Winco ULPSS20B4WA User Manual

PACKAGED STANDBY SYSTEM
INSTALLATION AND OPERATORS’ MANUAL
ULPSS20B4W/A
12110-00
1
60706-228
PROPER USE AND
This manual contains important instructions that should be followed during installation and main­tenance of the generator and battery. Read and understand all instructions in the manual before starting and operating the generator set.
USING THE MANUAL
Congratulations on your choice of a Winco genera­tor set. You have selected a high-quality, precision engineered generator set designed and tested to give you years of satisfactory service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem, please follow the “Troubleshooting Tables” near the end of this manual. The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future.
INSTALLATION
You must be sure your new engine generator set is: * Properly serviced before starting. * Operated in a well ventilated area. * Properly exhausted and gases safely dispersed. * Wired by a qualified electrician. * Operated only for its designed purposes. * Used only by operators who understand its operation. * Properly maintained.
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.
TABLE OF CONTENTS
INTRODUCTION 2 GUIDE TO PRODUCT SAFETY 3 BASIC INFORMATION Description 4 Specifications 5 PREPARING THE UNIT Unpacking the Unit 5 ENGINE GENERATOR INSTALLATION Installation 5 Fuel Installation 6 Vapor Fuel Pressure Tables 7 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 DC Electrical Connections 13 PREVENTIVE MAINTENANCE 16 TROUBLESHOOTING INFORMATION 17 WIRING DIAGRAMS AC & DC Generator Schematics 18 UL ATS Wiring Diagram 19 AC WIRING SCHEMATICS 20, 21 GENERATOR SET OUTLINE 22 GENERATOR SET PAD LAYOUT 23 GENERATOR WINDING DATA 24 MAINTENANCE LOG 26, 27 12 MONTH WARRANTY 28
MODEL__________________________________
SERIAL NUMBER_________________________
PURCHASE DATE_________________________
DEALER_________________________________
DEALER PHONE # ________________________
12110-00
2
60706-228
SAFETY INFORMATION
This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installa­tion or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
***********************************************************
DANGER:
DANGER indicates an imminently hazardous situ­ation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations. ***********************************************************
***********************************************************
WARNING:
WARNING indicates a potentially hazardous situ­ation which, if not avoided, could result in death or serious injury. ***********************************************************
2. FIRE HAZARD Natural gas, and L.P. present a hazard of possible explosion and/or fire.
a. Keep fuel containers out of reach of children. b. Do not smoke or use open flame near the gen­ erator set or fuel tank. c. Keep a fire extinguisher nearby and know its proper use. Fire extinguishers rated ABC by NFPA are appropriate. d. Store fuel only in an approved container, and only in a well ventilated area. e. Follow local codes for closeness to combust­ ible material.
3. DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon monoxide, an in­visible, odorless and deadly gas that must be mixed with fresh air.
a. Operate only in well ventilated areas. b. Never operate indoors. c. Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms (i.e. through windows, walls, floors).
4. NOISE HAZARD Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
***********************************************************
CAUTION:
CAUTION indicates a potentially hazardous situ­ation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. ***********************************************************
NOTE:
CAUTION is also used on the unit labels and in this manual to indicate a situation that could result in serious damage or destruction of the equipment and possible personal injury.
1. ELECTRICAL SHOCK The output voltage pres­ent in this equipment can cause fatal electric shock. This equipment must be operated by a responsible person.
a. Do not allow anyone to operate the generator without proper instruction. b. Guard against electric shock. c. Avoid contact with live terminals or receptacles. d. Use extreme care if operating this unit in rain or snow. e. Use only three-pronged grounded receptacles and extension cords. f. Be sure the unit is properly grounded to an external ground rod driven into the earth.
a. Use hearing protection when working around this equipment for long periods of time. b. Keep your neighbors in mind when permanent­ ly installing this equipment.
5. CLEANLINESS Keep the generator and sur­rounding area clean.
a. Remove all grease, ice, snow or materials that create slippery conditions around the unit. b. Remove any rags or other materials that could create a potential fire hazard. c. Carefully clean up any gas or oil spills before starting the unit.
6. SERVICING EQUIPMENT All service, includ­ing the installation or replacement of service parts, should be preformed only by a qualified technician.
a. Use only factory approved repair parts. b. Do not work on this equipment when fatigued. c. Never remove the protective guards, covers, or receptacle panels while the engine is running. d. Use extreme caution when working on electri­ cal components. High output voltage from this equipment can cause serious injury or death.
12110-00
3
60706-228
e. Always avoid hot mufflers, exhaust manifolds, and engine parts. They can cause severe burns instantly. f. Installing a generator set is not a “Do-it-your­ self” project. Consult a qualified, licensed elec­ trician or contractor. The installation must com­ ply with all national, state, and local codes.
TESTING POLICY
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current and frequency are carefully checked.
Rated output of generator is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other condi­tions specified by the manufacturer of the applicable engines.
INTRODUCTION AND DESCRIPTION
The package standby system is designed to au­tomatically provide standby power to unattended loads during electrical outages. Upon interruption of normal electrical service, the packaged standby system electrical control circuits will automatically start the engine. The generator will produce electri­cal power and the Automatic Transfer Switch (ATS) will automatically transfer the electrical loads to the engine-generator set. Upon restoration of normal electrical service the emergency transfer switch will sense return of the normal commercial power. The Automatic Transfer Switch will transfer the load back to the normal commercial power source. The engine control circuits will begin a cool-down cycle, after which the fuel supply will be shut off and the engine ignition system disabled.
These packaged standby systems consist of two major components:
1. AUTOMATIC TRANSFER SWITCH
A wall mounted ASCO 165 Automatic Transfer Switch (ATS) designed for inside or outside instal­lation. The transfer switch is UL1008 approved. A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment. The ATS also contains the power failure sensing circuitry neces­sary to start and stop the engine generator set. The transfer switch is also equipped standard with a 3 second start delay, and a 15 second transfer delay to allow the engine to warm up before transferring the load to the generator. When the line power is restored the ATS has a 5 minute transfer delay to allow the incoming utility to stabilize before trans­ferring back to line power and then an additional 1 minute engine cool down delay before the engine shuts down. Read and understand the ATS owners manual before installing, servicing or operating the transfer switch.
UL Automatic Transfer Switch Sizes
UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR ULPSS20B4W 100 AMPS 100 AMPS
200 AMPS 200 AMPS
Both the 100 amp and the 200 amp UL Switches are available in single phase only.
2. ENGINE / GENERATOR
The engine generator set consists of a Briggs & Stratton Vanguard, twin cylinder, four cycle air cooled engine, model 613277-0161-B1. The engine is factory equipped to run on LP or NG fuel. The en­gine operates at 3600 rpm and frequency regulation is maintained by the engine governor within 4 cycles variation (62.5 Hz - 58.5 Hz) from no load to rated load. The generator is a brushless, single bearing, direct drive, rotating field design. The generator is connected to the engine’s tapered (quill) crankshaft extension. The engine generator is mounted in a drip-proof enclosure for outside installation. Con­nection boxes and terminal blocks are provided for all customer connections (both AC output and DC control). A customer supplied 12 volt 500 CCA (BCI group 26) battery is required to complete the instal­lation.
12110-00
** NOTICE **
This unit will automatically transfer if a power outage occurs while running in an exercise mode.
4
60706-228
SPECIFICATIONS
GENERATOR
FUEL WATTS* VOLTS AMPS HZ PH RPM
LP 17000 120/240 70.8 60 1 3600
NG 15000 120/240 62.5 60 1 3600
* Continuous Rating. * Derate 3.5% per 1000 feet elevation above sea level.
“Concealed Damage” is understood to mean dam­age to the contents of a package which is not evident at the time of delivery by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in tran­sit. The title to goods rests with the consignee when generators are shipped F.O.B. factory, and only the consignee can legally file a claim. Please note, most carriers have a time limit for filing concealed damage claims.
**** CAUTION ****
FUEL CONSUMPTION
NATURAL GAS
1000 BTU/CU FT
CF/HR* 328 130.5
BTU/HR* 328,000 329,000
GAL/HR* N/A 3.61
* Based on full load operation.
LP VAPOR
2520 BTU/CU FT
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius).
TANK TEMPERATURE TANK SIZE
60° F (16° C) 150 GALLON
32° F (0° C) 250 GALLON
0° F (18° C) 500 GALLON
-20° F (-29° C) 1000 GALLON
These units are shipped with oil. Be sure to check oil levels before operating. See engine manufactur­er’s instruction manual for recommended oil require­ments before initial starting.
UNPACKING
1. Carefully remove the carton.
2. After inspecting the engine-generator and trans­ fer switch for external physical damage, check for the following items packed inside the carton. a. Owner’s manual. b. Engine manufacturer’s instruction manual.
3. Remove main frame hold down bolts. (4)
4. Unit can now be lifted from shipping pallet.
INSTALLATION
General Information
****************** ***** WARNING ***** ******************
Before proceeding with the installation be sure the operation selector switch is in the stop position.
ENGINE SPECIFICATIONS
Refer to engine operating and maintenance instruc­tions.
** NOTICE **
When unpacking the generator set, be sure to in­spect it carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make note of the loss or damage on the freight bill, or affix his signature under the consignor’s memo of the loss or damage. Contact the carrier for claim procedures.
When loss or damage is noted after delivery, segre­gate the damaged material, and contact the carrier for claim procedures. Be sure to retain the packag­ing material for carrier inspection.
12110-00
These engine generator sets are designed to be mounted on a concrete pad outdoors only. As an
option, a prefab pad may be used as long as proper attention is paid to site preparation to ensure the unit will not move after installation. The transfer switch is mounted next to your electrical entrance or distribu­tion panel inside or outside the building. Consult a qualified, licensed electrician or contractor to install and wire the transfer switch. The installation must
comply with all national, state and local codes.
Before beginning the installation process check the rating of the generator set and its transfer switch rating. Be certain they can handle the intended load and are compatible with the entrance voltage, phase and current ratings. Plans for installation should be prepared with proper attention to mechanical and electrical engineering detail to assure a satisfactory system installation. The information in this manual is offered only as a guide to finalizing your installation plans.
5
60706-228
ENGINE GENERATOR SET MOUNTING
WARNING - Personal Injury
The enclosures on these units can become very hot adjacent to the exhaust areas. Special care must be taken when installing these units to insure that the risk of contact by people is mini­mized.
The unit’s main frame should be bolted to a four to six inch thick cement pad. The engine-generator is mounted on a sub-frame which is isolated with spe­cial shock mounts on the main frame. This allows the engine-generator to vibrate without affecting the control panel on the main frame. (See page 23).
Do not install any shock mounts between the base frame and the concrete pad. Engine vibration will be transmitted to the control panel causing erroneous start/stop cycles and premature control failure.
These units should be mounted a minimum of 24” from a structure. This will allow for ample
room to maintain and work on the generator set. Units must be installed in accordance with all local, state, and national codes. Consult your local agency having jurisdiction for specific requirements.
FUEL INSTALLATION
The fuel supply should be as close as possible to the engine. This will reduce the installation cost of fuel runs. The information in this manual is offered to as­sist you in providing the proper fuel for your engine. However, this information is only provided to inform you of the engine’s requirements and assist in mak­ing you aware of the decisions you must make. In no case should the instructions and information pro­vided be interpreted to conflict with any local, state or national codes. If in doubt, always consult your local fire marshal, gas supplier or building inspector.
****************** ***** WARNING ***** ******************
FIRE HAZARD - All fuel runs should be installed by a licensed fuel supplier.
To connect the fuel line to the generator set you will connect your incoming fuel line to the 3/4 inch NPT fitting located on the left side of the engine-genera­tor set. This fitting is shipped with a plastic plug installed to insure the fuel system stays clean.
For all vapor fuel systems the delivery pressure of the fuel to the fuel solenoid on the unit must be four to six ounces psi (per square inch) or 7 to 11 inches W.C. (water column).
These fuel pressures are critical; failure to provide the proper pressure can cause many problems rang­ing from a unit that will not start to causing damage to the fuel system.
These units are normally tested on Natural Gas and will have a tag hanging on the fuel hose indicating on what fuel your unit was factory tested. If you are running on LP or have to change fuel types at any time, see information on page 8 on NG/LP CON-
VERSION.
INSTALLING THE FUEL LINE
** NOTICE **
The engine generator sets are properly adjusted before they leave the factory. A tag is attached to the unit that specifies the fuel, natural gas (NG) or propane vapor (LP) that the unit was set up and tested on.
NATURAL GAS or LP VAPOR PIPE SIZE
Size of pipe normally required for generators operat­ing on NATURAL GAS or LP VAPOR.
Unit location will determine the size of fuel line that is required to supply the engine with a constant fuel pressure and volume.
LIQUID PROPANE VAPOR (LP)
Refer to the tables on the following pages for fuel line size and recommended tank size. For distances of 100 feet or over, a two regulator fuel system is recommended. This is accomplished by installing a primary regulator at the tank which will reduce the tank pressure down to 10 to 15 lbs.
A low pressure regulator is installed to further reduce the fuel pressure to the required four (4) to six (6) oz. operating pressure. This low pressure regulator
must be at least 10 feet from the engine gen­erator set; any closer installation will require a larger line be installed to provide a fuel reservoir.
This is also true for the single low pressure regula­tor, it should also be a minimum of 10 feet from the unit. If this is not done, the demand regulator on the unit and the pressure regulator in the fuel line will interfere with each other. When the two (2) regula­tor system is used on LP, a fuel line size of 1/2 to 5/8 inch is generally adequate for distances up to 300 feet from the primary to the low pressure regula­tor. (Consult you local fuel supplier for your exact requirements). The appropriate line size from the table below is then installed from the low pressure regulator to the generator set.
12110-00
6
60706-228
FEET SIZE OF PIPE
up to 25 FT* 3/4 “ Pipe
25 - 100 FT* 1” Pipe
over 100 FT* Use a two regulator
system.
* Allow an additional 3 feet for each standard elbow. Do not use ‘street ells’ (restrictive).
NATURAL GAS (NG)
The primary regulator (fuel meter) on the building should deliver the correct volume and pressure to the generator set. This regulator must be sized to deliver the required BTU’s to the generator set and all other appliances in the building. If the primary
regulator (fuel meter) is a high pressure regu­lator, then a low pressure regulator must be installed to bring the pressure down to 4-6 oz. (7-11 inches water column) of pressure. This low pressure regulator must be at least 10 feet from the engine generator set; any closer installation will require a larger line be installed to provide a fuel reservoir. If this is not done, the demand regu-
lator on the unit and the pressure regulator in the fuel line will interfere with each other. This regulator must be sized to accommodate the demand of the generator set and any other appliance connected to it. See table below for the correct size of pipe to be installed.
FUEL PRESSURE
LP & NG VAPOR FUEL Correct fuel pressure can-
not be stressed enough. The most common cause for inoperative systems is an inadequate or incor­rect fuel pressure. Performance of the engine is in direct relation to the correctness of the fuel system. Shown below is a diagram of a typical LP vapor fuel installation. Notice the following tables give two (2) different units of measuring fuel pressure. The first and most accurate is the use of a simple water manometer. A manometer is calibrated in inches of water column. The second is with a pressure gauge calibrated in ounces per square inch.
Reference numbers 1 through 3 in the diagrams above are system parts supplied by the customer.
FEET SIZE OF PIPE
up to 25 FT* 3/4 “ Pipe
25 - 100 FT* 1” Pipe
over 100 FT* Consult Factory
* Allow an additional 3 feet for each standard elbow. Do not use ‘street ells’ (restrictive).
****************** ***** WARNING ***** ******************
PERSONAL DANGER - Do not use galvanized pipe in fuel line runs. The galvanized coating can be­come eroded and flake off, causing possible obstruc­tions in the regulator or fuel valve. The results could range from inoperative engine to hazardous fuel leaks.
**** CAUTION ****
Be careful when sealing gas joints. Excessive seal­ing compound can be drawn into the solenoid, regu­lator or carburetor causing an engine malfunction.
Reference number 4 is on the generator.
12110-00
7
60706-228
Shown below is a diagram of a natural gas (NG) installation.
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius).
TANK TEMPERATURE TANK SIZE
60° F (16° C) 150 GALLON
32° F (0° C) 250 GALLON
0° F (18° C) 500 GALLON
-20° F (-29° C) 1000 GALLON
Reference numbers 2 through 4 in the diagram above are system parts supplied by the customer. Reference number 4 is on the generator.
Below are tables of the fuel pressure readings at each reference in the system.
FUEL PRESSURE TABLES
Single Low Pressure Regulator (LP Vapor only)
REF # 1 3 4
UNIT OFF LINE PSI 7-11 IN
4-6 OZ
STARTING LINE PSI 7-11 IN
4-6 OZ
NO LOAD LINE PSI 7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI 7-11 IN
4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
Two (2) Regulator System (LP Vapor only)
REF # 1 2 3 4
UNIT
OFF
START-
ING
NO
LOAD
FULL
LOAD
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
NG/LP FUEL CONVERSION
These generator sets are factory tested on Natural Gas and will require no modifications for normal operation on Natural Gas. The carburetion system has been preset and anti-tamper plugs have been installed in the carburetor as required by the EPA.
To make a fuel conversion you will have to first remove the left side door. Looking down to your left you will see a decal and a plug. Remove the plastic plug with a screwdriver. Using a 5mm or 3/16” hex allen wrench turn LEFT about 1/4 turn until you feel a click and it will stop turning.
No other modifications to the unit are necessary. To switch from LP to NG you turn the selector to the right (NG) position.
Natural Gas
REF # 2 3 4
UNIT OFF 2 PSI 7-11 IN
4-6 OZ
STARTING 2 PSI 7-11 IN
4-6 OZ
NO LOAD 2 PSI 7-11 IN
4-6 OZ
FULL
LOAD
2 PSI 7-11 IN
4-6 OZ
12110-00
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
8
60706-228
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check to be sure the selector switch remains in the “off” position. This should be your last step before initial start-up.
A customer supplied twelve-volt battery is required to complete the installation. Installation of the high­est CCA rated battery, within the correct BCI group (size), will increase cold weather starting perfor­mance. Gel batteries should not be used with the battery tender installed in the generator enclosure.
Model Voltage BCI Group MINIMUM CCA Rating ULPSS20B4W 12 26 500
Installation and servicing of batteries must be performed or supervised only by personnel knowl­edgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When installing or replacing batteries, use the proper group/size starting battery. The battery should be a Maintenance Free lead acid design. Deep cycle batteries will not work for this application.
WARNING - The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following precautions must always be taken.
* Always wear full eye protection and protective clothing. * Where electrolyte contacts the skin, wash off im­ mediately with water. * If electrolyte contacts the eyes, flush thoroughly and immediately with water and seek immediate medical attention. * Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound of bicarbonate of soda (baking soda) to one gallon of water. The bicarbonate of soda solution is to be added until the evidence of reaction, foaming, has ceased. The resulting liquid is to be flushed with water and the area dried.
DANGER - Explosive Fire Risk
* Never smoke when near batteries. * Do not cause a flame or spark in the battery area. * Always discharge static electricity from your body before touching batteries by first touching a grounded metal surface.
CAUTION - PERSONAL DANGER
CAUTION - NEVER dispose of a battery in a fire. The battery is capable of exploding.
CAUTION - DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic.
These generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.
CAUTION - A battery presents a risk of electrical shock and high short circuit current. The following precautions must be observed when working with batteries.
1. Remove watches, rings and other metal objects.
2. Use tools with insulated handles.
3. Check both the battery cable ends and the bat­ tery posts to be sure they are free of corrosion.
4. Always connect the battery positive cable first and then connect the battery negative cable. When removing the battery cables from the bat­ tery, reverse the procedure and disconnect the negative cable first and then the positive cable.
5. Be sure all connections are tight and coat the terminals and cable ends with dielectric grease.
SERVICING BATTERIES
Batteries used on these units may over time lose water. This is especially true if you are using a trickle charger to maintain your battery. When refill­ing the battery with water, use only distilled water. Tap water will shorten the service life of the battery.
Never fill the battery above the fill line. Over filling above the upper level line may cause the electrolyte to overflow, resulting in corrosion to the engine or nearby parts. Immediately wash off any spilled elec­trolyte following the procedure above.
BATTERY CHARGING
Units equipped with electric start have a small fly­wheel charger built into the engine flywheel assem­bly for recharging the starting battery. This flywheel charger generates a small AC current that passes through a rectifier/regulator assembly on the engine to produce a DC charging current. This circuit is not designed to be used as a battery charging circuit to recharge dead batteries.
12110-00
9
60706-228
12110-00
10
60706-228
**** CAUTION ****
EQUIPMENT DAMAGE - Always connect the posi­tive cable first and the negative cable last. When disconnecting, remove the negative cable first and the positive cable last. Failure to connect and dis­connect in the proper sequence can cause equip­ment damage.
Observe polarities: connect the positive (+) battery terminal to the (+) cable from the engine starter; the negative (-) battery terminal is connected to the negative cable (ground) from the engine generator assembly. All connections must be clean and tight. Check the electrolyte (fluid) in the battery periodi­cally to be sure it is above the plates. Never allow the battery to remain in a discharged condition.
**** CAUTION ****
EQUIPMENT DAMAGE - NEVER JUMP START these units. Doing so will destroy the engine control module, rendering the unit non-operational. Remove and fully recharge the battery before attempting to start.
CONNECTING THE BATTERY CHARGER
A two-stage battery tender is provided on all PSS series generators. This battery tender charges at a rate of 750 mA until the battery is fully charged and then automatically switches to a 13.2 VDC float charger. The charger has an indicator light on it. Red indicates it is charging, and green indicates it is in the storage mode (float charge). This charger is mounted on the generator set which is located behind an access cover in the rear of the unit.
The battery tender receptacle is to be powered by a GFCI circuit and installed in accordance with the United States National Electric Code. These AC wires can be run in the same conduit as the other AC leads from the generator. It is suggested that this circuit be fused for 15 amps. Terminal block connections have been provided in the customer connection area of the engine generator set. See Page 10 for diagram.
** NOTICE **
The battery tender is not intended to recharge a battery which has become completely discharged. It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery.
MOUNTING THE AUTOMATIC TRANSFER SWITCH (ATS)
****************** ***** WARNING ***** ******************
EQUIPMENT DAMAGE - Protect the switch from construction grit and metal chips to prevent mal­function or shortened life of the switch. Contactors returned for warranty consideration with foreign materials inside of them will not be warranted.
Before installing the ATS you must first ensure that the transfer switch is large enough to handle your complete distribution panel. If you are installing a 100 amp transfer switch, the main line circuit breaker must not be larger than 100 amps. If you have a 125, 150, 200 amp or larger system and want to use a 100 amp transfer switch, you will not be able to transfer the complete electrical system. In this case it will be necessary to install a secondary emergency distribution panel.
AC ELECTRICAL CONNECTIONS
NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNEC­TIONS TO TERMINALS OF A CLASS 2 CIRCUIT.
****************** ***** WARNING ***** ******************
A main line circuit breaker has been provided inside the generator housing. During all wiring installation, make sure the breaker is in the off position and the generator operators switch is in the off position.
Note: This symbol always indicates ground where used.
GENERATOR CONNECTIONS
Minimum conductor sizes between the generator and the ATS. Based on wire type and temperature rating. Wire has been derated for 40° C ambient temperatures.
12110-00
11
60706-228
WIRE TEMPERATURE RATING
CU Connector AL Connector
75° C # 2 AWG # 1/0 AWG
90° C # 3 AWG # 2 AWG
To gain access to the customer connections, remove the end door panel opposite the muffler. All AC and DC connections to the ATS, 120 Volt power connec tion for battery charger, and battery installation are made behind this panel. See pages 22 and 23 for generator set and pad layout.
Two (2) hot leads, one (1) neutral and (1) ground lead are required between the generator and the ATS or distribution panel. The two power leads from the generator are marked G1 and G3. Next install the two leads, one neutral and one ground, from the generator set to the ATS or distribution panel.
In addition to the power leads, install a three wire 120 volt, 15 amp circuit from your distribution panel to the generator. This circuit will be used to power the battery charger, optional block heater and op­tional battery heater.
The last four wires you will install are the DC control leads (14 or 16 gauge) for the start circuit in the ATS. These connections will be discussed later in more detail.
WINCO UL ATS (ASCO 165)
See the ASCO installation manual for additional details on proper wiring of the Automatic Trans­fer Switch.
-
The ground leads from all locations are connected to the grounded terminal lugs also located on the side wall. This set of terminals is labeled “GROUND”.
INSTALLATION NOTES
The load current carrying wires (L) and (T) must be sized to handle the maximum load current without excessive voltage drop. By code, the wire must be heavy enough to handle the full current rating of the main line circuit breaker (or fuse) in the entrance (or sub-panel) protecting the contactor switch.
All wires should be installed in rigid or flexible con­duit. Because of the many different types of service, feeder, and distribution equipment, no specific wiring instructions can be provided. It is, however, recom­mended that copper wire be used. In all cases it is essential that while the load is connected to the gen­erator, there can be absolutely no feedback from the generator to the power line or the power line to the generator. When properly installed, the normal ATS control and safety systems will eliminate all paths for feedback. Check with your local electrical inspector on applicable local, state and federal codes.
****************** ***** WARNING ***** ******************
A service disconnect must be installed in front of the ATS panel, as the ATS is not service enterance rated. This will allow you to test the generator under load. Should you ever have to work on the switch, you will be able to disconnect the power and work on the switch cold without having the power company pull your meter.
The standby generator terminals in the ATS are marked “ALTERNATE L2 & L6”. The “hot” leads G1 and G3 from the generator are connected to the terminals L2 & L6.
The normal line power terminals in the ATS are marked “PREFERRED - L1 & L5”. The “hot” line power leads are L1 and L3 from your utility power supply are connected to terminals L1 and L5.
The load terminals in the ATS are marked “LOAD
- L3 & L7”. The leads to the load distribution panel are connected to terminals L3 & L7.
The neutral leads from all three locations are con­nected to the isolated terminal lugs on the sidewall of the cabinet. This terminal block is labeled “NEU­TRAL” and the terminal lugs are mounted on red isolation standoffs.
12110-00
To wire the automatic transfer switch into the exist­ing wiring, first determine which circuits will be on the emergency load circuit. If the entire load is to be transferred, the transfer switch can be wired in directly after the watt-hour meter and the service en­trance, providing the service entrance ampere rating is within the transfer switch’s rated capability.
If only specific circuits are to be powered under emergency power failure conditions, an additional distribution panel designated “emergency distribution panel” must be installed.
All selected emergency circuits are removed from main distribution panels and reinstalled in the emer­gency distribution panel. Suggested circuits: freez­er, refrigerator, furnace, emergency lights, sump pump, emergency outlet circuits, etc. Total running load must not exceed generator rating.
12
60706-228
DC ELECTRICAL INTERCONNECTION
The following is an optional way to interconnect the Generator and the Transfer Switch. the wires termi­nate on TB7 terminal as follows:
**** CAUTION ****
Never run the AC and DC wiring in the same con­duit.
ASCO 165 UL SWITCH
Your DC connection points in the ASCO 165 UL ATS are on the terminal block in the upper right hand corner of the ATS panel. The terminal block (TB7) is numbered 1 through 9. These terminals will accept # 22 - # 14 AWG stranded wire. It is recommended that you use # 16 AWG for distances up to 200 feet. You need to run four (4) wires from the generator set to the transfer switch.
WIRE # PURPOSE RECOMMEND
COLOR
# 5 Battery Positive Black
# 1 Battery Negative White
# 24 Fuel Solenoid Red
# 22 Start Orange
These wire colors are a recommendation only. The wires terminate on TB7 as follows:
WIRE # COLOR TB7 TERMINAL
# 1 White # 2
# 24 Red # 4
# 22 Orange # 7
The following leads are wire-nutted together:
WIRE # COLOR FROM
# 5 Black Generator
# 5 Black TB7 # 3
# 5 Black TB7 # 5
#5 Black TB7 # 8
WIRE # COLOR TB7 TERMINAL
# 5 Black # 3
# 1 White # 2
# 24 Red # 4
# 22 Orange # 7
Jumpers will need to be installed as follows:
WIRE # COLOR TB7 TERMINAL
# 5 Black # 3 & # 5
# 5 Black # 5 & # 8
12110-00
13
60706-228
INITIAL START UP
****************** ***** WARNING ***** ******************
DO NOT jump start these generator sets. Starting these units on a low battery by jump starting them will cause damage to the engine control module.
Use the following checklist to verify correct in­stallation before starting the engine:
Engine oil. Check level & fill as required with proper grade/quantity. Refer to engine owners manual for proper levels and types. Unit mounting base properly bolted down. Clearance for service and maintenance on all sides. Proper fuel line material and size. All fuel line connections tight. Fuel line protected and a moisture trap in stalled (may be required for NG). LP/NG pressure OK. 4-6 oz. (7-11 in. WC). Battery connections clean and tight. Battery fully charged. All AC and DC wiring installed and properly protected.
With the engine running smoothly, check the no load voltage and frequency at wire # 1 and # 4 (L2 and L6 in the ASCO ATS) on the generator terminal block in the ATS. The voltage should be 240 volts plus or minus nominal. The frequency should be between
61.5 to 62 hertz (Hz). The voltage should also be checked between the hot terminals (L2 and L6) and the neutral to be certain of a balanced voltage output and a solid neutral connection. The voltage should be about one half of the line to line voltage.
** NOTICE **
After completing the above checklist, the generator set is ready for the initial start-up test.
START UP PROCEDURE
Engine Generator Set only
Move the left hand toggle switch from OFF to the ON position. The alarm light should go out. Next
move the right hand toggle switch from the AUTO to the RUN position. You should hear the fuel solenoid engage at this time. Next lift the toggle switch to the START position and hold. The engine starter should engage and the engine will start. As soon as the engine starts, release the toggle switch and it will return to the RUN position. If the engine does not start after 15 seconds, release the switch and let the starter rest for 15 seconds and re-attempt to start. If the unit still will not start, consult the troubleshooting guide in the back of this manual.
If for any reason during the check out procedures the voltage and frequency are not correct, move the toggle switch to the “STOP” position and correct the trouble before proceeding. SEE PAGE 24 FOR
PICTORIAL INSTRUCTIONS FOR SETTING THE FREQUENCY.
After verifying the voltage and frequency are cor­rect, move the right hand toggle switch to the AUTO position. The unit should shut off with no time delay.
The right hand toggle switch must be left in the AUTO position for proper operation of the gen­erator. If you leave it in the RUN position, the fuel
solenoid will remain open and it will not shutdown properly after the next exercise period.
Transfer Switch & Engine Generator
This procedure checks the electrical operation of the automatic transfer switch. If the actual operation does not follow this procedure, consult the trouble­shooting section in the transfer switch manual.
1. Move the left hand toggle switch from the position to the ON position. The alarm light should go out. The unit is now ready to be operated from the Automatic Transfer Switch.
OFF
12110-00
14
60706-228
****************** ***** WARNING ***** ******************
PERSONAL INJURY HAZARD - Install front cover in transfer switch before operation. An electrical sys­tem fault could cause a flash and severe personal injury.
2. Turn on the preferred source (utility) circuit
breaker. The UTILITY acceptable light should now come on as well as the TRANSFER SWITCH on utility light. If these lights fail to come on, recheck your incoming power to insure you have 240 volts nominal. If not, troubleshoot your utility source be­fore continuing.
3. Turn on the alternate source (generator) circuit breaker.
3. To bypass the time delay or cancel the test, press and release the Push to Test button again.
4. The generator set stops and the GENERATOR
acceptacle light goes off.
WITH Load Transfer
1. Press and hold the the GENERATOR acceptable light comes on and stays on. Then release the button. This will start up your generator set.
This light indicates that the generator is running and the output voltage and frequency are within accept­able limits. Under normal conditions this light should come on in 5 to 10 seconds. If the light does not come on and stay on, a malfunction has occurred. Either the unit didn’t start or the voltage or frequency is incorrect. Correct the problem before continuing.
Push to Test button until
There are two ways to test your transfer switch operation: WITHOUT a load transfer or WITH a load transfer.
WITHOUT load transfer (normal exercise)
1. Press and release the The generator set should start immediately. In about 15 seconds the comes on and stays on.
2. The generator set runs for 20 minutes. The Transfer Switch does not transfer the load to the generator set. The TRANSFER SWITCH on utility
light stays on.
GENERATOR acceptable light
Push to Test button.
2. About 15 seconds after the acceptable light comes on, the automatic transfer switch should transfer the load from the utility to the generator. At that time the TRANSFER SWITCH on generator light should come on.
3. The generator will stay connected to the load for about 5 minutes at which time the transfer switch will transfer the load back to the utility. At the time it transfers back to utility the TRANSFER SWITCH
on UTILITY light should come on and the TRANS­FER SWITCH on generator light should go out. To
bypass this five minute time delay you can press and release the Push to Test button again at any time.
4. After the load retransfers to the utility, the gen­erator will continue to run for about 1 minute (without a load) and then shut down. The GENERATOR acceptable light will go off indicating the generator set has shut down.
This completes the functional test of the transfer switch and the generator set. If you want to leave the generator in the automatic start mode, you can leave the left hand toggle switch on the generator in the ON position. If you have additional work to do or don’t want to leave the engine generator set in the automatic position start mode, move the toggle switch to the OFF position. In the OFF postion the alarm light will come on and the generator set will not start or run.
GENERATOR
GENERATOR EXERCISER CIRCUIT
The automatic generator exerciser is configured to automatically exercise the generator for 20 minutes once every 14 days.
12110-00
15
60706-228
In order to set and test the exercise circuit the left hand toggle switch on the generator control panel must be in the ON position.
PREVENTIVE MAINTENANCE
SETTING THE EXERCISER CIRCUIT
Press and release the Automatic Generator Exerciser button. After about 8 seconds the Auto­matic Generator Exercisor light flashes 14 times to
indicate that the exerciser circuit has been set. The number of flashes indicates the number of days until the next exercise period. This 20 minute period will occur at approximately the same time of the day the button was pressed.
DISABLING THE EXERCISER CIRCUIT
Press and hold the Automatic Generator Exerciser button until the light goes off (the light flashes then goes off).
ENABLING THE EXERCISER CIRCUIT
Press and hold the Automatic Generator Exerciser button until the light goes off (the light flashes then goes off). After about 8 seconds the exerciser light flashes fourteen times to indicate that the exerciser circuit has be re-enabled.
Reasonable care in preventive maintenance will insure high reliability and a long life for the generator set and Automatic Transfer Switch.
***************** ***** WARNING ***** *****************
When performing any type of maintenance on this equipment make sure the selector switch on the generator set is in the off position. If you are work­ing on the Automatic Transfer Switch, confirm with a reliable meter that all power has been disconnected.
AUTOMATIC TRANSFER SWITCH
Clean and inspect the switch once a year. De-ener­gize all power sources, both line and generator set, then brush and vacuum away any excessive dust or dirt accumulation.At this time, with the contactor de­energized, you can remove the contactor covers and check the contacts. Make sure contacts are clean and not burned or pitted.
****************** ***** WARNING ***** ******************
WITH A TOTAL POWER FAILURE (UTILITY POWER FAILS AND THE GENERATOR FAILS TO START AND RUN) THE EXERCISER MUST BE RESET AFTER THE POWER IS RESTORED.
CLEARING AN “ERROR” CODE
An error code occurs on the ASCO control board if the generator set fails to start or there is some other malfunction. BOTH TRANSFER SWITCH lights will be blinking together. The Automatic Generator Ex- erciser light will be blinking a number of times then pause. This number gives the error code reason from page 8 of the ASCO 165 owner’s manual. To clear this code, press and release the Push to Test button once. Then troubleshoot the problem accord­ing to the ASCO 165 owner’s manual.
This completes your installation and unit testing. ALWAYS leave the system in automatic mode unless servicing the unit. For automatic operation, the left hand toggle switch on the generator control panel must be left in the “ON” position.
ENGINE GENERATOR SET
Service the engine in accordance with the engine manufacturer’s manual provided with your new equipment. Routinely remove debris and dirt from around the inside generator enclosure. Insure that the air intakes are free from leaves and other debris at all times.
Clean and inspect battery terminals a least twice a year. Check the battery water level at least twice a year.
Other than keeping the generator set clean and free of debris, there is no other routine or preventa­tive maintenance required as long as the generator is run biweekly to keep it dry and in good working order.
COLD WEATHER OPERATION
Extreme cold weather operation requires special considerations. Higher CCA batteries are required for cold weather starting; 650 CCA or larger are rec­ommended. In addition you should consider install­ing an oil heater kit and a battery warmer for reliable starting during cold weather.
12110-00
16
60706-228
TROUBLESHOOTING
ENGINE CRANKS BUT WILL NOT START
TABLES
******************** ****** WARNING ****** ********************
NEVER JUMP START THESE UNITS. JUMP STARTING THESE UNITS WITH LOW OR BAD BATTERIES WILL CAUSE PERMANENT DAMAGE TO THE ENGINE CONTROL MODULE.
UNIT WILL NOT CRANK WHEN THE POWER FAILS
1. Right generator control toggle switch not in “AUTO” position.
2. Low or dead battery, must hold 12 volts during cranking.
3. Incorrect wiring between transfer switch and generator.
4. Loose or dirty battery terminals.
5. Defective “ON/OFF” switch.
6. Defective starter.
7. Defective start solenoid.
8. Defective start/stop control in the transfer switch.
9. ATS panel in fault from previous run cycle.
10. Blown 3/4 amp fuse on generator control panel.
11. Blown 10 amp fuse on generator control panel.
12. Defective starter/fuel solenoid relay(s).
1. Improper fuel pressure being delivered to unit.
2. Fuel supply shut off.
3. Fuel supply empty.
4. Defective spark plug.
5. Defective engine ignition module.
6. Dirty air cleaner filter.
7. Defective fuel solenoid valve.
8. Low voltage from battery to fuel solenoid, must hold 12 volts during cranking.
9. Oil in the bottom of air cleaner from crankcase breather.
10. Defective starter/fuel solenoid relay(s).
ENGINE STARTS AND THEN STOPS AND FAULT LIGHT COMES ON
1. Engine is low on oil.
2. No AC output from generator to engage stop crank circuit.
ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS
1. Insufficient fuel volume getting to the unit. a. Fuel line too small. b. Low fuel pressure.
2. AC short circuit.
3. Wiring to the ATS panel crossed or shorted.
4. Unit is overloaded. Check load amperage.
ATS PANEL WILL NOT TRANSFER TO EMER­GENCY SUPPLY (GENERATOR)
1. No AC generator output from generator.
2. See Automatic Transfer Switch Manual.
ENGINE WILL NOT CRANK USING THE AUTO/ RUN/START SWITCH IN GENERATOR
1. Low or dead battery, must hold 12 volts during cranking.
2. Blown 3/4 amp fuse on generator control panel.
3. Blown 10 amp fuse on generator control panel.
4. Loose or dirty battery terminals.
5. Defective “AUTO/RUN/START” switch.
6. Defective starter.
7. Defective start solenoid.
8. Locked up engine generator set.
9. Defective starter/fuel solenoid relay(s).
12110-00
ATS PANEL WILL NOT PULL IN ON NORMAL POWER
See Automatic Transfer Switch Manual
NO AC OUTPUT FROM GENERATOR
1. Defective Diodes.
2. Defective Voltage Regulator.
3. Defective rotor.
4. Defective stator.
5. Defective exciter rotor.
6. Defective exciter stator.
7. AC short in the output leads.
6. Defective / Open Circuit Breaker
7. Wiring error.
17
60706-228
AC AND DC GENERATOR SCHEMATIC
12110-00
18
60706-228
WINCO UL ATS
Complete installation instructions for WINCO UL Automatic Transfer Switches
are contained in the operators manual with each switch. Read the complete
instructions before installing.
12110-00
CUSTOMER CONNECTION POINT
All control wires (18-14 AWG) must be torqued to 19 in. lbs.
19
60706-228
AC WIRING SCHEMATICS
ULPSS20-17/A
12110-00
ULPSS20-3/A
20
60706-228
AC WIRING SCHEMATICS
ULPSS20-18/A
12110-00
ULPSS20-4/A
21
60706-228
ENGINE GENERATOR SET
LAYOUT ULPSS20B4W/A
12110-00
22
60706-228
BASE & PAD LAYOUT
ENGINE GENERATOR SET
12110-00
23
60706-228
GENERATOR WINDING SPECIFICATIONS Mecc Alte Spa Model: ECP 28 2L/2
RESISTANCES:
ROTOR 5.523 Ohms STATOR 0.0863 Ohms AUXILIARY WINDING 1.173 Ohms EXCITER STATOR 10.60 Ohms EXCITER ROTOR 0.417
BEND THIS TAB TO CHANGE THE ENGINE SPEED (FREQUENCY). STRETCHING SPRING INCREASES THE FREQUENCY (INCREASES ENGINE SPEED). RELAXING SPRING DECREASES THE FREQUENCY (DECREASES ENGINE SPEED).
225 S. CORDOVA AVE. LECENTER, MN 56057 507-357-6821 SERVICE DEPT. 507-357-6831
12110-00
24
60706-228
THIS PAGE LEFT BLANK.
12110-00
25
60706-228
DATE
HOURS
MAINTENANCE LOG
ITEM WORK PERFORMED
12110-00
26
60706-228
DATE
HOURS
MAINTENANCE LOG
ITEM WORK PERFORMED
12110-00
27
60706-228
12 MONTH LIMITED WARRANTY
WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours, which ever occurs first, that goods manufactured or supplied by it will be free from de­fects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be de­fective in material or workmanship under normal use and service will be repaired or re­placed. For warranty service, return the product within 12 months or 1000 hours, which ever occurs first from the date of purchase, transportation charges prepaid, to your near­est WINCO Authorized Service Center or to WINCO, Inc. at LeCenter Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY.
To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular purpose, are limited to 12 months or 1000 hours, which ever occurs first from date of purchase. In no event is WINCO liable for incidental or conse­quential damages.
Note: Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply in every instance. This warranty gives you specific legal rights which may vary from state to state.
WINCO reserves the right to change or improve its products without incurring any obli­gations to make such changes or improvements on products purchased previously.
EXCLUSIONS:
WINCO does not warrant Engines. Engines are covered exclusively by the warranties of their respective manufacturers, see enclosed warranties.
WINCO does not warrant Batteries, or Other Component Parts that are warranted by their respective manufacturers.
WINCO does not warrant modifications or alterations which were not made by WINCO Inc.
WINCO does not warrant products which have been subjected to misuse and/or negli­gence or have been involved in an accident.
12110-00
28
60706-228
Loading...