Windhager VarioWIN Operating Manual

Page 1
VarioWIN
Pellet central heating boiler
pneumatic + direct
Operating Manual
05/2010 092945/01
Page 2
Table of contents: Page
Important information for system operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2 Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.3 Start-up and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.4 Checking the heating water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.5 Operating noises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.6 Filling the pellet store . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.7 Sources of danger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.1 Fire protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.2 Power failure (or if the blower is not running) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.3 Burner pot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.4 Heating door and ash door handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.5 Direct pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.6 Entering the pellet storage room, storage container . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.1 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.1.1 VarioWIN Premium . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.1.2 VarioWIN Exklusiv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.2 Functional elements and operating controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.2.1 VarioWIN with direct pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.2.2 VarioWIN with 41 kg reserve supply container, manual loading . . . . . . . . . . . . . . . . . . . . . .10
2.2.3 VarioWIN with pneumatic pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.3 Opening the cladding door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.4 Check before switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.5 Filling the reserve supply container . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.5.1 VarioWIN Exklusiv-S – Manual filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.5.2 VarioWIN Exklusiv-P – Pneumatic pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.5.3 VarioWIN Premium/Exklusiv-D – Direct pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.6 InfoWIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7.1 OFF mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7.2 ON mode, lighting ON, self-test, lighting OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7.3 Pellet feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.7.4 Solid fuel / buffer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.7.5 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.7.6 Flue cleaning function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.7.7 Shutdown procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.8 Operating phases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.1 Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.2 Purging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.3 Ignition phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.4 Flame stabilisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.5 Modulation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.6 Burnout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.8.7 Burner OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Page 3
Table of contents: Page
2.9 Information texts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.9.1 Next boiler cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.9.2 Operating hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.9.3 Total pellet consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.4 Flue gas temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.5 Boiler temperature setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.6 Current boiler output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.7 Display module software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.8 Main PCB software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.9.9 Boiler model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.10 Menu guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
2.10.1 Operator level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.10.2 Service level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
2.10.2 VarioWIN with REG standard control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
2.11 Heating system operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
2.11.1 VarioWIN with MES system control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Care, cleaning and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
3.1 Care of cladding and keyboard foil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
3.2 Cleaning and operating implements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
3.3 Overview of intervals between maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
3.4 Heating surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
3.5 Ash pan, ash on heating surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
3.6 Combustion chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
3.6.1 Baffle plate, thermocontrol sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
3.6.2 Burner pot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
3.7 VarioWIN reserve supply container . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
3.8 Top heating surfaces and linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
3.9 Blower wheel, blower box, exhaust pipe and rotary feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
3.9.1 Blower wheel, blower box and exhaust pipe to flue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
3.9.1 Rotary feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
4.1 No display on InfoWIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
4.2 Information messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
4.3 Fault messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
4.4 Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Guarantee and warranty limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
I\n\h\a\l\t\s\v\e\r\z\e\i\c\h\n\i\s\)[2020]>
Page 4
Important information for system operators
Dear Heating System Owners,
We would like to congratulate you on your new environmentally friendly boiler system. With the purchase of this high-quality product by WINDHAGER ZENTRALHEIZUNG, you have selected a system that provides more comfort and optimised fuel consumption while utilising an environmentally friendly means of saving resour­ces. Your boiler was manufactured under strict ISO 9001 certified standards, was subjected to extensive tests and all its components are recyclable.
On the following pages we have provided specific information and important tips regarding system operation, unit functions and cleaning. Please pay close attention to these instructions. Familiarity with the material in this document will allow you to enjoy long-term operation of the unit. We wish you all the best with your WIND­HAGER boiler!
Cordially,
WINDHAGER ZENTRALHEIZUNG
Caution symbols
Please take careful note of the following symbols on the pellet boiler and in these instructions.
Ignoring the warnings identified can lead to personal injury.
Ignoring the warnings identified can lead to malfunction of or damage to the boiler or heating system.
1.1 Safety precautions
The boiler and related accessories reflect the state of the art and meet all applicable safety regulations. Your boiler and all accessories operate using 230 V AC electric current. Improper installation or repair can pose
the danger of life-threatening electric shock. Installation may be performed only by appropriately qualified tech­nicians.
Please note: Risk of crushing from rotating auger. If you have to touch these parts, always deenergise the boiler.
Warning of hot surface: risk of burns! Before touching these surfaces, you must switch off the boiler and let it cool.
Page 5
Important information for system operators
1.3 Start-up and maintenance
Have Windhager Customer Service or one of our customer service PARTNERS put your new boiler into servi­ce. In this way, all functions of the new unit will be thoroughly checked; you will also benefit from the detailed information provided by the system installer. Installation by a qualified technician as well as the maintenance required by the guarantee limitations will guarantee the optimal use and service life of your boiler system. This is the only way to assure the benefits of this technologically advanced boiler and guarantee safe, environmentally friendly and energy-saving system operation.
The following preconditions must be met before you order the initial start-up:
1.) Boiler installed correctly.
2.) System fully wired up electrically.
3.) System rinsed, filled and vented – heat consumption must be possible.
4.) Boiler connected to domestic water and filled.
5.) Sufficient quantity of fuel available (pellets, split logs, oil or gas).
6.) The customer must be present during start-up.
The initial start-up cannot be carried out if any of these points are neglected. The customer will be charged for any unnecessary costs arising as a result.
Start-up and maintenance are part of the guarantee requirements as listed in the enclosed „guarantee limita­tions“.
Note:
During the first few weeks after start-up, condensation can occur in the combustion chamber, on the hea-
ting surfaces and in the ash pan. This has no effect on the function and service life of the boiler.
1.4 Checking the heating water
The chemical composition of the heating water must meet the specifications of ÖNORM H 5195 Part 1 or VDI 2035 T1. According to ÖNORM M 5195 Part 1, the condition of the heating water must be checked every 2 years by a heating technician in order to avoid corrosion and sediment accumulation in the heating system.
The check must be performed once every year in heating systems with more than 1500 litres of heating water.
In the event of repair work requiring a change of water in the heating system, the heating water is to be checked within 4 to 6 weeks after such work. Corrosion and sediment resulting from improper heating water are not covered by the guarantee and warranty.
The pellets must be stored in a dry place so that they can be transported without problems and in order to achieve trouble-free operation with optimum combustion and at maximum efficiency.
1.2 Fuel
The boilers are designed to burn the following fuels: Pellets according to ÖNORM M7135 and DIN
plus
.
Significant criteria based on the standards are as follows:
Diameter 6 mm Length 80% between 15 – 30 mm Smooth surface
Density at least 1.1 kg/dm
3
Residual moisture content max. 10%
Energy content min. 18 MJ/kg = 5 kWh/kg
(in water-free condition) Ash content max. 0.5% Abraded particles max. 2.3% Chemical/synthetic binding agents are strictly prohibited No impurities from varnish or paint residues, etc.
Page 6
1.6 Filling the pellet store
Fig. 2 Switching off the VarioWIN
Important information for system operators
1.5 Operating noises
The VarioWIN is a modern, fully automated pellet central heating boiler with a high level of convenience in terms of operation and cleaning. This automation means that operating noises may occur during normal operation.
Normal operating noises are:
Flame noises
– Natural flame noise can be heard depending on the size of the flames.
Light scratching and scraping noises
– Depending on the level of contamination, cleaning noises may occur during automated cleaning or shake-out. If these become louder over time ⇒ Clean the pellet central heating boiler, especially the burner pot.
Trickling of pellets and vacuum cleaner noise
– Fully automated pellet supply involves pellets being sucked from the storage room into the reserve supply container. During filling, the suction turbine generates a „vacuum cle­aner noise“ in the storage room and the feed hose, and the trickling of the pellets can be heard in the reserve supply container.
Clicking noises
– The relays switch on or off when the control unit is installed.
Liquid noise, gurgling
– This is caused by air in the heating water ⇒ Bleed the system.
Air induction noises
– Air induction noise occurs at the air supply induction point for combustion (air opening
in the device) ⇒ Use air supply pipes to relocate the induction point outside the house or into an adjacent room.
Note:
Due to these operating and flame noises, we do not recommend installing the device in bedrooms or
quiet rooms – see also the information in the VarioWIN „Assembly instructions“.
The pellet boiler must be switched off correctly at least 15 minutes before the store is filled – Fig. 2.
Press the ON/OFF button. Never switch off using the emergency OFF switch!
Pressing one of the six buttons firstly switches just the lighting and display on. The boiler is only switched off when the button is pressed for the 2nd time. Wait until burnout mode has finished (not indicated on the display) and open the combustion chamber doors.
During filling, negative pressure is created in the pellet store and this can cause burn-back in the pellet boiler. The­refore, the boiler must be stopped from operating during the filling procedure.
Fig 2a „Storage room fill“ sticker on the
storage room door
Every storage room fill should be documented by adding the date and volume to the „Storage room fill“ sticker – Fig. 2a.
002357/00
01/2010
Befüllung Lagerraum
Filling date and volume
Remplissage du silo de stockage
Datum/Date/Date
Menge/Volume/Quantité
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
Page 7
Never fill the burner pot with pellets by hand. Excessive combustion material in the burner pot means that the pellets will not be ignited optimally. Too much low temperature carburisation gas will be gene­rated and this can lead to deflagration.
1.7.3 Burner pot
Do not open the combustion chamber door, there is an increased risk of deflagration when opening the combustion chamber door. A self-test is performed following a power failure during combustion and then operation is continued automatically.
1.7 Sources of danger
1.7.1 Fire protection
The entire system must comply with technical fire protection requirements in accordance with the applicable regulations, standards and guidelines.
1.7.2 Power failure (or if the blower is not running)
Important information for system operators
1.7.5 Direct pellet feed
Do not attempt to enter an unaired storage room (particularly buried tanks).
1.7.6 Entering the pellet storage room, storage container
In certain conditions, higher concentrations of harmful gases (e.g. carbon monoxide) may build up in pellet sto­rage rooms. If these are allowed to build up over long periods, it may present a hazard. Even though there is no risk under normal circumstances, this scenario cannot be completely ruled out.
– When working in filled pellet storage rooms, in the interests of safety a second person should always remain
outside the storage room. Always air pellet stores thoroughly before entering.
– For stores that are difficult to access or only accessible from above (e.g. buried tanks), the person entering
the store should use additional safety equipment.
– Keep children away from the pellet store!
1.7.4 Heating door and ash door handles
Warning of hot surface: risk of burns! Before touching the combustion chamber and ash door handles, you must switch off the boiler and let
it cool.
Please note: Risk of crushing from rotating auger. Before entering the pellet store or handling the unit with the auger open, always de-energise the boiler. Never operate the boiler with the extraction port (auger) open!
Page 8
Operation
2.1 Functional description
The VarioWIN pellet central heating boiler and the Modular Energy System MES or the REG standard control combine to form a perfect unit. The VarioWIN automatically fires when the control system signals a heating requi­rement. Following „purging“ (safety function), ignition starts and the pellet metering auger switches on. The burner pot is automatically filled with pellets. When flame formation has been detected (by the thermocontrol sensor), the boiler enters flame stabilisation mode and then control mode (modulation mode) and keeps to the specified boiler temperature setpoint (between 60 °C and 75 °C). The boiler enters burnout mode if the output drops below the minimum nominal thermal output or no heating requirement is signalled by the control system. The blower continues to run until the burner pot has cooled down. Therefore, do not switch off the electricity supply to the device too soon.
2.1.1 VarioWIN Premium
Manual cleaning:
The heating surfaces are cleaned manually using the cleaning lever. The cleaning residues from the heating surfaces and the combustion residues from the burner pot drop into the ash pan or ash pan space.
VarioWIN Premium-D with direct pellet feed and extraction port for mounting a year-round pellet con­tainer
Direct pellet feed transports the pellets from a sheet steel tank or self-build pellet store via a rotary feeder to the burner pot.
2.1.2 VarioWIN Exklusiv
Automatic cleaning:
Fully automatic heating surface cleaning: A motor moves the heating surface cleaning system vertically and the heating surfaces remain clean.
Fully automated ash compactor: The fully automated ash compactor uses a motor and pressure plate to compress the ash in the ash container. This makes the emptying intervals up to 3 times longer.
VarioWIN Exklusiv-S with 41 kg pellet reserve supply container
The reserve supply container is loaded by hand.
VarioWIN Exklusiv-P with pneumatic pellet feed
The pellet feed uses a maintenance-free suction turbine to fill the VarioWIN reserve supply container fully auto­matically with pellets from a pellet storage room or storage container. The pellet feed is switched on by the lower fill level switch (proximity switch) in the reserve supply container or at the end of the enable time or the beginning of the start time, and runs for as long as the reserve supply container is full. Filling is not started if the boiler is in heating operation or the feed has been blocked by the control unit (outside the enable time, e.g. at night). If the boiler is operating when filling is necessary, the boiler switches to burnout mode.
Switching between suction probes 1, 2 and 3 is fully automatic. The system changes to the next suction probe after the reserve supply container has been filled a certain number of times. This means the storage room is emptied as evenly as possible.
VarioWIN Exklusiv-D with direct pellet feed and extraction port for mounting a year-round pellet con­tainer
Direct pellet feed transports the pellets from a sheet steel tank or self-build pellet store via a rotary feeder to the burner pot.
Page 9
Fig. 3 VarioWIN with direct pellet feed – View from right
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19 *
22
24
20
21
23
25
26
27
Operation
2.2 Functional elements and operating controls
2.2.1 VarioWIN with direct pellet feed
1 Ash pan 2 Ash door 3 Filling and evacuation cock 4 Primary air pin 5 Pressure gauge 6 Burner pot 7 Down chute 8 Combustion chamber door 9 Baffle plate 10 Thermocontrol sensor 11 Cladding door 12 Heating surface cover 13 Safety valve 14 Down channel 15 Exhaust pipe 16 Exhaust pipe cleaning opening 17 Blower motor 18 Blower box 19 Motor for ash compactor 20 Auger flange 21 Rotary feeder
Rotary feeder cleaning opening 22 Spur gear 23 Auger motor 24 Metering auger 25 Maintenance pipe 26 Rotary feeder proximity switch 27 Extraction port
Page 10
10
Operation
2.2.2 VarioWIN with 41 kg reserve supply container, manual loading
Fig. 5 VarioWIN with pneumatic pellet feed – View from right
1
2
3
5
6
7
9
10
13
17
16
18
19
20
4
8
11
12
22
21
23
24 25
15
1 Ash pan 2 Ash door 3 Filling and evacuation cock 4 Primary air pin 5 Pressure gauge 6 Burner pot 7 Down chute 8 Combustion chamber door 9 Baffle plate 10 Thermocontrol sensor 11 Cladding door 12 Heating surface cover 13 Safety valve 14 Reserve supply container cover 15 Protective grille 16 Rotary feeder 17 Metering auger and motor 18 Rotary feeder cleaning opening 19 Exhaust pipe 20 Exhaust pipe cleaning opening 21 Blower motor 22 Blower box 23 Motor for ash compactor
2.2.3 VarioWIN with pneumatic pellet feed
1
2
3
5
6
7
9
10
13
14
15
17
16
18
19
20
4
8
11
12
22
21
23
Fig. 4 VarioWIN with 41 kg reserve supply container – View from right
1 Ash pan 2 Ash door 3 Filling and evacuation cock 4 Primary air pin 5 Pressure gauge 6 Burner pot 7 Down chute 8 Combustion chamber door 9 Baffle plate 10 Thermocontrol sensor 11 Cladding door 12 Heating surface cover 13 Safety valve 15 Reserve supply container cover 16 Rotary feeder 17 Metering auger and motor 18 Rotary feeder cleaning opening 19 Exhaust pipe 20 Exhaust pipe cleaning opening 21 Blower motor 22 Blower box 23 Motor for ash compactor 24 Inspection cover 25 Coarse filter
Page 11
11
Operation
2.4 Check before initial start-up
a) System pressure (heating water pressure):
The system must be filled and vented. With the system cold, pressure should be at least 1.0 bar (maximum
1.8 bar) – Fig. 7. If you have any questions, your installer will gladly answer them.
Pressure gauge (system pressure)
Fig. 7 Filling the system
b) Ventilation:
If you are operating the device with room air, please make sure the room where it is installed is well venti­lated. The air supply must be as free of dust as possible.
c) Flue:
Please have the chimney sweep check the flue, and, if necessary, clean it.
Filling and evacuation cock
2.3 Opening the cladding door
Fig. 6 Opening the cladding door with the key.
Warning of hot surface: risk of burns! Before touching the combustion chamber and ash door handles, you must switch off the boiler and let
it cool.
Insert the key, turn a quarter turn to the left and open the cladding door – Fig. 6.
Page 12
12
2.5 Filling the reserve supply container
2.5.1 VarioWIN Exklusiv-S – Manual filling
Fold open the cover of the reserve supply container (Fig. 8) and fill the reserve supply container up to max. 1 cm below the edge. Close the cover.
Tip:
The reserve supply container should always be completely filled with pellets. This allows the incoming pel­lets to drop into the container better, reduces the size of the conical part of the pile and means that the contai­ner empties better.
Fig. 8 Folding open the cover
When filling, make sure no extraneous materials (e.g. shreds of the pellet bags resulting from cutting open the bags) get into the reserve supply container – they could block the rotary feeder!
2.5.2 VarioWIN Exklusiv-P – Pneumatic pellet feed
The reserve supply container is filled by the fully automatic pellet feed. WINDHAGER Customer Service or the customer service PARTNER will perform the first fill (start-up), take the boiler and its pellet supply into service and familiarise the customer with the operation and cleaning of the boiler, with reference to the Operating Manu­al.
Operation
2.5.3 VarioWIN Premium/Exklusiv-D – Direct pellet feed
The VarioWIN is supplied by the direct pellet feed from the year-round pellet reserve supply container. WIND­HAGER Customer Service or the customer service PARTNER will perform the first fill (start-up), take the boiler and its pellet supply into service and familiarise the customer with the operation and cleaning of the boiler, with reference to the Operating Manual.
Page 13
13
5s
RESET
Full-text display (illuminated display)
Manual operation / flue cleaning function
Signal lamp (LED) „Operation“ – green; „Malfunction“ – red
Menu buttons
ON/OFF button
Menu line
Operating phases are displayed here, including Standby, Burner OFF, etc.
Assignment of buttons to their specific function
Operation
The various operating modes are displayed on InfoWIN together with the corresponding operating phases.
The following operating modes exist: –OFF
– ON (with self-test, lighting ON, lighting OFF) – Pellet feed – Solid fuel / buffer mode – Manual operation – Flue cleaning function – Shutdown procedure
Corresponding operating phases: – Standby
– Purging – Ignition phase – Flame stabilisation – Modulation mode – Burnout – Burner OFF – Switch off heat generator
è
Boiler temperature
Standby
Info Menu
38
°C
Fig. 9 InfoWIN
2.6 InfoWIN
The InfoWIN is the boiler’s display and operating unit. The InfoWIN unit consists of a large text display, an ON/OFF button with an LED signal lamp indicating Opera-
tion (green) or Malfunction (red); a switch for the flue cleaning function and four individual menu buttons. The function of each menu button is displayed on the Menu line.
Page 14
14
5s
RESET
5s
RESET
5s
RESET
Operation
2.7 Operating modes
2.7.1 OFF mode
The boiler is switched off when in OFF mode. The display and all buttons, with the exception of the
ON/OFF
button, do not function.
The LED on the InfoWIN is not illuminated – Fig. 10.
2.7.2 ON mode, lighting ON,
self-test, lighting OFF
Press the ON/OFF button, lighting and display are switched on and the self-test starts automatically – Fig. 11.
Self-test:
Sensors, switches and motors are checked during the self-test. After a successful self-test, the display shows an operating phase
and the boiler water temperature (standard display). The LED sig­nal lamp lights green and the desired functions can be selected using the buttons – Fig. 12.
If the self-test was unsuccessful, an information message (e.g. infor­mation, fault, alarm) is displayed (see sections 4.3 and 4.4).
Fig. 12 Standard display
Fig. 13 Display lighting OFF
Lighting ON/OFF
The display lighting switches off automatically after 10 min. (Fig.
13). Pressing one of the six buttons switches the lighting on again for 10 min.
InfoWIN identifies and stores the various operating modes and sta­tes. Once the system is switched on, other operating modes may also be displayed instead of the standard display, such as manual operation or solid fuel/buffer mode; malfunctions are also display­ed. These operating modes and states are described later in these instructions.
Fig. 11 Self-test
5s
RESET
Fig. 10 OFF mode
Self-test active
.....
(Animated symbol)
Boiler temperature
(Operating phases)
Info Menu
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Page 15
15
Operation
2.7.4 Solid fuel/buffer mode
If the VarioWIN pellet central heating boiler is combined with a solid fuel boi­ler or an buffer tank, the WVF or BUL module automatically switches over bet­ween pellet and solid fuel/buffer mode.
Combustion of the VarioWIN is stopped when the WVF or BUL module sends the request to switch over to solid fuel/buffer mode – Fig. 16.
Following this, the system switches over to solid fuel/buffer mode and the VarioWIN burner is locked – Fig. 17
If the pellet central heating boiler is switched off using the ON/OFF button on the InfoWIN, an automatic switchover to solid fuel/buffer mode is performed in conjunction with a WVF module. Once the InfoWIN unit is switched on, the pellet central heating boiler may be locked for a maximum of 15 minutes due to the switch-over delay. This is displayed by InfoWIN – Fig. 17.
After an hour in solid fuel/buffer mode, the display is shut down fully and only the green LED is lit up. The display is switched back on by pressing a button or when there is a heating requirement.
Fig. 16
Fig. 17
Solid fuel/ buffer mode
Burnout
Info Menu
42
°C
Solid fuel/ buffer mode
Burner locked
Info Menu
42
°C
2.7.3 Pellet feed
Pellet feed – Burnout
Pellet feed from the storage room into the reserve supply container has been requested. Combustion is stopped. Pellet transport into the burner pot is stop­ped, the vacuum fan continues to run until all the remaining pellets have been burned and the burner pot has cooled down – Fig. 14.
Pellet feed in operation
The pellet feed is in operation. Pellets are supplied from the storage room into the reserve supply container. The burner is locked – Fig. 15.
Fig. 14
Fig. 15
Pellet feed
Burnout
Info Menu
42
°C
Pellet feed in operation
Burner locked
Info Menu
42
°C
Page 16
16
5s
RESET5sRESET
5s
RESET5sRESET
Operation
2.7.5 Manual operation
Fig. 18
Pressing the
Cancel
button or the
Manual operation / flue cleaning
function
button terminates the function – Fig. 19. The boiler returns
to automatic operation.
Setpoint adjustment for manual operation
By pressing the + or – button the display switches to the set tem­perature adjustment mode – Fig. 20. Use the
+
or –button to chan­ge the setpoint in 1 K steps. The temperature set in this mode is not permanently saved. The original set temperature is used once manual operation ends.
By pressing the
Back
button (Fig. 21) or after waiting 45 seconds,
the screen returns to its previous display.
Press for 5 seconds
The various operating phases are displayed here, inclu­ding Burner in operation, Burner OFF, etc.
Fig. 19
Fig. 20
Fig. 21
Pressing one of the six buttons switches the lighting and display on. Manual operation starts if the Manual operation / flue cleaning func­tion button is pressed for more than five seconds – Fig. 18. This sets the boiler temperature to the setpoint fixed for manual operation (standard value 60 °C). The control system is not affected by this. The lighting is switched off after the lighting timer has counted down (10 min.); the function or display remains unchanged.
Note:
Manual operation cannot be started in „solid fuel/buffer mode“. Manual operation must not be started if an installed solid fuel boiler is operating (heated up). Manual operation may be started if there is no solid fuel boiler installed or if this is not operating and only the buffer tank is active. In this case, first set the operating mode switch on the WVF module to relay test 2 or on the BUL module to relay test 1 (see WVF or BUL modu­le operating manual).
16
Manual operation Boiler temperature
(Operating phases)
– Cancel +
42
°C
(Symbol flashes)
Manual operation Boiler temperature
(Operating phases)
– Cancel +
42
°C
(Symbol flashes)
Manual operation Set temperature
– Back +
70
°C
Manual operation Set temperature
– Back +
70
°C
(Symbol flashes)
Page 17
17
5s
RESET5sRESET
5s
RESET5sRESET
Briefly pressing the
Manual operation / flue cleaning function
button switches on the display illumination. Pressing the button again starts the flue cleaning function – Fig. 22. The boiler temperature is set to approx. 60 °C for 45 min.
Operation
2.7.6 Flue cleaning function
This function aids the performance of legally-required emissions testing.
The flue cleaning function ends – when the
Cancel
button is pressed – Fig. 24.
– automatically after about 45 minutes.
The various operating phases are displayed here, including Burner in operation, Burner OFF, etc.
Fig. 24
Fig. 23
Fig. 22
2.7.7 Shutdown procedure
The boiler is switched off – Fig. 25.
Fig. 25
The green LED flashes
Note:
The flue cleaning function cannot be started in „solid fuel/buffer mode“. The flue cleaning function must not be started if an installed solid fuel boiler is operating (heated up). The flue cleaning function may be star­ted if there is no solid fuel boiler installed or if this is not operating and only the buffer tank is active. In this case, first set the operating mode switch on the WVF module to relay test 2 or on the BUL module to relay test 1 (see WVF or BUL module operating manual).
Pressing the corresponding menu button enables the boiler to be ope­rated with 30 % or 100 % output – Fig. 23. The lighting is switched off after the lighting timer has counted down (10 min.); the function or display remains unchanged. When the button is first pressed only the lighting is switched on.
When the
Manual operation / flue cleaning function
button is pres-
sed again the operating time is reset to 45 min.
Flue cleaning function Power 100% 45min
(Operating phases)
30% Cancel 100%
42
°C
(Symbol flashes)
Flue cleaning function Power 30% 45min
(Operating phases)
30% Cancel 100%
42
°C
(Symbol flashes)
Flue cleaning function Power 30% 45min
(Operating phases)
30% Cancel 100%
42
°C
(Symbol flashes)
Shutdown procedure
Burnout
Info Menu
42
°C
Page 18
18
2.8.6 Burnout
Combustion is stopped. Pellet transport into the burner pot is stopped, the vacuum fan continues to run until all the remaining pellets have been burned and the burner pot has cooled down – Fig. 31.
2.8.7 Burner OFF
There is a heating requirement from the control system, but the boiler tem­perature (actual value) is higher than the boiler temperature setpoint. This means combustion is stopped and the burner is switched off – Fig. 32.
Fig. 31
Fig. 32
Boiler temperature
Burnout
Info Menu
42
°C
Boiler temperature
Burner OFF
Info Menu
42
°C
2.8 Operating phases
2.8.1 Standby
During this operating phase, the control system does not transmit requests for heat. The burner is switched off and the boiler temperature setpoint is 0 °C – Fig. 26.
After an hour in standby mode, the display is shut down fully and only the green LED is lit up. The display is switched back on by pressing a button or when there is a heating requirement.
2.8.2 Purging
The vacuum fan runs, the combustion chamber of the VarioWIN is flushed through with fresh air. This phase can last several minutes before the burner fires – Fig. 27.
2.8.5 Modulation mode
The burner is in modulation mode. The output can be infinitely varied between 30 % and 100 % – Fig. 30.
Operation
2.8.3 Ignition phase
The vacuum fan runs, pellets are transported into the burner pot and are igni­ted. When flame formation is detected, the system switches over to flame sta­bilisation – Fig. 28.
2.8.4 Flame stabilisation
Following the ignition procedure, even combustion is established and then the system switches over to modulation mode – Fig. 29.
Fig. 26
Fig. 27
Fig. 28
Fig. 29
Fig. 30
Boiler temperature
Standby
Info Menu
42
°C
Boiler temperature
Purging
Info Menu
42
°C
Boiler temperature
Ignition phase
Info Menu
42
°C
Boiler temperature
Flame stabilisation
Info Menu
42
°C
Boiler temperature
Modulation mode
Info Menu
42
°C
Page 19
19
5s
RESET5sRESET5sRESET
Operation
Fig. 33
2.9 Information text
Pressing the
Info
button calls up the most important VarioWIN infor-
mation – Fig. 33. The
arrow
buttons select and display sub-menus – Fig. 34. By pres-
sing the
Back
button (Fig. 35) or waiting 45 seconds, the screen
returns to the standard display.
Fig. 34
Fig. 35
Boiler temperature
(Operating phases)
Info Menu
42
°C
The following information texts exist: – Next boiler cleaning in about[h]
– Operating hours [h] – Pellet consumption total [t] – Flue gas temperature [°C] – Boiler temperature setpoint [°C] – Current boiler output [%] – Display module software version – Firing automate software version – Boiler model
Next boiler cleaning in about
Back
300
h
Next boiler cleaning in about
Back
300
h
2.9.2 Operating hours
The total number of burner operating hours is displayed – Fig. 37
Fig. 37
2.9.1 Next boiler cleaning
Display of the operating time in hours remaining until the next boiler cleaning – Fig. 36.
Note:
The operating time remaining until the next boiler cleaning depends on the operating method and is constantly recalculated. Therefore, there may be deviations from the normal operating hours.
Fig. 36
Next boiler cleaning in about
Back
300
h
Operating hours
Back
1.234
h
Page 20
20
Operation
2.9.6 Current boiler output
The current boiler output is displayed in %. The boiler output (modulation mode) can be set from 30 % to 100 % – Fig. 41.
Fig. 41
Current boiler output
Back
70
%
2.9.4 Flue gas temperature
If a flue gas temperature sensor (accessory) is connected, this function displays the current flue gas temperature – Fig. 39.
Fig. 39
Flue gas temperature
Back
114
°C
2.9.3 Pellet consumption total
The total amount of pellets consumed is displayed in tonnes – Fig. 38.
Note:
The „Pellet consumption total“ is a calculated value and can differ from the actual value by ±15%.
Fig. 38
Pellet consumption total
Back
1. 30
t
2.9.5 Boiler temperature setpoint
The display indicates the boiler temperature setpoint as calculated by the con­trol system. This setpoint is used to control the burner – Fig. 40.
Fig. 40
Boiler temperature setpoint
Back
63
°C
The flue gas temperature is measured directly on the flue outlet. It may therefore deviate from a standard measurement.
2.9.7 Display module software version
The current software version of the display module (InfoWIN) is displayed – Fig. 42.
Fig. 42
Software version display module
Back
4.00
2.9.8 Firing automate software version
The current software version of the firing automate (main PCB) is displayed – Fig. 43.
Fig. 43
Software version firing automate
Back
4.10
2.9.9 Boiler model
The boiler model of the VarioWIN is displayed – Fig. 44.
Fig. 44
Boiler model
Pellet boiler 120K Boiler 0
Back
Page 21
21
5s
RESET5sRESET
5s
RESET
5s
RESET
Operation
2.10 Menu guide
Pressing the
Menu
button changes the menu display to operator
level or service level – Fig. 45. Use the
arrow
buttons to select the operator level or service level
(Fig. 46) and confirm with the
Choose
button – Fig. 47.
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 48) or after a delay of 45 seconds.
Fig. 45
Fig. 46
Fig. 47
Fig. 48
Only trained service personnel may perform system modi­fications in the service level.
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Operator level
Service level
Choose Back
Operator level
Service level
Choose Back
Page 22
22
Menu structure:
Operator level
Service level
(reserved for trained service
personnel only)
Time
Feed
operating mode
1)
Time profile
feed
1)
Probe
switching
1)
Menu
With enable
time
With start time
Without
time control
Switched off
Automatic Only probe 1 Only probe 2 Only probe 3
With enable time:
Start/finish
With start time:
Start
Operation
Time profile
ash com.
Boiler
cleaning
Start time 1
08:00
Start time 2
22:00
1)
Only displayed with a VarioWIN - VAE 120 P with pneumatic feed (suction system) when the unit has been adjusted by a trained service technician in the service level.
Page 23
23
5s
RESET5sRESET
5s
RESET5sRESET
Fig. 49
Fig. 50
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 52) or after a delay of 45 seconds.
2.10.1 Operator level
Pressing the
Menu
button changes to the „Operator level“ and
„Service level“ – Fig. 49.
Fig. 51
Operation
Use the
arrow
buttons to select „Operator level“ and confirm with
the
Choose
button – Fig. 50.
On the operator level, use the
arrow
buttons to select the requi-
red sub-menu (Fig. 51) and confirm with the
Choose
button.
Adjusting the: Boiler cleaning: 2.10.1.1 Time: see section 2.10.1.2. Feed operating mode: see section 2.10.1.3. Time profile feed: see section 2.10.1.4. Probe switching: see section 2.10.1.5. Time profile ash compression: see section 2.10.1.6
Fig. 52
Note:
The menu items „Feed operating mode“, „Time profile feed“ and „Probe switching“ are only shown with a VarioWIN - VAE 120 P with pneumatic feed (suction system) when service level is activa­ted.
Boiler cleaning
Time Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Boiler cleaning
Time Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
Page 24
24
Operation
5s
RESET
5s
RESET
5s
RESET
5s
RESET
5s
RESET
Fig. 53
Fig. 54
Fig. 55
Fig. 56
Press the
Menu
button – Fig. 54.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 55.
Use the
arrow
buttons to select the „Boiler cleaning“ sub-menu
item – Fig. 56.
Confirm the selected „Boiler cleaning“ sub-menu item by pressing the
Choose
button – Fig. 57.
Fig. 57
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Boiler cleaning
Time Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
Boiler cleaning
Time Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
2.10.1.1 Boiler cleaning -
Resetting the cleaning request
After boiler cleaning has been performed (section 3.1), boiler cle­aning must be confirmed so that the operating time until the next boiler cleaning is restarted.
Pressing one of the six buttons switches the lighting and display on – Fig. 53.
Boiler cleaning must not be reset if cleaning has not been carried out.
Page 25
5s
RESET
5s
RESET
Pressing the
Yes
button resets the boiler cleaning – Fig. 58. The display shows „Parameter is saved“ for a few seconds (Fig. 59) and then changes back to the previous level – Fig. 60.
Fig. 58
Fig. 59
Has boiler and burner cleaning been performed?
Confirm
– Yes Back +
Parameter is saved
.....
(Animated symbol)
Operation
25
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 60) or after a delay of 45 seconds.
5s
RESET
Fig. 60
Boiler cleaning
Time Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
Page 26
26
5s
RESET5sRESET
5s
RESET
5s
RESET
5s
RESET
Operation
2.10.1.2 Time
This time is used for the time control of the pellet feed, automatic heating surface cleaning and automatic ash compression.
If the VarioWIN is operated with an MES control, the time is auto­matically adopted from the module and the time set here is over­written.
If the VarioWIN is operated with REG standard control, the time must be set here too.
Pressing one of the six buttons switches the lighting and display on – Fig. 61.
Fig. 61
Fig. 62
Fig. 63
Fig. 64
Fig. 65
Press the
Menu
button – Fig. 62.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 63.
Confirm the selected sub-menu item „Time“ by pressing the
Choo-
se
button – Fig. 64.
Use the
arrow
buttons to set the required time – Fig. 65.
Set time
Save
– Yes No +
13:50
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler cleaning
Time
Feed operating mode Time profile feed Probe switc hing Time profile ash comp.
Choose Back
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Page 27
27
5s
RESET
5s
RESET
5s
RESET
Fig. 66
Operation
Save the changed time by pressing the
Yes
button – Fig. 66. The display shows „Parameter is saved“ for a few seconds (Fig. 67) and then changes back to the previous level – Fig. 68.
Fig. 67
Fig. 68
Parameter is saved
.....
(Animated symbol)
Set time
Save
– Yes No +
13:50
Boiler cleaning
Time
Feed operating mode Time profile feed Probe switching Time profile ash comp.
Choose Back
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 68) or after a delay of 45 seconds.
Page 28
28
5s
RESET5sRESET5sRESET5sRESET
5s
RESET
Operation
2.10.1.3 Feed operating mode
1)
This menu item sets: – whether the feed is switched off, or
– whether the feed should fill the pellet boiler with or without time
control.
Pressing one of the six buttons switches the lighting and display on – Fig. 69.
Fig. 69
Fig. 70
Fig. 71
Fig. 72
Press the
Menu
button – Fig. 70.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 71.
Use the
arrow
buttons to select the sub-menu item „Feed opera-
ting mode“ – Fig. 72.
Confirm the selected sub-menu item „Feed operating mode“ by pressing the
Choose
button – Fig. 73.
Fig. 73
Boiler cleaning Time
Feed operating mode
Time profile feed Probe switching Time profile ash comp.
Choose Back
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Boiler cleaning Time
Feed operating mode
Time profile feed Probe switching Time profile ash comp.
Choose Back
1)
Only displayed with a VarioWIN - VAE 120 P with pneumatic feed (suction system) when the unit has been adjusted by a trained service technician in the service level.
Page 29
29
Burning duration with 25 kg pellets
VarioWIN Burning duration at nominal output
VAE 120 P approx. 10 h
5s
RESET5sRESET
5s
RESET
5s
RESET
The factory setting for „Feed operating mode“ is „switched off“.
Without time control: Select this if the feed noise (suction turbine)
is not audible or intrusive in the living area (or adjacent premi­ses). This mode guarantees the fewest possible feeds because the reserve supply container is always „run to empty“.
Functional description: The pellet feed is automatically switched on if required at any time.
With start time: Select this if you want the feed to start at the same
time every day. Functional description: The reserve supply container is filled
every day if required at the set time (see page 31). Interim fills are also performed if the filling amount is not sufficient for 24 hours.
With enable time: Select this if the feed noise (suction turbine) is
audible or intrusive in the living area (or adjacent premises). Functional description: The pellet feed is enabled during a time
period that can be set (see page 32) and is automatically star­ted at this time if required. The reserve supply container is fully refilled at the end of the enable time, if required.
Tip: A complete fill sucks in about 25 kg of pellets. Even if more pellets are required during the blocked time, there is no automatic fill and the VarioWIN switches off (fault message 381). Therefore, do not select a lock-out time that is too long.
Fig. 74
Operation
Fig. 75
Fig. 77
It is only ever possible to select one menu item at a time. The „Time profile feed“ corresponding to this selected menu item can then be set in section 2.10.1.4.
Fig. 76
Use the
arrow
buttons to select the required sub-menu item – Fig. 74.
Save the changed feed operating mode by pressing the
Yes
button – Fig. 75. The display shows „Parameter is saved“ for a few seconds (Fig. 76) and then changes back to the previous level – Fig. 77.
The menu item or sub-menu item is exited by pressing the
Back
but-
ton (Fig. 77) or after a delay of 45 seconds.
Feed operating mode
with enable time with start time without time control
switched off
Save
Yes No
Feed operating mode
with enable time
with start time without time control switched off
Save
Yes No
Parameter is saved
.....
(Animated symbol)
Boiler cleaning Time
Feed operating mode
Time profile feed Probe switching Time profile ash comp.
Choose Back
Page 30
30
5s
RESET
5s
RESET
5s
RESET
5s
RESET
5s
RESET
Operation
2.10.1.4 Time profile feed
1)
The „Time profile feed“ menu item displays the corresponding set­ting option depending on the setting in the „Feed operating mode“ menu item (see section 2.10.1.3).
Setting: „with enable time“ see page 32 Setting: „with start time“ see page 31 Setting: „without time control“ or „switched off“ see page 33
Pressing one of the six buttons switches the lighting and display on – Fig. 78.
Fig. 78
Fig. 79
Fig. 80
Fig. 81
Press the
Menu
button – Fig. 79.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 80.
Use the
arrow
buttons to select the sub-menu item „Time profile
feed“ – Fig. 81.
Confirm the selected sub-menu item „Time profile feed“ by pres­sing the
Choose
button – Fig. 82.
Fig. 82
Boiler cleaning Time Feed operating mode
Time profile feed
Probe switching Time profile ash comp.
Choose Back
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Boiler cleaning Time Feed operating mode
Time profile feed
Probe switching Time profile ash comp.
Choose Back
1)
Only displayed with a VarioWIN - VAE 120 P with pneumatic feed (suction system) when the unit has been adjusted by a trained service technician in the service level.
Page 31
31
5s
RESET
5s
RESET
5s
RESET
5s
RESET
„with start time“
A time can be set here in the „Time profile feed“ menu item for fil­ling the reserve supply container if the „with start time“ setting is active in the „Feed operating mode“ menu item (see section
2.10.1.3). The reserve supply container is filled every day at the set time. Interim fills are also performed if the filling amount is not suf­ficient for 24 hours.
Factory setting „Feed start time“: Start 20:00
Pressing the
+
or –button changes the time in 1 min. steps – Fig. 83.
Fig. 83
Operation
Fig. 84
Fig. 86
Save the changed time by pressing the
Yes
button – Fig. 84. The display shows „Parameter is saved“ for a few seconds (Fig. 85) and then changes back to the previous level – Fig. 86.
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 86) or after a delay of 45 seconds.
Fig. 85
31
Feed start time
Start 20:00
Save
– Yes No +
Feed start time
Start 20:00
Save
– Yes No +
Boiler cleaning Time Feed operating mode
Time profile feed
Probe switching Time profile ash comp.
Choose Back
Parameter is saved
.....
(Animated symbol)
Page 32
32
5s
RESET
5s
RESET5sRESET
5s
RESET
5s
RESET
„with enable time“
The start and end of the enable time can be set here in the „Time profile feed“ menu item if the „with enable time“ setting is active in the „Feed operating mode“ menu item (see section 2.10.1.3).
Factory setting „Feed enable time“: Start 07:00
End 22:00
Use the
arrow
buttons to select the time you want to change,
„Start“ or „End“ – Fig. 87. Confirm the selected time by pressing the
Choose
button – Fig. 88.
Fig. 87
Operation
Fig. 88
Fig. 89
Fig. 90
Fig. 91
Pressing the +or –button changes the time in 15 min. steps – Fig.
89.
Save the changed time by pressing the
Yes
button – Fig. 90. The display shows „Parameter is saved“ for a few seconds (Fig. 91) and then changes back to the previous level.
Feed enable time
Start 07:00
End 22:00
Choose Back
Feed enable time
Start 07:00
End 22:00
Choose Back
Feed enable time
Start 07:00
End 22:00
Save
– Yes No +
Feed enable time
Start 07:00
End 22:00
Save
– Yes No +
Parameter is saved
.....
(Animated symbol)
Page 33
33
5s
RESET
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 92) or after a delay of 45 seconds.
Operation
Fig. 92
Feed enable time
Start 07:00
End 22:00
Choose Back
5s
RESET
„without time control“ or „switched off“
No setting is possible here in the „Time profile feed“ menu item if the „without time control“ or „switched off“ setting is active in the „Feed operating mode“ menu item (see section 2.10.1.3) – Fig. 94.
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 94) or after a delay of 45 seconds.
Fig. 94
Feed without time control or switched off
Back
5s
RESET
Fig. 93
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 93) or after a delay of 45 seconds.
Boiler cleaning Time Feed operating mode
Time profile feed
Probe switching Time profile ash comp.
Choose Back
Page 34
34
5s
RESET
5s
RESET
5s
RESET
5s
RESET
5s
RESET
34
Operation
2.10.1.5 Probe switching
1)
If the VarioWIN is equipped with a pneumatic feed (suction system) with 2 or 3 probes, it is possible to set here which probe is used for sucking pellets from the pellet storage room. There are four dif­ferent setting options:
– Automatic: Removal from all 3 probes, automatic switching. – Only probe 1:Removal from probe 1 only, no switching – Only probe 2:Removal from probe 2 only, no switching – Only probe 3:Removal from probe 3 only, no switching
Note: If „Pellet feed system, operation with 2 probes“ is set in the „Service level“, the option of „Only probe 3“ is not displayed here.
Fig. 95
Fig. 96
Fig. 97
Fig. 98
Pressing one of the six buttons switches the lighting and display on – Fig. 95.
Press the
Menu
button – Fig. 96.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 97.
Use the
arrow
buttons to select the „Probe switching“ sub-menu
item – Fig. 98.
Confirm the selected sub-menu item „Probe switching“ by pressing the
Choose
button – Fig. 99.
Fig. 99
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Boiler cleaning Time Feed operating mode Feed tiame profile
Probe switching
Time profile ash comp.
Choose Back
Boiler cleaning Time Feed operating mode Time profile feed
Probe switching
Time profile ash comp.
Choose Back
1)
Only displayed with a VarioWIN - VAE 120 P with pneumatic feed (suction system) when the unit has been adjusted by a trained service technician in the service level.
Page 35
35
5s
RESET5sRESET
5s
RESET
5s
RESET
Use the
arrow
buttons to select the required probe switching –
Fig. 100.
Fig. 100
Operation
Fig. 101
Fig. 103
Save the changed probe switching by pressing the
Yes
button – Fig. 101. The display shows „Parameter is saved“ for a few seconds (Fig. 102) and then changes back to the previous level.
Tip: This menu item is also needed for „Pellet store maintenance“ in order to switch off one specific probe at a time – see also the pel­let store planning documents.
The menu item or sub-menu item is exited by pressing the
Back
button (Fig. 103) or after a delay of 45 seconds.
Fig. 102
Probe switching
Automatic
Only probe 1 Only probe 2 Only probe 3
Save
Yes No
Parameter is saved
.....
(Animated symbol)
Probe switching
Automatic
Only probe 1 Only probe 2 Only probe 3
Save
Yes No
Boiler cleaning Time Feed operating mode Time profile feed
Probe switching
Time profile ash comp.
Choose Back
Page 36
36
5s
RESET
5s
RESET5sRESET
5s
RESET
5s
RESET
2.10.1.6 Time profile ash compression (Exklusiv version only)
The ash in the ash pan is only compressed at the 2 set start times and when approx. 15 kg of fuel has been consumed. The start times can be set in steps of 15 minutes (start time 1 and start time 2).
Factory setting: Start time 1: 08:00
Start time 2: 22:00
Pressing one of the six buttons switches the lighting and display on – Fig. 104.
Fig. 104
Fig. 105
Fig. 106
Fig. 107
Press the
Menu
button – Fig. 105.
Confirm the selected menu item „Operator level“ by pressing the
Choose
button – Fig. 106.
Use the
arrow
buttons to select the sub-menu item „Time profile
ash comp.“ – Fig. 107.
Confirm the selected sub-menu item „Time profile ash comp.“ by pressing the
Choose
button – Fig. 108.
Fig. 108
Boiler cleaning Time Feed operating mode Time profile feed Probe switching
Time profile ash comp.
Choose Back
Boiler temperature
(Operating phases)
Lighting ON
42
°C
Boiler temperature
(Operating phases)
Info Menu
42
°C
Operator level
Service level
Choose Back
Operation
Boiler cleaning Time Feed operating mode Time profile feed Probe switching
Time profile ash comp.
Choose Back
Page 37
37
5s
RESET5sRESET5sRESET
5s
RESET
5s
RESET
Use the
arrow
buttons to select the start time you want to change,
1 or 2 – Fig. 109. Confirm the selected start time by pressing the
Choose
button – Fig. 110.
Fig. 109
Fig. 110
Fig. 111
Fig. 112
Fig. 113
Pressing the +or –button changes the time in 15 min. steps – Fig. 111.
Save the changed time by pressing the
Yes
button – Fig. 112. The display shows „Parameter is saved“ for a few seconds (Fig. 113) and then changes back to the previous level.
Start times for ash compression
Start time 1 08:00
Start time 2 22:00
Choose Back
Start times for ash compression
Start time 1 08:00
Start time 2 22:00
Save
– Yes No +
Parameter is saved
.....
(Animated symbol)
Operation
Start times for ash compression
Start time 1 08:00
Start time 2 22:00
Choose Back
Start times for ash compression
Start time 1 08:00
Start time 2 22:00
Save
– Yes No +
Page 38
38
Operation
5s
RESET
5s
RESET
5s
RESET
2.10.2 Service level
System parameters, start-up and the actuator test can be display­ed, performed and/or modified in the service level.
Fig. 115
Fig. 114
Changes in the service level may be performed only by trai­ned service personnel (for setting instructions, see the VarioWIN „Assembly instructions“).
Fig. 116
The menu item or sub-menu item is exited by pressing the
Back
but-
ton (Fig. 116) or after a delay of 45 seconds.
Operator level
Service level
Choose Back
Service level only for trained service personnel
5 s
Parameters
Start-up Actuator test
Choose Back
Page 39
39
Operation
2.11 Heating system operation
2.11.1 VarioWIN with MES system control
Switching on – Automatic operation:
1. Press the ON/OFF button on the InfoWIN panel, the display lighting is switched on, the signal lamp lights
up green and a self-test is performed (see also section 2.7.2). After a successful self-test and if a setpoint is transferred by the control system, the VarioWIN automatically starts operation.
2. Set the operating mode switch(es) on the MES control module(s) to „Automatic operation“ . The system
is operated (temperatures and operating times set) using the user module (installed in the living area) – ple­ase refer to the instructions.
Fig. 117 InfoWIN operating unit
ON/OFF button
Operating mode switch
Switching off:
1. Set the operating mode to „Standby“ using the user module (installed in the living area).
2. If the boiler has been out of service for an extended period during the summer months, press the ON/OFF button
on the InfoWIN unit.
Flue cleaning function:
This is operated using the InfoWIN unit – see section 2.7.6.
Emergency operation:
In the event that the control system fails, selecting the „Manual operation“ mode on the MES control module and InfoWIN unit (see section 2.7.5) will activate emergency operation to maintain heat and hot water .
For operation of the MES and user module(s), please see the respective operating instructions.
The anti-freeze function is not active when the boiler is shut off.
InfoWIN operating unit
Fig. 118 Control panel behind right side panel
Page 40
40
Operation
2.10.2 VarioWIN with REG standard control
Switching on – Automatic operation:
1. Press the ON/OFF button on the InfoWIN panel, the display lighting is switched on, the signal lamp lights
up green and a self-test is performed (see also section 2.7.2). After a successful self-test and if a setpoint is transferred by the control system, the VarioWIN automatically starts operation.
2. Set both manual switches to the “Automatic” position.
3. Set the operating mode switch on the REG standard control unit RAM 786 to “Automatic operation“ . The
REG standard control unit RAM 786 (installed in the living area) is used to operate the system (set the des­ired temperatures and operating times) – please refer to the separate operating instructions.
The time must be set on the InfoWIN (see section 2.10.1.2). The time is used for the time control of the pel­let feed, automatic heating surface cleaning and automatic ash compression.
Operating mode switch
Switching off:
1. Set “Standby” operating mode on the REG standard control unit (installed in the living area).
2. If the boiler has been out of service for an extended period during the summer months, press the ON/OFF
button on the InfoWIN unit.
Flue cleaning function:
This is operated using the InfoWIN unit – see section 2.7.6.
Emergency operation:
If the control system fails, you can use the two manual switches and on the boiler control panel and the button on the InfoWIN unit (see section 2.7.5) to activate emergency operation to maintain heat and hot water.
The anti-freeze function is not active when the boiler is shut off.
Manual switch for heating
Manual switch for hot water tank
Automatic operation
Fig. 119 InfoWIN operating unit
Fig. 121
REG standard control RAM 786
ON/OFF button
InfoWIN opera­ting unit
Fig. 120 Control panel behind right side panel
Page 41
41
Operation
How to switch to emergency (manual) operation
Heating emergency operation:
1. There must be power to the boiler. The unit is switched on (otherwise, press the ON/OFF button on the InfoWIN unit).
2. Select “Manual operation” on the InfoWIN unit – see section 2.7.5.
3. Set the manual switch to the „Heating manual operation” position.
4. Also set the motorised mixing valve to manual operation and select the desired flow temperature. The boi­ler temperature will be maintained at the selected temperature (60 to 75 °C). Exercise caution if you have
underfloor heating.
Emergency operation of boiler reservoir with feed pump:
1. There must be power to the boiler. The unit is switched on (otherwise, press the ON/OFF button on the InfoWIN unit).
2. Select „Manual operation” on the InfoWIN unit – see section 2.7.5.
3. Set the manual switch to the „Hot water tank manual operation” position.
4. Once the desired hot water temperature has been reached, set the manual switch to the „Hot water tank auto­matic operation” position.
Emergency operation of hot water tank loading with charging valve:
1. There must be power to the boiler. The unit is switched on (otherwise, press the ON/OFF button on the InfoWIN unit).
2. Select „Manual operation” on the InfoWIN unit – see section 2.7.5.
3. Set both manual switches and to the „Manual operation“ position.
Page 42
42
3.1 Care of cladding and keyboard foil
Clean the cladding and the keyboard foil with a damp cloth as needed. In the event of heavy soiling, use soapy water or diluted suds (do not use strong cleaners or sharp cleaning instruments).
3.3 Overview of intervals between maintenance
A clean boiler saves fuel and protects the environment. Fly ash and combustion residues must be cleaned off the pellet central heating boiler at regular intervals. Therefore always clean your boiler as required!
Annual maintenance is required in addition to cleaning. This is performed
by WINDHAGER Customer Service or
the customer service PARTNERS and is a prerequisite of the guarantee limitations. The cleaning and ash removal intervals may be reduced or extended depending on the pellets used (e.g. ash
proportion) and the power consumed by the heating system (frequently switching on and off). The VarioWIN is equipped with a cleaning interval display. The cleaning request for the combustion chamber
and burner pot is displayed on the InfoWIN and must be reset after cleaning is finished – see section 2.10.1.1.
Care, cleaning and maintenance
3.2 Cleaning and operating implements
Install the hanger with the instructions folder, cleaning and operating implements, dowels and bolts on a wall in the boiler room / installation room – Fig. 122.
1 . . . . .Folder containing instructions
2 . . . . .Key for cladding door and manual
heating surface cleaning with VarioWIN Premium
3 . . . . .Spatula
4 . . . . .Cleaning brush
5 . . . . .Hanger for installation on the wall
6 . . . . .Cleaning tool or removal device for cone
Fig. 122 Instructions folder, cleaning and ope-
rating implements with hanger
1
2
3
4
5
6
Page 43
43
Care,
cleaning and
ash removal intervals
VarioWIN Premium-D VarioWIN Exklusiv-S VarioWIN Exklusiv-P/D
Depending on pellet con-
sumption
Approx. every 41 kg
(~ 20 operating hours)
–
Add pellets to
reserve supply container
–
Depending on pellet con-
sumption
Approx. every 400 kg
(~ 250 operating hours)
Empty the ash pan
Operate the heating surface
cleaning lever
Frequent use of the lever increases
efficiency
– –
Display
Clean boiler and
burner
IN 580
FE 390
Clean combustion chamber
and burner pot
Empty the ash pan
Operate the heating surface
cleaning lever
Frequent use of the lever increases
efficiency
– –
Display
Clean boiler and
burner
IN 580
FE 390
–
Clean combustion chamber
and burner pot
Check reserve supply
container VarioWIN,
if necessary
remove dust
Empty the ash pan
Clean combustion chamber
and burner pot
Check reserve supply
container VarioWIN,
if necessary
remove dust
Empty the ash pan
At least once per
heating season
Clean top heating surfaces
and linkage
Clean blower wheel and
blower box
Clean exhaust pipe to flue
Check the storage container, if
necessary remove dust
Clean top heating surfaces
and linkage
Clean blower wheel and
blower box
Clean exhaust pipe to flue
Remove dust from reserve
supply container and
clean filter
Clean the top heating surfaces
and linkage
Clean blower wheel and
blower box
Clean exhaust pipe to flue
Remove dust from reserve
supply container and
clean filter
Check the storage room or sto-
rage container, if necessary
remove dust
Care, cleaning and maintenance
Page 44
44
Tip: Position newspaper or the like to protect the floor against fly ash before opening the combustion chamber door.
– Open the cladding door and ash door, empty the ash pan under the combustion chamber and the ash pan
for the heating surfaces – Fig. 125.
Assembly:
– Push in the ash pans, close the doors. – Switch the VarioWIN back on with the ON/OFF button.
Fig. 123 Connect the key and operate it
Fig. 124 Switching off the VarioWIN Fig. 125 Emptying the ash pan
Always switch the boiler off first with the ON/OFF button (Fig. 124) and wait until burnout mode has finished. Do not open the combustion chamber and ash door during operation.
3.5 Ash pan, ash on heating surface
Care, cleaning and maintenance
3.4 Heating surfaces
VarioWIN Premium
Optimum efficiency is achieved when the heating surfaces are cleaned as often as possible using the key. Howe­ver, no later than before the ash pan is emptied or ash is removed from the heating surfaces, the key should be connected on the right-hand side and moved back and forth several times – Fig. 123.
Ash pan for heating surfaces
When emptying the ash pans, remember that there could still be embers in the ash!
VarioWIN Exklusiv
The heating surfaces are cleaned fully automatically after the set start times (see section 2.10.1.6) and when approx. 15 kg of fuel has been consumed ⇒ on average 1x a day.
Ash pan for combustion chamber
Page 45
45
Care, cleaning and maintenance
Do not open the combustion chamber door during operation. Always switch the boiler off first with the ON/OFF button (Fig. 126) and wait until burnout mode has finished. It is essential to let the boiler cool down before cleaning.
Thermocontrol sensor
Fig. 127 Removing and cleaning the baffle plate
Fig. 128 Cleaning the thermocontrol sensor
(with cleaning brush)
Fig. 126 Switching off the VarioWIN
3.6 Combustion chamber
The VarioWIN is equipped with a cleaning interval display. The cleaning request for the combustion chamber and burner pot is displayed and must be reset after cleaning is finished – see section 2.10.1.1. „Boiler cleaning
- Resetting the cleaning request“.
3.6.1 Baffle plate, thermocontrol sensor
– Open the combustion chamber door, lift the baffle plate at the right and guide it out at an angle, sloping
down to the left – Fig. 127, Removing the baffle plate and fly ash.
– If necessary, remove fly ash from the thermocontrol sensor with a cleaning brush. The thermocontrol sen-
sor is located at the top left of the combustion chamber behind the baffle plate – Fig. 128.
Assembly:
By working through these steps in reverse order.
Page 46
46
Care, cleaning and maintenance
Do not open the combustion chamber door during operation. Always switch the boiler off first with the ON/OFF button and wait until burnout mode has finished. It is essential to let the boiler cool down befo­re cleaning.
Before cleaning with a vacuum cleaner, check that there are no longer any embers in the combustion residue!
The glow ignition is located in the primary air tube so avoid shaking the burner pot violently – risk of breakage!
– Lift out the cone (3) using the cleaning tool (1) – Fig.
129.
– Use the spatula to scrape off the deposits from all
sides of the cone (3), but particularly on the undersi­de.
– Vacuum out the burner pot, remove the primary air pin
(4) and carefully clean the holes with a small screw­driver or drill bit if necessary (holes must be clear).
– Lift out and remove the grate plate (5) from below
through the base of the burner pot. Scrape off ash resi­dues from the grate plate (5) and from the hole in the middle using the spatula to clean it. Tip: Dampen stubborn residue with water before scra­ping off.
– Scrape combustion residue off the burner pot base by
turning the cleaning tool (1) – Fig. 129. The pipe for the primary air pin serves as a guide for the cleaning tool – see detail. Use the spatula to scrape the edges of the burner pot base clean. All secondary air holes (6) must be clear - clean them with a small screwdriver or drill bit if necessary.
– Remove combustion residue from the burner pot with
a vacuum cleaner. Vacuum the ash out of the primary air tube (in the middle of the burner pot).
Clean the burner pot once the secondary air holes or the holes in the primary air pin are partly blocked or the unit prompts you to clean the burner pot with a fault message.
Fig. 129 Fig. 130
Assembly:
– Insert the grate plate (5), making sure the projection/opening of the grate plate (5) projects through the dri-
ver of the driving rod and rests fully on the bottom grate plate – Fig. 130. Important: Before inserting the primary air pin (4), once again vacuum out the primary air tube in the midd-
le of the burner pot. Make sure there is no debris in the tube (to avoid damage to the ignition element!). – Insert the primary air pin (4) (groove must engage with anti-twist device). – Place the cone (3) into the burner pot using the cleaning tool (1). The guide groove (2) on the cone must
engage with the lock (7) – Fig. 129. – Note: After cleaning, the cleaning request for the combustion chamber and burner pot is reset on the Info-
WIN – see Section 2.10.1.1.
1 Cleaning tool or removal device for cone 2 Guide groove for locking the cone in the burner pot 3 Cone 4 Primary air pin 5 Grate plate 6 Secondary air holes 7 Lock for cone 8 Burner pot
Detail
3.6.2 Burner pot
Page 47
47
Care, cleaning and maintenance
3.7 VarioWIN reserve supply container
It is necessary to clean the reserve supply container if too much dust has collected on the sides or at the ope­ning above the auger, or there are foreign bodies in the reserve supply container. In order to be able to check this, there must not be any pellets in the reserve supply container. Therefore, allow the pellets in the reserve supply container to be consumed or, in the case of the VarioWIN with pneumatic feed (suction system), switch off the feed on the day before (see section 2.10.1.3 Setting the feed operating mode).
Fig. 131 Switching off the VarioWIN
Fig. 132 Folding open the cover
Cleaning
VarioWIN Exklusiv-S with manual filling: – Switch off the VarioWIN with the ON/OFF button on the InfoWIN (Fig. 131) and wait until the display has gone
out. – Open the cover of the reserve supply container (Fig. 132) and vacuum out the pellets, dust or foreign bodies
through the mesh using a vacuum cleaner.
Page 48
48
Care, cleaning and maintenance
– Remove both knurled screws (Fig. 135) and fold open the inspection cover (Fig. 136). – Remove dust (bridge formation) from the container and from both Fill level switch (proximity switch) using
a vacuum cleaner. – Close the inspection cover again and screw it on with knurled screws.
Fig. 135 Removing the two knurled screws
Fig. 136 Folding open the inspection
cover, removing dust
Fig. 137 Removing the knurled screws
Fig. 138 Removing the coarse filter,
removing pellets and dust
– Remove both knurled screws at the back from the coarse filter (Fig. 137) and remove the coarse filter (Fig. 138). – Remove pellets and dust using a vacuum cleaner. – Put the coarse filter back on and screw it on with knurled screws.
Assembly:
By working through these steps in reverse order.
VarioWIN Exklusiv with pneumatic feed (suction system): – Switch off the VarioWIN with the ON/OFF button on the InfoWIN (Fig. 133) and wait until the display has gone
out. – Open the cover of the reserve supply container – Fig. 134.
Fig. 133 Switching off the VarioWIN
Fig. 134 Folding open the cover
Fill level switch (proximity switch)
Page 49
49
3.8 Top heating surfaces and linkage
These parts are automatically checked and cleaned as part of the annual maintenance by WINDHAGER Customer Service or the customer service PARTNER.
Fig. 140 Removing the cover
Fig. 141 Removing the wing nuts and cover
Fig. 142 Removing the jet protection plate
Care, cleaning and maintenance
Fig. 143 Cleaning top heating surfaces and linkage
Fig. 139 Switching off the VarioWIN
– Unscrew two wing nuts from the heating surface cover and remove the complete cover – Fig. 141. – Remove the jet protection plate (tip: vacuum out fly ash first using a vacuum cleaner) – Fig. 142.
Fig. 144 Connect the key and move it back
and forth several times
Fig. 145 Emptying the ash pan
– Empty the ash pan for heating surfaces – Fig. 145.
– Vacuum down the top heating surfaces and linkage or clean with a cleaning brush – Fig. 143. – For VarioWIN Premium only (manual heating surface cleaning): Connect the key on the right-hand side and
move it back and forth several times – Fig. 144.
Always switch the boiler off first with the ON/OFF button (Fig. 139) and wait until burnout mode has finished. It is essential to let the boiler cool down before cleaning.
– Remove the front cover – Fig. 140.
Page 50
50
3.9.1 Blower wheel, blower box and exhaust pipe to flue
Fig. 147 Disconnecting the blower
plug
Fig. 150 Removing the wing nuts and cleaning
opening – cleaning the exhaust pipe
– Disconnecting the blower plug – Fig. 147. – Unscrew two wing nuts from the blower box and remove the complete blower unit – Fig. 148.
Fig. 149 Cleaning the blower wheel
Fig. 148 Removing wing nuts, removing the
blower unit
– Clean the blower wheel using a spatula and brush – Fig. 148. – Inside of blower box: Clean fly ash with a vacuum cleaner. – Unscrew two wing nuts from the exhaust pipe and remove the cleaning cover (Fig. 150). Clean fly ash out of the
exhaust pipe with a vacuum cleaner. Close the cleaning cover again.
Care, cleaning and maintenance
It is essential to let the boiler cool down before cleaning.
– Unhook the rear right side panel cladding and disconnect the mains power plug over the control panel – Fig. 146 – Remove the screw under the mains power plug on the control panel (Fig. 148) and swivel open the control panel.
These parts are automatically checked and cleaned as part of the annual maintenance by WINDHAGER Custo­mer Service or the customer service PARTNER.
Fig. 146 Removing the power plug and screw
3.9 Blower wheel, blower box, exhaust pipe and
rotary feeder
Mains power plug
Page 51
51
Care, cleaning and maintenance
Assembly:
– Screw the screw plug back in and refit the cladding parts 1– 4. – Close the control panel, connect the securing mechanism and mains power plug at the top using a screw and
hook in the side panel.
3.9.1 Rotary feeder
VarioWIN S/P with 41 kg reserve supply container / pneumatic pellet feed:
Cleaning:
– Unscrew the screw plug (WAF 22) from the rotary feeder (Fig. 151) and vacuum pellet dust out of the rotary fee-
der using a vacuum cleaner.
Fig. 153 Removing dust from the rotary feeder
Screw plug
1
2
3
4
Fig. 152 Removing cladding parts 1–4 in the
case of direct pellet feed
VarioWIN D with direct pellet feed:
Cleaning:
– In the case of the VarioWIN with direct pellet feed, cladding parts 1 to 4 must be removed from the actuator
first – Fig. 152
– Unscrew the screw plug (WAF 22) from the rotary feeder (Fig. 153) and vacuum pellet dust out of the rotary fee-
der using a vacuum cleaner.
Fig. 151 Removing dust from the rotary feeder
Screw plug
Assembly:
– Guide the blower unit in at the back using the stay bolts and attach at the front with two wing nuts. – Reconnect the blower plug.
Assembly:
– Screw the screw plug back in. – Close the control panel, connect the securing mechanism and mains power plug at the top using a screw and
hook in the side panel.
Page 52
52
5s
RESET5sRESET5sRESET
Troubleshooting
The VarioWIN pellet boiler is self-monitoring during operation. All deviations from normal operation are display­ed on the InfoWIN by information, fault or alarm messages. If one of these messages appears, the LED lights up red, an information, fault or alarm symbol flashes, and an information code is displayed along with a brief description in full text – Fig. 154.
Pressing the
Info
button (Fig. 154) displays the related information text (Fig. 155). To exit the information text
menu, press the
Back
button (Fig. 155) or wait 10 seconds and the information, fault or alarm message is display-
ed again – Fig. 154. With almost all messages, it is necessary to press the
Reset
button after rectifying the cause of the informa-
tion, fault or alarm message. In these cases, „Reset“ is displayed in the menu line – Fig. 154. If „Reset“ is not displayed in the menu line, the boiler starts operating again automatically after the cause of
the information, fault or alarm message has been rectified. Pressing the
Te st
button changes to the actuator test immediately – Fig. 156. This function is only intended for
trained service personnel (for setting instructions, see the VarioWIN „Assembly instructions“). Pressing the
Back
button (Fig. 157) exits the actuator test.
Fig. 154
LED „red“
Brief description
Flashing symbol
Information code
Information
text
Fig. 155
If you wish to call WINDHAGER Customer Service or your customer service PARTNER due to a malfunction, please first make a note of the following data from the rating plate:
- Model
- Factory number
- Year of manufacture The rating plate is located behind the cladding door between the com-
bustion chamber door and the ash door – Fig. 158.
Rating plate
Fig. 158 Rating plate
Fig. 157
Induced draught fan defective
AL 016
Info Reset Test
42
°C
!
Clean blower wheel and blower box. Press Reset.
Note operating manual.
Back
Induced draught fan
Auger conveyor Ash removal Ignition element Ash compression Suction turbine
Choose Back
All safety functions are deactivated during the actuator test!
5s
RESET
Induced draught fan defective
AL 016
Info Reset Test
42
°C
!
Fig. 156
Page 53
53
Troubleshooting
4.2 Information messages
Code Meaning/effect Cause/remedy
IN 581
Replenish fuel
The reserve supply container is almost empty. Top up pellets.
Boiler continues to heat until the remaining fuel quantity has been consumed. a) VarioWIN without feed or with direct pellet feed:
Fill fuel into the reserve supply or year-round container (see section 2.5).
b) VarioWIN with pneumatic feed (suction system):
Feed is switched off in „feed operating mode“ (see section 2.10.1.3). In „Feed operating mode“ menu item, set to „with enable time“, „with start time“ or „without time control“.
IN 582
Reserve supply container empty
The reserve supply container is empty. Top up pellets. Burner is locked.
The reserve supply container is empty. a) VarioWIN without feed or with direct pellet feed:
Fill fuel into the reserve supply or year-round container (see section 2.5).
b) VarioWIN with pneumatic feed (suction system):
Feed is switched off in „feed operating mode“ (see section 2.10.1.3). In „Feed operating mode“ menu item, set to „with enable time“, „with start time“ or „without time control“.
IN 590
Clean boiler and burner
Perform cleaning and confirm in opera­tor level.
Boiler and burner are still operating. Boiler and burner must be cleaned or the both ash pans (see Fig. 159) emp-
tied (see sections 3.4, 3.5 and 3.6). Following cleaning, confirm cleaning on the InfoWIN in operator level (see section 2.10.1.1).
IN 595
Door open
Burner locked. Only open the door when the burner is switched off.
Cladding door is open, burner locked.
a) Close the cladding door.
b) Door switch on cladding door does not switch correctly, adjust – see assem-
bly instructions.
Code Meaning/effect Cause/remedy
–
No display
Boiler is off, cannot be switched on with the ON/OFF button.
a) No electricity, check the cable to the device and the building fuse.
b) No electricity, device fuse defective – check and replace if necessary – see
page 56, Fig. 160.
c) InfoWIN plug loose or poorly connected or not connected together during
installation – check and connect together firmly if necessary, plug is loca­ted at top behind cover – see assembly instructions; Installing the cladding.
4.1 No display on InfoWIN
Page 54
54
Troubleshooting
Code Meaning/effect Cause/remedy
FE 238
Feed is not sucking any pellets in
Check pellet supply in storage room and feed hose. Press Reset.
No pellet feed is possible. The boiler does not operate. a) No pellets at the suction probe – Set „probe switching“ to „automatic“ or
select another probe (see section 2.10.1.5). Press the Reset button
b) Feed hose blocked at the cyclone intake or entry to the changeover unit –
clear it. Press the Reset button.
c) Inform Windhager Customer Service or a heating technician.
Emergency operation: Switch off the feed unit (see section 2.10.1.3). Fill the reser­ve supply container with pellets by hand, boiler is allowed to continue operating without feed.
FE 239
Probe switching defective
Check the changeover unit. Press Reset.
No pellet feed is possible. The boiler does not operate. Press the Reset button. If the fault reoccurs after a reset, inform Windhager
Customer Service or a heating technician.
Emergency operation: Switch off the feed unit (see section 2.10.1.3). Fill the reser­ve supply container with pellets by hand, boiler is allowed to continue operating without feed.
FE 381
Reserve supply container empty
Time programme blocking feed. Change enable time in menu/operator level.
Feed is outside the enable time. Enable time for the feed has been set too short, which means the pellets in the reserve supply container are used up and the feed is blocked.
Extend the enable time for the feed in the „Feed operating mode“ menu item (see section 2.10.1.3) or operate „with start time“ or „without time control“.
FE 382
Fill level switch in reserve supply container defective
Check the switch in the reserve supply container. Press Reset.
The boiler does not operate.
a) Fill level switch (proximity switch) dirty, remove the dust (see section 3.7),
press the Reset button.
b) Fill level switch (proximity switch) in the reserve supply container defecti-
ve – inform Windhager Customer Service or a heating technician.
Emergency operation: Switch off the feed unit (see section 2.10.1.3). Fill the reser­ve supply container with pellets by hand, boiler is allowed to continue operating without feed.
FE 390
Emergency operation! Clean boiler and burner
Perform cleaning and confirm in operator level.
The boiler is in cyclic operation, i.e. has idle times. a) Boiler and burner must be cleaned or the both
ash pans (see Fig. 159) emp­tied (see sections 3.4, 3.5 and 3.6). Following cleaning, confirm cleaning on the InfoWIN in operator level (see section 2.10.1.1).
b) Motor or limit switch of ash compactor defective, inform Windhager Custo-
mer Service or a heating technician.
4.3 Fault messages
Fig. 159 Emptying the ash pan
Ash pan for heating surfaces
Ash pan for combustion chamber
Page 55
55
Troubleshooting
Code Meaning/effect Cause/remedy
AL 005
Shake-out defective
Shake-out defective or sticking. Clean the burner pot. Press Reset.
Shake-out motor no longer moves or no longer reaches the end position, boi­ler switches to burnout mode.
a) Burner contamination; close combustion chamber doors, press reset but-
ton; once the alarm message is rectified, clean the burner pot as descri­bed in section 3.6.
If the alarm message remains active, clean the burner pot as described in section 3.6. Note: Grate plate at top can only be raised and removed when closed. If the grate plate is not fully closed, vacuum it out. Close combus­tion chamber door, press reset button, if the alarm message remains in place, repeat the process or inform Windhager Customer Service or a hea­ting technician.
b) Grate plate not inserted correctly or check correct installation position (see
section 3.6).
c) Motor for shake-out defective, inform Windhager Customer Service or a
heating technician.
d) Limit switch defective, inform Windhager Customer Service or a heating
technician.
AL 006
Auger conveyor motor defective
Auger conveyor motor defective. Press Reset.
Boiler enters burnout mode, vacuum fan is stopped immediately. a) Auger conveyor or rotary feeder jammed due to a foreign body, clean the
reserve supply container, opening above auger conveyor or rotary feeder (see section 3.9) and remove the foreign body. Press the Reset button. The alarm message AL 171 may light on up to 2 occasions until the boiler starts operating again, press the Reset button.
b) Control thermostat defective, inform Windhager Customer Service or a
heating technician.
c) Press the Reset button. If the malfunction recurs immediately after a short
period, or recurs at regular intervals, contact Windhager Customer Servi­ce or your heating technician.
d) Renew the auger conveyor motor, inform Windhager Customer Service or
a heating technician.
AL 016
Vacuum fan defective
Clean blower wheel and blower box. Press Reset.
The actual speed is different from the nominal speed. The boiler switches to burnout mode.
a) The blower wheel and blower box are dirty; clean them (see section 3.9).
Press the Reset button. If the malfunction recurs immediately after a short period, or recurs at regular intervals, contact Windhager Customer Servi­ce or your heating technician.
b) Renew the vacuum fan motor, inform Windhager Customer Service or a
heating technician.
AL 062
Air intake/exhaust flap defective
Air intake/exhaust flap defective or not opening. Check flap. Press Reset.
External air choke (optional) does not open. a) Check the air choke, press the Reset button.
b) Inform Windhager Customer Service or a heating technician.
AL 071
Safety / emergency switch open
Check switch position of safety / emer­gency switches.
Boiler enters burnout mode but the blower does not run. Switch on emergency heating/OFF switch.
4.4 Alarm messages
The glow ignition is located in the primary air tube so avoid sha­king the burner pot violently – risk of breakage!
Page 56
56
Troubleshooting
Fig. 160 VarioWIN control panel, rear right side panel removed
Cover of safety thermostat B7
Cover of safety thermostat auger tube B7a
Device fuse T 6.3 A
Code Meaning/effect Cause/remedy
AL 076
Boiler sensor defective
Check the boiler sensor and connec­tions. Press Reset.
The boiler switches to burnout mode.
a) Press the Reset button. If the malfunction recurs immediately after a short
period, or recurs at regular intervals, contact Windhager Customer Servi­ce or your heating technician.
b) Renew the boiler sensor, inform Windhager Customer Service or a heating
technician.
AL 078
Thermocontrol sensor defective
Check the thermocontrol sensor and connections. Press Reset.
The boiler switches to burnout mode. a) Thermocontrol sensor is too cold < 0 °C. Sensor warm up. b) Press the Reset button. If the malfunction recurs immediately after a short
period, or recurs at regular intervals, contact Windhager Customer Servi­ce or your heating technician.
c) Renew the thermocontrol sensor, inform Windhager Customer Service or
a heating technician.
AL128
No flame formation in control mode
Clean boiler and burner. Press Reset.
The flame goes out in modulation mode. The boiler switches to burnout mode.
a) Clean the burner and the boiler. Check the exhaust pipe to the flue and
clean it if necessary, press the Reset button.
b) Auger conveyor or rotary feeder jammed due to a foreign body. Clean the
reserve supply container, opening above auger conveyor or rotary feeder (see section 3.9) and remove the foreign body. Press the Reset button. The alarm message AL 171 may light on up to 2 occasions until the boiler starts operating again, press the Reset button.
c) Inform Windhager Customer Service or a heating technician.
AL 133
Safety temperature shut­down
Check the system and filling pressure. Press Release button on boiler.
Boiler temperature is above 100 °C, boiler enters burnout mode, vacuum fan is switched off immediately.
a) Check the water level or pressure in the heating system – refill, bleed the
air.
b) Air in the heating system – bleed air.
c) The heat pump or boiler feed pump is sticking or is defective – start pump
manually or have it repaired.
Once the boiler water temperature falls below 90 °C, remove the cover, press the Release button of the safety thermostat B7 firmly – Fig. 160.
If the malfunction occurs after a short period, or recurs at regular intervals, contact Windhager Customer Service or your heating technician.
AL 135
Excess temperature in the auger tube
Check the burner. Press Release button B7a on control panel.
The boiler switches to burnout mode.
a) Check the burner, remove all pellets from the burner pot. b) Remove the cover from the safety thermostat auger tube B7a, press the
Release button firmly (see Fig. 160). If the ignition does not function first time (AL 171), press the Reset button (pellets in the auger conveyor will have been damaged due to the higher temperature).
Page 57
57
Troubleshooting
Code Meaning/effect Cause/remedy
AL 171
Maximum heating up time excee­ded
Clean the burner pot. Press Reset.
a) VarioWIN D without feed or with direct pellet feed:
The reserve supply container is empty. Fill fuel into the reserve supply or year-round pellet container (see section 2.5). Press the Reset button until the boiler starts operating again. The alarm message AL 171 may light up again on up to 2 occasions, press the Reset button.
b) Clean the burner pot (see section 3.6), empty the ash pan, press the Reset
button.
c) Too much dust in the reserve supply container – bridge formation, remo-
ve the dust (see section 3.6), press the Reset button.
d) Auger conveyor or rotary feeder jammed due to a foreign body. Clean the
reserve supply container, opening above auger conveyor or rotary feeder (see section 3.9) and remove the foreign body. Press the Reset button. The alarm message AL 171 may light on up to 2 occasions until the boiler starts operating again, press the Reset button.
e) VarioWIN with pneumatic feed (suction system):
Pellets stuck in the hose before the entry to the reserve supply container – move the hoses at the connection pieces, press the Reset button.
f) Ignition defective, inform Windhager Customer Service or a heating tech-
nician.
AL 187
No communication with main PCB
Check connection for main PCB and connections. Press Reset.
The boiler switches to burnout mode.
a) Check the connection cable or InfoWIN plug connection to the main PCB,
inform Windhager Customer Service or a heating technician.
b) Connect the main PCB, inform Windhager Customer Service or a heating
technician.
AL 188
Internal error occurred ErrorCode 188 Current TablelD 4
Internal communication error. The boiler switches to burnout mode. A reset is performed automatically after 1 minute if this error occurs.
If the malfunction occurs after a short period, or recurs at regular intervals, contact Windhager Customer Service or your heating technician.
Page 58
58
Declaration of conformity
for the VarioWIN pellet boiler series Issued by: WINDHAGER ZENTRALHEIZUNG Technik GmbH
Anton-Windhager-Strasse 20 A-5201 Seekirchen
Subject of the declaration: VarioWIN pellet boiler series The appliances comply with the requirements in the following documents:
Seekirchen, 16. 2. 2010 WINDHAGER ZENTRALHEIZUNG
Technik GmbH
Johann Thalmaier, Board of Directors
Document no. Title
2006/42 EC 2004/108 EC 89/106 EEC
Machinery Directive EMC Directive Construction Products Directive
Standard Edition EN 14785 2006
EN 60335-1 2001 EN 61000-6-1 2001 EN 61000-6-3 2001
Page 59
59
Page 60
60
The guarantee and warranty limitations require that the boiler and related accessories be properly installed and started up by WINDHAGER Customer Service or Customer Service PARTNER; otherwise the manufacturer’s gua­rantee will not be honoured.
Malfunctions resulting from improper operation or adjustment as well as use of poor or not recommended fuel types are not covered by the guarantee and warranty. Further, the warranty shall be void if equipment other than that provided by WINDHAGER is installed. The special warranty restrictions for your system are available in the „Warranty Conditions“ folder supplied with your boiler.
Guarantee and warranty limitations
Start-up and regular maintenance following the terms of the „Warranty Conditions“ will assure safe, environmentally friendly and economical operation of your system. We recommend that you obtain a maintenance service contract.
Subject to technical modifications. AWP-vor-übersetzt von 023821/01
Windhager Zentralheizung GmbH A-5201 Seekirchen bei Salzburg Anton-Windhager-Str. 20 Tel. +43 (0) 62 12/2341-0 Fax +43 (0) 62 12/42 28 E-mail: [email protected]
www.windhager.com
Windhager Zentralheizung GmbH D-86405 Meitingen bei Augsburg Deutzring 2 Tel. +49 (0) 82 71/80 56-0 Fax +49 (0) 82 71/80 56-30 E-mail: [email protected]
Windhager Zentralheizung Schweiz AG CH-6203 Sempach-Station bei Luzern Industriestrasse 13 Tel. +41 (0) 41/46 94 69-0 Fax +41 (0) 41/46 94 69-9 E-mail: [email protected]
Austria: Germany: Switzerland:
Loading...