This manual contains important instructions that
should be followed during installation and maintenance
of the generator and batteries.
Read and understand all instructions in the manual
before starting and operating the generator set.
USING THIS MANUAL
Congratulations on your choice of a Winco generator set.
You have selected a high-quality, precision-engineered
generator set designed and tested to give you years of
satisfactory standby service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the
operating instructions in this manual.
Should you experience a problem please follow the “Things
To Check” near the end of this manual. The warranty listed
in this manual describes what you can expect from WINCO
should you need service assistance in the future.
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as
yours. It is important that you record the number and other
vital information here. If you should ever need to contact us
on this unit it will help us to respond to your needs faster.
MODEL_____________________________________
SERIAL NUMBER____________________________
PURCHASE DATE____________________________
DEALER____________________________________
TABLE OF CONTENTS
INTRODUCTION i
GUIDE TO PRODUCT SAFETY1
BASIC INFORMATION2
Description 2
DSE 7110 Engine Control2
Specification Table 3
PREPARING THE UNIT
Unpacking the unit 3
ENGINE GENERATOR INSTALLATION
Installation4
Fuel Line Installation 4
Fuel Pressure Tables5
LP Liquid Withdrawal5
Lubrication5
Coolant5
Battery Installation6
Battery Charger/Block Heater Wiring6
AC Electrical Connections7
DC Electrical Connections8
ENGINE CONTROL PANEL LAYOUT9
DSE 7110 CONTROLLER10
INITIAL START-UP11
START-UP PROCEDURE11
EXERCISER CLOCK12
TROUBLESHOOTING INFORMATION12
CHANGING THE FUEL TYPE13
VOLTAGE REGULATOR WIRING13
AC WIRING - THREE PHASE
277/480 Volt14
120/208 Volt14
120/240 Volt15
AC WIRING - SINGLE PHASE
120/240 Volt15
DC SCHEMATIC - WIRING DIAGRAM16
OUTLINE DRAWING17
DSE7110 CONTROL ICONS18
WARNING ALARM ICONS19
SHUTDOWN ALARM ICONS20
ACCESING FRONT PANEL CONFIGURATION21
12 MONTH WARRANTY22
PROPER USE AND INSTALLATION
You must be sure your new engine generator set is:
*Properly serviced before starting
*Operated in a well ventilated area
*Properly exhausted and gases safely dispersed
*Wired by a qualified electrician
*Operated only for its designed purposes
*Used only by operators who understand its operation
*Properly maintained
Page i
IMPORTANT SAFETY
2.FIRE HAZARD - NG and LP present a hazard of possible
explosion and/or fire.
INSTRUCTIONS
SAVE THESE INSTRUCTION
This manual contains important instructions that
should be followed during installation and maintenance
of the generator and batteries.
Read and understand all instructions in the manual
before starting and operating the generator set.
This engine generator set has been designed and manufactured
to allow safe, reliable performance. Poor maintenance, improper
or careless use can result in potential deadly hazards; from
electrical shock, exhaust gas asphyxiation, or fire. Please read
all safety instructions carefully before installation or use. Keep
these instructions handy for future reference. Take special note
and follow all warnings on the unit labels and in the manuals.
DANGER indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury. This signal word
is to be limited to the most extreme situations.
a.Do not smoke or use open flame near the generator
set.
b.Keep a fire extinguisher nearby and know its proper use.
Fire extinguishers rated ABC by NFPA are appropriate.
3.DEADLY EXHAUST GAS - Exhaust fumes from any gasoline engine contain carbon monoxide, an invisible, odorless
and deadly gas that must be mixed with fresh air.
a.Operate only in well ventilated areas.
b.Never operate indoors.
c.Never operate the unit in such a way as to allow exhaust
gases to seep back into closed rooms (i.e. through
windows, walls or floors).
4.NOISE HAZARD - Excessive noise is not only tiring, but
continual exposure can lead to loss of hearing.
a.Use hearing protection equipment when working
around this equipment for long periods of time.
b.Keep your neighbors in mind when permanently install-
ing this equipment.
5.CLEANLINESS - Keep the generator and surrounding area
clean.
a.Remove all grease, ice, snow or materials that create
slippery conditions around the unit.
b.Remove any rags or other material that could create
potential fire hazards.
c.Carefully wipe up any gas or oil spills before starting the
unit.
d.Never allow leaves or other flammable material to build
CAUTION indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be
used to alert against unsafe practices.
CAUTION is also used on the unit labels and in this manual to
indicate a situation that could result in serious damage or
destruction of the equipment and possible personal injury.
1.ELECTRIC SHOCK - The output voltage present in this
equipment can cause a fatal electric shock. This equipment
must be operated by a responsible person.
a.Do not allow anyone to operate the generator without
proper instruction.
b.Guard against electric shock.
c.Avoid contact with live terminals or receptacles.
d.Use extreme care if operating this unit in rain or snow.
e.Use only three-prong grounded receptacles and
extension cords.
f.Be sure the unit is properly grounded to an external
ground rod driven into the earth.
6.SERVICING EQUIPMENT - All service, including the
installation or replacement of service parts, should be
performed only by a qualified technician.
a.Use only factory approved repair parts.
b.Do not work on this equipment when fatigued.
c.Never remove the protective guards, cover, or recep-
tacle panels while the engine is running.
d.Use extreme caution when working on electrical compo-
nents. High output voltages from this equipment can
cause serious injury or death.
e.Always avoid hot mufflers, exhaust manifolds, and
engine parts. They all can cause severe burns instantly.
f.Installing a generator set is not a “do-it-yourself” project.
Consult a qualified, licensed electrician or contractor.
The installation must comply with all national, state, and
local codes.
g.Always make sure unit is disabled before placing your
hands anywhere near the fan, belts, alternator or water
hoses.
60706-213
Page 1
1270-10 REV B
TESTING POLICY:
Before any generator is shipped from the factory, it is fully
checked for performance. The generator is loaded to its full
capacity, and the voltage, current, and frequency are carefully
checked.
Rated output of generators is based on engineering tests of
typical units, and is subject to, and limited by, the temperature,
altitude, fuel, and other conditions specified by the manufacturer
of the applicable engines.
INTRODUCTION AND
DESCRIPTION
With the addition of an Automatic Transfer Switch this packaged
standby system includes all items necessary for a completely
automatic standby power system..
DESCRIPTION
This package power system is designed to automatically provide
standby power to unattended loads during electrical outages.
Upon an interruption of normal electrical service this package
power system's electrical control circuits will automatically start
the engine. The generator will produce electrical power and the
Automatic Transfer Switch (A.T.S.) will automatically transfer the
electrical loads to the engine-generator set. Upon restoration of
normal electrical service the A.T.S. will sense return of the normal
commercial power and retransfer the load back to normal
commercial power source. The engine control circuits shut off the
run signal to the engine generator set.
2) ENGINE/GENERATOR
PSS60LS- The engine generator set consists of a GM 5.7L, V-8
industrial, liquid cooled engine equipped to run on L.P./N.G. fuel.
The engine operates at 1800 rpm and frequency regulation is
maintained by the electronic governor within .5 cycles variation,
from no load to rated load. The 60,000 watt (60kW) generator is
a single bearing, direct drive, rotating field design. The generator
is connected to the engine flywheel via flexible drive disks. The
engine generator is mounted in a weather proof enclosure for
outside installation. Connection boxes are provided to all
customer connections (both AC output and DC control). A
customer supplied 12 Volt, 650 CCA (BCI group 24) battery is
required to complete the installation. Engine operation is controlled by a Digital Genset Controller (DGC) mounted in the
engine generator enclosure.
PSS90LS - The engine generator set consists of a GM 5.7L,
Turbocharged/Aftercooled V-8 industrial, liquid cooled engine
equipped to run on L.P./N.G. fuel. The engine operates at 1800
rpm and frequency regulation is maintained by the engine
governor within .5 cycles variation, no load to rated load. The
90,000 watt (90kW) generator is a single bearing, direct drive,
rotating field design. The generator is connected to the engine
flywheel via flexible drive disks. The engine generator is mounted
in a weather proof enclosure for outside installation. Connection
boxes are provided to all customer connections (both AC output
and DC control). A customer supplied 12 Volt, 650 CCA (BCI
group 24) battery is required to complete the installation. Engine
operation is controlled by a Digital Genset Controller (DGC)
mounted in the engine generator enclosure.
** NOTICE **
These units will automatically transfer if a power outage occurs
while running in an exercise mode.
These package power systems consist of two major components:
1) AUTOMATIC TRANSFER SWITCH (UL LISTED)
The Automatic Transfer Switches (A.T.S.) is a wall mount switch
designed for inside installation. A electronic exerciser circuit is
installed in the A.T.S. as standard equipment. The A.T.S. also
contains the power failure sensing circuitry necessary to send a
start/stop signal to the engine generator set. The following is a list
of recommended A.T.S. sizes for each model. Outside switches
as well as additional sizes are available, consult your sales rep
for additional information.
Additional optional A.T.S. sizes are available to meet specific
needs. Contact your local WINCO dealer or the WINCO Sales
Department for a quote.
ENGINE CONTROL MODULE (DSE 7110 Series)
The DSE 7110 Series control modules provide integrated engine
and generator set control, protection and metering in a single
package. Microprocessor based technology allows for exact
measurement, set point adjustment, and timing functions. Front
panel controls and indicators enable quick and simple operation.
Fully configurable via PC software, allows units to be easily
customized for each application. Includes selected front panel
programming for on site changes. A wide temperature-range
liquid crystal display (132 x 64) with backlighting can be viewed
under a wide range of ambient light and temperature conditions.
FEATURES
DSE 7110 Control Modules have the following features:
¨ Local and Remote Generator Control
¨ Engine and Generator Protection
¨ CAN Bus compatible
¨ Programmable Logic
¨ Five-key Menu Navigation
¨ Engine Exercise Mode
1270-10 REV B
Page 2
60706-213
FUNCTIONS
DSE 7110 Series Control Modules perform the following protection and metering functions:
ENGINE SPECIFICATIONS:
Refer to engine operating and maintenance instructions
Generator Protection and Metering
Generator protection includes over voltage, under voltage, under
frequency, over frequency and overload protection. Each generator protection function has an adjustable pickup and time delay
setting. Metered generator parameters include voltage, current,
real power (watts), power factor (PF)
Engine Protection and Metering
Engine protection features include oil pressure and coolant
temperature monitoring, over crank protection, ECU specific
protection elements, and diagnostic reporting.
These units will automatically transfer if a power outage occurs
while running in an exercise mode
SPECIFICATIONS
GENERATOR
MODEL WATTSVOLTSAMPHZPHRPM
** NOTICE **
Regarding Engines - This manual covers the generator portion of
these units. See the separate engine instruction manual for
engine-related problems, detailed engine information and engine
warranty.
** CAUTION **
EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specified in the engine manual.
The engine manufacturer has established an excellent worldwide
engine service organization; engine service is available from a
nearby authorized dealer or distributor; check the Yellow Pages
of the telephone directory under “engines,” or ask the dealer from
whom you purchased the power plant.
The rated power of each engine-generator is limited by the
temperature, altitude and all other ambient conditions specified
by the engine manufacturer. Engine power will decrease 3-1/2%
for each 1000 ft. above sea level, and will decrease an additional
1% for each 100 Fahrenheit above 600 Fahrenheit. Units should
not be operated in ambient temperature greater than 40
Minimum required L.P. Tank size for L.P. Vapor withdrawal
operating at various outside temperatures given in degrees
Fahrenheit (Celsius)
TANK TEMPERATUREMODEL60 F(16 C)30 F(0 C) 0 F(-18 C) -20 F(-29 C)
PSS60500 Gal1000 Gal2000 Gal*5000 Gal*
PSS901000 Gal.1000 Gal. 2000 Gal.* 5000 Gal.*
*Recommend liquid withdrawal at these temperatures.
** NOTICE **
When unpacking the generator set, be sure to inspect it carefully
for freight loss or damage. If loss or damage is noted at the time
of delivery, require that the person making the delivery make note
of the loss or damage on the freight bill, or affix his signature
under the consignees’s memo of the loss or damage. Contact
the carrier for claim procedures.
When loss or damage is noted after delivery, segregate the
damaged material, and contact the carrier for claim procedures.
“Concealed Damage” is understood to mean damage to the
contents of a package which is not in evidence at the time of
delivery by the carrier, but which is discovered later. The carrier
or carriers are responsible for merchandise lost or damaged in
transit. The title to goods rests with the consignee when generators are shipped FOB factory, and only the consignee can legally
file a claim.
**** CAUTION ****
EQUIPMENT DAMAGE - These units are shipped with oil, and a
50/50 mix of coolant. Be sure to check all fluid levels before
operating. See engine manufacturer’s instruction manual for
recommended oil requirements before initial starting.
60706-213
Page 3
1270-10 REV B
UNPACKING:
1.Carefully remove the carton.
2.After inspecting the engine-generator for external physical
damage, check for the following items packed inside the
carton:
a.Owner’s manual and wiring diagram.
b.Engine manufacturer’s instruction manual.
3.Remove main frame hold down bolts, (6).
4.Unit can now be lifted from shipping rails.
INSTALLATION
***************
**** WARNING ****
***************
PERSONAL INJURY - Before proceeding with the installation, be
sure the operation selector switch is in the "stop" position.
General Information
Note: Roof access panels have been provide to check/fill the
engine oil and the coolant. Side panels may be removed by
removing the thumb screws on the bottom under side of
each panel
These engine generator sets are for outdoor installation. These
units must be bolted solidly to a concrete pad. The transfer
switch is mounted next to your distribution panel inside the
building. Consult a qualified, licensed electrician or contractor to
install and wire the transfer switch. The installation must always
comply with all national, state, and local codes.
These units should be mounted to allow for ample working room
around it. Units must be installed in accordance with all local,
state and national codes. Consult your local agency having
jurisdiction for specific requirements.
FUEL INSTALLATION
The fuel supply should be as close as possible to the engine.
This will reduce the installation cost of fuel runs. The information
in this manual is offered to assist you in providing the proper fuel
for your engine. However, this information is only provided to
inform you of the engine’s requirements and assist in making you
aware of the decisions you must make. In no case should the
instructions or information provided be interpreted to conflict with
any local, state or national codes. If in doubt, always consult your
local fire marshal or gas supplier.
**************
**** WARNING ****
****************
FIRE HAZARD - All fuel runs should be installed by a licensed
fuel supplier.
Connect the fuel supply to the inlet of the fuel solenoid (see table
for recommended line size). The pressure at the secondary
demand regulator must be four to six ounces psi (per square
inch) or 7 to 11 inches W.C. (Water column) for vapor withdrawal
units. On units equipped with liquid withdrawal fuel systems full
tank pressure is plumbed to the fuellock strainer mounted on the
generator rails. The fuel converter mounted on the unit will
handle both vaporization of the fuel and pressure reduction.
INSTALLING THE FUEL LINE
***** CAUTION *****
EQUIPMENT DAMAGE - These units must be mounted on a
solid concrete pad to prevent air from exiting under the unit.
Allowing air to exit under the unit may cause the unit to overheat
from lack of proper air flow.
Before beginning the installation process recheck the rating of the
generator set and its transfer switch rating. Be certain they can
handle the intended load and are compatible with the entrance
voltage, phase and current ratings. Plans for installation should
be prepared with proper attention to mechanical and electrical
engineering detail to assure a satisfactory system installation.
The information in this manual is offered only as a guide to
finalizing your installation plans. For full service switching the
A.T.S. must have a fusible disconnect (circuit breaker) installed
before the switch to protect the contacts.
ENGINE GENERATOR SET MOUNTING
The unit’s main frame should be bolted solidly to a 4 to 6 inch
thick cement pad. The engine-generator is mounted on a subframe which is attached with special shock mounts to the main
frame. This allows the engine-generator free movement without
affecting the control panel which is mounted on the main frame.
Do not shock mount the main frame. Engine vibration will be
transmitted to the control panel causing erroneous start/stop
cycles and premature control failure.
** NOTICE **
The engine generator sets are properly adjusted before they
leave the factory for a specific fuel, either NG (natural gas), LP
(liquid propane vapor) or LPG (liquid withdrawal propane). This
fuel type is noted in your model number. If it becomes necessary
to change the fuel type in the field see information on page 12.
Line Size (vapor system)
Unit location will determine the size of fuel line that is required to
supply the engine with a constant fuel pressure. Refer to the
tables below for fuel line size, fuel consumption and recommended tank size. For distances of 25 feet and over, a two
regulator fuel system is recommended. This is accomplished by
installing a primary regulator at the tank which will reduce the
tank pressure down to 10 to 15 lbs. A secondary regulator is
installed to further reduce the fuel pressure to the required six (6)
oz operating pressure. This secondary regulator must be at least
10 feet from the engine generator set. Any closer installation will
require a larger line be installed to provide a fuel reservoir. If this
is not done, the demand regulator on the unit and the pressure
regulator in the fuel line will interfere with each other. When this
two (2) stage regulator system is used, a fuel line size of 3/4 to 1
inch is generally adequate for distances up to 200 feet from the
primary to the secondary regulator. (Consult your local fuel
supplier for your exact requirements). The appropriate line size
from the table below is then installed from the secondary regulator to the generator set.
1270-10 REV B
Page 4
60706-213
***************
**** WARNING ****
***************
PERSONAL DANGER - Do not use galvanized pipe in fuel line
runs. The galvanized coating can become eroded and flake off,
causing possible obstructions in the regulator or fuel valve. The
results could range from inoperative engine start to hazardous
fuel leaks.
Size of pipe normally required for generators operating on NG/LP:
up to 25 feet* over 25 feet*
PSS60 1.25" pipe not recommended
PSS90 1.25" pipe use a two regulator system
* Allow an additional 3 feet for each standard elbow.
Do not use ‘street ells’ (restrictive).
**** CAUTION ****
EQUIPMENT DAMAGE - Be careful when sealing gas line joints.
Excessive sealing compound can be drawn into the solenoid,
regulator or carburetor causing an engine malfunction.
FUEL PRESSURE (vapor system)
Correct fuel pressure cannot be stressed enough. The most
common cause for inoperative systems is an inadequate or
incorrect fuel pressure. Performance of the engine is in direct
relation to the correctness of the fuel system. Shown below is a
block diagram of a typical L.P. or N.G. Installation.
Supply Primary SecondaryGenerator
Tank Regulator Regulator Set
1 23 4
TWO (2) REGULATOR FUEL SYSTEM
Supply PrimaryGenerator
TankRegulator Set
124
SINGLE REGULATOR FUEL SYSTEM
Reference numbers 1 through 3 in the block diagrams above are
fuel lines supplied by customer.
Reference number 4 is the engine generator set.
Below is a table of the fuel pressure readings at each reference in
the system.
Fuel Pressure Table
Single Regulator (L.P. Vapor only)
123
UNIT OFFTANK PSI7-11 in7-11 in
4-6 oz4-6 oz
STARTINGTANK PSI7-11 in7-11 in
4-6 oz4-6 oz
NO LOADTANK PSI7-11 in7-11 in
4-6 oz 4-6 oz
FULL LOADTANK PSI7-11 in7-11 in
4-6 oz4-6 oz
Two (2) Regulator System (L.P. Vapor only)
1234
UNIT OFFTANK PSI 10-15 lbs7-11 in7-11 in
4-6 oz4-6oz
STARTINGTANK PSI 10-15 lbs7-11 in7-11 in
4-6 oz4-6 oz
NO LOADTANK PSI 10-15 lbs7-11 in7-11 in
4-6 oz4-6 oz
FULL LOAD TANK PSI 10-15 lbs7-11 in7-11 in
4-6 oz4-6 oz
Natural Gas
124
UNIT OFFLINE PSI7-11 in7-11 in
4-6 oz4-6 oz
STARTINGLINE PSI7-11 in7-11 in
4-6 oz4-6 oz
NO LOADLINE PSI7-11 in 7-11 in
4-6 oz4-6 oz
FULL LOADLINE PSI7-11 in.7-11 in
4-6 oz4-6 oz
Notice the preceding tables give two (2) different units of measuring fuel pressure. The first is with a pressure gauge calibrated in
ounces per square inch. The second and most accurate is the
use of a simple water manometer. A manometer is calibrated in
inches of water column.
LP LIQUID WITHDRAWAL SYSTEMS
When installing a unit equipped the LP liquid withdrawal a
primary regulator is not required on the supply tank. The supply
line is connected to a liquid withdrawal valve on the supply tank
and runs directly to the fuellock strainer mounted on the engine
generator set. Normally a 3/8 inch copper line is acceptable for
this type of fuel installation. You must be sure that the valve you
have connected to on the supply tank is in fact a liquid supply
valve and has a drop tube inside the tank that is pulling fuel from
the bottom of the supply tank. Before starting the unit you must
confirm that you have a good liquid supply at the unit. Engine
generator sets equipped for liquid withdrawal will not run
properly when supplied with high pressure vapor fuel.
LUBRICATION
Before starting the engine, check the oil level in the crankcase. If
it is low, refill to the full mark with the proper weight/grade of oil as
recommended by the engine manufacturer’s maintenance
instructions. The necessity of using the correct oil, and keeping
the crankcase full cannot be over emphasized. Failure to use the
proper oil and keep the crankcase properly filled will cause
excessive engine wear and shorten its useful life.
COOLANT
Before starting the engine, check the coolant level in radiator. If it
is low, refill as specified in the engine manufacturer’s maintenance instructions. The radiator should be filled to about 1 inch
below the filler neck. For additional information on engine coolant
requirements see engine manufacturer’s maintenance instructions.
60706-213
Page 5
1270-10 REV B
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check to be sure
the selector switch remains in the “stop” position. This should be
your last step before initial start-up.
A customer supplied twelve-volt battery is required to complete
the installation. Installation of the highest CCA rated battery,
within the correct BCI group, will increase cold weather starting
performance. Gel batteries should not be used with the battery
tender installed in the generator enclosure.
MINIMUM
ModelVoltageBCI Group CCA Rating
PSS60 1224650
PSS90 1224650
Installation and servicing of batteries must be performed or
supervised only by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away from
batteries.
When installing or replacing batteries, use the proper group/size
starting battery. The battery should be a Maintenance Free lead
acid design. Deep cycle batteries will
tion.
not work for this applica-
ately with water and seek immediate medical attention.
*Spilled electrolyte is to be washed down with an acid neutral
izing agent. A common practice is to use a solution of one
pound of bicarbonate of soda (baking soda) to one gallon of
water. The bicarbonate of soda solution is to be added until
the evidence of reaction, foaming, has ceased. The resulting
liquid is to be flushed with water and the area dried.
DANGER – Explosive Fire Risk
*Never smoke when near batteries.
*Do not cause a flame or spark in the battery area.
*Always discharge static electricity from your body before
touching batteries by first touching a grounded metal surface.
SERVICING BATTERIES
Batteries used on these units may over time lose water. This is
especially true if you are using a trickle charger to maintain your
battery. When refilling the battery with water use only distilled
water. Tap water will shorten the service life of the battery.
Never fill the battery above the fill line. Over filling above the
upper level line may cause the electrolyte to overflow, resulting in
corrosion to the engine or nearby parts. Immediately wash off
any spilled electrolyte following the procedure above.
CAUTION – PERSONAL DANGER
CAUTION - NEVER dispose of a battery in a fire. The battery is
capable of exploding.
CAUTION - DO NOT open or mutilate the battery. Released
electrolyte is known to be harmful to the skin and eyes and to be
very toxic.
These engine generator sets are all NEGATIVE ground. Be very
careful not to connect the battery in reverse polarity, as this may
short circuit the battery charging system on the engine.
CAUTION – A battery presents a risk of electrical shock and high
short circuit current. The following precautions must be observed
when working with batteries.
1. Remove watches, rings and other metal objects.
2. Use tools with insulated handles.
3. Check both the battery cable ends and the battery posts to be
sure they are free of corrosion.
4. Always connect the battery positive cable first and then
connect the battery negative cable. When removing the
battery cables from the battery reverse the procedure,
disconnect the negative cable first and then the positive
cable.
5. Be sure all connections are tight and coat the terminals and
cable end with dialectic grease.
WARNING – The electrolyte is a diluted sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and
corrosive. The following precautions must always be taken.
*Always wear full eye protection and protective clothing.
*Where electrolyte contacts the skin, wash off immediately
with water.
*If electrolyte contacts the eyes, flush thoroughly and immedi
NOTE: Always make sure that a new battery is fully charged
before installing it on a generator set. Failure to do so can cause
damage to the engine control module in the generator set.
All connections must be clean and tight. Check the electrolyte
(fluid) in the battery periodically to be sure it is above the plates.
Never allow the battery to remain in a discharged condition.
CONNECTING THE BATTERY CHARGER &
BLOCKHEATER
A three-stage battery charger is provided standard for all 12 volt
standby systems. The standard charger is a Automatic Battery
Charger & Maintainer. This Charger has three rates of charging.
During the first stage, know as BULK Charging, the charging
current is limited to 2 Amps at a voltage of up to 14.5 volts. The
green LED will blink during this stage. During stage two, know as
ABSORPTION Charging, the charging voltage is held at 14.5
volts and the charging rate gradually reduces the amount of
current (amps) flowing to the battery. The green LED will also
blink during this stage. Stage three is called MAINTENANCE
Charging. During this stage the voltage will drop to 13.3 volts and
the charge rate will drop to as low at .1 amps. This keeps your
batteries in a fully charged condition without over charging them.
During this stage the green LED is constantly lit
** NOTICE **
The trickle charger is not intended to recharge a battery which
has become completely discharged. It is designed to produce
just enough current to maintain a fully charged battery.
The battery tender receptacle is to be powered by a GFCI circuit
and installed in accordance with the United States National
Electric Code. These AC wires can be run in the same conduit as
the other AC leads from the generator. It is suggested that this
circuit be fused for 15 amps, then both the battery charger and
the block heater can be connected to the same circuit. A 120 volt
1270-10 REV B
Page 6
60706-213
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.