Winco ULPSS12H4WE User Manual

PACKAGED STANDBY SYSTEM
INSTALLATION AND OPERATORS MANUAL
ULPSS12H4W/E
11075-00
1
60706-208
PROPER USE AND
This manual contains important instructions that should be followed during installation and main­tenance of the generator and battery. Read and understand all instructions in the manual before starting and operating the generator set.
USING THE MANUAL
Congratulations on your choice of a Winco genera­tor set. You have selected a high-quality, precision engineered generator set designed and tested to give you years of satisfactory service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem please follow the “Troubleshooting Tables” near the end of this manual. The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future.
INSTALLATION
You must be sure your new engine generator set is: * Properly serviced before starting. * Operated in a well ventilated area. * Properly exhausted and gases safely dispersed. * Wired by a qualified electrician. * Operated only for its designed purposes. * Used only by operators who understand its operation. * Properly maintained.
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.
TABLE OF CONTENTS
INTRODUCTION 2 GUIDE TO PRODUCT SAFETY 3 BASIC INFORMATION Description 4 Specifications 5 PREPARING THE UNIT Unpacking the Unit 5 GENERATOR SET INSTALLATION Installation 5 Fuel Installation 6,7 Fuel Conversions 6 Vapor Fuel Pressure Tables Battery Installation 8 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 DC Electrical Connections 12 INITIAL START UP 13 PREVENTIVE MAINTENANCE 16 TROUBLESHOOTING INFORMATION 17 WIRING DIAGRAMS AC & DC Generator Schematics 18 UL ATS Wiring Diagram 19 GENERATOR SET OUTLINE 20 GENERATOR SET PAD LAYOUT 21 12 MONTH WARRANTY 22 MAINTENANCE LOG 23
MODEL__________________________________
SERIAL NUMBER_________________________
PURCHASE DATE_________________________
DEALER_________________________________
DEALER PHONE # ________________________
11075-00
2
60706-208
SAFETY INFORMATION
This generator set has been designed and manu­factured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future refer­ence. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
***********************************************************
DANGER:
DANGER indicates an imminently hazardous situ­ation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations. ***********************************************************
2. FIRE HAZARD Natural gas and L.P. present a hazard of possible explosion and/or fire.
a. Do not refuel when the engine is running or hot. Allow the engine to cool at least two minutes before refueling. b. Keep fuel containers out of reach of children. c. Do not smoke or use open flame near the gen­ erator set or fuel tank. d. Keep a fire extinguisher nearby and know its proper use. Fire extinguishers rated ABC by NFPA are appropriate. e. Store fuel only in an approved container, and only in a well ventilated area. f. Follow local codes for closeness to combust­ ible material.
3. DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon monoxide, an in­visible, oderless and deadly gas that must be mixed with fresh air.
***********************************************************
WARNING:
WARNING inducates a potentially hazardous situ­ation which, if not avoided, could result in death or serious injury. ***********************************************************
***********************************************************
CAUTION:
CAUTION indicates a potentially hazardous situ­ation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. ***********************************************************
NOTE:
CAUTION is also used on the unit labels and in this manual to indicate a situation that could result in serious damage or destruction of the equipment and possible personal injury.
1. ELECTRICAL SHOCK The output voltage pres­ent in this equipment can cause fatal electric shock. This equipment must be operated by a responsible person.
a. Do not allow anyone to operate the generator without proper instruction. b. Guard against electric shock. c. Avoid contact with live terminals or receptacles. d. Use extreme care if operating this unit in rain or snow. e. Use only three-pronged grounded receptacles and extension cords. f. Be sure the unit is properly grounded to an external gound rod driven into the earth.
a. Operate only in well ventilated areas. b. Never operate indoors. c. Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms (i.e. through windows, walls, floors).
4. NOISE HAZARD Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a. Use hearing protection when working around this equipment for long periods of time. b. Keep your neighbors in mind when permanent­ ly installing this equipment.
5. CLEANLINESS Keep the generator and sur­rounding area clean.
a. Remove all grease, ice, snow or materials that create slippery conditions around the unit. b. Remove any rags or other materials that could create a potential fire hazard. c. Carefully clean up any gas or oil spills before starting the unit.
6. SERVICING EQUIPMENT All service, includ­ing the installation or replacement of service parts, should be preformed only by a qualified technician.
a. Use only factory approved repair parts. b. Do not work on this equipment when fatigued. c. Never remove the protective guards, covers, or receptacle panels while the engine is running. d. Use exteme caution when working on electri­ cal components. High output voltage from this equipment can cause serious injury or death.
11075-00
3
60706-208
e. Always avoid hot mufflers, exhaust manifolds, and engine parts. They can cause severe burns instantly. f. Installing a generator set is not a “Do-it-your­ self” project. Consult a qualified, licensed elec­ trician or contractor. The installation must com­ ply with all national, state, and local codes.
TESTING POLICY:
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current and frequency are carefully checked.
Rated output of generators is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other condi­tions specified by the manufacturer of the applicable engines.
These packaged standby systems consist ot two major components:
1) AUTOMATIC TRANSFER SWITCH
A wall mounted ASCO 165 Automatic Transfer Switch (ATS) designed for inside installation. The transfer switch is UL1008 approved. A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment. The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set. The transfer switch is also equipped standard with a 3 second start delay, and a 15 second transfer delay to allow the engine to warm up before transferring the load to the gen­erator. When the line power is restored the ATS has a 5 minute retransfer delay to allow the incoming util­ity to stabilize before transferring back to line power and then an additional 1 minute engine cool down delay before the engine shuts down. Read and understand the ATS owners manual before installing, servicing or operating the transfer switch.
INTRODUCTION AND DESCRIPTION
The package standby system includes all times necessary for a completely automatic standby power system as standard equipment.
DESCRIPTION
The package standby system is designed to au­tomatically provide standby power to unattended loads during electrical outages. Upon an interruption of normal electrical service the packaged standby system electrical control circuits will automatically start the engine. The generator will produce electri­cal power and the Automatic Transfer Switch (ATS) will automatically transfer the electrical loads to the generator set. Upon restoration of normal electri­cal service the emergency transfer switch will sense return of the normal commercial power. The Auto­matic Transfer Switch will retransfer the load back to the normal commercial power source. The engine control circuits will begin a cool-down cycle, after which the fuel supply will be shut off and the engine ignition system disabled.
UL Automatic Transfer Switch Sizes
UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR ULPSS12H4W 100 AMPS 100 AMPS
200 AMPS 200 AMPS
Both the 100 amp and the 200 amp UL Switches are available in single phase only.
2) ENGINE / GENERATOR
The engine generator set consists of a Honda, twin cylinder, four cycle air cooled engine. The engine is factory equipped to run on LP or NG fuel. The en­gine operates at 3600 rpm and frequency regulation is maintained by the engine governor within 4 cycles variation (62.5 Hz - 58.5 Hz) from no load to rated load. The generator is a brushless, single bearing, direct drive, rotating field design. The generator is connnected to the engine’s tapered (quill) crankshaft extension. The engine generator is mounted in a drip-proof enclosure for outside installation. Con­nection boxes and terminal blocks are provided for all customer connections (both AC output and DC control). A customer supplied 12 volt 500 CCA (BCI group 26) battery is required to complete the instal­lation.
11075-00
** NOTICE **
This unit will automatically transfer if a power outage occurs while running in an exercise mode.
4
60706-208
SPECIFICATIONS
**** CAUTION ****
GENERATOR
MODEL WATTS* VOLTS AMPS HZ PH RPM
PSS12 12000 120/240
* Derate 16% for Natural Gas operation. Derate to 7192 watts when operating on Natural Gas pressure of 4-6 inches water column. Derate 3.5% per 1000 feet elevation above sea level.
50.0 60 1 3600
FUEL CONSUMPTION
NATURAL GAS
1000 BTU/CU FT
CF/HR 190 76.6
BTU/HR 190,000 194,000
GAL/HR N/A 2.1
LBS/HR* N/A 9.0
* Based on full load operation.
LP VAPOR
2520 BTU/CU FT
ENGINE SPECIFICATIONS
Refer to engine operating and maintenance instruc­tions.
** NOTICE **
When unpacking the generator set, be sure to in­spect it carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make note of the loss or damage on the freight bill, or affix his signature under the consignor’s memo of the loss or damage. Contact the carrier for claim procedures.
These units are shipped with oil. Be sure to check oil levels before operating. See engine manufactur­er’s instruction manual for recommended oil require­ments before initial starting.
UNPACKING
1. Carefully remove the carton.
2. After inspecting the engine-generator and trans­ fer switch for external physical damage, check for the following items packed inside the carton. a. Owner’s manual. b. Engine manufacturer’s instruction manual.
3. Remove main frame hold down bolts. (4)
4. Unit can now be lifted from shipping pallet.
INSTALLATION
General Information
****************** ***** WARNING ***** ******************
Before proceeding with the installation be sure the operation selector switch is in the stop position.
These engine generator sets are designed to be mounted on a concrete pad outdoors only. As an
option a prefab pad may be used as long as proper attention is paid to site preparation to insure the unit will not move after installation. The transfer switch is mounted next to your electrical entrance or distribu­tion panel inside or outside the building. Consult a qualified, licensed electrician or contractor to install and wire the transfer switch. The installation must
comply with all national, state and local codes.
When loss or damage is noted after delivery, segre­gate the damaged material, and contact the carrier for claim procedures. Be sure to retain the packag­ing material for carrier inspection.
“Concealed Damage” is understood to mean dam­age to the contents of a package which is not evi­dent at the time of delivery by the carrier, but wheich is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in tran­sit. The title to goods rests with the consignee when generators are shipped F.O.B. factory, and only the consignee can legally file a claim. Please note, most carriers have a time limit for filing concealed damage claims.
11075-00
Before beginning the installation process check the rating of the generator set and its transfer switch rating. Be certain they can handle the intended load and are compatible with the enterance voltage, phase and current ratings. Plans for installation should be prepared with proper attention to me­chanical and electrical engineering detail to assure a satisfactory system installation. The information in this manual is offered only as a guide to finializing your installation plans.
5
60706-208
ENGINE GENERATOR SET MOUNTING
WARNING - Personal Injury
The enclosures on these units can become very hot adjacent to the exhaust areas. Special care must be taken when installing these units to insure that the risk of contact by people is mini­mized.
The unit’s main frame should be bolted to a four to six inch thick cement pad. The engine-generator is mounted on a sub-frame which is isolated with spe­cial shock mounts on the main frame. This allows the engine-generator to vibrate without affecting the control panel on the main frame. (See page 20).
Do not install any shock mounts between the base frame and the concrete pad. Engine vibration will be transmitted to the control panel causing erroneous start/stop cycles and premature control failure.
These units should be mounted a minimum of 24” from a structure. This will allow for ample
room to maintain and work on the generator set. Units must be installed in accordance with all local, state, and national codes. Consult your local agency having jurisdiction for specific requirements.
These fuel pressures are critical; failure to provide the proper pressure can cause many problems rang­ing from a unit that will not start to causing damage to the fuel system.
These units are normally tested on Natural Gas and will have a fuel line connected to the NG port on the fuel outlet tee. If you are going to operate on LP you will need to move the fuel line from the NG port to the LP port on the fuel outlet tee. These two ports have different orifice inserts installed in them, which provide proper operation with no further adjust­ments.
When moving the fuel line from one port to the other be sure not to kink or bend the line. Use a large sweeping curve as possible and never shorten the fuel line. For proper operation the fuel line must stay the same length as it was shipped.
FUEL INSTALLATION
The fuel supply should be as close as possible to the engine. This will reduce the installation cost of fuel runs. The information in this manual is offered to as­sist you in providing the proper fuel for your engine. However, this information is only provided to inform you of the engine’s requirements and assist in mak­ing you aware of the decisions you must make. In no case should the instructions and information pro­vided be interpreted to conflict with any local, state or national codes. If in doubt, always consult your local fire marshal, gas supplier or building inspector.
****************** ***** WARNING ***** ******************
FIRE HAZARD - All fuel runs should be installed by a licensed fuel supplier.
To connect the fuel line to the generator set you will connect your incoming fuel line to the 3/4 inch NPT fitting located on the left side of the engine-genera­tor set. This fitting is shipped with a plastic plug installed to insure the fuel system stays clean.
For all vapor fuel systems the delivery pressure of the fuel to the fuel solenoid on the unit must be four to six ounces psi (per square inch) or 7 to 11 inches W.C. (water column).
INSTALLING THE FUEL LINE
** NOTICE **
The engine generator sets are properly adjusted before they leave the factory. A tag is attached to the unit that specifies the fuel, natural gas (NG) or propane vapor (LP) that the unit was set up and tested on.
NATURAL GAS or LP VAPOR PIPE SIZE
Size of pipe nomally required for generators operat­ing on NATURAL GAS or LP VAPOR.
Unit location will determine the size of fuel line that is required to supply the engine with a constant fuel pressure and volume.
LIQUID PROPANE VAPOR (LP)
Refer to the tables below for fuel line size and rec­ommended tank size. For distances of 100 feet or over, a two regulator fuel system is recommended. This is accomplished by installing a primary regula­tor at the tank which will reduce the tank pressure down to 10 to 15 lbs.
11075-00
6
60706-208
A low pressure regulator is installed to further reduce the fuel pressure to the required four (4) to six (6) oz. operating pressure. This low pressure regulator
must be at least 10 feet from the engine gen­erator set, any closer installation will require a larger line be installed to provide a fuel reservoir.
This is also true for the single low pressure regula­tors, it should also be a minimum of 10 feet from the unit. If this is not done the demand regulator on the unit and the pressure regulator in the fuel line will interfere with each other. When the two (2) regula­tor system is used on LP, a fuel line size of 1/2 to 5/8 inch is generally adequate for distances up to 300 feet from the primary to the low pressure regula­tor. (Consult you local fuel supplier for your exact requirements). The appropriate line size from the table below is then installed from the low pressure regulator to the generator set.
****************** ***** WARNING ***** ******************
PERSONAL DANGER - Do not use galvanized pipe in fuel line runs. The galvanized coating can be­come eroded and flake off, causing possible obstruc­tions in the regulator or fuel valve. The results could range from inoperative engine to hazardous fuel leaks.
**** CAUTION ****
Be careful when sealing gas joints. Excessive seal­ing compound can be drawn into the solenoid, regu-
lator or carburetor causing an engine malfunction.
FUEL PRESSURE
FEET SIZE OF PIPE
up to 25 FT* 3/4 “ Pipe
25 - 100 FT* 1” Pipe
over 100 FT* Use a two regulator
system.
* Allow an additional 3 feet for each standard elbow. Do not use ‘street ells’ (restrictive).
NATURAL GAS (NG)
The primary regulator (fuel meter) on the building should deliver the correct volume and pressure to the generator set. This regulator must be sized to deliver the required BTU’s to the generator set and all other appliances in the building. If the primary
regulator (fuel meter) is a high pressure regu­lator then a low pressure regulator must be installed to bring the pressure down to 4-6 oz. (7-11 inches water column) of pressure. This low pressure regulator must be at least 10 feet from the engine generator set, any closer installation will require a larger line be installed to provide a fuel reservoir. If this is not done the demand regu-
lator on the unit and the pressure regulator in the fuel line will interfere with each other. This regula­tor must be sized to accomidate the demand of the generator set and any other appliance connected to it. See table below for the correct size of pipe to be installed.
LP & NG VAPOR FUEL Correct fuel pressure can­not be stressed enough. The most common cause for inoperative systems is an inadequate or incor­rect fuel pressure. Performance of the engine is in direct relation to the correctness of the fuel system. Shown below is a diagram of a typical LP vapor fuel installation. Notice the following tables give two (2) different units of measuring fuel pressure. The first and most accurate is the use of a simple water manometer. A manometer is calibrated in inches of water column. The second is with a pressure gauge calibrated in ounces per square inch.
FEET SIZE OF PIPE
up to 25 FT* 3/4 “ Pipe
25 - 100 FT* 1” Pipe
over 100 FT* Consult Factory
* Allow an additional 3 feet for each standard elbow. Do not use ‘street ells’ (restrictive).
11075-00
7
60706-208
Shown below is a diagram of a natural gas (NG) installation.
Reference numbers 2 through 4 in the diagram above are system parts supplied by the customer. Reference number 4 is on the generator.
Below are tables of the fuel pressure readings at each reference in the system.
FUEL PRESSURE TABLES
Single Low Pressure Regulator (LP Vapor only)
Natural Gas
REF # 2 3 4
UNIT OFF 2 PSI 7-11 IN
4-6 OZ
STARTING 2 PSI 7-11 IN
4-6 OZ
NO LOAD 2 PSI 7-11 IN
4-6 OZ
FULL
LOAD
2 PSI 7-11 IN
4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
LP TANK SIZING
Required LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius).
TANK TEMPERATURE TANK SIZE
60° F (16° C) 150 GALLON
32° F (0° C) 250 GALLON
0° F (18° C) 500 GALLON
-20° F (-29° C) 1000 GALLON
REF # 1 3 4
UNIT OFF LINE PSI 7-11 IN
4-6 OZ
STARTING LINE PSI 7-11 IN
4-6 OZ
NO LOAD LINE PSI 7-11 IN
4-6 OZ
FULL
LOAD
LINE PSI 7-11 IN
4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
Two (2) Regulator System (LP Vapor only)
REF # 1 2 3 4
UNIT
OFF
START-
ING
NO
LOAD
FULL
LOAD
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
LINE PSI 10-15
LBS
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
LP/NG FUEL CONVERSION
The ULPSS12H4W/E generator sets have been tested on NATURAL GAS prior to shipment. If you are going to use them on LP vapor, follow the pro­cedures in FUEL INSTALLATION. See Page 6.
INSTALLING THE BATTERY
**** CAUTION ****
In the following battery installation procedure, check to be sure the selector switch remains in the “off” position. This should be your last step before initial start-up.
A customer supplied twelve-volt battery is required to complete the installation. Installation of the high­est CCA rated battery, within the correct BCI group (size), will increase cold weather starting perfor­mance. Gel batteries should not be used with the battery tender installed in the generator enclosure.
Model Voltage BCI Group MINIMUM CCA Rating ULPSS12H4W 12 26 500
11075-00
Installation and servicing of batteries must be per­formed or supervised only by personnel knowledge­able of batteries and the required precautions. Keep unauthorized personnel away from batteries.
8
60706-208