
WSC 304 6102 install 1806-UK ©WindowMaster 2009, 2018 ®WindowMaster is a registered trademark used under licence by WindowMaster International A/S
WindowMaster International A/S, Skelstedet 13, DK-2950 Vedbæk
WSC 304 6102
Smoke control unit
Operating manual / Technical information
Table of contents:
Safety information
Operating elements and fuse review
Technical data
Installation
Cable lengths table
Cable plan
Standard wiring diagram
Various wiring diagrams
Commissioning
Maintenance
DK +45 4567 0300 info.dk@windowmaster.com
DE +49 (0) 40 87 409 -560 Vertrieb / -484Technik info.de@windowmaster.com
CH +41 (0) 62 289 22 22 info.ch@windowmaster.com
UK +44 (0) 1536 614 070 info.uk@windowmaster.com
Other markets +45 4567 0300 info.dk@windowmaster.com www.windowmaster.com

Safety information
__________________________________________________________________________
2
Only allow correspondingly trained, qualified
and skilled personnel to carry out installation work.
Reliable operation and the avoidance of
damage and hazards is only guaranteed if
installation and settings are carried out carefully
in accordance with these instructions.
Check the technical data on the system plate.
Hazards to persons ensuing from flaps and
wings operated by electric motors.
The forces occurring in the automatic mode can
be such that parts of the body could get crushed.
ed, actuators could protrude into the
For this reason, measures have to be taken
prior to starting up the actuators which exclude
With wings tilting inwards or outwards, the wing
must be protected from hinging down once the
actuator is unhooked (e.g. for window cleaning).
For safety reasons we recommend the use of
In the event that wings or flaps are subjected to
high wind loads, we recommend to connect the
central control unit to a wind detector which
automatically close the flaps.
The fastening methods are exclusively intended
for the intended use for which they are designed
The manufacturer does not assume any liability
for possible damage resulting from inappropriate
Can cause death, severe injury or considerable
The connection of the control system is reserved
Disconnect all poles of the unit from the supply
voltage prior to opening, installation or
assembling. Adhere to the national regulations.
230V AC dangerous voltage
Cable routing and electrical connection
Leave the insulation of the power supply
cable in place up to the mains terminal.
Manufacturer's declaration
The central control system is exclusively designed
for the automatic closing of smoke extraction
systems, windows, flaps or doors.
Always check that your system meets the valid
Pay particular attention to the opening cross section,
the opening time and opening speed. The cable cross
sections depend on the cable length and current
Where devices are used in smoke and heat
extraction systems, ensure that they are checked,
maintained and, if necessary, repaired a
Remove all soiling from the devices,
check the fastening and clamping screws for firm
seating. Trial run the entire system.
Defective devices may only be repaired in our factory
Only use original spare parts.
The supplied accumulators are subject to regular
checks and must be replaced every 4 years.
Fuse the 230V AC power supply cable separately on
Adhere to the DIN and VDE regulations (Germany)
or equivalent in your country.
Establish the cable types, if necessary, wi
approval bodies or the fire protection authority.
Do not conceal flexible cables. Junction box
must be accessible for maintenance purposes.
Disconnect all poles of the mains voltage and the
accumulators prior to starting maintenance work or
making changes to the system.
Secure the system to prevent unintentional switching
Design cable types, lengths and cross sections in
accordance with the technical information.
Route all low voltage cables (24V DC) separate from
The devices have been inspected and manufactured
in accordance with the European directives.
A corresponding manufacturer's declaration is
You are only authorised to use the devices if a
conformity declaration is issued for the entire system.
Adherence to the following information is mandatory:

Operating elements and fuse review
____________________________________________________________________________
3

Technical data
____________________________________________________________________________
4
Smoke and heat extraction system alarm trip:
The acoustic signal will only sounds in the break glass unit if the door is closed or if the door contact switch is
pressed.
Break glass unit:
Break the glass in the break glass unit! Press the red button min. 0,5 sec.. The smoke extraction opens.
An acoustic alarm signal sounds (continuous sound) in the break glass unit.
All ventilation functions are out of operation.
Display: The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit.
Smoke detector:
If smoke develops, the smoke extraction system automatically opens.
An acoustic alarm signal sounds (continuous sound) in the break glass unit.
All ventilation functions are out of operation.
Display: The red alarm LED in the smoke control unit, the red LED in the break glass unit, and the red LED at
the tripped automatic detector are lit.
Reopening the actuators
The first 30 min. after a SHE-trig the actuators will be cyclically activated every 2 min in OPEN direction (to
loosen frost fastened windows, domes e.g.).
Resetting a tripped smoke control unit:
Press the „CLOSE button“ in the break glass unit or the „Reset button” in the smoke control unit.
The acoustic alarm signal in the break glass unit stops sounding.
The ventilation functions are operational again once the smoke extraction system has closed.
(Prior to resetting, blow out or replace the detector after it was tripped by an automatic detector).
Display: The red alarm LED in the smoke control unit, the red LED in the break glass unit, and the red LED at
the tripped automatic detector extinguish.
Resetting a trip caused by high temperature:
The smoke extraction system can be closed again by pressing the „Reset button“ in the smoke control unit or
the „CLOSE button“ in the break glass unit.
After operating the CLOSE function, an acoustic pulse tone sounds, and the flashing malfunction LED is only
displayed in the break glass unit. The green operation LED remains lit as a special fault diagnosis.
Operating the ventilation button, OPEN or STOP will lead to the tripping of another alarm.
Note:
The built-in thermal switch will then be irreversibly destroyed. The smoke control unit has to be returned for
checking.
Option: Alarm trip caused by a malfunction signal:
When this function is activated (SW2/1 = ON), the smoke control unit will trip in the event of a motor, smoke
detector or break glass unit circuit malfunction. An acoustic alarm signal sounds (continuous sound) in the
break glass unit.
If the temperature exceed 73°C the automatically SHE-alarm will be activated.
An acoustic alarm signal in the smoke control unit will start.
No trip occurs as a result of a malfunction in the mains or battery circuit.
Display: The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit.
The yellow malfunction LED in the break glass unit and the corresponding yellow malfunction
LED in the smoke control unit flash.
Option: Accumulative signalling of the alarm or malfunction signal
Module WSA 301:
It is possible to send an alarm or malfunction signal potential free, by plugging in the alarm/malfunction
signalling module.
The sending of the alarm can be stopped. If this is done, the yellow LED on the module will lit.

Technical data
____________________________________________________________________________
5
Cascading smoke control units:
The smoke control units can be cascaded by a monitored 2 wire connection from the alarm module of the
master smoke control unit to the smoke detector input of the slave central panel.
A malfunction in the cascaded smoke control units is detected via the 2 wire BUS cable. The malfunction is
only displayed in the corresponding smoke control unit and in the break glass unit connected to the master
smoke control unit.:
Ventilation functions:
Ventilation OPEN:
With the dead man's circuit activated (SW2/2 = ON), the actuators only move open for as long as the OPEN
button of the ventilation button is kept pressed.
If no dead man's function is activated (SW2/2 = OFF), the actuators open after pressing the OPEN button
(self hold).
Display: The ventilation open LED in the ventilation button is lit (only with LED integrated in the button).
Ventilation stop:
The actuators stop when both buttons are pressed.
Display: The ventilation open LED in the ventilation button remains lit (only with LED integrated in the button).
Ventilation closed:
The actuators close after pressing the CLOSED button.
Display: The ventilation open LED in the ventilation button has extinguished (only with LED integrated in the
button).
Option: Ventilation time module
Timemodule WSA 303:
Time to be set between 1 and 30 min. Once this time has elapsed, the actuators close after ventilation „OPEN“
or ventilation „STOP“. This function is not operative if the setting potentiometer is on the right-hand stop.
Wind/rain CLOSE:
The actuators close when the wind/rain sensor has tripped (potential free contact in the sensor switches). The
ventilation functions are out of operation as long as a tripped situation is pending.
The tripped signal is shown with the green wind/rain LED.
Alarm tripping has 1. priority.
Option: Transmission of the wind/rain signal
Module WSA 302:
The trip signal of the wind/rain sensor can be transmitted potential free to the next smoke control unit.
CLOSE after a power failure:
2 minutes after a power failure actuators opened for natural ventilation will automatically.
In the event of alarm, this function will be out of operation.
General information:
EMC protection:
All inputs and outputs are protected from coupled in interferences.
Short-circuit protection:
All outputs are protected against short-circuit and overload.