Winco TB4000, TB1500C, TB6000, TB2400C, TB7200 Owner's Manual

...
Page 1
BRUSHLESS
TWO-BEARING
A
Div~sion
of
Technology
Znc
INSTALLATION, OPERA TION,
and
MAINTENANCE INSTRUC-
TIONS
OWNERS MANUAL
--
-
A
Division
of
-Dy& Techno/oogy
fnc
Page 2
Read and understand all instructions in the manual before starting and operating the generator set.
USING THIS MANUAL
Congratulations on your choice of a Wnco generator set. You have selected a high-quality, precision-engi­neered generator set designed and tested to give you
years of satisfactory portable service.
To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem please follow the "Things To Check" near the end of this manual. The warranty listed in this manual describes what you can expect from WlNCO should you need service assistance in the future.
TABLE OF CONTENTS
INTRODUCTION
12
MONTH WARRANTY
GUIDETOPRODUCTSAFETY
BASIC INFORMATION
Specification Table Unit Capabilities Unpacking the unit
lNSTALLATIONlOPERATlON
Assembly Plan The Installation Connecting The Load Common Problems
PROPER USE AND INSTALLATION
You must be sure your new generator set is:
*
Properly serviced before starting
*
Wired by a qualified electrician
*
Operated only for its designed purposes
*
Used only by operators who understand its operation Properly maintained
COPY YOUR MODEL AND SERIAL
NUMBER HERE
No other WlNCO generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.
MODEL SERIAL NUMBER
i
PURCHASE DATE
i
1
DEALER
WINCO,
Inc.
12
Month Limited
Warranty
WINCO, Incorporated warrants to the original purchaser for
12
months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with
Winco written instructions.
WINCO's sole liability, and Purchaser's sole remedy fora failure under this warranty, shall be limited to the repairof the
product. At
WINCO's option, material found to be defective in material or workmanship under normal use andservice
will be repaired or replaced. For warranty service, return the product within
12
months from the date of purchase, transportation charges prepaid, to your nearest WlNCO Authorized Service Center or to WINCO, Inc. at Le Center Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY. To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular
purpose, are limited to
12
months from date of purchase. In no event is WINCO liable for incidental or consequential
damages. Note: Somestates do notallowlimitation on the duration ofimplied warrantyandsomestates do notallowthe exclusion
or limitation of incidental or consequential damages, so the above limitations may not apply in every instance. This warranty gives you specific legal rights which may vary from state to state.
WlNCO reserves the right to change or improve its products without incurring any obligations to make such changes or improvement on products purchased previously.
EXCLUSIONS:
WlNCO does not warrant engines, batteries, or other component parts that are warranted by their respective
manufacturers.
WlNCO does not warrant modifications or alterations which were not made by WINCO, Inc.
Page 3
GUIDE TO PRODUCT SAFETY
This engine generator set has been designed and manu­factured to allow safe, reliable performance.
Poor
mainte-
L
nance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxi­ation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
2.
FIRE HAZARD-Gasolineand otherfuelsalways present a hazard of possible explosion andlor fire.
a. Do not refuel when the engine is running or hot. Allow
the engine to cool at least two minutes before refueling. b. Keep fuel containers out of reach of children. c. Do not smoke or use open flame near the generator set
or fuel tank. d. Keep a fire extinguisher nearby and know its proper
use. Fire extinguishers rated ABC by NFPA are appro­priate.
e. Store fuel only in an approved container, and only in a
well-ventilated area.
DANGER:
DANGER indicates an imminently hazard-
ous situation which,
if
not avoided, will
result
in
death w serious injury. This signal word is to be limited to the most extreme situations.
WARNING:
WARNING indicates a potentially hazard-
oussituation which,
if
notavoided, could
result
in
death or serious injury.
CAUTION:
CAUTION indicatesa potentially hazardous
situation which,
if
not avoided, may re-
sult
in
minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE:
CAUTION
is
also usedon the unitlabels and
in
this
manual to indicate a situation that
could result
in
serious damage or de-
struction of the equipmentandpossible
personalinjury.
1.
ELECTRIC SHOCK- The output voltage present in this equipmentcan
causeafatalelectric shock. Thisequip-
ment must be operated by a responsible person. a. Do not allow anyone to operate the generator without
proper instruction. b. Guard against electric shock. c. Avoid contact with live terminals or receptacles. d. Use extreme care if operating this unit in rain or snow. e. Use only three-prong grounded receptacles and exten-
L
sion cords. f. Be sure the unit is properly grounded to an external
ground rod driven into the earth.
3.
DEADLY EXHAUST GAS -Exhaustfumesfrom any gaso­line enginecontain carbon monoxide, an invisible, odor­less and deadly gas that must be mixed with fresh air.
a. Operate only in well ventilated areas. b. Never operate indoors. c. Never operate the unit in such
a
way as to allow exhaust gases to seep back into closed rooms (i.e. through windows, walls or floors).
4.
NOISE HAZARD - Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a.Use hearing protection equipment when working
around this equipment for long periods of time.
b. Keep your neighbors in mind when permanently in-
stalling this equipment.
5.
CLEANLINESS- Keep the generator and surrounding area clean.
a. Remove all grease, ice, snow or materials that create
slippery conditions around the unit.
b. Remove any rags or other material that could create
potential fire hazards.
c. Carefully wipe up any gas or oil spills before starting the
unit.
d. Never allow leaves or other flammable material to build
up around the engine exhaust area.
6.
SERVICING EQUIPMENT-All service, including the
in-
stallation or replacement of service parts, should be
performed only by a qualified technician.
a. Use only factory approved repair parts.
b. Do not work on this equipment when fatigued.
c. All belts,
pullies andlor drive shafts must have protec­tive guards andlor covers permanently installed by the assembler.
d. Never remove the protective guards, cover, or recep-
tacle panels while the engine is running.
e. Use extreme caution when working on electrical com-
ponents. High output voltages from this equipment can cause serious injury or death.
f. Always avoid hot mufflers, exhaust manifolds, and
engine parts. They all can cause severe burns in­stantly.
Page
1
TB
SERIES
Page 4
BASIC INFORMATION
TESTING POLICY:
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked.
Rated output of generators is based on factory tests of typical units, and is subject to, and limited by the ambient operating temperature. The generator will not provide full power output unless driven by a prime mover of adequate horsepower. The prime mover (engine or other input power source) horsepower is also affected by temperature as well as a number of other factors such as: fuel, altitude, and all other conditions specified by the prime mover manufacturer.
INTRODUCTION AND DESCRIPTION
The generator is a 3600 rpm two bearing, belt driven, brushless, revolving field design. The generator is self excited and inherently regulated to
+I-
(plus or minus)
7%
-
no load to full rated load. It can be operated
under any load within its rating without being dam-
aged. The frequency regulation is determined by the
sensitivity of the customer supplied prime movers' governor. It is desirable to maintain this speed to
within 3 cycles variation (61.5 Hz
-
58.5
Hz) no load to
full rated load (3690 rpm
-
3510 rprn).
Generator Specifications
MODEL WATS VOLTS AMPS HZ PH RPM
UNIT CAPABILITIES
1. Generator Coni-lections - The diagram below represents a typical ordinary 4000 watt generator. Only 2000 watts at
120 volts (16.7 Amps) can be taken from the generator at receptacle A and up to 2000 watts at 120 volts from receptacle C. On an ordinary generator, CAUTION MUST BE
EXERCISEDTO PREVENTOVERLOADING EITHER
OF THE 120 VOLT CIRCUITS (A OR C).
CONVENTIONAL DUAL VOLTAGE
120/240 VOLT SCHEMATIC
-
Neutral
A
A
--
E
120
Volts
Gro~nd~k'2$ocles
r\
TYPICAL
4000
WATT GENERATOR
The following currents (measured in amps) are produced at 120
&
240 volts for typical wattage shown.
AMPS AT
120
VOLT
240
VOLT
RECEPTACLE ID
MODEL A C
B
TB1500C 12.5 NIA NIA TB2400C 20 NIA NIA TB4000C 16.7 16.7 16.7 TB4000* 16.7 16.7 16.7 TB6000C
2
5 2 5 25
TB6000*
25
2
5
25
TB7200** 30 3 0 30
'Customer connections are made on the back side of the circuit breaker
** This unit has a junction box rather than recep­tacles. Ref.
"amis the GI lead, Ref. "c" is the G3 lead
and Ref.
"b"
is GI to G3 rating
2. Starting Electric Motors - Electric motors require much more current (amps) to start them than to run them. Some
motors, particularly low cost split-phase motors, are very
hard to start and require 5 to 7 times as much current to start
them as to run them. Capacitor motors are easier to start
and usually require 2 to 4 times as much current to start them as to run them. Repulsion Induction motors are the easiest to start and usually require 1-112 to 2-112 times as much to start them as to run them.
Most fractional horsepower motors take about the same amount of current to run them whether they are of Repul­sion-Induction (RI), Capacitor (Cap), or Split-Phase (SP) type. The chart below shows the approximate current
required to start and run various types of sizes of 120 volt
-
60 cycle electric motors under average load conditions.
TB
SERIES
Page
2
60706-098
Page 5
BASIC
INFORMATION
RUNNING STARING AMPS
HP AMPS SP CAP
RI
-
116 3.2 16T0 22 6 TO13 ST0 8 114 4.5
22TO32 9T018 7T012 113 5.2 26TO35 10T02 18T017 112 7.2 NOTMADE
14TO2911TO18
1 13.0 NOTMADE 26 TO 52 20 TO 33
The figures given above are for average load such as a blower or fan. If the electric
motor is connected to a hard starting load such as an air compressor, it will require more starting current. If it is connected to a light load, or no load such as a power saw, it will require less starting current. The exact requirement will also vary with the brand or design of the motor.
For 240 volt motors, the "running" current is half as much as shown for the 120 volt motors of the same size. Some dual voltage 1201240 volt motors are difficult to start on 240 volts when driven by enginelgenerators and can be started more easily when connected to operate on 120 volts. This is particularly true of "capacitor start-induction run" motors. Sometimes a 240 volt motor which cannot be started on the 240 volt circuit of a
1201240volt generator
can be started on a 120 volt circuit and then auicklv
Generator Model
Motor Size (code
"G"
capacitor start)
Trying to start a larger motor or higher code (ie. J or
K)
motor may result in damage to both the generatorand the electric motor especially
120
volt motors.
UNPACKING INSTRUCTIONS
**
NOTICE
**
When unpacking the generator, be sure to inspect it
carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make a note of the loss or damage on the freight bill, or affix his signature under the consigner's memo of the loss or damage. Contact the carrier for claim procedures.
switched to the 240 volt circuit after it is started.
c his
cai
be done in applications where the motor is manually
When loss or damage is noted after delivery, segre-
controlled and is started under "no load" conditions.
gate the damaged material, and contact the carrier for claim procedures.
A self-excited generator responds differently to severe overloading than the power line. To illustrate, suppose
-,
that a 240 volt 10
H.P.
"capacitor start-Induction Run"
motor is connected to the generator. The engine would not be able to supply enough power to bring the electric motor up to operating speed. The generator would re­spond with high initial starting current, but the engine would be very severely overloaded. The speed would probably drop sharply and possibly stall the engine. If allowed to operate at very low speeds, the electric motor startwinding would burn out in a shorttime. The generator winding might also be damaged.
On the other hand, suppose a smaller electric motor that requires just a little more output than the generator can produce is connected to it. It will try to run but will not reach a high enough speed for the internal centrifugal switch to disconnect the starting winding. The generator output, instead of being 120 volts, may drop to 70 or 80 volts.
RUNNING THE GENERA TOR SET UN­DER EITHER OF THESE CONDITIONS
"CONCEALED DAMAGE" is understood to mean damage to the contents of a package which is not in evidence at the time of delivery by the carrier, but which
is discovered later. The carrier or carriers are respon­sible for merchandise lost or damaged in transit. The title to goods rests with the consignee when genera­tors are shipped fob factory, and only the consignee can legally file claims.
1. Carefully open carton.
2. After inspecting the generator for external physical
damage, check for the owner's manual (operating
instructions, wiring diagram, parts list) inside the
carton.
2. Remove generator hold down bolts.
4. Unit can now be lifted from shipping base.
****
CAUTION
****
COULD
RESULT IN DAMAGE TO THE
Before proceeding with the installation, be sure that you
GENERATORSTATORAS WELLAS THE
have completely read and understand the assembly
MOTOR WINDING.
and installation instructions.
Because the heavy surge of current required for starting motors is required for only an instant, the generator will
ASSEMBLY
not be damaged if it can bring the motor up to speed in a
few seconds of time. If difficulty is experienced in starting
1. An engine with adequate horsepower and a close
motors, turn all other electrical loads off and if possible
regulating (fixed speed) governor is required for
L
reduce the load on the electric motor.
satisfactory operation of any alternating current
3.
Motor Starting Ca~acitv - listed below vou will find the
generator.
motor starting ~>~al;ilit~ bf your engine ienerator set.
60706-098
Page
3
TB SERIES
Page 6
INSTALLATION
These units require approximately two (2) horsepower for every 1000 watts of generator output. Theoretically you should be able to produce 1000 watts with
1.4
Horsepower, but this is only possible with 100%
efficiencies in both the engine and the generator.
Between engine and generator efficiencies of only
80%
to 90% and the losses through the drive system the two
horsepower requirement is more realistic. For example, this 1,500 watt generator output will
require a 3 or 4
h.p. Engine for full output, good speed
I
voltage regulation, and satisfactory load performance.
2. When determining the prime mover I generator pulley ratio to drive the generator at the correct operating speed, bear in mind that the power rating of most prime movers (usually an engine) varies with the speed-that is, it produces more power at higher speeds, less when slowed. The prime mover must be run fast enough to reach the desired horsepower for good generator set operation.
The drive belt system must be of adequate size and must be tight enough to power the generator without slippage. Be careful not to overtighten to the extent that it puts excessive strain on the
bearings--doing so can cause bearing failure and other possible damage to the generator.
Alignment of the generator to the prime mover is important. Misalignment of the
pullies will cause excessive belt and pulley wear and unnecessary stress on the prime mover.
3.
The following table shows the effect of various operating
speeds and electrical loads on a typical generator when matched and mounted to an adequate prime mover
together with the natural "voltage drop" within the generator itself due to load current and heating of the windings, results in a slightly lower voltage than when
--
the generator is running idle. The normal, slight variations in speed also directly affect
the frequency of the output current. This frequency variation has no appreciable effect in the operation of most loads (such as motors, lights and most small appliances). However, timing devices and clocks will not keep perfect time unless the engine can keep the generator running at exactly 3600 rpm at all times. Since this is not usually possible, minor time errors in clocks occur.
The speed of the engine is usually adjusted so that the generator produces proper voltage. If the adjustment is made "cold", set the voltage a little higher than normal since it will drop a few volts as the generator warms up.
**"
CAUTION
****
When operating continuously at full load the generator shell becomes very warm. It will be uncomfortable to the touch-this is normal for any high performance
inherently regulated generator.
Output voltage should be checked periodically to
insure proper operation of the generating plant and
appliances.
****
CAUTION
"**
-
Low voltage may damage any motors or appliances
connected to it. Running the generator at excessively
high speeds results in too high voltage which will also damage electrical devices connected to it. Excessively high speed may also cause damage to the generator stator windings.
Although individual units and models may vary slightly, the normal voltage and frequency of typical 60 cycle generators described in this book are approximately as
follows when powered by a typical prime mover (engine)
run first with no load applied, then at half the generator capacity and finally when loaded to its full capacity as rated on the nameplate:
GENERATOR
LOAD SPEED FREQUENCY VOLTAGE NONE 3690 RPM 61 112 HZ
129VOLTS HALF 3600RPM 60HZ 120VOLTS FULL 3510 RPM
58
112
HZ
115VOLTS
****
CAUTION
****
Required generator speed must be maintained at 3600
+I-
90 rpm under all load conditions.
4.All engines have a tendency to slow down when a load is applied. The governor on the engine is designed to hold the engine speed nearly constant. When the electrical load connected to the generator is increased, the engine is more heavily loaded and as a result the speed drops slightly. This slight decrease in speed
PLAN THE INSTALLATION
Plans for installation should be prepared with proper attention to mechanical and electrical engineering detail to assure a satisfactory system installation. The information in this manual is offered as a guide to finalizing your installation plans. The installation sequence is summarized below:
Generally these two bearing generators are used on
portable equipment. For best service consider the
following
:
1 .All electrical equipment should be protected from
excessive moisture. Failure to do so will result in deterioration of the insulation and will result in short circuits and grounds.
2.
The generator should be installed in a sheltered area. If the unit must be
left in the open, it should always be
protected with a weather cover such as a tarp or large
-
piece of canvas after each use to keep out water and dust.
TB
SERIES
P
'age
4
60706-098
Page 7
BASIC OPERATION
"*
CAUTION
****
Always allow the generator and prime mover to cool
-
before covering with a flammable weather covering.
****
CAUTION
*"*
The generator must be mounted with the engine to a common rigid base to prevent stress on the engine and generator shafts and bearings due to vibration displacement. For permanent installations, the engine-generator is usually mounted on a
sub­frame which can be shock mounted with special neoprene pads on the main frame.
CONNECTING THE LOADS
1. Applying The Load - A shortwarm-up time will permit the engine to work more efficiently when the load is applied and will reduce the wear and extend its life.
a. Rece~tacles have been Drovided on the control Dane1
pump and other items to be powered directly into the generator receptacles. Before
plugging in all the tools and cord sets, recheck the rating of the generator set. Be sure it can handle the intended load and is compatible with the voltage, phase, and current ratings.
f. 'Hard Wiring' this unit directly into a temporary construc-
tion site electrical system is NOT A SIMPLE DO-IT­YOURSELF JOB. For your safety all wiring must be done by a qualified electrician and conform to the National Electric Code and comply with all state and local codes and regulations. Check with local authori­ties before proceeding.
****WARNING""
PERSONAL DANGER A fully isolated, double pole double throw manual transfer switch must be installed any time a generator is being connected to an existing distribution system.
tocohect the loads on the models,
TBI
~OOC,
TB~~OOC,
TB4000C, TB6000C. On the models TB2400, TB4000,
**"CAUTION"*
TB6000 the connections are made on the back side of
EQUIPMENT DAMAGE - Failure to properly limit and bal-
the circuit breakers. The TB7200 has a junction box
ance the load applied to the generator will cause the
mounted on the top of the generator. The loads should
generator to produce low voltage and may damage the
be applied gradually. If a large motor is being started
engine generator set. It may also cause severe damage
or multiple motors are being started, they should be
to the loads connected to the generator at that time.
started individually and the largest should be started
Improper loading of the generator set constitutes abuse
first.
and will not be covered by warranty.
L
**"
CAUTION
****
EQUIPMENT OVERLOAD-Keep the generator load within
the generator and receptacle nameplate rating. Over-
loading may cause damage to the generator
andlor the
loads b. Most electric tools and appliances will have the voltage
and amperage requirements on their individual name-
plates. When in doubt consult the manufacturer or a
local electrician. The nameplate amperage rating for electric motors can be misleading. See "Starting Elec­tric Motors" in Specification Section.
c. These engine generator sets are inherently self regu-
lating based on engine speed. The engine governor will automatically adjust itself to the load. No harm to the generator will result if it is operated with no load connected.
d. Proper. utilization amperage is necessary to prevent
damage to either the
receptacleslbreakers or the gen­erator. The generator is a limited source of electrical power, therefore pay special attention to the receptacle and generator ratings. The nameplate rating can be
obtained through a combination of receptacles or a single receptacle as long as the receptacle amperage
rating is not exceeded. Both the 120 and
240volt output can be utilized at the same time. See Specification Section for proper load separation.
e. Plug your tools such as drills, saws, blowers, sump
COMMON PROBLEMS
Sometimes problems can be easily solved by checking a few basic things. Check below before you call or take your unit to a service center. It could save you time and money.
Voltage too low
*Engine speed is too low. *Generator overloaded. *Defective stator. *Defective rotor (field).
Circuit Breaker Trips 'Defective load.
*Defective receptacle.
Voltagetoo high
*Engine speed is too high.
Generatoroverheating *Overloaded.
*Insufficient ventilation.
Nooutputvoltage *Short in load (disconnect).
*Broken or loose wire. *Defective receptacle. *Defective capacitor. *Defective diode. *No residual magnetism in
generator. *Defective stator. "Defective rotor (field).
60706-098
Page
5
TB
SERIES
Page 8
UNMARKED
WIRING DIAGRAMS
EXCl TATlON
WINDING
(STATOR)
LEADS EXCITATION
FIELD RECTIFIERS COILS
(ROTOR)
CIRCUIT
BREAKERS
A.C. OUTPUT
WINDING
(STATOR)
1
EXClTATlON WINDING
CIRCUIT BREAKER
RECEPTACLES
7
*--
CAPACITOR
UNMARKED
RECTIFIERS
LEADS
COILS
(ROTOR)
EXCITATION WINDING
EXCITATION
UNMARKED
RECTIFIERS
LEADS
COILS
(ROTOR)
CIRCUIT BREAKER
wd
,
rn
A.C. OUTPUT
f
WlNDlNG
120
VOLTS
VOLTS
120
1
kr_,
BREAKER
vOrl
A
Division of
DTL
Dp Techno/ogy fnc
225
South Cordova Avenue
Le Center, Minnesota
56057
Loading...