4A connected to the WMB
WMB 811/812 */**
10 2 10 4 20 4 20
* Do not exceed the total power consumption of the motor line ** When having two locking actuators per motor line, it must be one of each type: 1 x WMB 811 and 1 x WMB 812
4 Accessories and spare parts
Accessories
Fieldbus card with field bus interface for KNX incl. cover – sold separately, not factory mounted
WCA 3FK
Fieldbus card with field bus interface for BACnet / MSTP incl. cover - sold separately, not factory mounted
WCA 3FM
Fieldbus card with field bus key for BACnet-IP incl. cover - sold separately, not factory mounted
WCA 3FB
Back-up battery for WSC 310 - 7Ah (2 x WSA 007 per panel )
WSA 007
Back-up battery for WSC 320 - 12Ah (2 x WSA 012 per panel)
WSA 012
Break glass unit, primary, with data communication, PVC housing. Has connection for possibility for comfort keypads and smoke detector. (x=colour of the housing: 1=red, 2=yellow, 3=grey, 4=blue, 5=orange) Only one unit per line
WSK 501 000x
Break glass unit, primary, with data communication, metal housing. Has connection for possibility for comfort keypads and smoke detector. (x=colour of the housing: 2=yellow, 3=grey, 5=orange) Only one unit per line
WSK 502 000x Break glass unit, primary, with data communication, PVC housing. Has no connection possibility for comfort keypads and smoke detector. (x=colour of the housing: 1=red, 2=yellow, 3=grey, 4=blue, 5=orange)
WSK 503 000x
Break glass unit, primary, with data communication, metal housing. Has no connection possibility for comfort keypads and smoke detector. (x=colour of the housing: 2=yellow, 3=grey, 5=orange)
WSK 504 000x
Page 9
9
Fireman override switch
WSK 601
Smoke detector
WSA 300
Rain sensor
WLA 331
Rain/wind speed sensor
WLA 330
Rain/wind speed sensor, with pulse output
WLA 340
Wind speed sensor & Wind direction sensor
WOW 201 &
WOW 202
Bracket for junction box
WOW 203
Junction box for WOW 201 and WOW 202
WOW 204
End of line motor module
WSA 510
End of line smoke detector module (10kΩ resistor), 10 pcs.
WSA 501
Fire alarm system cable surveillance module
WSA 306
Cable for wind and rain sensor WLA 340, 4m UV-resistant cable 4 x 2 x 0,75mm2
WLL 604
Cables for smoke ventilation – see separate data sheet for further information
WLL 8xx
Spare parts
10A power supply unit for WSC 310
WCA 3P1
20A power supply unit for WSC 320
WCA 3P2
Main control card for Plus version WSC 310 / WSC 320 incl. cover + 2 end of line modules (WSA 510)
WCA 3SP
Motor line card with 8 motor lines incl. cover + 8 end of line modules (WSA 510)
WCA 3M8
Input card with 10 inputs for e.g. key pads incl. cover (requires WCA 3M8)
WCA 3KI
Plastic covers for the cards in the WSC 310 /WSC 320 Plus version
WCA 301
Fieldbus card with fieldbus interface for KNX incl. cover
WCA 3FK
Fieldbus card with fieldbus interface for BACnet / MSTP incl. cover
WCA 3FM
Lock cylinder incl. 2 keys for WSC 310/320 panel
WCA 307
Replacement glass for break glass units type WSK 501 / 502 / 503 / 504, 5 pcs.
WSK 397
Keys for break glass units type WSK 501 / 503, 5 pcs.
WSK 398
Keys for break glass units type WSK 502 / 504, 1 pcs.
WSK 453
Lockable replacement PVC housing for break glass unit x=colour of the housing: 1 = red, 2 = yellow, 3 = grey, 4 = blue, 5 = orange
WSK 399 000x
Back-up battery cable kit for WSC 310 / 320 (cable between WCA 3SP / 3SS and the batteries and between the batteries)
WSA 330 0101 20A battery fuse. The battery fuse on the WCA 3SP/3SS, 10 pcs
WSA 331 0101
5 Technical data
Technical data
Output current (nominal)
WSC 310: 10A / WSC 320: 20A
Secondary voltage
Voltage 24V DC (±15%) Open circuit voltage (no load) 27,6V DC @ 20°C Ripple at max load max. 6% (3,5Vpp)
Motor lines
Motor groups
Smoke zones
WSC 310/320 0202: max 2, WSC 320 1012: max 10 A motor line can contain either ±24V standard motors or MotorLink® motors
WSC 310/320 0202: max 2, WSC 320 1012: max 10 Via the software more motor lines can be connected in the same group
WSC 310/320 0202: max 2, WSC 320 1012: max 10
Page 10
10
Primary voltage
WSC 310: 230V AC, 50Hz (85-264V AC, 47-63Hz) WSC 320: 230V AC, 50Hz (85-264V AC, 47-63Hz)
Power consumption
WSC 310: min 3.2W
1+2
, typ. 4.8W
1+3
. At max load 300W
WSC 320: min 5.0W
1+2
, typ. 5,6W
1+3
. At max load 600W
1) no load: system operational but no actuators are running
2) min: 1 x break glass unit WSK 501 and 1 x smoke detector WSA 300
3) max load: 1 x break glass unit WSK 501, 4 x break glass unit WSK 503 and 10 x smoke detector WSA 300
Inrush current on primary site
70A<5ms Max. 3 x WSC 310/320 per 10A supply group Circuit breaker “C” chracteristic
±24V change over time
min 500ms
Back-up batteries
WSC 310: 2 x WSA 007 (12V / 7Ah) WSC 320: 2 x WSA 012 (12V / 12Ah)
Expected lifetime max 4 years, only use genuine WindowMaster batteries
Emergency power
>72 hours in accordance with EN 12101-10
Automatic smoke triggering
Smoke triggering when the temperature inside the compact unit exceeds 72ºC
Charging unit (integrated in WCA 3SP card)
Charging voltage: 27,7 – 27,8V at 20ºC Charging current: 1.7A, current limited
Priority
Smoke signal has always highest priority
Cable monitoring
±24V standard actuators with end of line module and smoke detectors are monitored by closed-circuit
Actuators with MotorLink® and break glass units are monitored by data communication
Back-up batteries are monitored by cyclic measuring
LED message OK, fault and alarm
Green Yellow Red
all OK fault fire
Reopening the actuators
Every 2.min. in 30min. after a SHE open (selectable) Pre-set: no reopening
Connection cable
Actuators Other components
flexible max 6 mm² / solide max 10 mm² min 0,2mm² / max 1,5mm²
Operating conditions
-5°C - +40°C, max. 95% relative humidity (not condensing) EN 12101-10: Operation class A, Environmental class 1, with IP value increased to IP 54 (according to EN 12101-10 is min. IP 30 required)
Max actuator activation duration (duty cycle)
ED 40% (4min. per 10min.)
Max allowed current drawn from the battery when the primary power source is disconnected
WSC 310: 10A WSC 321: 20A
Max interruption time during switching between power sources
<2.0sec
Break glass unit
Up to 10 break glass units type WSK 50x can be connected to the WCA 3PS, but only 1 WSK 501 / 502 per line, meaning max 2 WSK 501 / 502 per panel.
Smoke detectors and ventilation keypads can only be connected to break glass units type WSK 501 / 502. Up to 10 smoke detectors can be connected to each WSK 501 / 502, and 10 smoke detectors can be connected to the smoke detector input on the main board, which give a total maximum of 30 smoke detectors. There is no limit on the number of ventilation keypads connected to the WSK 501 / 502. Smoke detectors and ventilation keypads cannot be connected to WSK 503 /
504.
Number of motor lines per card
WCA 3SP WCA 3M8
2 x 10A motor line for ±24V standard or MotorLink® actuators 8 x 10A motor line for ±24V standard or MotorLink® actuators
Page 11
11
Material
Metal housing for surface mounting
Colour
Grey (RAL 7035)
Size
WSC 310: 300 x 400 x 120mm (HxWxD) WSC 320: 300 x 400 x 210mm (HxWxD)
Weight
WSC 310: 6kg no batteries, 10.8kg with batteries (2 x WSA 007) WSC 320: 8.6kg no batteries, 16.6kg with batteries (2 x WSA 012)
Protection class
IP54
Approval / certification
Approved and certified according to EN 12101-10
Delivery
CompactSmoke™ smoke ventilation panel with WSA 501 (10kΩ resistors, 10
pcs.) and 2 oder 10 pcs. end of line module WSA 510 Back-up batteries included.
Note
We reserve the right to make technical changes
6 Mounting
The smoke ventilation panel is fixed to the wall through the Ø8.5mm holes in the
back plane of the housing.
If the panel is fixed in different way, the holes are to be blinded with the 4 blind
grommets, this way the IP class is maintained.
The door is turnable.
When turning the door also move the blind grommets to the new holes.
The smoke ventilation panel is to be located in a safe place, protected from the
effects of fire and smoke.
7 Installation
7.1 Cable routing
For cable routing, we recommend the use of fire protected cables retaining their function E90 or E30.
See also chapter 8 “Cable dimensioning” in this instruction.
However, this has to be agreed with the Engineer or, if necessary, with the local fire protection department.
Do not reduce the cable cross sections specified in the cable lengths table.
All cables of the control (except the mains supply cable) carry 24V DC and have to be routed separate from the mains supply
cable.
Adhere to the pertinent national and local regulations when routing the cables.
7.2 Cables into housing
All connection terminals (except the mains terminals) are of the plug-in type. Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made correctly. Incorrect cable clamping, mixing up numbers or colours could lead to malfunctions of the control panel or of the external components. Ensure that the electrical cables are always routed according to the valid national and local regulations.
7.3 Connection of safety earth wire and 230V AC
See chapter 10 ‘Description of cards’, section 10 for further description.
7.4 Installation of the break glass unit, ventilation keypad and smoke detector
Ensure that the break glass unit and the ventilation buttons are visible and well accessible. Do not install behind protruding walls, door panels or hidden by the building structure. Note: Installation height of the break glass unit 1.5 – 1.7m above floor. Install the smoke detectors in accordance with their enclosed instructions.
Page 12
12
7.5 Assembly instructions
Always have assembly, installation, repair and maintenance of smoke and heat extraction systems carried out by qualified personnel trained for this purpose.
Rules to be adhered to for setting up and installation
The following safety relevant rules have to be adhered to when planning the use of a smoke and heat extraction system and its set-up and installation:
• The Provincial Building Ordinance of the provinces,
• The regulations of the competent fire protection authority,
Accident prevention regulations
Adhere to the general accident prevention regulations (APR), the APR for power operated windows and doors, and the installation rules in your country.
CAUTION:
Live components are directly accessible after opening the system housing. Prior to inserting / removing cards disconnect to the panel from the mains supply and the back-up batteries.
• adhere to the installation instructions and your local energy providers
• select the place of installation such that free access is guaranteed for maintenance purposes
• select cables according to regulations in this instruction - take the calculation of the actuators supply cable lengths
into account when laying the cables
• power cables entered via the cable glands
• connect the cables in accordance with the drawings provided by the manufacturer
• route the cables in the building according to the regulations in this instruction
• after the smoke panel is installed the back-up batteries will be fully charged after ca. 8 hours
• check all system functions
Electric cable routing for smoke and heat extraction systems
Electrical cables always have to be laid in accordance with the national and local rules in your country. Do not use the PE wire / green/yellow wire! Cables of type NYM, concealed, can be used. For surface laying, halogen free safety cables are recommended (see cable plan). If possible, the use of cable types should be agreed with the Technical Services and the competent fire protection authority.
For the maximum permissible cable lengths of the actuator supply cables for the WSC 3xx system, taking the specified cable cross sections into account (cable information for surface laying), please refer to chapter 8 “Cable dimensioning”.
8 Cable dimensioning
8.1 Maintaining the cable functions
According to valid national regulations. The cable network for smoke ventilation systems (“Cable system“) ends normally at the interface (junction box) for the actuator! The flexible, heat resistant connection cable of actuator is part of the system component‚ electric actuator actuation, and is not a part of the electrical installation!
We recommend in all cases to discuss the type of cable routing with the competent fire fighting authorities.
8.2 Max. cable Length
Maximum permissible cable length from the smoke ventilation panel to the actuators taking into account the cable cross-section is shown in the following tables for “± 24V standard actuators“ and “MotorLink® actuators“.
8.2.1 Formula for the calculation of the maximum actuator cable length
Max. cable length = permissible voltage drop 2V (UL) x conductivity of copper(56) x cable cross section in mm2 (a) max. actuator current total in amps (I) x 2
For both ±24V standard actuators and actuators with MotorLink® the cross section of the cable must not be less than 0.75mm2 regardless of the result of above formula.
Maximum actuator cable length: Always measured from the smoke to the last junction box Permissible max. voltage drop in the line: 2 Volt Actuating current: Sum of all actuator power consumption per motor line
Note: do not use the PE wire / green/yellow wire!
Example
Max actuator cable length with cable cross section 0.75mm2 and actuator current 2A: (2 x 56x0.75) : (2 x 2) = 21m
Page 13
13
8.2.2 Max cable length – ±24V standard actuators
The actuator supply cable must have 3 wires: 2 wires current carrying / 1 wire for monitoring.
±24V standard actuators
Do not use the PE wire / green/yellow wire!
cable cross
section [a]
Total actuator current [I]
3 wire
0,75mm²
3 wire
1,50 mm²
5 wire
1,50 mm²
2 wire
parallel
3 wire
2,50 mm²
5 wire
2,50 mm²
2 wire
parallel
3 wire
4,00 mm²
1A
42m
84m
168m
140m
280m
224m
2A
21m
42m
84m
70m
140m
112m
3A
14m
28m
56m
47m
93m
75m
4A
11m
21m
42m
35m
70m
56m
5A
8m
17m
34m
28m
56m
45m
6A
7m
14m
28m
23m
47m
37m
7A
6m
12m
24m
20m
40m
32m
8A
5m
11m
21m
18m
35m
28m
9A
9m
18m
15m
31m
25m
10A
8m
16m
14m
28m
22m
20A
4m
8m
7m
14m
11m
8.2.3 Max cable length – actuators with MotorLink®
The actuator supply cable must have 3 wires: 2 wires current carrying / 1 wire for communication.
When a 5 wire cable is used for MotorLink® It is not recommended to use parallel-wire.
ML-comm = MotorLink® communication.
Page 14
14
When using actuators with MotorLink® the max cable length is 50m regardless of the result of the above mentioned formula.
Actuators with MotorLink®
Do not use the PE wire / green/yellow wire!
cable cross
section [a]
Total actuator current [I]
3 wire
0,75mm²
3 wire
1,50 mm²
5 wire
1,50 mm²
2 wire
parallel
3 wire
2,50
mm²
5 wire
2,50 mm²
2 wire
parallel
3 wire
4,00 mm²
1A
42m
50m
2A
21m
40m
50m
3A
14m
28m
50m
47m
50m
4A
11m
21m
42m
35m
5A
8m
17m
34m
28m
50m
45m
6A
7m
14m
28m
23m
47m
37m
7A
6m
12m
24m
20m
40m
32m
8A
5m
11m
21m
18m
35m
28m
9A
9m
18m
15m
31m
25m
10A
8m
16m
14m
28m
22m
20A
4m
8m
7m
14m
11m
Page 15
15
9 Cable plan for connection to WSC 310 / 320 Plus version
The above plan shows a WSC 310 panel, where the power supply unit is located in the left side of the panel wherefrom also mains is pulled. The power supply unit for the WSC 320 panel is located underneath the main control and motor line card and mains is pulled from the top right side. See section 10.1 for illustrations.
Page 16
16
10 Description of cards and mains connection
Each panel includes a power supply unit (SMPS) and a main control card. Motor line can input cards for additional motor lines and inputs (e.g. for key pads) as well as a fieldbus card can be added when necessary.
The size of the power supply unit determines the size of the panel and the number and/or types of actuators, which can be connected to the panel. See table with overview of max number of allowed actuators per motor line/panel (chapter 3.2).
The size of the power supply also determines the physical design of the panel inside the cabinet and thereby eg. where mains is connected to the main control board (WCA 3SP).
10.1 WSC 310 mains connection and power supply unit (WCA 3P1)
WSC 310 – WCA 3P1
With 300W SMPS unit The power supply is located to the left of the main
control card. The cable inlet is in the top left corner of the panel. The panel must be grounded by means of protective
earth on the top panel plate.
10.2 WSC 320 mains connection and power supply unit (WCA 3P2)
WSC 320 - WCA 3P2
With 600W SMPS unit The power supply is located underneath the main
control and the motor line card. The cable inlet is in top right corner of the panel. The panel must be grounded by means of protective
earth on the top right side of the panel.
Page 17
17
10.3 Connections between cards
An overview of how the different cards are connected are shown below.
10.4 Main control card WCA 3SP – Plus Version
Each WCA 3SP contains the
following:
- 2 motor lines for ±24V
standard or Motorlink® actuators
- 2 input for keypads for comfort
ventilation
- 2 input for break glass units
- 1 input for smoke detector
- 1 input for 24V/48V
- Output for fault signal to Fire
Alarm System
- Input for weather station incl. wind
direction (WLA 330 / 331 / 340 /
WOW 201 / 202)
- Input for master / slave connection
(ISO line)
- connection of power supply
- Power for motor line card
- Connection for battery back-up
- Connection for motor line card
- Two connections for Ethernet
- Connection for USB host and
USB device
- Connection for fieldbus card
- Touch screen for configuration,
commissioning and maintenance
Page 18
18
X1 / X2
The WCA 3SP card has 2 motor lines (X1 and X2) for connection of ±24V standard or MotorLink® actuators.
±24V standard actuators
1.1 24V / 0V
1.2 Cable monitoring
1.3 0V / 24V
2.1 24V / 0V
2.2 Cable monitoring
2.3 0V / 24V
MotorLink® actuator
1.1 0V
1.2 Communication
1.3 24V
2.1 0V
2.2 Communication
2.3 24V
The number of actuators per motor line depends on the actuator type, the total power consumption of actuators
connected to a motor line can max be 10A and the total max power consumption for both motor lines must not
exceed 10A or 20A depending on panel type.
Besides actuators, also locking actuators (espagnolettes actuators) type WMB 801/802 and WMB 811/812 can
be connected. The power consumption of the locking actuators are not to be included in the 10A / 20A as
actuaators and locking actuators do not run at the same time.
All actuators on the same motor line will run/be operated simultaneously.
All actuators on the same motor line must be of the same type.
Connection / cable diameter: flexible max 6 mm² / solid max 10 mm².
Cable length: see the chapter "Cable dimensioning".
If cable monitoring is wanted, an “end of line motor module” type WSA 510 must be added in the last junction
box. When using non-WindowMaster actuators the WSA 510 is added and the cable monitoring is set to
“simple”, see section “Cable monitoring of Actuators”.
Standard ±24V actuators
Examples with 20A power
consumption
a) 20 pcs. WMX 826-1
b) 10 sets of 2 pcs. WMX 826-2
c) 4 pcs. WMU 885-1
d) 2 sets of 2 pcs. WMU 885-2
Connection of standard actuators on motor line X1 (with cable monitoring)
MotorLink® actuators
Examples with actuators per
motor line
Ex. 1: 4 pcs. WMX 823-1
Ex. 2: 2 pcs. WMX 885-2
Ex. 3: 3 pcs. WMU 826-3
Allowed actuator combinations on a MotorLink® motor line
The two motor lines on the SP card can each be connected to one of the below shown combinations.
-1 (single): one window with one single window
actuator. Up to four windows each with one
single window actuator can be connected
-2 (double): one window with two double window
actuators.
-3 (triple): one window with three triple window
actuators.
-4 (quad): one window with four quad window
actuators.
Page 19
19
X3 / X4
For connection of comfort keypads.
With the default values are input:
”Active” if the contact resistance is smaller than 2kΩ
”Inactive” if the contact resistance is bigger than 3kΩ.
Input has pull up current of approx. 0.8mA. (min 0.7mA, max 1mA )
Example: comfort keypad connected to input X3
X3 / X4 can also be used as configurable inputs
Input 1
3.1 input 1.1
3.2 input 1.2
3.3 GND 1 / 0V
Input 2
4.1 input 2.1
4.2 input 2.2
4.3 GND 2 / 0V
Fire Alarm System shown with cable monitoring type 1 and type 2:
Cable monitoring Type "1"
Type "1" is used with WSA 501.
This kind of cable monitoring detects only
interruption.
Cable monitoring type "2"
Type "2" is used in conjunction with WSA 306.
This type of cable monitoring is the most secure
because it detects both interruption and short circuit.
Data
3.1 Open
3.2 Close
3.3 GND / 0V
4.1 Open
4.2 Close
4.3 GND / 0V
Input circuit (simplified)
Page 20
20
X5 / X6
For connection of break glass unit type WSK 50x.
Data
Break glass unit bus 1
5.1 24V
5.2 Communication
5.3 0V
Break glass unit bus 2
6.1 24V
6.2 Communication
6.3 0V
As the break glass units are monitored, the
connection of the break glass units depends
therefore of the number of smoke zones.
- 1 smoke zone: connect to break glass unit bus 1. It is optional if they are connected in a ring.
- 2 smoke zones: connect to break glass unit bus 1 respectively to break glass unit bus 2. It is optional if they are connected in a ring.
- 3 or more smoke zones: break glass units are always to be connected in a ring
Break glass units connected in a ring bus are not as sensitive to errors on the cables, as units which are not connected in a ring bus.
Smoke detectors and keypads can also be connected on the break glass unit type WSK 501 / 502.
Per panel up to 10 break glass units can be connected. But only 2 of these 10 (one per line) can be a type WSK 501 / 502 to which keypads or smoke detectors can be connected. The remaining break glass units must be type WSK 503 / 504.
Page 21
21
Example: 2 smoke zones and connected components; 2 break glass units type WSK 501 / 502 and 1 break glass unit type WSK 503 / 504, 3 smoke detectors WSA 300, 2 resistances WSA 501 and 3 comfort keypads.
See chapter 9 "Cable plan for connection to WSC 3xx" for cable types and lengths.
Connection of different types of smoke detectors to CompactSmoke™
Smoke detector type
WSA 300
Hekatron
MSD 523
(max 5 pcs)
Hekatron
SSD 521/a
(WSA 200 6101)
Apollo, Orbis ORB-OH-13001-AP0 ORB-OP-12001-AP0
Connect to WCA 3SP X1,1
L1 In 2 2
In +
X1,2
L2 1 1
Com -
Connect to WSK p 7
L2 1 1
Com -
p 8
L1 In 2 2
In +
ALWAYS connect 10 KOhm in between
L2
and
L1 Out
1
and
3
1
and
3
Com –
and
Out +
Page 22
22
X7
For connection of smoke detector type WSA 300. Data
7.1 +
7.2 ­Imax = 3,4mA
For connection of a different type smoke detector, see above. When no smoke detector is connected to X7, a 10kΩ resistor is connected to the input.
X8
24/48V free configurable input from e.g. Fire Alarm System (used primarily in France).
Data
8.1 +
8.2 ­Active at voltages between 18 and 50V
Passive below 1V Max.50V
Connection example
X9
Solid state outputs, one solid state output for transmission of fault signal to Fire Alarm System and 2 free configurable
Data
9.1 Fault – Open contact = Fault, closed contact = OK
9.2 Fault – Open contact = Fault, closed contact = OK
9.3 Output A
9.4 Output A
9.5 Output B
9.6 Output B
Solid state output for transmission of fault signal to Fire Alarm System. A fault must last a minium of 20 seconds before the relay indicate a fault.
Data Max voltage: 30 Vp (peak) Max output: 150 mA Typical On-resistance: 4,7 Ω Max On-resistance: 8 Ω Max switching speed: 2 ms
Page 23
23
2 free configurable solid state outputs
9.3 Output A
9.4 Output A
9.5 Output B
9.6 Output B Data
Max voltage: 30 Vp (peak) AC/DC Max current: 150 mA Typical On-resistance: 4,7 Ω Max On-resistance: 8 Ω Max switching speed: 2 ms, only for DC-voltage
Output circuit (simplified)
Example with solid state and relay (polarization is not important)
X10
For connection of weather station with wind direction. Connection of wind / rain sensors type WLA 330 or WLA 340, rain sensor WLA 331.
Or connection of intelligent weather station (wind direction dependent smoke and heat extraction), e.g. wind speed sensor WOW 201, wind direction sensor WOW 202, junction box and brackets WOW 203 + 304 and rain sensor WLA 331.
Data
10.1 24V UPS
10.2 Wind speed
10.3 GND / 0V
10.4 24V
10.5 Rain
10.6 GND / 0V With the default values are input:
”Active” if the contact resistance is smaller than 4kΩ ”Inactive” if the contact resistance is bigger than 8kΩ. For values between 4 and 8kΩ the result will depend on the supply voltage.
Input has pull up current approx. 1mA. (min 0.7mA, max 1.4mA)
Input circuit (simplified)
Page 24
24
Example 1: Wind/rain and rain sensors
WLA 330 and WLA 331– the settings of the sensors are set on the sensor. WLA 340 – the settings of the sensor are programmable on the smoke panels touch screen.
Data
10.1 24V UPS
10.2 Wind speed
10.3 GND / 0V
10.4 24V
10.5 Rain
10.6 GND / 0V
Page 25
25
Example 2: Wind direction dependent smoke and heat exhaust ventilation (intelligent weather station) Data
10.1 24V UPS
10.2 Wind speed / Direction
10.3 GND / 0V
10.4 24V
10.5 Rain
10.6 GND / 0V As the weather station is monitored by both communication and time out (wind without time), any cable errors will
be registered.
Page 26
26
X11
For connection of master / slave connection via WSK-Link™. Data:
11.1 24V IN
11.2 Communication IN
11.3 0V IN On the master panel, either input X5 or X6 – the inputs also used for break glass units - are used for the
connection. On the slave panel, the connection is done via X11. It is possible to connect several panels in a master slave connection. However, the max total number of panels
AND break glass units on the bus must not exceed 10 units. The max cable length between two units must not exceed 200m, see examples below, for how to connect the panels.
Smoke panel #2 and #3 are both master and slave panels.
Page 27
27
Both slave and break glass units are connected to the master on input X5 like above example 1 – limiting the available cable length.
Slaves and break glass units are connected on both input X5 and X6 like above example 2. E.g. slave panels are connected to input X5 and break glass units are connected to input X6 – increasing the available cable length.
Even though the connecting method of panels shown in example 2 enables a physical larger system, with longer distances between panels and break glass units, WindowMaster recommends connecting the master slave panels as shown in example 1. As only the master panel sends smoke commands and slave panels only responds to commands received from the master panel, the response time in example 2 is heavily increased in comparison with the response time in example 1.
J1
Connection for power supply
J2
Power to motor line card
J3
Connection for battery (power back-up)
J4
Connection for motor line card (WCA 3M8)
J7
2 x Ethernet connection
J8
USB host. Used to store configurations and to start an event log for e.g. trouble shooting
J9
USB device. Used for remote control and to flash the panel.
J10
Connection for fieldbus card
P1
Power supply control
R / P
Reset / programming (used for firmware updates)
LED
Shows the status of the panel Red = alarm Yellow = fault, flashing yellow = service timer expired, time for service Green fast flickeing = all OK (CPU working), Green constant = CPU communication stopped (possible reset or contact WindowMaster)
↓ ↑
Close / open all windows
Page 28
28
10.5 Motor line card – WCA 3M8
The motor line card WCA 3M8, allows connection of additional 8 motor lines either ±24V standard or MotorLink®.
The WCA 3M8 is connected to WCA 3SP via a CAN-cable (J3 on the WCA 3M8 and J4 on the WCA 3SP).
X1 – X8
For connection of ±24 Standard actuators or MotorLink® actuators. Data: x.1 24V / 0V x.2 Cable monitoring / Communication x.3 0V / 24V
For actuator connections, please see explanation in section “WCA 3SP main control card” under “X1 / X2” and “Max number of actuators per card”.
J3
Connection to main control card (WCA 3SP)
J4
Power connection from control card (WCA 3SP)
J6
Connection to input input card (WCA 3KI)
J7
Power supply control
Page 29
29
10.6 Keypad card – WCA 3KI
The keypad card allows connection of 10 keypads. WCA 3KI requires the WCA 3M8 actuator card.
The WCA 3KI is connected to WCA 3M8 via cable (J1 on the WCA 3KI and J6 on the WCA 3M8).
X1 – X10
Data: x.1 Open x.1 x.2 Close x.2 x.3 GND / 0V
For input connections, please see explanation in section “WCA 3SP main control card” under “X3 / X4”.
J1
Connection to motor line card (WCA 3M8)
10.7 Fieldbus cards
Different versions of fieldbus cards are available
- WCA 3FK Fieldbus card with KNX interface
- WCA 3FM Fieldbus card with BACnet MSTP interface
- WCA 3FB Fieldbus card with BACnet IP interface
The connection of a fieldbus card enables communication and access to the available bus-objects depending on the chosen system. Smoke extraction function has always higher priority than comfort commands from the fieldbus and it is recommended only to use fieldbus for comfort purposes. There is a set of KNX and BACnet objects available for each motor line, motor group and smoke zone, which provides the options for status and commands.
Status options
E.g. actual position, fault and operation status and the max opening angle (degrees).
Command options
E.g. target position commands with different priority and MotorLink® actuator speed. See "WCA 3FK Application Programming Description.pdf" and BACnet PICS for further information on available KNX and BACnet communication objects.
Page 30
30
11 Cable monitoring of actuators
Actuators with MotorLink® are monitored by data communication. When using ±24V standard actuators either diodes or 10kΩ resistors can be used for cable monitoring, see below.
Configuration of cable monitoring with ±24V actuators
Configuration of cable monitoring
10kΩ-resistors (WSA 510) – monitors ever single core for interruption. Works with all WindowMaster actuators (default setting).
Diodes (WSA 432) – monitors every single core for interruption. Works with all WindowMaster actuators.
10kΩ- resistors, simple (WSA 510) – monitors for interruption on the entire cable. Works with all WindowMaster actuators and most non­WindowMaster actuators.
11.1 Usage of non-WindowMaster actuators
When using non-WindowMaster actuators the cable monitoring ist set to ”simple”’.
Configuration of cable monitoring with non-WindowMaster actuators
Configuration of cable monitoring
If cable monitoring of non-WindowMaster® actuators connected to the
CompactSmoke™ is required the cable monitoring type is set to
”simple”.
12 Back-up batteries
Connect 2 pcs. back-up batteries type WSC 007 for WSC 310 and type WSA 012 for WSC 320.
See section 22 “Maintenance” for further information.
Example of WSC 310 panel with back–up batteries.
Page 31
31
13 Touch screen
The plus version of the smoke ventilation panel comes with a touch screen. All connected components (actuators, break glass units, keypads, weather station etc.) are to be configured on the touch screen.
The menu of the touch screen is in steps: Step 1: main menu Step 2: sub menu Step 3: configuration / showing / operation of the sub menu
Step 1: Main menu Step 2: Sub menu
Step 3: Configuring the sub menu Step 4: Showing the sub menu
Help text
Help text
The touch screen has a help function with text explaining the menu item. The help text occurs when the menu item is pressed (text on white
background). For displaying the help text:
→ press the item e.g. “Motor type” → the help text appears → to turn off the help text press the screen.
13.1 Icons
The smoke ventilation panel has icons for quick viewing of: fire conditions, hardware OK and hardware error:
Fire conditions: smoke alarm has been triggered.
Hardware OK: actuators and break glass units have been configured correctly.
Hardware error: hardware error or connected actuators and break glass units has not been configured
correctly in motor lines, motor groups or smoke zones.
Page 32
32
13.2 Rotation of the touch screen
The picture on the touch screen can be rotated 180°
14 Configuration – main menu
All connected components (actuators, break glass units, keypads, weather station etc.) are to be configured. As the panel has pre-settings for PIN code for access to level 3, the code is to be entered before it is possible to begin the
configuration (see chapter 14.15 “Log in”). Before starting on the configuration it can be an advantage to change some of the pre-set settings. Ex. the language can be
changed from English to Danish or German (see section 14.15 “System”) and the orientation of the text on the touch screen can be rotated for a better viewing angle (see section 13.2 ”Rotation of the touch screen”). It is also possible to change the log out time, which is the time that the access to the access level is open/the touch screen in on (see section 0 “Log in”)
To configure a sub menu:
→ press the light blue number field → enter value / the number of the motor line / change factory settings etc. The setting which can be entered depends of the
type of the sub menu.
→ accept on A menu can consist of more screen plays. To get to the next screen: → press
14.1 Motor lines – motor groups – smoke zones
All the components are to be assigned to groups and zones:
- motor lines are to be assigned to motor groups
- motor groups can be assigned to smoke zones
- break glass units and smoke detectors are to be assigned to smoke zones
- keypads are to be assigned to one or more motor groups
14.1.1 Examples with motor lines / motor groups / smoke zones
- 6 motor lines: one or more actuators connected to the lines
- 3 motor groups: the actuators in the motor group are operated simultaneously on the keypad
- 2 smoke zones: the actuators in the smoke zone are operated simultaneously on the break glass unit
Page 33
33
14.2 Motor line
Actuators are to be connected on the motor lines. ±24V standard actuators and actuators with MotorLink® can be connected to all motor lines, but a motor line can only be connected to one type of actuators – either ±24V standard or MotorLink® actuators.
14.2.1 Motor line - numbering
All motor lines are numbered and they are all to be configured.
14.2.2 Motor line - configuration
Press ”Motor line” and the overview of the motor lines in the smoke ventilation panel is shown.
Overview configuration motor lines
One motor line is marked with a
as the configuration is missing.
All motor lines are configured.
Both actuators outputs on the main control card as well as the eight actuators outputs on the motor line card – if such is connected – are to be configured:
- Motor lines with actuators connected are to be configured in “motor group
-
- Motor lines with no actuator connected are set to “none“
Since ±24V actuators and actuators with MotorLink® are not to be configured exactly the same way, both type of actuators are listed below with the settings that are to be configured for each actuator type. Be aware that both types of actuators can be connected to the smoke panel at the same time.
For ±24V actuators the full chain length is define as a runtime of 60 seconds. When the smoke panel is to be 100% sure that the windows ae 100% open or closed, the chain length is run twice (120). This can have an influence when configuring the a sequence control.
Page 34
34
Motor lines configuration
±24V actuator configuration
The ±24V actuators are to be configured in:
1. Output mode: informs the type of the actuator selected
2. Motor configuration
3. Stroke time
4. Motor group
5. Manual command - auto off-period
6. Retry during alarm
7. Sequential control type
8. Sequential control position limit
9. Sequential control with
10. Sequential control with no
11. Sequential control position logic
12. Sequential control position
13. Sequential control position
The appendix contains all the menus that can be configured - see appendix for detailed explanation.
The MotorLink® actuators are to be configured in:
MotorLink® motor configuration
1. Output mode: informs the type of the actuator selected
2. Expected no. of motors (displayed if actuator type =
MotorLink®)
3. Motor group
4. Expected no. of locking motors
4.1 No. of found locking motors (see appendix)
5. Manual speed
6. Auto. speed
7. Manual command – auto off period
8. Retry during alarm
9. Max unexpected overcurrent
10. Max unexpected overcurrent (motor)
11. Sequential type
12. Sequential position limit
13. Sequential control with
14. Sequential control with no
15. Sequential control position logic
16. Sequential control position
17. Sequential control position
The appendix contains all the menus that can be configured - see appendix for detailed explanation.
Motor lines – maximum current configuration
Whether ±24V or MotorLink™ actuators are used, the motor line
can be configured to a maximum current of either 5, 10 or 20A. The configuration is made in the “Motor Line” menu under “View
all details”. The total power consumption of all connected actuators must not
exceed 10A or 20A depending on panel size.
Page 35
35
14.2.3 Colour code - motor line
The overview fields on the touchscreen have colour codes for the motor lines:
Colour
Meaning
Yellow triangle icon
The motor line are to be configured or there is a fault in the actuator
Strikethrough grey
No configuration of the motor line / the motor line doesn’t exists
Black text
The motor line are configured, the actuator has not been closed
Green
The motor line has been configured; the actuator has been closed MotorLink® motor lines will be marked in green, if the actuator / actuators on the motor
line has been closed 100% and the point zero of the actuator has been determined.
Light grey number
The motor line are configured with ‘No actuator are connected’
Blue ?
Configuration is missing or there is a mistake in the configuration
Red
The motor line has been given alarm signal
14.3 Motor group
All motor groups are to be assigned to a smoke zone and multiple motor groups can be assigned to the same smoke zone. See the example "Example of motor lines / motor groups / smoke zones" in the beginning of this chapter for further details.
When configuration specify the number of the smoke zone that are to control the motor group.
14.3.1 Motor group - configuration
Press ”Motor group” and the overview of the motor groups in the smoke ventilation panel is shown.
Motor group configuration
Motor group overview
Motor groups are to be configured in:
1. Controlling smoke zones
2. Comfort open position
3. Comfort open close time
4. Use ‘safety‘ from smoke zone
5. Wind directions where to close during alarm
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
14.3.2 Colour code – motor group
The overview fields on the touch screen have colour codes for the motor groups:
Colour
Meaning
Yellow triangle icon
One or more of the assigned motor lines has a failure
Black text
The motor group is configured
Green field
All the assigned motor lines are closed
Light grey number
The motor group is configured but no motor lines are assigned
Blue ?
Configuration is missing or there is a mistake in the configuration
Red
The motor group has been given alarm signal
14.4 Break glass unit
A break glass unit shall be assigned to a smoke zone and multiple break glass units can be assigned to the same smoke zone. See the example "Example of motor lines / motor groups / smoke zones" in the beginning of this chapter for further details.
14.4.1 Break glass unit – configuration
First the break glass units must be configured according to the topology (if they are connected one by one or in a ring) and then follow the individual configuration of the break glass units according to smoke zones, comfort motor groups etc.
To be sure it is the right glass break unit that is configured; it is possible to locate the break glass unit in one of two ways:
1. Press the reset button and a blue speech bubble will appear in the selected break glass unit in the overview of the break glass units.
Page 36
36
2. Press the number of the selected break glass unit on the overview on the touch screen → press until the menu point appears – “bip 1min for locating” is shown → press ”No” → select ”Yes”. The selected break glass unit will now beep if the door on the break glass unit is closed.
Topology
The break glass units are monitored and the connection of the break glass units to the smoke ventilation panel depends of the number of smoke zones:
1. when 1 smoke zone the break glass units are connected in series and connected directly to the WCA 3SP card
2. when 2 smoke zones the break glass units are connected in each their series and connected directly to the WCA 3SP card
3. when 3 smoke zones the break glass units are connected in a ring See section ”10.4 main control card WCA 3SP” for further information on connection of break glass units. Note: The break glass unit must be set in ring and the setting to "Yes" to have the error indication on the ‘All’ (group field) on the
overview of the break glass units.
Break glass unit configuration
Overview ’Break glass units
Overview ’Break glass units
Break glass units are to be configured in:
Configuration of ‘Topology’
‘All’
1. Bus topology is ring - see text about “Topology” below
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
Configuration of a selected ‘Break glass unit’
- shown for no.1
The numbered break glass units
1. Device type
2. Serial number: the break glass unit’s unique serial no. is shown
(cannot be configured)
3. Associated smoke zone
4. Use comfort inputs in smoke zone
5. Comfort motor group
6. Br.glass unit+sensor same smoke zone
6.1 Smoke sensor associated with smoke zone (displayed
only if ‘Other smoke zone‘ is selected)
7. Unit beep 1min for locating
8. Delete this unit
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
Page 37
37
14.4.2 Colour code – break glass unit
The overview fields on the touch screen have colour codes for the break glass units:
Colour
Meaning
Yellow triangle icon
Sensor error
Black text
The break glass unit are assigned to a smoke zone
Blue speech bubble
The reset-button in the break glass unit is pressed down (used when detecting break glass unit)
Light grey number
The break glass unit is not assigned to a smoke zone
Blue ?
Configuration is missing or there is a mistake in the configuration
Red
The alarm button in the break glass unit is pressed down (alarm signal)
14.5 Smoke zone
Here is to be configured master/slave and control zones. Here can also be configured e.g. different opening limits of the windows when alarm is triggered.
Smoke zones configuration
Overview ’Smoke zones’
Overview ’Smoke zones
The smoke zone are to be configured in:
Configuration of ’All’
All
1. High temp. target smoke zones
2. High temp. target smoke zone function
3. Slave target Smoke zone
4.
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
Configuration of a specific ’Smoke zone’
The numbered smoke zones
1. Reset higher priority than break glass unit (Line A) – see
explanation and table below
2. Buzzer active during alarm
3. Controlled smoke zone
3.1 Target smoke zone function (displayed only if one or
more smoke zones is/are selected)
4. Error generates alarm
5. Line B (smoke detector) smoke opening pos.
6. Use comfort commands
7. Wind direction speed threshold
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Page 38
38
Line
Some of the functions referrers to ‘Line’
The % value for the lines is configurable for each smoke zone. This is done in ‘View all details’. Furthermore, in “View all details”
– “Smoke zone” Line E and Line F can be given the highest priority, this is only used for fireman’s override panels.
Line % Function
Used for
A
100%
open
break glass unit
B
100%
open
smoke detector
(Switzerland: the value is often set to 0%, thus the windows will close when smoke)
C
100%
open
D
0%
close
E
100%
open
F 0%
close
Reset
if this is selected the chosen function(s) will be reset
Number of smoke detectors to give an alarm:
If it is selected, that the alarm is only triggered when more smoke detectors give alarm, the smoke detectors are to be connected to separate break glass unit – see drawing:
14.6 Local input
The smoke control unit has nine inputs on the main control card. If further inputs are needed, the input card WCA 8KI (requires the motor line card) can be added. This card has ten local inputs.
The touch screen has an overview of the local inputs.
14.6.1 Numbering of local inputs
All local inputs are numbered. The number of the input depends on its location on a card - see overview below.
Smoke ventilation panel with input card
Page 39
39
14.6.2 Local input - configuration
If component are installed in one or more inputs, these inputs are to be configured. Which item to be configured depends on the type of input – see description below.
Local input - configuration
Overview ’Local input’
Example of overview ’Local input’ with connected input card (WCA 3KI)
Overview ’Local input’ - more
“S3 Close” and “S3 Open” are the two buttons on the board. Pressing “-“ in the “Local Input” menu, the status of the local and
Master safety signal are shown. Used to associate Master Safety signal to Motor groups.
Local inputs are to be configured in:
Configuration of local input on X7
Input X7 on WCA 3SP (smoke detector)
If a smoke detector is connected in the local input X7 on the WCA 3SP card, it shall be configured in:
1. Input type: informs the type “smoke detector” (not to be configured)
2. Control smoke zones
2.1 Function in controlled smoke zones (displayed only
if ‘Control smoke zones‘ is selected)
3. Active state
4. Threshold short-circuit error
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Page 40
40
Configuration of local input X3 and X4
Input X3 and X4 on WCA 3SP and X1-X10 on WCA 8KI (binary)
If local inputs are connected on the card/cards WCA 3SP and/or WCA 8KI, it/they shall be configured in:
1. Input type: informs the type of the input “Binary) (not to be configured)
2. Control smoke zones*
2.1 Function in controlled smoke zones (displayed only
if ‘Control smoke zones‘ is selected)
3. Control motor groups*
3.1 Function in controlled motor groups
3.2 Short output function
4. Active state
5. Thresholds configuration
* The input can either control smoke zones or motor groups. When
one is selected the other option will disappear from the touch screen.
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Configuration of local input X8 on
the WCA 3SP card
Input X8 on WCA 3SP (24V/48V) (primary used in France)
If there is connection in X8 on the card WCA 3SP, it shall be configured in:
1. Input type informs the type “24/48V” (not to be configured)
2. Control smoke zones
2.1 Function in controlled smoke zones (displayed only
if ‘Control smoke zones‘ is selected)
3. Active state
The appendix contains all the items that can be configured - see appendix for detailed explanation.
14.6.3 Usage of wind/rain sensors - WLA 33x
Usage of wind/rain sensors WLA 33x with motor groups (MG):
The used input e.g. S1X10.5 is configured to “Control motor groups”, the groups are chosen.
Then, in the menu “Active function in controlled motor groups” the
function “Safety” is selected.
Then, a function for the motor group when inactive can be selected “Inactive function in the controlled motor groups”.
By each motor group it is possible to define the max opening for
“Safety”, meaning it is possible to allow windows and louvers inside
the building to open despite “Safety” (wind/rain). Facade windows, which are allowed to open e.g. 10%, to open
despite it rains.
Input shall be configured in:
Configuration of local input
1. In the motor groups configure the input with the function “Safety“.
2. Configure the motor groups when anything else than close (0%) is desired.
Note: motor groups also receive “Safety” signals from the smoke
zones they are associated with, see below for further information.
Page 41
41
Usage of wind/rain sensors WLA 33x with smoke zones (SZ):
The used input e.g. S1X10.5 is configured as “Control smoke zones”
with the function “Comfort safety”
When an input is configured as “Smoke zones” and “Comfort safety”
has been selected, there must in the configuration of all the motor groups be selected “Yes” to “Use ‘safety’ from smoke zone”.
If there in the configuration of the smoke zone has been chosen a slave-smoke zone, safety information is automatically transmitted to the slave smoke zone.
Input shall be configured in:
Configure the input with “Comfort safety” as “Function in controlled
smoke zones”.
1. Configure the motor groups to “Use ‘safety’ from smoke zone” = Yes.
2. Configure if needed also the motor groups in the slave zones with
“Use ‘safety’ from smoke zone” = Yes.
Note: when associating an Input with “Safety comfort” function with
either a motor group or a smoke zone, all smoke zones will receive a “Local Safety” signal. If a motor group associated with a smoke zone, should not react to safety signals, you have to configure the motor group with “Use ‘safety’ from Smoke zone” = No.
14.7 Local output
On the WCA 3SP card the smoke ventilation panel always has one output (X9.1 / X9.2) for fault signal to Fire Alarm System (not configurable output).
Page 42
42
14.7.1 Numbering of local output
All local outputs on the WCA 3SP card are numbered. The number of the output depends on its location on the card - see overview below.
As the output (fault signal to Fire Alarm System) on the WCA 3SP card cannot be configured it is not numbered.
Smoke ventilation panel with motor line and input cards
14.7.2 Local output - configuration
If component are installed in one or more outputs, these outputs are to be configured. Which item to be configured depends on the type of output – see description below.
Local output - overview
Overview ’Local output’
Overview ’Local output’
Local output shall be configured in:
Configuration of a local output
(shown for S1 X9.3/4)
1. Output type: informs the type ‘Binary output’ (is not to be configured)
2. Output mode
2.1 Controlled by smoke zones (displayed only when ‘Siren‘ is
selected)
2.2 Time out
2.3 Smoke zones output functions
3. Controlled by smoke zones* (displayed only when ‘output
mode is selected to ‘Binary output‘)
3.1 Smoke zone output functions
3.2 Logic function
3.3 Status when active
3.4 Time out
4. Controlled by motor groups a) Motor group output function b) Logic function c) Status when active d) Time-out
* The output can either control smoke zones or motor groups. When one is selected the other option will disappear from the touch screen.
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Page 43
43
14.8 Weather station type
Here is to be selected which type of weather station –none, WOW or WLA - that is connected.
(The menu “Weather” is only used for input from WCA 3SP input S1X10.2 for wind speed from WLA 340. Input S1X10.2 is also
used in combination with weather station WOW 201/202/204 for wind direction dependent smoke ventilation - see section 10.4 in the installation instruction).
WLA 33x is not considered as a weather station and is connected directly to the input X10.5, see section 14.6.3
Weather - configuration
Overview ’Sensor type’
Overview ’Sensor type’ (selection of type of weather station).
If several WSC 3x0 panels are connected via a WSK-Link™, the WSK-Link™ allows the panels to share weather data. The panel with the connected weather station will be the master. The first time a slave panel discovers a master panel, the “WSK­Link™ Master present” will become true.
In the slave panels ”Sensor type” should subsequently be set to “WSK-Link™” in order for them to receiver weather data from the master.
Weather shall be configured in:
Configuration of the sensor
None
(no configuration)
WOW
1. Filter constant
2. Slow filter constant
3. Use RMS in filter
The appendix contains all the items that can be configured - see appendix for detailed explanation.
WLA
1. Pulses/sec. per m/s
2. Filter constant
3. Slow filter constant
4. Use RMS in filter
The appendix contains all the items that can be configured - see appendix for detailed explanation.
From WSK Link™
(no configuration)
Only to be set in slave panels connected to a master panel with connected weather station.
Page 44
44
14.9 Sequence control
The sequence control functionality is used where the movement of a motor line must depend on an external event or situation/stage. To be used where window flabs are overlapping or where the windows cannot open (more than 15%) if the blinds are down a.s.o.
The sequence control can be controlled depending on;
- the position of a different motor line
- the state of a local input
- the state of a KNX object
- the state of a BACnet object
Sequence control configuration
Activation of sequence control
The activation of sequence control is to be done for each motor line.
Sequence control configuration
The function for the sequence control is to be configured for each motor line
1. None - This motor line does not use sequence control
2. Open - This motor line must wait for a “result” before opening
3. Close - This motor line must wait for a “result” before closing
Sequence control configuration – motor line
1. Sequential control position limit the max position the motor line is allowed to have without the „result“ is being fulfilled. For MotorLink® motor lines stepless variable. For ±24 Volt motor lines 0 or 100%
2. Sequential control with (upon what should the motor line wait?)
1. Motor line.
2. Local input
3. The state of a KNX object
4. The state of a BACnet object
3. Sequential control with No Upon which number should the motor line wait
4. Sequential control position logic In which positions should the sequential control be active
14.10 Magnetic clamp (magnetic door retainer)
Motor lines (only ±24 Volt motor output) can be defined as magnetic clamps. Per panel up to max. 6A for WSC 320 and max. 3A for WSC 310 can be used for magnetic clamps, the remaining 14A and 7A respectively are reserved for motors. If a motor line is defined as magnetic clamp there will be power on the output as long as the panel is not triggered in fire condition. If a motor line is defined as a magnetic clamp there will be no need of cable monitoring, as a cable error will have the same function as fire condition. The cable monitoring can be selected if an error on the cables is to be shown. Note, in case of mains power failure, the output will also loose its power and the magnetic clamp will release the door.
Technical data:
- Power consumption per magnetic clamp: minimum 5mA
- Current for magnetic clamp: maximum 6A for WSC 320 and maximum 3A for WSC 310
Page 45
45
The CompactSmoke™ is tested with Hekatron THM 425-1. Technical data (of Hekatron):
Configuration of magnetic clamp
Configuration of magnetic clamp
The configuration of magnetic clamp must be done for each motor line.
Under the configuration of Motors line select Magnetic clamp.
Each motor line which is configured to a magnetic clamp must be associated with a motor group.
14.11 Master / Slave connection of smoke zones
The master/slave connection between two panels is done via input X5 or X6 on the master panel – the input, also used for connection to a break glass unit – and input X11 on the slave panel. A smoke panel can have a master/slave connection to several smoke panels. However, the total max number of connected slaves AND break glass units on the bus must not exceed 10 units.
The total cable length must not exceed 200m, see examples below for how to connect the panels. A slave panel can only have one master, whereas a master panel can have several slaves and a panel can both be a slave and
a master to other panels.
Page 46
46
When panels are physically connected through the WSK-Link™ (the Master/Slave connection), safety signals and weather data signals are automatically distributed among the connected panels. Use the [ - ] button in the “Local Input” menu to associate Motor Groups with a Safety signal coming from the WSK-Link™. All Motor Groups are associated with this signal as a default. All smoke zones are automatically associated with the safety signal, this include smoke zones, which are independent from the master-slave setup. If a motor group associated with a smoke should not react to safety signals, you have to configure the
motor group with “Use ’Safety’ from Smoke zone” = ‘No’ “. Select “From WSK-Link™” in the “Weather” “Sensor type” menu to be able to use wind speed and wind direction signals coming
from the Master panel.
Configuration of Master – Slave system:
A connected slave panel is shown on the master
panel’s touch screen.
When two panels are connected to each other in a master-slave connection, the slave panel will appear as a green break glass unit on the master’s touch screen.
Connected panels (#1) are always shown before connected break glass units (#2 & #3).
The slave panel’s appearance on
the master panel
On the master’s touch screen the Device type of the slave will
appear as a WSC 3xx.
Page 47
47
Configuration of master slave connection
on master panel
To associate the slave panel with a smoke zone enter the smoke zone on the master panel.
The associated smoke zone on the slave panel
The smoke zone will immediately be sent to the slave panel.
Components – break glass units, comfort key pads etc. – connected to the slave panel are configured in the same way components connected to the master or a normal panel.
All signals from components connected to the slave panel are automatically sent to the master panel, which then sends commands (smoke, comfort and safety) back to the slave panel. The slave panel only react to commands from their master, never from its local signals.
Signals from slaves and the master’s own connected components are treated on equal terms. To get the fastest response, it is recommended that break glass units are connected to the master.
14.12 Network
For configuring network addresses. The WCA 3SP card has a 10/100Mbit Ethernet connection. The connection support DHCP or static IP address as well as
Gateway It is possible to configure different power consumption profiles for the Ethernet connection. To burden the 72 hours back-up
batteries as little as possible, use the setting ‘Off’ or ‘Auto’ (factory setting). The appendix contains all the items that can be configured - see appendix for detailed explanation.
Network is used in with BACnet IP interface – contact WindowMaster for further information.
Network shall be configured in:
Configuration of ’Network’
1. DHCP
2. Power setting The appendix contains all the items that can be configured - see
appendix for detailed explanation.
Page 48
48
14.13 Log in
The access level to the smoke ventilation panel is set in four levels.
Level
Access to
Who has access
1
Public You can see the smoke ventilation panel from the outside with the door closed and locked
Everyone
2
Operation You can open the panel house and operate the touch screen for showing the status and manual operating of the windows.
All the menus on the touch screen can be viewed but no values can be changed.
Chosen persons with a special key
3
Configuration You can open the panel house and operate the touch screen for showing status, manual operating of the windows as well as configuration and changing the pre­set values.
All the menus and sub menus can be seen and the values can be changed. Access Level 3 can be locked with a PIN code, so there is only access to the
level when the PIN is entered
Chosen persons with a special key and having the PIN code for access to level 3.
PIN code pre-set to
4321. The user is on access level 2
The user is at access level 2. To open for access level 3, enter the PIN for access level 3.
Enter PIN code
Enter PIN code.
Access approved to login level 3
The user is at access level 3.
Page 49
49
Login shall be configured in:
Configuration of login
The access levels can be locked and access to the level is only possible with a PIN code. Each level has a unique PIN code.
1. PIN 3: Configuration
2. Log out time-out (the period of access to the level before the
system automatically lock the level)
The appendix contains all the items that can be configured - see appendix for detailed explanation.
It is possible to lock the touch screen before the time has expired: press followed by pressing
14.14 Configuration files on USB
The panel has a plug in for an USB stick. It is possible to save all the configurations of the panel and this way save the stick as documentation. It is also possible to reinstall from the USB stick.
Files on the USB stick can be printed from a computer.
Configuration ‘Configuration, files on USB’ -
overview
Configuration files on USB – overview.
Configuration of ‘Configuration files on USB -
no.1’.
Configuration of configuration files on USB – shown for no. 1.
14.15 System
It is possible to change settings on the touch screen e.g. language, clock setting, date display, service timer etc.
System can be configured in:
Configuration of ’System’
1. Language
2. Backup time stamp (not to be configured)
3. Unsaved changes… (not to be configured)
4. Configuration command
5. Time
6. Date
7. Reset service timer
8. The interval between service
9. LCD rotate view
10. Enable parameter set from network
11. Enable remote control
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Page 50
50
14.15.1 Service timer
Configuation of interval between maintenance:
Reset off service timer
”Reset service timer” set the last maintenance date as today.
Configuration of interval between service
The timer is set in “The interval between service”. Typically, on most
markets, this will be 365 days. If the interval between maintenances is set to 0, the timer is disabled.
Under “View all details” the acoustic notification can be activated or
deactivated.
Message when the service timer expires
When the service timer expires the touch screen will show a maintenance text and a clear beeping will sound from the panel.
Under “View all details” the acoustic notification can be activated or
deactivated.
Main overview when the service timer
has been postponed
If you confirm the service timer by touching the touch screen, it will be mute for a week, before the beeping sound starts again.
A maintenance icon will appear on the touch screen.
Under “View all details” the acoustic notification can be activated or
deactivated.
Page 51
51
14.16 Fieldbus (KNX and BACnet)
Only when an Fieldbus card with a fieldbus interface is added to the smoke panel will the menus associated with the vairious fieldbus options be shown.
Fieldbus example
An optional card with fieldbus interface is added to the panel and the menus (e.g. configuration) now includes KNX and BACnet.
When the Fieldbus card is mounted a set of KNX or BACnet objects are available for each motor line, motor group and smoke zone, which provides the options for status and commands.
Status objects
E.g. actual position, fault and operation status and the max opening angle (degrees).
Command objects
E.g. target position commands with different priority and MotorLink® motor speed.
Fieldbus link - "Conn. 1-10 "
The KNX or BACnet has also 10 configurable binary communication objects. These can either be used for sending comfort commands to one or more motor groups or to give selected status from smoke zones or motor groups.
See "KNX Application Program Description or "BACnet PICS” on the home pages (www.windowmaster.com) for further information
on available KNX or BACnet communication objects.
14.16.1 KNX configuration
KNX bus overview – object configuration
Overview of the KNX objects. For each KNX object a direction must be configured
- None
- Input
- Output
When objects are configured as inputs or outputs, the controlled motor group or smoke zone as well as its function must also be configured.
KNX bus shall be configured in:
For all the objects the Power setting for the KNX bus must be configured.
Page 52
52
14.16.2 BACnet configuration
BACnet overview – object configuration
Overview of the BACnet objects. For each BACnet object a direction must be configured
- None
- Input
- Output
When objects are configured as inputs or outputs, the controlled motor group or smoke zone as well as its function must also be configured.
BACnet shall be configured in:
For all the objects
1. BACnet IP UDP port number
2. BACnet IP device instance
3. Actual position COV increment
4. Actual max. position COV increment
5. High speed COV increment
6. Wind direction COV increment
7. Register as “foreign device”
15 Status – main menu
In 'Status' you can see the status of all the menu items that can be configured under 'Configuration' as well as e.g. the status of the power supply (including mains and battery status) and slots (inform the type of card in the slot).
Main overview: status of the system
Under ‘Status’ is possible to view the status for:
1. Motor line
2. Motor group
3. Break glass unit
4. Smoke zone
5. Local input
6. Local output
7. Power supply
8. Network
9. Slots
10. Configuration files, USB
11. System
It is not possible to configure the items in ’Status’ mode. The appendix contains all the items shown in ‘Status’ - see appendix for detailed explanation.
16 Manual operation – main menu
It is possible to operate the motor lines, the motor groups and the smoke zones direct on the touch screen.
Main overview: manual operation
What to be manually operated:
1. Motor line – see text below
2. Motor group
3. Smoke zone
Page 53
53
Operation types
Motor lines and motor groups They can be operated absolutely (percentage of full open) or relatively on the keypad ‘open/stop/close’ showed on the touch screen.
Smoke zones They can be operated in ‘Alarm’ or ‘Reset’
Example
Manual operation of a motor line
- If ’All’ is selected all the actuators are operated simultaneously.
- If a motor line number is selected only the selected motor line is operated.
Motor line – overview
One motor line is selected
Manual operation on the touch screen
17 Configuration missing – main menu
If any components, motor lines, motor groups or smoke zones are not configured they are listed here. If you are logged into access level 3 it is also possible to configure from this menu.
18 Hardware error – main menu
If there are any hardware error on the panel, they will be displayed here. E.g. if the motor lines are not configured, the main supply is cut of, the back-up batteries are not connected, the type of weather station is not selected etc.
If you are logged into access level 3 it is also possible to configure from this menu.
18.1 Error on the Power supply
Mains power failure will trigger an error on the “Power supply”. Within the first minut after the failure has been detected, the green LED in the break glass unit will start to blink. After 30 minutes (parameter setting), the error is indicated on the touch screen and the windows will open (if this has been specified).
Futhermore, non connected, wrong connected or ”dead” batteries can trigger an error on the ”Power supply”.
Error on the power supply
Error on the Battery status
Page 54
54
18.1.1 Blown battery fuse – 20A fast
Additionally, an error on the ”Battery status” can also be triggered if the fuse (20A fast) is blown.
The fuse is located in bottom left corner of the main card.
Location of 20A fast fuse
19 View all details – main menu
To make the configuration of the smoke ventilation panel as simple as possible during configuration, it is only possible to configure the most used functions.
Under 'View all details' is displayed all of the above functions together with detailed functions that are not used as often, but are possible to configure. If you are logged into access level 3 it is also possible to configure from this menu.
It is possible to view all details for:
Motor line Motor group Break glass unit Smoke zone Local input Local output Weather Power supply Network Slots Log in Configuration files, USB System
20 Remote control of CompactSmoke™
It is possible to remote control a CompactSmoke™ from a PC. When the CompactSmoke™ is on a standard computer network (Ethernet) you can from any PC with the
“WMaFlexiSmokeRemote” program control the CompactSmoke™ just like if you were standing in front of the panel. If the CompactSmoke™ is not connected to a network then it can be remote controlled via a USB connection using the “WMaFlexiSmokeRemote” program.
The program ”WMaFlexiSmokeRemote” can be downloaded from our webpages (www.windowmaster.com) under WSC 310 or WSC 320.
Page 55
55
Remote control can be configured in:
Configuration of remote control
To enable remote control of the panel it is necessary to allow remote control. This is done in the configuration of the system.
Identification of the IP-address
IP-address of the CompactSmoke™
Screen shot from the PC when controlling
the FlexiSmoke™ remotely
Start the ’WMaFlexiSmokeRemote program’ on the connected PC. Enter the IP-address and press ’Connect’.
21 Commissioning and test run
In case of hardware error, please see chapter 18 “The menu ‘Hardware error’” The break glass unit WSK 50x will only give an acoustic fault signal if the door on the break glass unit is closed or if the door contact on the break glass unit is pressed.
We recommend that the software of the panel is updated during the annual maintenance check! We recommend that the commissioning of the smoke panel should be done by a competent smoke ventilation controls installer.
21.1 The control ventilation panel is completely installed, without the operating voltage applied
a) Check all mechanical and electrical components for damage. b) Check all screw and plug connections for tightness and/or firm seating c) Check that all external components are installed:
1) ±24V actuators: Is the motor end module inserted in the last or only actuator?
2) Automatic smoke detectors: Is the passive end module inserted in the last or only smoke detector?
21.2 With mains voltage, without accumulator
Adhere to the relevant regulations! Connect the mains cables and reapply the mains voltage.
Page 56
56
21.3 With mains voltage, with accumulator
a) Remove the protection film from one face of the supplied foam rubber. Glue each foam rubber to the bottom side of the
accumulators. Connect the accumulators to the black accumulator bridge according to the wiring diagram, then connect the red and the black connection cable to the red and the black flat plug. Remove the bottom protection film of the foam rubber and insert the batteries in the smoke ventilation panel according to chapter 12 “Back-up batteries”, and firmly press down to the housing bottom!
b) Plug the red connection cable to the + and the black connection to the flat plug of the control panel.
Note: Check correct polarity!
c) The smoke ventilation panel can now be configured as described in chapter 14 “Configuration – main menu”
21.4 Ventilation keypad
Closely observe the actuators during opening and closing. They must not be impaired in any position by the building structure. Observe that the actuator cables are not being subject to pulling or pinching. Check each ventilation keypad individually.
21.5 Break glass unit WSK 50x
a) Open the door and press the red Open button. The actuators move open through to the end position. The red alarm LED
(also in the control panel) is ON; at the same time a permanent acoustic signal sounds (door contact on the break glass unit is pressed!).
b) Press the Reset/Closed button in the break glass unit. The actuators close through to the end position. The comfort
ventilation function is released again. The red alarm LED (also in the smoke ventilation panel) and the acoustic smoke alarm are turned off.
21.6 Smoke detectors
a) Spray test aerosol on the smoke detectors (aerosol item no. 9549). b) The actuators move open through to the end position. The red LED in the smoke detector, the red alarm LED (also in the
smoke ventilation panel) and the permanent acoustic signal in the break glass unit are ON.
c) Press the Reset/Closed button in the break glass unit - the actuators close through to the end position.
The comfort ventilation function is released again. The red alarm LED in the break glass unit and in the smoke control panel as well as the acoustic smoke alarm are turned off.
21.7 Emergency power supply test
a) Disconnect the mains power. See also national guidelines. b) When a mains error have occurred the green LED in the break glass units will flash for 30 minutes. The green LED on the
WCA 3SP card in the smoke ventilation panel is still on and the yellow LED is turned off.
c) After 30 minutes the green LEDs will turn off and all the yellow LEDs in the smoke ventilation panel and the break glass units
will lit continuously. d) Check that the comfort ventilation keypads are deactivated. e) Check that the break glass units are working (section 22.5) f) Connect the main power. g) The green mains and operating LED's are on, the yellow LED is off, the malfunction message at the break glass unit is off.
21.8 Wind/rain detector
a) Open the actuators with the comfort ventilation keypads. b) Wet the rain sensor, the actuators will fully close. c) While the actuators are running, press the Open button at the keypad. The actuators must neither open nor stop!
Exception: If set to a manual override time (Man. operation after auto comm.). d) Any smoke and heat extraction signal will always take priority over the wind/rain signal. e) While the rain sensor is active (wet) the smoke ventilation panel is activated (alarm) and the actuators move open through to
the end position (alternatively to the SHE position) If the start-up was successful, close the doors of the break glass units and of the smoke ventilation panel.
If the start-up was unsuccessful (error with one of the test run processes), please see chapter 10 “Description of cards”. If necessary, check the wiring in accordance with the cable plan – see chapter 9 “Cable plan for connection to WSC 3xx”.
22 Maintenance
The panels of the smoke and heat exhaust ventilation system have to be checked, serviced and, if necessary, repaired at least once per year by the manufacturer or an authorized partner.
Remove all soiling from the units of the smoke and heat exhaust system. Check fastening and clamping screws for firm seating. Carry out a test run of the entire system (see chapter 20 ‘Commissioning and test run). Only have defective units repaired in our factory. Only install original spare parts.
Check the operational condition at regular intervals. We recommend a WindowMaster service contract is taken out to ensure the right function of the smoke and heat exhaust system.
All back up batteries coming with the smoke control panel as standard; have to be subjected to regular checks.
Page 57
57
The smoke ventilation panel will signal fault on the batteries if the battery voltage is below 17V. Within the framework of the service, they have to be replaced after the specified maximum 4 year operating period.
Dispose of used batteries according to the National regulation. CAUTION: RISK OF EXPLOSION IF BATTERIES ARE REPLACED BY AN INCORRECT TYPE.
We recommend that the software of the panel is updated during the annual maintenance check! The expected minimum lifetime for the CompactSmoke™ is 10 years excluding the batteries.
22.1 Maintenance agreements
Be aware that regular inspection of smoke ventilation systems is a legal requirement. The legislation requires that the smoke ventilation system's owner inspects and tests the system once every year. WindowMaster offer maintenance agreements for the smoke ventilation system and every year we inspect the complete system to ensure it complies with the applicable legislation. Maintenance of the smoke ventilation system includes checking windows, window actuators and emergency power and checking that triggering and control functions are fully functional.
Contact our service department for further information: telephone +44 1536 61 4070 or [email protected]
22.2 Replacement cards
22.2.1 Replacement of 3M8 and 3KI cards
1. Disconnect the 230 V and the batteries.
2. Wait until the display has completely turned off before removing the card.
3. Insert the replacement card.
4. Turn on the 230 V and connect the batteries.
5. The system will be ready again after approx. 2 seconds.
22.2.2 Replacement of 3SP card
1. Save a backup of the configuration on a USB stick (recommended).
2. Disconnect the 230 V and the batteries.
3. Wait until the display has completely turned off before removing the card.
4. Insert the 3PS replacement card.
5. Insert the USB stick into the new card.
6. Turn on the 230 V and connect the batteries.
7. Load the parameters from the USB stick
8. The system will be ready again after approx. 2 seconds. If the WCA 3SP card, which is to be replaced, is completely without function then go straight to point 2. If there is no backup of the configurations, these are to be entered manually.
It is therefore recommended to take a backup, on a USB stick, when the panel is running, if necessary please see section 14.14.
23 Declaration of Conformity and Declaration of Perfomance
The smoke ventilation panels are manufactured and tested accordingly to the European requirements. The total system is not to be put into service until a declaration of conformity for the total system has been made.
The “Declaration of Conformity” and the EN certificate are supplied with panel as separate documents.
Loading...