Window Master WCC 310 UL, WCC 320 UL Installation Instructions Manual

Page 1
US
  +1 650 543 8166
Other markets
  +45 4567 0300
WCC 3xx install 1711-Firmware v123 UL - UK ©WindowMaster 2016, 2017 ®WindowMaster is a registred trademark used under the license by WindowMaster International A/S WindowMasterInternational A/S, Skelstedet 13, DK-2950 Vedbæk
WCC 310 & WCC 320 UL
Plus versions
Installation instruction
UL MotorController
(Version 1711 – for firmware from version 1.23 (main card) &
from version 1.06 (motor line card))
Save this installation instruction to the end user
Page 2
2
1 Safety information ........................................................................................................................................................ 4
Safety ................................................................................................................................................................ 4
120V AC ............................................................................................................................................................ 4
Application ......................................................................................................................................................... 4
Cable routing and electrical connection ............................................................................................................. 4
2 Structure of the MotorController ................................................................................................................................ 5
3 Variants of MotorControllers ....................................................................................................................................... 6
MotorController version ..................................................................................................................................... 6
Max numbers of actuators per motor line and
MotorController ............................................................................. 6
4 Accessories and spare parts ...................................................................................................................................... 7
5 Technical data .............................................................................................................................................................. 8
6 Mounting ....................................................................................................................................................................... 9
7 Installation .................................................................................................................................................................... 9
Cable routing ..................................................................................................................................................... 9
Cables into housing ........................................................................................................................................... 9
Connection of safety earth wire and 120V AC ................................................................................................... 9
Installation of the ventilation keypad .................................................................................................................. 9
Assembly instructions ........................................................................................................................................ 9
8 Cable dimensioning ................................................................................................................................................... 10
Max. cable Length ............................................................................................................................................10
8.1.1 Formula for the calculation of the maximum actuator cable length ............................................................. 10
8.1.2 Max cable length – ±24V standard actuators .............................................................................................. 10
8.1.3 Max cable length – actuators with MotorLink® ............................................................................................. 11
9 Cable plan for connection to WCC 310 / 320 Plus version ..................................................................................... 12
10 Description of cards and mains connection ............................................................................................................ 13
WCC connection to mains and power supply units – WCA 3P3, WCA 3P4 and WCA 3P6 .............................13
Connections between cards .............................................................................................................................13
Main control card WCA 3CP – Plus Version ....................................................................................................14
Motor line card – WCA 3M4 / WCA 3M8 ..........................................................................................................21
Keypad card – WCA 3KI ..................................................................................................................................22
Power supply card – WCA 3P6 ........................................................................................................................23
Fieldbus cards ................................................................................................ ..................................................23
11 Touch screen .............................................................................................................................................................. 24
Icons .................................................................................................................................................................24
Rotation of the touch screen ............................................................................................................................25
12 Configuration – main menu ....................................................................................................................................... 25
Motor lines – motor groups ...............................................................................................................................25
12.1.1 Examples with motor lines / motor groups ................................................................................................... 25
Motor line .........................................................................................................................................................26
12.2.1 Motor line - numbering ................................................................................................................................ 26
12.2.2 Motor line - configuration ............................................................................................................................. 26
12.2.3 Colour code - motor line .............................................................................................................................. 27
Motor group ......................................................................................................................................................27
12.3.1 Motor group - configuration ......................................................................................................................... 27
12.3.2 Colour code – motor group .......................................................................................................................... 27
Local input ........................................................................................................................................................28
12.4.1 Numbering of local inputs ............................................................................................................................ 28
Page 3
3
12.4.2 Local input - configuration ........................................................................................................................... 28
12.4.3 Usage of wind/rain sensors - WLA 33x ...................................................................................................... 29
Local output ......................................................................................................................................................29
12.5.1 Numbering of local output ........................................................................................................................... 29
12.5.2 Local output - configuration ......................................................................................................................... 30
Weather station type ........................................................................................................................................30
Sequence control .............................................................................................................................................31
WSK-Link™ - master/slave connection ............................................................................................................32
Network ............................................................................................................................................................32
Log in ...............................................................................................................................................................33
Configuration files on USB ...............................................................................................................................34
System .............................................................................................................................................................35
Fieldbus (KNX and BACnet) .............................................................................................................................35
12.13.1 KNX configuration ....................................................................................................................................... 35
12.13.2 BACnet configuration .................................................................................................................................. 36
13 Status – main menu ................................................................................................................................................... 36
14 Manual operation and main menu ............................................................................................................................ 37
15 Configuration missing – main menu ........................................................................................................................ 37
16 Hardware error – main menu ..................................................................................................................................... 37
17 View all details – main menu ..................................................................................................................................... 37
18 Remote control of MotorController .......................................................................................................................... 38
19 Commissioning and test run ..................................................................................................................................... 38
The MotorController is completely installed, without the operating voltage applied .........................................38
With mains voltage ...........................................................................................................................................39
Ventilation keypad ............................................................................................................................................39
Wind/rain detector ............................................................................................................................................39
20 Maintenance ............................................................................................................................................................... 39
Maintenance agreements .................................................................................................................................39
Replacement cards ..........................................................................................................................................39
20.2.1 Replacement of 3M4, 3M8 and 3KI cards ................................................................................................... 39
20.2.2 Replacement of 3CP card ........................................................................................................................... 39
21 Declaration of Conformity ......................................................................................................................................... 39
Page 4
4
1 Safety information
Safety
Only allow correspondingly trained, qualified and skilled personnel to carry out installation work. Reliable operation and the avoidance of damage and hazards are only guaranteed if installation and settings are carried out
carefully in accordance with these instructions. There may be personal danger by electrically operated windows:
- the forces occurring in the automatic mode can be such that parts of the body could get crushed
- when opened, actuators (spindles) could protrude into the room For this reason, measures have to be taken prior to starting up the actuators, which exclude the danger of injury.
For safety reasons we recommend to install opening restrictors on bottom-hung windows. In the event that windows are subjected to rain and/or high wind loads, we recommend connecting a wind/rain sensor to the
MotorController for the automatically closing of the windows. The MotorController is to be located in a safe place, protected from the effects of fire and smoke.
The MotorController is to be surface mounted. The MotorController is supplied by 120 V AC The manufacturer does not assume any liability for possible damage resulting from inappropriate use.
120V AC
120V AC can cause death, severe injury or considerable damage to assets. The connection of the MotorController is reserved for qualified personnel. Disconnect all poles of the MotorController from the supply voltage prior to opening, installation or assembling. Installation and use according to the national regulations.
Application
The MotorController is exclusively designed for the automatic opening and closing of windows, flaps or doors. Always check that your system meets the valid national regulations. Pay particular attention to the opening cross section, the opening time and opening speed. The cable cross sections depend on the cable length and current consumption (amperage).
Cable routing and electrical connection
Fuse the 120VAC power supply cable separately on site. Cable routing and connection - adhere to national regulations. Establish the cable types, if necessary, with the local approval bodies. Do not conceal flexible cables. Junction box must be accessible for maintenance purposes. Disconnect all poles of the mains voltage prior to starting maintenance work or making changes to the system. Secure the system to prevent unintentional switching on again. Route all low voltage cables (24VDC) separate from the power current cables. Design cable types, lengths and cross sections in accordance with the technical information. Cable specifications is a guide only, the overall responsibility resides with the electrical contractor on site. Installation must be in accordance with the national electrical regulations.
Page 5
5
2 Structure of the MotorController
Sizes & Versions
The WCC 310 and WCC 320 MotorControllers are available in two different versions namely a Standard and a Plus version. This installation instruction only deals with the Plus versions. Please see separate installation instruction for the Standard versions of WCC 310 and WCC 320.
Cards
Each MotorController contains a power supply unit (SMPS), either a WCA 3P3 or a WCA 3P4 for the 10A or 20A version respectively, as well as a 5W auxiliary power supply. Aside from the power supply unit the Plus version also includes a main control card type WCA 3CP, which includes a touch screen for easy configuration of the MotorController. Motor line and input cards, as well as fiedbus cards, can be added to the MotorController depending on requirements.
Selection of cards
The Main control card type WCA 3CP allows connections of 2 motor lines and 2 keypads. If more than 2 motor lines or 2 keypads are required, the necessary cards can be added. Cards:
- WCA 3M4 motor line card, allows additional 4 motor lines.
- WCA 3M8 motor line card, allows additional 8 motor lines.
- WCA 3KI input card, allows additional 10 keypads (requires WCA 3M4 or WCA 3M8).
A fieldbus card must be added, if communication via KNX or BACnet is required. Fieldbus cards:
- WCA 3FK fieldbus card, fieldbus interface for KNX
- WCA 3FM fieldbus card, fieldbus interface for BACnet / MSTP
- WCA 3FB fieldbus card, fieldbus interface for BACnet IP
Installation of cards may only be done when there is no power on the MotorController. Motor line and input cards are ordered together with the MotorController and mounted to the MotorController from the factory side, whereas the fieldbus cards are delivered as individual products and are to be mounted by the customer – see separate installation manual for mounting of fieldbus card.
The item no. of the MotorController specifies the type and mounting of the cards - see "Variants of MotorController" for more information
Motor groups and motor lines
A motor group consists of one or more motor lines and all the motor lines are operated simultaneously. The motor lines on both the main control card (WCA 3CP) and the motor line cards (WCA 3M4 or WCA 3M8) can all be
configured for either a ±24V standard actuators or MotorLink® actuators. A motor group can contain motor lines with both ±24V standard actuators and MotorLink® actuators, whereas a motorline only can have ±24V standard or MotorLink® actuators connected.
Adding MotorControllers
The natural ventilation installation can be expanded by adding more MotorControllers and creating a master/slave connection among them. The master/slave connection is done directly on the WSA 3CP card. The total cable length between 2 MotorControllers must not exceed 200m.
Page 6
6
3 Variants of MotorControllers
Item composing
WCC 3
xx P xx
xx U1
U1 = UL Std. 325 and product version number 1
Input card* 02 = No input card 12 = Input card (10 additional keypad inputs)
Motor line card 02 = No motor line card 06 = Motor line card (4 additional lines) 10 = Motor line card (8 additional lines)
MotorController version P = Plus
MotorController size 10 = 10A 20 = 20A
MotorController series 3
*requires a motor line card
MotorController version
Number of motor lines and other functions
Cards
Item number
WCC 310 versions
Plus version 2 motor lines 2 keypads / inputs
1 x WCA 3CP
WCC 310 P 0202 U1
Plus version 10 motor lines 12 keypads / inputs
1 x WCA 3CP 1 x WCA 3M8 1 x WCA 3KI
WCC 310 P 1012 U1
WCC 320 versions
Plus version 6 motor lines 12 keypads / inputs
1 x WCA 3CP 1 x WCA 3M4 1 x WCA 3KI
WCC 320 P 0612 U1
Plus version 10 motor lines 12 keypads / inputs
1 x WCA 3CP 1 x WCA 3M8 1 x WCA 3KI
WCC 320 P 1012 U1
Max numbers of actuators per motor line and
MotorController
The table shows the maximum number of actuators, which can be connected per motor line and MotorController depending on the type of the actuator, MotorController and connected card. The total power consumption of all the connected actuators must not exceed 10A for WCC 310 and 20A for WCC 320.
Per motor linie
Per 10A MotorController
Per 20A MotorController
± 24V
actuators
MotorLink®
actuators
± 24V actuators
MotorLink® actuators
(10 Motor lines)
± 24V actuators
MotorLink® actuators
(10 Motor lines)
WMU 836-1
4 4 10
10
20
20
WMU 836-2
4 2 10
10
20
20
WMU 836-3
3 3 9 9 18
18
WMU 836-4
4 4 8 8 20
20
WMU 861-1
4 4 6 6 12
12
WMU 861-2
4 2 6 6 12
12
WMU 861-3
3 3 6 6 12
12
WMU 861-4
4 4 4 4 12
12
WMU 842 / 862 / 882-1
4 4 4 4 8
8
WMU 842 / 862 / 882-2
4 2 4 4 8
8
WMU 863 / 883-1
3 3 3 3 6
6
WMU 864 / 884-1
1 1 2 2 4
4
Page 7
7
Per motor linie
Per 10A MotorController
Per 20A MotorController
± 24V
actuators
MotorLink®
actuators
± 24V actuators
MotorLink® actuators
(10 Motor lines)
± 24V actuators
MotorLink® actuators
(10 Motor lines)
WMX 503 / 504 / 523 / 526-1
8 4 20
20
40
40
WMX 503 / 504 / 523 / 526-2
8 2 20
16
40
20
WMX 503 / 504 / 523 / 526-3
6 3 18
18
39
30
WMX 503 / 504 / 523 / 526-4
8 4 20
20
40
40
WMX 803 / 804 / 823 / 826-1
4 4 10
10
20
20
WMX 803 / 804 / 823 / 826-2
4 2 10
10
20
20
WMX 803 / 804 / 823 / 826-3
3 3 9 9 18
18
WMX 803 / 804 / 823 / 826-4
4 4 8 8 20
20
WMB 801/802*
max. 4A tilsluttet på WMB
WMB 811/812 */**
4 2 10
10
20
20
* Do not exceed the total power consumption of the motor line ** When having two locking actuators per motor line, it must be one of each type: 1 x WMB 811 and 1 x WMB 812
4 Accessories and spare parts
Accessories
Fieldbus card with field bus interface for KNX incl. cover – sold separately, not factory mounted
WCA 3FK
Fieldbus key with field bus interface for BACnet / MSTP incl. cover - sold separately, not factory mounted
WCA 3FM
Fieldbus card with field bus interface for BACnet-IP incl. cover - sold separately, not factory mounted
WCA 3FB
Rain sensor
WLA 331
Rain/wind speed sensor
WLA 330
Rain/wind speed sensor, with pulse output
WLA 340
Wind speed sensor & Wind direction sensor
WOW 201 & WOW 202
Bracket for junction box
WOW 203
Junction box for WOW 201 and WOW 202
WOW 204
Spare parts
10A power supply unit for WCC 310
WCA 3P3
20A power supply unit for WCC 320
WCA 3P4
5W 120 AC / 24V DC
WCA 3P6
Main control card for Plus version WCC 310 / WCC 320 incl. cover
WCA 3CP
Motor line card with 4 motor lines incl. cover
WCA 3M4 UL
Motor line card with 8 motor lines incl. cover
WCA 3M8 UL
Input card with 10 inputs for e.g. key pads incl. cover (requires WCA 3M4 or WCA 3M8)
WCA 3KI
Plastic covers for the cards in the WCC 310 / WCC 320 Plus version
WCA 301
Fieldbus card with field bus interface for KNX incl. cover
WCA 3FK
Fieldbus card with field bus interface for BACnet / MSTP incl. cover
WCA 3FM
3.15A fuse for motorline, 10 pcs (Littelfuse 807 13150440)
WCA 308
Page 8
8
5 Technical data
Technical data
Output current (nominal)
WCC 310: 10A / WCC 320: 20A
Secondary voltage
Voltage 24V DC (±15%) Open circuit voltage (no load) 27.6V DC @ 20°C Ripple at max load max. 6% (3.5Vpp)
AUX
24V DC, 0.23A
Motor lines
Motor groups
WCC 310 0202: max 2, WCC 320 1012: max 10 A motor line can contain either ±24V standard or MotorLink® actuators
WCC 310 0202: max 2, WCC 320 1012: max 10 Via the touch screen motor motorlines can be connected in the same group
Primary voltage
120V AC, 60Hz (85-264V AC, 47-63Hz)
Power consumption
Idle consumption WCC 310: min 2W1, typ. 4.2W
2
WCC 320: min 2W1, typ. 5W3
1) min.: 1 MotorLink® actuator
2) min.: 20 MotorLink® actuators + rain sensor
3) min.: 40 MotorLink® actuators + rain sensor Max:
WCC 310: At max load 305W WCC 320: At max load 605W
Inrush current on primary site
70A<5ms. Max 3 x WCC 310/320 per 10 A supply group. Circuit breaker “C” characteristic.
±24V change over time
min 500ms
Cable monitoring
±24V standard actuators with end of line module are monitored by closed-circuit Actuators with MotorLink® are monitored by data communication
LED message OK and fault
Green Yellow
CPU working fault
Connection cable
Actuators
Other components
Mains
flexible max 6 mm² / solide max 10 mm² Min. 22AWG, 300V, 80°C Listed / Recognized to UL 13
min 0.2mm² / max 1.5mm² Listed / Recognized to UL 13
Mains must be done per relevant Electrical Code.
For permanent connection (rigid or flexible 1/2’’ conduit or equivalent) use the supplied 1/2’’ adaptor
in the Knockout. Use 10, 12, or 14AWG conductors (same size).
Operating conditions
-5°C - +40°C, for indoor only, MotorController must not be covered
Max actuator activation duration (duty cycle)
ED 40% (4min. per 10min.)
Number of motor lines per card
WCA 3CP WCA 3M4 WCA 3M8
2 x 10A motor line for ±24V standard or MotorLink® actuators 4 x 10A motor line for ±24V standard or MotorLink® actuators 8 x 10A motor line for ±24V standard or MotorLink® actuators
Material
Metal housing for surface mounting
Colour
White (RAL 9010)
Size
355 x 320 x 76mm (HxWxD)
Weight
WCC 310: 4kg WCC 320: 4.8kg
Protection class
IP 20
Certification
UL 325 and CSA C22.2 no 247-14 approved
Delivery
MotorController
Note
We reserve the right to make technical changes
Page 9
9
6 Mounting
The MotorController is fixed to the wall through the Ø6mm holes in the back plane of the housing.
The MotorController is to be located in a safe place, protected from the effects of fire and smoke.
7 Installation
Cable routing
See also chapter 8 “Cable dimensioning” in this instruction. However, this has to be agreed with the Engineer. Do not reduce the cable cross sections specified in the cable lengths table. All cables of the control (except the mains supply cable) carry 24V DC and have to be routed separate from the mains supply cable. Adhere to the pertinent national and local regulations when routing the cables.
Cables into housing
All connection terminals (except the mains terminals) are of the plug-in type. Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made correctly. Incorrect cable clamping, mixing up numbers or colours could lead to malfunctions of the control MotorController or of the external components. Ensure that the electrical cables are always routed according to the valid national and local regulations.
Connection of safety earth wire and 120V AC
See chapter 10 ‘Description of cards’, for further description.
Installation of the ventilation keypad
Ensure that the ventilation buttons are visible and well accessible. Do not install behind protruding walls, door MotorControllers or hidden by the building structure.
Assembly instructions
Always have assembly, installation, repair and maintenance of ventilation systems carried out by qualified personnel trained for this purpose.
Rules to be adhered to for setting up and installation
The following safety relevant rules have to be adhered to when planning the use of a ventilation system and its set-up and installation:
• The Provincial Building Ordinance of the provinces
Accident prevention regulations
Adhere to the general accident prevention regulations (APR), the APR for power operated windows and doors, and the installation rules in your country.
CAUTION:
Live components are directly accessible after opening the system housing. Prior to inserting / removing cards disconnect to the MotorController from the mains supply.
• adhere to the installation instructions and your local energy providers
• select the place of installation such that free access is guaranteed for maintenance purposes
• select cables according to regulations in this instruction - take the calculation of the actuators supply cable lengths
into account when laying the cables
• connect the cables in accordance with the drawings provided by the manufacturer
• route the cables in the building according to the regulations in this instruction
• check all system functions
Page 10
10
8 Cable dimensioning
Max. cable Length
Maximum permissible cable length from the MotorController to the actuators taking into account the cable cross-section is shown in the following tables for “± 24V standard actuators“, “MotorLink® actuators“.
8.1.1 Formula for the calculation of the maximum actuator cable length
Max. cable length = permissible voltage drop 2V (UL) x conductivity of copper(56) x cable cross section in mm2 (a) max. actuator current total in amps (I) x 2
For both ±24V standard actuators and actuators with MotorLink® the cross section of the cable must not be less than 0.75mm2 regardless of the result of above formula.
Maximum actuator cable length: Always measured from the Motorcontroller to the last junction box + actuator cable Permissible max. voltage drop in the line: 2 Volt Actuating current: Sum of all actuator power consumption per motor line
Note: do not use the PE wire / green/yellow wire in the actuator cable!
Example
Max actuator cable length with cable cross section 0.75mm2 and actuator current 2A: (2 x 56 x 0.75) : (2 x 2) = 21m
8.1.2 Max cable length – ±24V standard actuators
The actuator supply cable must have 2 wires. If monitoring is desired use min. 3: 2 wires current carrying / 1 wire for monitoring.
±24V standard actuators
Do not use the PE wire / green/yellow wire!
cable cross
section [a]
Total actuator current [I]
3 wire
0.75mm²
3 wire
1.50 mm²
5 wire
1.50 mm² 2 wire
parallel
3 wire
2.50 mm²
5 wire
2.50 mm² 2 wire
parallel
3 wire
4.00 mm²
1A
42m
84m
168m
140m
280m
224m
2A
21m
42m
84m
70m
140m
112m
3A
14m
28m
56m
47m
93m
75m
4A
11m
21m
42m
35m
70m
56m
5A
8m
17m
34m
28m
56m
45m
6A
7m
14m
28m
23m
47m
37m
7A
6m
12m
24m
20m
40m
32m
8A
5m
11m
21m
18m
35m
28m
9A
9m
18m
15m
31m
25m
10A
8m
16m
14m
28m
22m
20A
4m
8m
7m
14m
11m
Page 11
11
8.1.3 Max cable length – actuators with MotorLink®
The actuator supply cable must have 3 wires: 2 wires current carrying / 1 wire for communication.
When a 5 wire cable is used for MotorLink® It is not recommended to use parallel-wire.
ML-comm = MotorLink® communication.
When using actuators with MotorLink® the max cable length is 50m regardless of the result of the above mentioned formula.
Actuators with MotorLink®
Do not use the PE wire / green/yellow wire!
cable cross
section [a]
Total actuator current [I]
3 wire
0.75mm²
3 wire
1.50 mm²
5 wire
1.50 mm²
2 wire
parallel
3 wire
2.50 mm²
5 wire
2.50 mm² 2 wire
parallel
3 wire
4.00 mm²
1A
42m
50m
2A
21m
40m
50m
3A
14m
28m
50m
47m
50m
4A
11m
21m
42m
35m
5A
8m
17m
34m
28m
50m
45m
6A
7m
14m
28m
23m
47m
37m
7A
6m
12m
24m
20m
40m
32m
8A
5m
11m
21m
18m
35m
28m
9A
9m
18m
15m
31m
25m
10A
8m
16m
14m
28m
22m
20A
4m
8m
7m
14m
11m
Page 12
12
9 Cable plan for connection to WCC 310 / 320 Plus version
The above plan shows a WCC 320 MotorController
Page 13
13
10 Description of cards and mains connection
Each MotorController includes a power supply unit (SMPS), an auxiliary power supply (AUX) and a main control card. Motor line can input cards for additional motor lines and inputs (e.g. for key pads) as well as a field bus card can be added when necessary.
The size of the power supply unit determines the number and/or types of actuators, which can be connected to the MotorController. See table with overview of max number of allowed actuators per motor line/MotorController (chapter 3.2).
WCC connection to mains and power supply units – WCA 3P3, WCA 3P4
and WCA 3P6
The MotorController WCC 310 is supplied with a 305W SMPS power supply – WCA 3P3. The MotorController WCC 320 is supplied with a 605W SMPS power supply – WCA 3P4.
The power supply is, regardless of size, placed in the bottom of the MotorController beneath the motor line and input card. An AUX – WCA 3P6 – to which mains is connected, is located to the right of the power supply.
Outlet to mains is in the top right of the MotorController. The MotorController is grounded by means of protective earth via the green screw next to WCA 3P6.
,
Connections between cards
An overview of how the different cards are connected are shown below.
Page 14
14
Main control card WCA 3CP – Plus Version
Each WCA 3CP contains the following:
- 2 motor lines for ±24V standard or Motorlink® actuators
- 2 input for keypads for comfort ventilation
- Input for weather station incl. wind direction (WLA 330 / 331 / 340 / WOW 201 / 202)
- Input for master / slave connection (WSK-Link™)
- connection of power supply
- connection to AUX
- Power for motor line card
- Connection for motor line card
- Two connections for Ethernet
- Connection for USB host and USB device
- Connection for fieldbus card
- Touch screen for configuration, commissioning and maintenance
S1 X1 / X2
The WCA 3CP card has 2 motor lines (X1 and X2) for connection of ±24V standard or MotorLink® actuators.
±24V standard actuators
1.1 24V / 0V
1.2
1.3 0V / 24V
2.1 24V / 0V
2.2
1.3 0V / 24V
MotorLink® actuator
1.1 0V
1.2 Communication
1.3 24V
2.1 0V
2.2 Communication
2.3 24V
The number of actuators per motor line depends on the actuator type, the total power consumption of actuators connected to a motor line can max be 4A and the total max power consumption for both motor lines must not exceed 10A or 20A depending on MotorController type.
Page 15
15
Besides actuators, also locking actuators (espagnolettes actuators) type WMB 801/802 and WMB 811/812 can be connected. The power consumption of the locking actuators are not to be included in the 10A / 20A as actuaators and locking actuators do not run at the same time.
All actuators on the same motor line will run/be operated simultaneously. All actuators on the same motor line must be of the same type.
Connection / cable diameter: flexible max 6 mm² / solid max 10 mm². Cable length: see the chapter "Cable dimensioning".
Standard ±24V actuators
Examples with 20A power consumption a) 8 pcs. WMX 826-1 b) 4 sets of 2 pcs. WMX 826-2 c) 4 pcs. WMU 861-1 d) 2 sets of 2 pcs. WMU 842-2
Connection variant of standard actuators on motor line X1
MotorLink® actuators
Examples with actuators per motor line Ex. 1: 4 pcs. WMX 823-1 Ex. 2: 2 pcs. WMU 842-2 Ex. 3: 3 pcs. WMU 826-3
Allowed actuator combinations on a MotorLink® motor line
The two motor lines on the CP card can each be connected to one of the below shown combinations.
-1 (single): one window with one single window actuator. Up to four windows each with one single window actuator can be connected
-2 (double): one window with two double window actuators.
-3 (triple): one window with three triple window actuators.
-4 (quad): one window with four quad window actuators.
Page 16
16
S1 X3 / X4
For connection of comfort keypads.
With the default values are input:
”Active” if the contact resistance is smaller than 2kΩ ”Inactive” if the contact resistance is bigger than 3kΩ.
Input has pull up current of approx. 0.8mA. (min 0.7mA, max 1mA ) Example: comfort keypad connected to input X3
X3 / X4 can also be used as configurable inputs
Input 1
3.1 input 1.1
3.2 input 1.2
3.3 GND 1 / 0V
Input 2
4.1 input 2.1
4.2 input 2.2
4.3 GND 2 / 0V
Data
3.1 Open
3.2 Close
3.3 GND / 0V
4.1 Open
4.2 Close
4.3 GND / 0V
S1 X5 / X6
Connection of master / slave connection via WSK-Link™. X5 and X6 are used on the master panel, whereas X11 is used on the slave panel.
For connection of WSK-Link™ see X11
Data
5.1 24V
5.2 Communication
5.3 0V
6.1 24V
6.2 Communication
6.3 0V
S1 X9
Solid state outputs, one solid state output for transmission of fault signal and 2 free configurable Data
9.1 Fault – Open contact = Fault, closed contact = OK
9.2 Fault – Open contact = Fault, closed contact = OK
9.3 Output A
9.4 Output A
9.5 Output B
9.6 Output B Solid state output for transmission of fault signal.
A fault must last at minimum of 20 seconds before te relay indicate a fault. Data
Max voltage: 30 Vp (peak) Max output: 150 mA Typical On-resistance: 4.7 Ω Max On-resistance: 8 Ω Max switching speed: 2 ms
Input circuit (simplified)
Page 17
17
2 free configurable solid state outputs
9.3 Output A
9.4 Output A
9.5 Output B
9.6 Output B Data
Max voltage: 30 Vp (peak) AC/DC Max current: 150 mA Typical On-resistance: 4.7 Ω Max On-resistance: 8 Ω Max switching speed: 2 ms, only for DC-voltage
Output circuit (simplified)
Example with solid state and relay
(polarization is not important)
S1 X10
For connection of weather station with wind direction. Connection of wind / rain sensors type WLA 330 or WLA 340, rain sensor WLA 331.
Or connection of intelligent weather station (wind direction dependent ventilation), e.g. wind speed sensor WOW 201, wind direction sensor WOW 202, junction box and brackets WOW 203 + 304 and rain sensor WLA 331.
Data
10.1 24V AUX
10.2 Wind speed
10.3 GND / 0V
10.4 24V (not active in power saving)
10.5 Rain
10.6 GND / 0V With the default values are input:
”Active” if the contact resistance is smaller than 4kΩ ”Inactive” if the contact resistance is bigger than 8kΩ. For values between 4 and 8kΩ the result will depend on the supply voltage.
Input has pull up current approx. 1mA. (min 0.7mA, max 1.4mA)
Input circuit (simplified)
Page 18
18
Example 1: Wind/rain and rain sensors
WLA 330 and WLA 331– the settings of the sensors are set on the sensor. WLA 340 – the settings of the sensor are programmable on the MotorControlle’s touch screen.
Data
10.1 24V AUX
10.2 Wind speed
10.3 GND / 0V
10.4 24V
10.5 Rain
10.6 GND / 0V
Example 2: Wind direction dependent ventilation (intelligent weather station) Data
10.1 24V AUX
10.2 Wind speed / Direction
10.3 GND / 0V
10.4 24V
10.5 Rain
10.6 GND / 0V As the weather station is monitored by both communication and time out (wind without time), any cable errors will
be registered.
Page 19
19
S1 X11
For connection of master / slave connection via WSK-Link™. Data:
11.1 24V IN
11.2 Communication IN
11.3 0V IN A master-slave connection via WSK-Link™ enables signals to be distributed between several MotorControllers
or/and the MotorController may be used as slave in a 120V UPS smoke ventilation system. On the master MotorController, either use input X5 or X6 for the master-slave connection. On the slave
MotorController, the connection is done via X11. It is possible to connect several MotorControllers in a master slave connection. However, the max total number
of MotorControllers on the WSK-Link™ must not exceed 10 units. The max cable length between two units must not exceed 200m, see examples below, for how to connect the MotorControllers.
Sharing of signals from weather station
Example 1
Example 2
MotorController #2 and #3 are both master and salve MotorControllers. See under X10 for connection of weather station
WCC 3xx as slave in a 120V UPS supplied smoke ventilation system
Example 1
Example 2
See WSC 3xx instruction for further information about connection to smoke ventilation system.
Page 20
20
Even though the connecting method of MotorControllers shown in the #2 example, enables a physical larger system, with longer distances between MotorControllers, WindowMaster recommends connecting the master slave MotorControllers as shown in example #1. As only the master sends e.g. smoke commands and slaves only respond to commands received from the master, the response time in example 2 is heavily increased in comparison with the response time in example 1.
F2 - F3
3.15A fuse for motorline (WCA 308)
J1
Connection for power supply
J2
Power to motor line card (WCA 3M4 / WCA 3M8)
J3
Connection to AUX (WCA 3P6) – 120V supply
J4
Connection for motor line card (WCA 3M4 / WCA 3M8)
J7
2 x Ethernet connection
J8
USB host. Used to store configurations and to start an event log for e.g. trouble shooting
J9
USB device. Used for remote control and to flash the MotorController.
J10
Connection for fieldbus card
P1
Power supply control
R / P
Reset / programming (used for firmware updates)
LED
Shows the status of the MotorController Yellow = fault, flashing yellow = service timer expired, time for service Green fast flickeing = CPU working, Green constant = CPU communication stopped (possible reset or contact WindowMaster)
↓ ↑
Close / open all windows
Page 21
21
Motor line card – WCA 3M4 / WCA 3M8
The motor line cards WCA 3M4 and WCA 3M8, allows connection of additional 4 and 8 motor lines respectively either ±24V standard or MotorLink®
The WCA 3M4 / WCA 3M8 is connected to WCA 3CP via a CAN-cable (J3 on WCA 3M4 / WCA 3M8 and J4 on the WCA 3CP).
S2 X1 - X8
For connection of ±24 Standard actuators or MotorLink® actuators. Data: x.1 24V / 0V x.2 ML Communication x.3 0V / 24V
For actuator connections, please see explanation in section “WCA 3CP main control card” under “X1 / X2” and “Max number of actuators per card”.
F1 - F8
3.15A fuse for motorline (WCA 308)
J3
Connection to main control card (WCA 3CP)
J4
Power connection from control card (WCA 3CP)
J6
Connection to input card (WCA 3KI)
J7
Power supply control
Page 22
22
Keypad card – WCA 3KI
The keypad card allows connection of 10 keypads. WCA 3KI requires the WCA 3M4 / WCA 3M8 actuator card.
The WCA 3KI is connected to WCA 3M4 / WCA 3M8 via cable (J1 on the WCA 3KI and J6 on the WCA 3M4 / WCA 3M8).
S3 X1 – X10
Data: x.1 Open x.1 x.2 Close x.2 x.3 GND / 0V
↓↑
For input connections, please see explanation in section “WCA 3CP main control card” under “X3 / X4”.
J1
Connection to motor line card (WCA 3M4 and WCA 3M8)
Page 23
23
Power supply card – WCA 3P6
Mains and protective earth is connected to the MotorController via the power supply card.
S4 X1
Connection to mains.
S4 X2
AUX connection to WCA 3CP.
S4 X3
Connection to power supply WCA 3P3 (10A) or WCA 3P4 (20A)
Protective earth (PE).
Fieldbus cards
Different versions of fieldbus cards are available
- WCA 3FK Fieldbus card with KNX interface
- WCA 3FM Fieldbus card with BACnet MSTP interface
- WCA 3FB Fieldbus card with BACnet IP interface
The connection of a fieldbus card enables communication and access to the available bus-objects depending on the chosen system. There is a set of KNX and BACnet objects available for each motor line and motor group, which provides the options for status and commands.
Status options
E.g. actual position, fault and operation status and the max opening angle (degrees).
Command options
E.g. target position commands with different priority and MotorLink® actuator speed. See "WCA 3FK Application Programming Description.pdf" and BACnet PICS for further information on available KNX and BACnet communication objects.
Page 24
24
11 Touch screen
The plus version of the MotorController comes with a touch screen. All connected components (actuators, keypads, weather station etc.) are to be configured on the touch screen.
The menu of the touch screen is in steps: Step 1: main menu Step 2: sub menu Step 3: configuration / showing / operation of the sub menu
Step 1: Main menu Step 2: Sub menu
Step 3: Configuring the sub menu Step 4: Showing the sub menu
Help text
Help text
The touch screen has a help function with text explaining the menu item. The help text occurs when the menu item is pressed (text on white
background). For displaying the help text:
→ press the item e.g. “Motor type” → the help text appears → to turn off the help text press the screen.
Icons
The MotorController has icons for quick viewing of: fire conditions, hardware OK and hardware error:
Hardware OK: actuators have been configured correctly.
Hardware error: hardware error or connected actuators have not been configured correctly in motor lines or motor
groups
Page 25
25
Rotation of the touch screen
The picture on the touch screen can be rotated 180°
12 Configuration – main menu
All connected components (actuators, keypads, weather station etc.) are to be configured. As the MotorController has pre-settings for PIN code for access to level 3, the code is to be entered before it is possible to begin
the configuration (see chapter 12.10 “Log in”). Before starting on the configuration it can be an advantage to change some of the pre-set settings. Ex. the language can be
changed from English to Danish or German (see chapter 12.12 “System”) and the orientation of the text on the touch screen can be rotated for a better viewing angle (see chapter 12.12 ”System”). It is also possible to change the log out time, which is the time that the access to the access level is open/the touch screen in on (see chapter 12.10 “Log in”)
To configure a sub menu:
→ press the light blue number field → enter value / the number of the motor line / change factory settings etc. The setting which can be entered depends of the
type of the sub menu.
→ accept on A menu can consist of more screen plays. To get to the next screen: → press
Motor lines – motor groups
All the components are to be assigned to groups:
- motor lines are to be assigned to motor groups
- keypads are to be assigned to one or more motor groups
12.1.1 Examples with motor lines / motor groups
- 6 motor lines: one or more actuators connected to the lines
- 3 motor groups: the actuators in the motor group are operated simultaneously on the keypad
Page 26
26
Motor line
Actuators are to be connected on the motor lines. ±24V standard actuators and actuators with MotorLink® can be connected to all motor lines, but a motor line can only be connected to one type of actuators – either ±24V standard or MotorLink® actuators.
12.2.1 Motor line - numbering
All motor lines are numbered and they are all to be configured.
12.2.2 Motor line - configuration
Press ”Motor line” and the overview of the motor lines in the MotorController is shown.
Overview configuration motor lines
One motor line is marked with a
as the configuration is missing.
All motor lines are configured.
Both actuators outputs on the main control card as well as the four or eight actuators outputs on the motor line card – if such is connected – are to be configured:
- Motor lines with actuators connected are to be configured in “motor group
-
- Motor lines with no actuator connected are set to “none“
Since ±24V actuators and actuators with MotorLink® are not to be configured exactly the same way, both type of actuators are listed below with the settings that are to be configured for each actuator type. Be aware that both types of actuators can be connected to the MotorController at the same time.
For ±24V actuators the full chain length is define as a runtime of 60 seconds. When the MotorController is to be 100% sure that the windows ae 100% open or closed, the chain length is run twice (120). This can have an influence when configuring the a sequence control.
Motor lines configuration
±24V actuator configuration
The ±24V actuators can be configured in:
1. Output mode: informs the type of the actuator selected
2. Motor configuration
3. Stroke time
4. Motor group
The appendix contains all the menus that can be configured - see appendix for detailed explanation.
Page 27
27
The MotorLink® actuators are to be configured in:
MotorLink® motor configuration
1. Output mode: informs the type of the actuator selected
2. Expected no. of motors (displayed if actuator type =
MotorLink®)
3. Motor group
4. Expected no. of locking motors
4.1 No. of found locking motors (see appendix)
The appendix contains all the menus that can be configured - see appendix for detailed explanation.
12.2.3 Colour code - motor line
The overview fields on the touchscreen have colour codes for the motor lines:
Colour
Meaning
Yellow triangle icon
Fault in the configuration or actuator
Strikethrough grey
No configuration of the motor line / the motor line doesn’t exists
Black text
The motor line are configured, the actuator has not been closed
Green
The motor line has been configured; the actuator has been closed MotorLink® motor lines will be marked in green, if the actuator / actuators on the motor
line has been closed 100% and the point zero of the actuator has been determined.
Light grey number
The motor line are configured with ‘No actuator are connected’
Blue ?
Configuration is missing
Motor group
Motorlines can be assigned to motor groups. See the example "Example of motor lines / motor groups" in the beginning of this chapter for further details.
12.3.1 Motor group - configuration
Press ”Motor group” and the overview of the motor groups in the MotorController is shown.
Motor group configuration
Motor group overview
Motor groups are to be configured in:
1. Comfort open position
2. Comfort open close time
3. Wind directions where to close during alarm
The appendix contains all the items that can be configured
- see appendix for detailed explanation.
12.3.2 Colour code – motor group
The overview fields on the touch screen have colour codes for the motor groups:
Colour
Meaning
Yellow triangle icon
One or more of the assigned motor lines has a failure
Black text
The motor group is configured
Green field
All the assigned motor lines are closed
Light grey number
The motor group is configured but no motor lines are assigned
Blue ?
Configuration is missing
Page 28
28
Local input
The MotorController has two programmable inputs and one input for wind/rain. If further inputs are needed, the input card WCA 8KI (requires the motor line card) can be added. This card has ten local inputs.
The touch screen has an overview of the local inputs.
12.4.1 Numbering of local inputs
All local inputs are numbered. The number of the input depends on its location on a card - see overview below.
MotorController with input card
12.4.2 Local input - configuration
If component are installed in one or more inputs, these inputs are to be configured. Which item to be configured depends on the type of input – see description below.
Local input - configuration
Overview ’Local input’
Example of overview ’Local input’ with connected input card
(WCA 3KI)
“S1 Close” and “S1 Open” are the two buttons on the board.
Configuration of local input X3 and X4
Input X3 and X4 on WCA 3CP and X1-X10 on WCA 8KI (binary)
If local inputs are connected on the card/cards WCA 3CP and/or WCA 8KI, it/they shall be configured in:
1. Input type: informs the type of the input “Binary) (not to be configured)
2. Control motor groups
2.1 Function in controlled motor groups
2.2 Short output function
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Page 29
29
12.4.3 Usage of wind/rain sensors - WLA 33x
Usage of wind/rain sensors WLA 33x with motor groups (MG):
The used input e.g. S1X10.5 is configured to “Control motor groups”, the groups are chosen.
Then, in the menu “Active function in controlled motor groups” the function “Safety” is selected.
Then, a function for the motor group when inactive can be selected “Inactive function in the controlled motor groups”.
By each motor group it is possible to define the max opening for
“Safety”, meaning it is possible to allow windows and louvers inside
the building to open despite “Safety” (wind/rain). Facade windows, which are allowed to open e.g. 10%, to open
despite it rains.
Input shall be configured in:
Configuration of local input
1. In the motor groups configure the input with the function “Safety“.
2. Configure the motor groups when anything else than close (0%) is desired.
Note: motor groups also receive “Safety” signals from the smoke
zones they are associated with, see below for further information.
Local output
On the WCA 3CP card the MotorController always has one output (X9.1 / X9.2) for fault signal (not configurable output).
12.5.1 Numbering of local output
All local outputs on the WCA 3CP card are numbered. The number of the output depends on its location on the card - see overview below.
As the output (fault signal) on the WCA 3CP card cannot be configured it is not numbered.
MotorController with motor line and input cards
Page 30
30
12.5.2 Local output - configuration
If component are installed in one or more outputs, these outputs are to be configured. Which item to be configured depends on the type of output – see description below.
Local output - overview
Overview ’Local output’
Overview ’Local output’
Local output shall be configured in:
Configuration of a local output
(shown for S1 X9.3/4)
1. Output type: informs the type ‘Binary output’ (is not to be configured)
2. Output mode
3. Controlled by motor groups
a) Motor group output function b) Logic function c) Status when active d) Time-out
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Weather station type
Here is to be selected which type of weather station –none, WOW or WLA - that is connected. (The menu “Weather” is only used for input from WCA 3CP input S1X10.2 for wind speed from WLA 340. Input S1X10.2 is also
used in combination with weather station WOW 201/202/204 for wind direction dependent smoke ventilation - see chapter 10.3). WLA 33x is not considered as a weather station and is connected directly to the input X10.5, see chapter 12.4.3.
Weather - configuration
Overview ’Sensor type’
Overview ’Sensor type’ (selection of type of weather station)
Page 31
31
Weather shall be configured in:
Configuration of the sensor
None
(no configuration)
WOW
1. Filter constant
2. Slow filter constant
3. Use RMS in filter
The appendix contains all the items that can be configured - see appendix for detailed explanation.
WLA
1. Pulses/sec. per m/s
2. Filter constant
3. Slow filter constant
4. Use RMS in filter
The appendix contains all the items that can be configured - see appendix for detailed explanation.
From WSK Link™
(no configuration)
Sequence control
The sequence control functionality is used where the movement of a motor line must depend on an external event or situation/stage. To be used where window flabs are overlapping or where the windows cannot open (more than 15%) if the blinds are down a.s.o.
The sequence control can be controlled depending on;
- the position of a different motor line
- the state of a local input
- the state of a KNX object
- the state of a BACnet object
Sequence control configuration
Activation of sequence control
The activation of sequence control is to be done for each motor line.
Sequence control configuration
The function for the sequence control is to be configured for each motor line
1. None - This motor line does not use sequence control
2. Open - This motor line must wait for a “result” before opening
3. Close - This motor line must wait for a “result” before closing
Page 32
32
Sequence control configuration – motor line
1. Sequential control position limit
the max position the motor line is allowed to have without the „result“ is being fulfilled. For MotorLink® motor lines stepless variable. For ±24 Volt motor lines 0 or 100%
2. Sequential control with (upon what should the motor line wait?)
1. Motor line.
2. Local input
3. The state of a KNX object
4. The state of a BACnet object
3. Sequential control with No
Upon which number should the motor line wait
4. Sequential control position logic
In which positions should the sequential control be active
WSK-Link™ - master/slave connection
The WSK-Link™ connection between to MotorControllers is done via input X5 or X6 on the master and input X11 on the slave. A MotorController can have a master/slave connection to several MotorControllers. However, the total max number of connected slaves on the bus must not exceed 10 units.
The total cable length must not exceed 200m, see S1 X11 for examples for connection of MotorControllers. A slave can only have one master, whereas a master can have several slaves and a MotorController can both be a slave and a
master to MotorControllers.
Configuration of Master – Slave system:
A connected slave MotorController is shown on
the master MotorController’s touch screen.
When two MotorControllers are connected to each other in a master-slave connection, the slave will appear as a green break glass unit on the master’s touch screen.
The slave MotorController’s appearance on
the master MotorController
On the master’s touch screen the Device type of the slave will appear as a WCC 3xx.
Network
For configuring network addresses. The WCA 3CP card has a 10/100Mbit Ethernet connection. The connection support DHCP or static IP address as well as
Gateway The appendix contains all the items that can be configured - see appendix for detailed explanation.
Network is used in with BACnet IP interface – contact WindowMaster for further information.
WCC 3XX
Page 33
33
Network shall be configured in:
Configuration of ’Network’
1. DHCP
2. Power setting
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Log in
The access level to the MotorController is set in four levels.
Level
Access to
Who has access
1
Public You can see the MotorController from the outside with the door closed and locked
Everyone
2
Operation You can open the MotorController and operate the touch screen for showing the status and manual operating of the windows.
All the menus on the touch screen can be viewed but no values can be changed.
Chosen persons with a special key
3
Configuration You can open the MotorController and operate the touch screen for showing status, manual operating of the windows as well as configuration and changing the pre-set values.
All the menus and sub menus can be seen and the values can be changed. Access Level 3 can be locked with a PIN code, so there is only access to the
level when the PIN is entered
Chosen persons with a special key and having the PIN code for access to level 3.
PIN code pre-set to
4321.
The user is on access level 2
The user is at access level 2. To open for access level 3, enter the PIN for access level 3.
Enter PIN code
Enter PIN code.
Page 34
34
Access approved to login level 3
The user is at access level 3.
Login shall be configured in:
Configuration of login
The access levels can be locked and access to the level is only possible with a PIN code. Each level has a unique PIN code.
1. PIN 3: Configuration
2. Log out time-out (the period of access to the level before the system automatically lock the level)
The appendix contains all the items that can be configured - see appendix for detailed explanation.
It is possible to lock the touch screen before the time has expired: press followed by pressing
Configuration files on USB
The MotorController has a plug in for an USB stick. It is possible to save all the configurations of the MotorController and this way save the stick as documentation. It is also possible to reinstall from the USB stick.
Files on the USB stick can be printed from a computer.
Configuration ‘Configuration, files on USB’ -
overview
Configuration files on USB – overview.
Configuration of ‘Configuration files on USB -
no.1’.
Configuration of configuration files on USB – shown for no. 1.
Page 35
35
System
It is possible to change settings on the touch screen e.g. language, clock setting, date display, service timer etc.
System can be configured in:
Configuration of ’System’
1. Language
2. Backup time stamp (not to be configured)
3. Unsaved changes… (not to be configured)
4. Configuration command
5. Time
6. Date
7. LCD rotate view
8. Enable parameter set from network
9. Enable remote control
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Fieldbus (KNX and BACnet)
Only when an Fieldbus card with a fieldbus interface is added to the MotorController will the menus associated with the vairious fieldbus options be shown.
Fieldbus example
An optional card with fieldbus interface is added to the MotorController and the menus (e.g. configuration) now includes KNX and BACnet.
When the Fieldbus card is mounted a set of KNX or BACnet objects are available for each motor line and motor group, which provides the options for status and commands.
Status objects
E.g. actual position, fault and operation status and the max opening angle (degrees).
Command objects
E.g. target position commands with different priority and MotorLink® motor speed.
Fieldbus link - "Conn. 1-10 "
The KNX or BACnet has also 10 configurable binary communication objects. These can either be used for sending comfort commands to one or more motor groups or to give selected status from smoke zones or motor groups.
See "KNX Application Program Description or "BACnet PICS” on the home pages (www.windowmaster.com) for further information on available KNX or BACnet communication objects.
12.13.1 KNX configuration
KNX bus overview – object configuration
Overview of the KNX objects. For each KNX object a direction must be configured
- None
- Input
- Output
When objects are configured as inputs or outputs, the controlled motor group or smoke zone as well as its function must also be configured.
Page 36
36
KNX bus shall be configured in:
For all the objects the Power setting for the KNX bus must be configured.
12.13.2 BACnet configuration
BACnet overview – object configuration
Overview of the BACnet objects. For each BACnet object a direction must be configured
- None
- Input
- Output
When objects are configured as inputs or outputs, the controlled motor group or smoke zone as well as its function must also be configured.
BACnet shall be configured in:
For all the objects
1. BACnet IP UDP port number
2. BACnet IP device instance
3. Actual position COV increment
4. Actual max. position COV increment
5. High speed COV increment
6. Wind direction COV increment
7. Register as “foreign device”
13 Status – main menu
In 'Status' you can see the status of all the menu items that can be configured under 'Configuration' as well as e.g. the status of the power supply and slots (inform the type of card in the slot).
Main overview: status of the system
Under ‘Status’ is possible to view the status for:
1. Motor line
2. Motor group
3. Local input
4. Local output
5. Power supply
6. CAN (local)
7. Network
8. Slots
9. Configuration files, USB
10. System It is not possible to configure the items in ’Status’ mode.
The appendix contains all the items shown in ‘Status’ - see appendix for detailed explanation.
Page 37
37
14 Manual operation and main menu
It is possible to operate the motor lines, the motor groups and the smoke zones direct on the touch screen.
Main overview: manual operation
What to be manually operated:
1. Motor line – see text below
2. Motor group
Operation types
Motor lines and motor groups They can be operated absolutely (percentage of full open) or relatively on the keypad ‘open/stop/close’ showed on the touch screen.
Example
Manual operation of a motor line
- If ’All’ is selected all the actuators are operated simultaneously.
- If a motor line number is selected only the selected motor line is operated.
Motor line – overview
One motor line is selected
Manual operation on the touch screen
15 Configuration missing – main menu
If any components, motor lines or motor groups are not configured they are listed here. If you are logged into access level 3 it is also possible to configure from this menu.
16 Hardware error – main menu
If there are any hardware error on the MotorController, they will be displayed here. E.g. if the motor lines are not configured, the main supply is cut of, the type of weather station is not selected etc. If you are logged into access level 3 it is also possible to configure from this menu.
17 View all details – main menu
To make the configuration of the MotorController as simple as possible during configuration, it is only possible to configure the most used functions.
Under 'View all details' is displayed all of the above functions together with detailed functions that are not used as often, but are possible to configure. If you are logged into access level 3 it is also possible to configure from this menu.
It is possible to view all details for:
Motor line Motor group Local input Local output Weather Power supply Network KNX-bus BACnet Slots Log in Configuration files, USB System
Page 38
38
18 Remote control of MotorController
It is possible to remote control a MotorController from a PC or via USB device. When the MotorController is on a standard computer network (Ethernet) you can from any PC with the “WMaFlexiSmokeRemote”
program control the MotorController just like if you were standing in front of the itl. If the MotorController is not connected to a network then it can be remote controlled via a USB connection using the “WMaFlexiSmokeRemote” program. The program ”WMaFlexiSmokeRemote” can be downloaded from our webpages (www.windowmaster.com) under WCC 310 or WCC 320.
Remote control can be configured in:
Configuration of remote control
To enable remote control of the MotorController it is necessary to allow remote control. This is done in the configuration of the system.
Identification of the IP-address
IP-address of the MotorController
Screen shot from the PC when controlling
the FlexiSmoke™ remotely
Start the ’WMaFlexiSmokeRemote program’ on the connected PC. Enter the IP-address and press ’Connect’.
19 Commissioning and test run
In case of hardware error, please see chapter 16 “Hardware error’” We recommend that the software of the MotorController is updated during the annual maintenance check!
The MotorController is completely installed, without the operating voltage
applied
a) Check all mechanical and electrical components for damage. b) Check all screw and plug connections for tightness and/or firm seating c) Check that all external components are installed:
1) ±24V actuators: Is the motor end module inserted in the last or only actuator?
Page 39
39
With mains voltage
Adhere to the relevant regulations! Connect the mains cables and reapply the mains voltage.
Ventilation keypad
Closely observe the actuators during opening and closing. They must not be impaired in any position by the building structure. Observe that the actuator cables are not being subject to pulling or pinching. Check each ventilation keypad individually.
Wind/rain detector
a) Open the actuators with the comfort ventilation keypads. b) Wet the rain sensor, the actuators will fully close. c) While the actuators are running, press the Open button at the keypad. The actuators must neither open nor stop!
Exception: If set to a manual override time (Man. operation after auto comm.).
If the start-up was successful, mount the doors of the MotorController and make back-up. If the start-up was unsuccessful (error with one of the test run processes), please see chapter 10 “Description of cards”.
If necessary, check the wiring in accordance with the cable plan – see chapter 9 “Cable plan for connection to WCC 3xx”.
20 Maintenance
Control and maintenance should only be done by the manufacturer or an authorized partner. If the MotorController is a part of a smoke ventilation system control and maintenance must be documented by a mark on the MotorController and in the service book.
Remove all soiling from the MotorController. Check fastening and clamping screws for firm seating. Carry out a test run of the entire system (see chapter 19 ‘Commissioning and test run). Only have defective units repaired in our factory. Only install original spare parts.
We recommend that the software of the MotorController is updated during the annual maintenance check! The expected minimum lifetime for the MotorController is 10 years.
Maintenance agreements
WindowMaster offer maintenance agreements for the MotorController. Contact our service department for further information: telephone +44 1536 510990 or [email protected]
Replacement cards
20.2.1 Replacement of 3M4, 3M8 and 3KI cards
1. Disconnect the 120V.
2. Wait until the display has completely turned off before removing the card.
3. Insert the replacement card.
4. Turn on the 120V .
5. The system will be ready again after approx. 2 seconds.
20.2.2 Replacement of 3CP card
1. Save a backup of the configuration on a USB stick (recommended).
2. Disconnect the 120V .
3. Wait until the display has completely turned off before removing the card.
4. Insert the 3PS replacement card.
5. Insert the USB stick into the new card.
6. Turn on the 120V.
7. Load the parameters from the USB stick
8. The system will be ready again after approx. 2 seconds. If the WCA 3CP card, which is to be replaced, is completely without function then go straight to point 2. If there is no backup of the configurations, these are to be entered manually.
It is therefore recommended to take a backup, on a USB stick, when the MotorController is running, if necessary please see chapter
12.11.
21 Declaration of Conformity
The MotorControllers are manufactured and tested accordingly to the European requirements. The total system is not to be put into service until a declaration of conformity for the total system has been made.
The “Declaration of Conformity” is supplied with MotorController as separate documents.
Loading...