Read and understand all instructions in the manual
before starting and operating the generator set.
TABLE OF CONTENTS
USING THIS MANUAL
Congratulations on your choice of a Winco generator set.
You have selected a high-quality, precision-engineered
generator set designed and tested to give you years of
satisfactory portable service.
To get the best performance from your new engine
generator set, it is important that you carefully read and
follow the operating instructions in this manual.
Should you experience a problem please follow the
“Things To Check” near the end of this manual. The
warranty listed in this manual describes what you can
expect from WINCO should you need service assistance
in the future.
PROPER USE AND INSTALLATION
You must be sure your new engine generator set is:
*Properly serviced before starting
*Operated in a well ventilated area
*Exhaust gases are dispersed safely
*Wired by a qualified electrician
*Operated only for its designed purposes
*Used only by operators who understand its operation
*Properly maintained
FRONT PANEL DESCRIPTION4
RECEPTACLE AND BREAKERS4
FULL POWER CONNECTIONS5
VOLTAGE REGULATOR5
SELECTING THE CORRECT
VOLTAGE5
START-UP PROCEDURE6
CONNECTING THE LOADS6
UNIT STORAGE7
50 CYCLE OPERATION7
MAINTENANCE8
PREVENTIVE MAINTENANCE8
WARRANTY9
WIRING DIAGRAMS
DC ELECTRICAL SCHEMATIC10
RECEPTACLE PANEL11
CIRCUIT BREAKER PANEL11
AC SCHEMATIC12
AC WIRING DIAGRAM13
COPY YOUR MODEL AND SERIAL NUMBER
BELOW FOR FUTURE REFERENCE.
No other WINCO generator has the same serial number
as yours. It is important that you record the number and
other vital information here, if you should ever need to
contact us on this unit it will help us to respond to your
needs faster.
MODEL____________________________________
SERIAL NUMBER____________________________
PURCHASE DATE____________________________
DEALER___________________________________
Page i
GUIDE TO PRODUCT SAFETY
This engine generator set has been designed and
manufactured to insure your personal safety. Improper
use can result in potential deadly hazards, from electrical
shock, exhaust gas asphyxiation, or fire. Please read all
safety instructions carefully before installation or use.
Keep these instructions handy for future reference. Take
special note and follow all warnings on the unit and in the
manuals.
************************************************************
CAUTION: Possible Damage to Equipment.
CAUTION notes indicate any condition or practice, which
if not strictly observed or remedied, could result in
damage or destruction of the equipment.
************************************************************
************************************************************
WARNING: Personal Danger.
WARNING notes indicate any condition or practice,
which if not strictly observed, could result in personal
injury or possible loss of life.
***********************************************************
1. ELECTRIC SHOCK - The output voltage present in
this equipment can cause a fatal electric shock. This
equipment must be operated by a responsible person.
A. Do not allow anyone to operate the generator without
proper instruction.
B. Guard against electric shock.
C. Avoid contact with live terminals or receptacles.
D. Use extreme care if operating this unit in rain or snow.
E. Use only three-prong grounded receptacles and
extension cords.
F. Be sure the unit is properly grounded to an external
ground rod driven into the earth.
2. FIRE HAZARD - Diesel fuel and other fuels always
present a hazard of possible explosion and/or fire.
A. Do not refuel when the engine is running or hot. Allow
the engine to cool at least two minutes before refueling.
B. Keep fuel containers out of reach of children.
C. Do not smoke or use open flame near the generator
set or fuel tank.
D. Keep a fire extinguisher nearby and know its proper
use. Fire extinguishers rated ABC by NFPA are appropriate.
E. Store fuel only in an approved container, and only in a
well-ventilated area.
4. NOISE HAZARD - Excessive noise is not only tiring,
but continual exposure can lead to loss of hearing.
A. Use hearing protection equipment when working
around this equipment for long periods of time.
B. Always operate with the housing doors closed to
reduce the operational noise level.
5. CLEANLINESS - Keep the generator and surrounding
area clean.
A. Remove all grease, ice, snow or materials that create
slippery conditions around the unit.
B. Remove any rags or other material that could create
potential fire hazards.
C. Carefully wipe up any gas or oil spills before starting
the unit.
D. Never allow leaves or other flammable material to
build up around the engine exhaust area.
6. SERVICING EQUIPMENT - All service, including the
installation or replacement of service parts, should be
performed only by a qualified technician.
A. Use only factory approved repair parts.
B. Do not work on this equipment when fatigued.
C. Never remove the protective guards, cover or receptacle panels while the engine is running.
D. Never wear neckties or other loose clothing that can
be caught in moving parts while you are servicing or
operating this equipment.
E. Use extreme caution when working on electrical
components. High output voltages from this equipment
can cause serious injury or death.
F. When servicing this unit always avoid hot mufflers,
exhaust manifolds, and engine parts. They all can cause
severe burns instantly.
G. Installing and wiring a standby generator is not a “do it
yourself” project. Consult a qualified, licensed electrician
or contractor. The installation must comply with all
national, state, and local codes.
7. LIFTING THE EQUIPMENT - When lifting always
make sure that the area under the equipment is kept
clear.
A. Be certain rigging is designed to lift unit safely.
B. Never attempt to lift the equipment unless you are
certain the lifting device has sufficient capacity.
C. Never allow the equipment to swing while suspended.
D. Be certain the supporting structure is adequate to
handle the load.
3. DEADLY EXHAUST GAS - Exhaust fumes from any
internal combustion engine contain carbon monoxide, an
odorless and deadly gas that must be mixed with fresh
air.
A. Operate only in well ventilated areas.
B. Never operate indoors.
C. Never operate the unit in such a way as to allow
exhaust gases to seep back into closed rooms (i.e.
through windows, walls or floors).
8. TOWING THE EQUIPMENT - When towing this
equipment always use a vehicle large enough for safe
operation.
A. Never tow without the safety chains secured.
B. Always use the proper size hitch ball on the vehicle.
C. Never attempt to tow with a vehicle that does not have
side mirrors installed.
Page 1
SPECIFICATIONS
UNPACKING
GENERATOR SPECIFICATIONS
MDS50R3/B
KILOWATT40 kW
KILOVOLT-AMPS (.8 PF)50 KVA
AMPERAGE277/480 VOLT 3 PHASE 60 AMPS*
120/240 VOLT 3 PHASE 120 AMPS*
120/208 VOLT 3 PHASE 138 AMPS*
120/240 VOLT 1 PHASE 166 AMPS
*Based on .8 power factor at 130 degrees C.
Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).
GENERATOR RESISTANCE
MDS50R3/B
Main Stator 0.085 ohms
Main Rotor 3.2 ohms
Exciter Stator 0.35 ohms
Exciter Rotor 25 ohms
Exciter Voltage (F1-F2)
No Load 9.5 VDC
Full Load 36 VDC
Exciter Amperage (F1-F2)
No Load 0.4 Amps
Full Load 1.3 Amps
When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If
you have questions, contact your local authorized dealer.
If you see evidence of loss or damage at the time of
delivery, have the driver sign and describe the loss or
damage in the “memo of loss or damage” section on the
freight bill. Then contact the carrier to get instructions on
filing a claim.
When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any damaged material and contact the carrier for proper procedures to file a “concealed damage” claim.
OIL REQUIREMENTS
This engine was filled at the factory with John Deere
Engine Break-In Oil. This break-in oil should be drained
and the oil filter changed after the first 100 hours of
operation.
During the break-in period, add John Deere Engine
Break-In Oil as needed to maintain the specified oil level.
A second 100-hour service interval with John Deere
Engine Break-In Oil may be required if the engine is
operated under light loads during the first 100 hours.
ENGINE SPECIFICATIONS
See John Deere Operation and Maintenance Manual for
complete engine specifications.
NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator
manual for specific maintenance and care information
regarding the engine. Read ALL instructions in the
manuals provided before attempting to operate the
generator set.
After the break-in period, use John Deere Torq-Grad
Supreme Plus-50 or other heavy -duty diesel engine oil
as recommended in the John Deere Engine manual. See
your engine operator's manual for recommended oil
grades and types under different operating temperatures.
OIL QUANTITYUS Qt. Liters
MDS50R3/B 9.0 8.5
FUEL REQUIREMENTS
See your engine operator's manual for complete type and
grade fuel information.
Filling the Fuel Tank
Standard Trailer - The standard trailer is equipped with a
single 80 gallon fuel tank. Use caution when filling the
tank not to overflow the tank into the trailer.
WARNING PERSONAL DANGER
Never refuel a running engine,. Always stop the engine
and allow to cool before refueling.
Never allow the fuel tank to run completely empty, as air
may enter the fuel system making it necessary to bleed
the engine when restarting.
Page 2
COOLANT REQUIREMENTS
The cooling system of this engine has been filled at the
factory with a 50% water and 50% ethylene-glycol
antifreeze and the proper amount of supplemental
coolant additives. This mixture provides protection to -37
degrees F.
When replenishing coolant or changing coolant refer to
your John Deere engine manual for the proper type and
mixture of water, antifreeze and supplemental coolant
additives.
WARNING: EQUIPMENT DAMAGE
Failure to properly follow John Deere’s requirements for
antifreeze and supplemental coolant additives can lead to
permanent damage to your engine cylinder liner walls.
COOLANT QUANTITYUS GalLiters
MDS50R3/B 6.67 25.3
BATTERY CONNECTION INSTRUCTIONS
The MDS50R3/B requires a customer supplied 12 volt
group 27 battery with minimum 675 CCA. A battery
mounting kit has been supplied loose with the unit. When
connecting the battery, ALWAYS CONNECT THE
POSITIVE CABLE FIRST and THE NEGATIVE CABLE
LAST! Disconnecting the battery is done in reverse,
disconnecting the negative cable first and then the
positive cable.
WARNING - POTENTIAL BATTERY EXPLOSION
THIS UNIT USES A NEGATIVE GROUND. CONNECTING THE NEGATIVE CABLE FIRST MAKES THE
BATTERY POSITIVE TERMINAL HOT. CONNECTING
THE POSITIVE CABLE LAST MAY RESULT IN ACCIDENTAL SHORT CIRCUIT OF THE POSITIVE BATTERY TERMINAL TO ANY OF THE SURROUNDING
METAL SURFACES. (I.E. DROPPING A TOOL,
WRENCH SWING ETC.) USE EXTREME CAUTION
WHENEVER MAKING OR BREAKING THE BATTERY
CONNECTIONS AND FOLLOW THE CORRECT
SEQUENCE CAREFULLY.
WARNING! EQUIPMENT DAMAGE
FAILURE TO PUT THE ENGINE CONTROL SWITCH IN
THE ‘OFF’ POSITION PRIOR TO CONNECTING THE
BATTERY CABLE(S) MAY RESULT IN DAMAGE TO
THE ECM. (SOLID STATE ENGINE CONTROL MODULE).
NEVER ATTEMPT TO JUMP START THIS ENGINE.
If the battery should accidentally become discharged
disconnect the battery cables and recharge the battery
before attempting to start the unit. Boost/jump starting
this unit improperly will result in PERMANENT DAMAGE
TO THE ENGINE CONTROL MODULE (ECM).
DESCRIPTION AND IDENTIFICATION
A. FRONT PANEL
1. Starting Controls (1)- This unit is equipped for
manual key start only. A three position key switch controls
the engine starting.
Page 3
a. “OFF” - This switch position stops the engine and
disconnects the power to the engine controls. It is intended to safely allow service and maintenance checks
on the engine
b. “RUN” - This switch position engages the ignition
circuitry on the engine and powers up the engine control
panel and the engine sensors.
c.“START” - When the switch is rotated to this
position the starter will engage, starting the engine. When
the switch is released, it is spring loaded back to the run
position.
2. Murphy Switchgauge (2) - The switchgauge will
shut down the engine in case of low oil pressure or high
water temperature. When starting the unit the button on
the switchgauge must be depress as the key switch is
rotated to the start position. It is released after the engine
builds oil pressure.
3. DC Control Circuit Breaker (DCCB)(3)- The 15
amp DC Circuit Breaker protects the engine control and
the engine ignition circuit against faults in wiring or control
equipment.
lected, the switch may be locked to prevent it from
accidentally being changed during operation. Three
output voltage combinations are available with this
selector switch:
4. Engine Instruments
a. Oil pressure monitor gauge (OPG) (4)- The oil
pressure gauge is mounted on the front control panel and
indicates the engine oil pressure. The gauge serves a
dual function. In addition to displaying the oil pressure it
also provides the shutdown signal to the switchgauge if
the pressure should drop too low. The shutdown signal is
factory preset at 15 psi (103 kPa/m sq).
b. Coolant temperature monitor gauge (CTG) (5)-
The coolant temperature gauge indicates engine coolant
temperature. The gauge serves a dual function. In
addition to displaying the water temperature it also
provides the shutdown signal to the switchgauge if the
water temperature gets too high. The shutdown signal is
preset to operate at 225 f (407 k)
c.Battery Voltage Meter (6)- This DC voltmeter
monitors the VOLTAGE of the battery under static (at
rest) conditions, and under cranking and charging
conditions. The voltmeter indicates not only the condition
of the charging system, but also indicates the battery
reserve under cranking load in cold weather.
d. Running Time Meter (7)- This DC meter records
the total hours the engine has run.
1. 120/240 Three Phase* (series Delta
configuration)
2. 120/208 Three Phase (Low or Parallel “WYE”
configuration)
3. 277/480 Three Phase (High or series “WYE”
configuration)
*This selector position is also used for single phase 120/
240 output by using only the L1 and L2 leads. The three
phase L3 output lead is the “wild” leg in the delta configuration.
6. AC Generator Instruments
a. VM/AM Selector Switch (11)- This selector switch
allows you to check the amperage being drawn from
each generator leg and your line to line voltage.
b. AC Voltmeter (VM) (12)- Monitors generator
output line to line voltage, for all voltage operations.
c.AC Ammeter (AM) (13)- Monitors the amperage
that is being drawn from each leg of the generator.
d. AC Frequency Meter (14)- Monitors the generator
frequency.
5. AC Generator Controls
a. Voltage adjust rheostat (8)- Controls the output
voltage of the generator by varying voltage regulators
reference voltage.
b. Field circuit breaker (FCB) (9)- Protects voltage
regulator and exciter field in the event of a load short
circuit or equipment malfunction.
c.Voltage selector power switch (10)- This heavy
duty three position switch allows the operator to quickly
and safely reconnect the 12 lead generator to any one of
three output voltages. Once the output voltage is se-
Page 4
7. Panel Light (15) (16) - A panel light is provided for
your convenience. It is activated by the panel light switch.
B. RECEPTACLES and CIRCUIT
BREAKERS
1. 120 Volt 20 Amp Ground Fault Interupter Duplex. This
duplex receptacle is protected by a 20 Amp circuit
breaker mounted just above the duplex. With the “T” slot
design both 15 and 20 amp 120 volt cords can be
plugged in.
2. 120 Volt 20 Amp 3 wire twist lock, NEMA Spec L5-
20. This twistlock receptacle is also protected by a 20
Amp circuit breaker. This receptacle is wired in series
with the GFCI receptacle which provides it with GFCI
protection.
3. 240 Volt 20 Amp 3 wire twist lock, NEMA Spec L6-
20. This twistlock receptacle is protected by a two pole
240 volt circuit breaker.
4. 120/240 Volt 50 Amp 4 wire twistlock. This receptacle
is rated for dual voltage, 120 or 240 volt use. It is a four
wire receptacle, with a center grounding pin. Four wire
drop cords plugged into this receptacle may be split into
120 volt receptacles at a distribution box. This receptacle
is protected by a two pole 50 amp circuit breaker mounted
just above it. THIS RECEPTACLE UTILIZES A SPECIAL
HUBBELL PLUG. (HUBBELL PART NUMBER “CS
6365”.)
C. FULL POWER LOAD CONNECTIONS and
BREAKERS
This Mobile Diesel Power System is equipped with both
high voltage (480) and low voltage (208/240) main line
breakers. The breakers are interlocked with a lockable
bar to insure that only one breaker can be turned on at a
time.
2. Description - The Basler model VR63-4C voltage
regulator is a completely encapsulated unit. The regulator
controls the DC exciter field voltage on brushless generators to regulate the output voltage. Regulation is provided
by sensing the generator output voltage, converting it to
a DC signal and comparing the signal to a reference
voltage signal. An error signal is developed and used to
control the DC field power in order to maintain a constant
generator output.
3. Operation of Voltage Regulator - The voltage
regulator has been installed in the Mobile Diesel Generator set and tested at the factory prior to shipment. No
additional setup is required when changing from one
voltage to another. The only adjustment required is to
fine tune the exact voltage you want using the voltage
adjustment rheostat located on the front panel. The
adjustment range is 10% of the nominal voltage.
Some minor changes must be made for 50 cycle operation. Refer to 50 Hz operation later in this section for
setup procedures.
a. During periods of operation at reduced speed use
the field circuit breaker to remove the power from the
regulator.
A full power output terminal block is provided. This
terminal block is located below the main power breakers
and is accessible through the access door located just
below the main line breakers. If this access door is
opened with the unit running a safety switch will disable
the 12 volt system shutting the unit down. This door must
remain closed and latched at all times during normal
operations.
DANGER: PERSONAL INJURY
This unit will start as soon as the door is closed if the
start switch is in the run position. Do not use the switch
on this door to shutdown a unit to connect to the full load
terminal block , this is a safety switch only.
E. VOLT/HERTZ VOLTAGE REGULATOR
The purpose of the voltage regulator is to maintain the
voltage output of the Generator Set within a specified
percentage of its rated output from no load to full load.
The voltage regulator controls the voltage output of the
main generator by regulating the amount of current
delivered to the exciter field.
1. Location -Access to the voltage regulator assembly
is gained by removing the control panel access door
located through the left rear housing door.
b. If the exciter field voltage exceeds 95 VDC, the
regulator senses over excitation and automatically
removes the field current after a time delay. This time
delay is inversely proportional to the magnitude of the
detected over voltage condition. At approximately 140
VDC, the field voltage is removed instantaneously.
Upon detection of over excitation and the resulting field
voltage shutdown, the regulator will not reset or return to
an operational condition until the generator output voltage
drops to less than 6 VAC for ten seconds (minimum). TO
ACCOMPLISH THIS ON A MOBILE DIESEL GENERATOR SET THE FIELD CIRCUIT BREAKER MUST BE
TURNED OFF FOR TEN SECONDS.
OPERATING THE UNIT
A. SELECTING THE CORRECT VOLTAGE
A variety of voltages are available from the three position
selector switch. The three basic connection patterns are,
Delta (120/240), Low or Parallel WYE (120/208), and High
WYE (277/480). Single phase 120/240 is available with
the switch in the 120/240 (Delta) position.
Before connecting this unit to a distribution panel or any
other loads, be sure you have the selector switch set for
the right voltage and locked. If you have any doubts as to
Page 5
the voltage in your area compare your incoming power or
load name plates to the voltage table below.
1. 120/240 Three Phase* (Delta/Series configuration) This configuration will produce the following line-to-line
and line-to-neutral voltage. In this selector switch position, all of the receptacles on the front panel are powered.
L1 - L2 - L3 240 Volts three phase
L1 - L2 240 volts single phase
L2 - L3 240 volts single phase
L1 - L3 240 volts single phase
L1 - N 120 Volts
L2 - N 120 Volts
L3 - N 208 volts
*This selector position is also used for single phase120/240 output, using only the L1 and L2 leads. The
L3 three phase output lead is the “wild” leg in the delta
configuration and is used only for three phase loads.
B. STARTUP CHECKLIST
Before initial start up and each subsequent start complete
the following checklist:
1.Check oil level, refill with proper grade oil.
2.Check coolant level, refill with proper mixture of
coolant. See engine manual.
3.Check for loose bolts or hardware.
4.Check tire pressure. (35 psi)
5.Trailer level to within 15 degrees.
6.Battery securely fastened, connection clean and
tight, and proper fluid level.
7.Fuel tank filled with the proper grade of diesel
fuel.
8.Check the fan belt for tightness and excessive
wear.
9.Check hoses and clamps for leakage.
10.Check the air cleaner indicator. Service only
when indicated. Do not over-service.
11.Clean out dust cup on the air cleaner.
2. 120/208 Three Phase (Low/Parallel WYE configuration) This configuration will produce the following line-toline and line-to-neutral voltage. Use of this selector
switch position allows utilization of the 120 volt receptacle
only. The 240 volt receptacles cannot be used as the
voltage at them will be 208 volts, the line to line voltage.
L1 - L2 - L3 208 Volts three phase
L1 - L2 208 volts single phase
L2 - L3 208 volts single phase
L1 - L3 208 volts single phase
L1 - N 120 Volts
L2 - N 120 Volts
L3 - N 120 volts
3. 277/480 Three Phase (High/Series WYE configuration) This configuration will produce the following line-toline and line-to-neutral outputs. The 120 volt receptacles
are the only panel receptacles powered in this voltage
configuration. They are limited to 12 Amps total.
L1 - L2 - L3 480 Volts three phase
L1 - L2 480 volts single phase
L2 - L3 480 volts single phase
L1 - L3 480 volts single phase
L1 - N 277 Volts
L2 - N 277 Volts
L3 - N 277 volts
After you have selected the correct voltage for your
application and locked the selector switch, do the same
with the main line circuit breakers. Be sure to secure the
lock bar in place. This will prevent the incorrect breaker
from being turned on.
C. STARTING
CAUTION: EQUIPMENT DAMAGE
DO NOT ATTEMPT TO JUMP/BOOST START THIS
UNIT. TURN THE DC BREAKER “OFF” AND RECHARGE THE BATTERY WITH A BATTERY
CHARGER.
1. Select the desired voltage on the voltage selector
switch and lock in place.
2. Turn off both main line circuit breakers.
3. Rotate the start switch to the “run” position. In this
position without the engine running the safety latching
relay will pop out.
4. While depressing the safety latching relay, rotate the
start switch to the start position. This will engage the
starter and the fuel solenoid allowing the engine to
start.
5. As the engine starts release the start switch but keep
the safety latching relay depressed. This will allow
the spring loaded start switch to return to the run
position.
6. After the engine has built up at least 15 psi of oil
pressure, you can release the safety latching relay. If
you release the safety latching relay before the
engine has built oil pressure, the button will pop out,
shutting the engine back down.
7. After the engine is running at proper speed, adjust the
voltage to the desired level using the external voltage
rheostat.
8. Turn on the proper main line breaker (either high or
low voltage) and padlock the lock bar to prevent the
incorrect breaker from being turned on.
9. To stop the unit simply turn the start switch to the off
position. This will disconnect the 12 Volt DC to the
fuel solenoid shutting the unit down.
Page 6
D. CONNECTING THE LOADS
50 CYCLE (HZ) OPERATION
There are two ways the loads may be connected to a
Mobile Diesel Generator.
1. FRONT PANEL - A variety of receptacles have been
provided for your convenience on the front panel. The
120 volt receptacles are powered when the voltage
selector switch is in the 120/240 or 120/208 volt position.
The 240 volt receptacles (although powered in both
positions) are only usable in the 120/240 volt position. In
the 120/208 volt position the 240 volt receptacles have
only 208 volts at them.
2. FULL POWER LOAD CONNECTION TERMINALBLOCK - For remote connections and connecting load
distribution boxes, heavy duty terminal blocks have been
provided. These terminal blocks are located behind the
access door on the side of the unit, just below the main
line circuit breakers. This access door has a safety switch
installed on it and cannot be open while the engine is
running. Opening this door with the engine running will
cause the safety latching relay to trip, shutting the unit
down. The neutral and ground are bonded together at this
panel. For use with an isolated neutral, remove the
jumper strap between the neutral connection block and
the ground lug. This will isolate the neutral from the
ground and allow you single point grounding at a distribution panel. When using these terminal blocks be sure to
use wire rated large enough to carry your full load or the
full rated load of the generator.
WARNING - EQUIPMENT DAMAGE
FAILURE TO PROPER TIGHTEN THESE TERMINAL
LUGS CAN AND WILL CAUSE DAMAGE TO BOTH
THE TERMINAL BLOCK AND THE GENERATOR. IF
NOT PROPERLY TIGHTENED THESE LUGS CAN
START TO ARC INTERNALLY CAUSING DAMAGE TO
THE TERMINAL LUGS AND GENERATOR DAMAGE.
3. GROUNDING THE UNIT - To comply with current
safety standards this generator set must be properly
grounded. Ground the Mobile Diesel Generator set by
driving an 8 ft. copper ground rod into the earth. Then
connect a #4 AWG ground cable from the grounding lug
on the generator to the ground rod.
With a couple of minor changes these Mobile Diesel
Generators are capable of producing 50 Hz power. Two
changes must be made.
A. The engine must be reduced to 1500 RPM governed
speed. Consult your local John Deere Service Center for
the proper procedure for reducing the engine speed and
setting up the governor to operate at 1500 RPM.
B. The automatic volt/hertz regulator must also be reset
to operate at 50 HZ instead of the standard 60 HZ. This
is done by cutting the two leads marked HZ that come
out of the regulator. This will change the regulator for 60
HZ operation to 50 HZ operation. If it should become
necessary to change it back to 60 HZ, you would need to
splice the leads together again.
MAINTENANCE
The ultimate aim of a preventive maintenance program is
to maintain the equipment in optimum condition, either in
service or ready for service, for the maximum amount of
time during the useful life of the equipment. The detection of faults before they develop into major sources of
difficulty will decrease the incidence of repair. To this
end, a regular schedule of cleaning and inspection will go
far toward assuring trouble-free operation. Personnel
responsible for maintenance should set up a schedule for
inspection, and cleaning at intervals calculated to keep
the equipment in good condition. In making up a schedule, keep the following in mind:
A. New equipment must be carefully monitored until
extended operation has demonstrated that it is performing satisfactorily.
B. Old equipment requires more frequent inspection
(and possibly servicing) than similar equipment that has
seen less service.
C. Time spent in cleaning, inspecting and correcting
minor defects before they become major troubles means
time saved in overhaul and repair.
F. UNIT STORAGE
Certain precautions must be taken if a Mobile Diesel
Generator set is to be stored for a long period of time.
The unit must be stored in a dry location to prevent the
generator winding from drawing moisture. The unit should
also be thoroughly cleaned prior to storage.
For engine storage procedures consult your local John
Deere engine dealer. They have certain procedures that
must be followed in order to prevent engine damage, i.e.
cylinder rust and injector deterioration.
Page 7
PREVENTIVE MAINTENANCE
A. Daily Maintenance Checklist
** Oil level is between the “L” low mark and the “H” high
mark on the dipstick.
** Fuel tank full of proper grade of diesel fuel.
** Water and sediment drained from water separator.
** Radiator filled with the proper coolant mixture.
** Check air cleaner service indicator. Change the filter
element when the red indicator flag is at the raised
position
** Inspect for any fluid leaks
** Look for any loose or damaged parts
** Check belts for cracks or frays
** Check trailer hitch and safety chains for fitness
** Check tires for proper pressure
** Battery for proper fluid level.
** Check the generator control panel for loose or dam-
aged parts.
** Check the unit for general appearance and cleanliness.
Page 8
WINCO, INC.
12 Month Limited Warranty
WINCO, Incorporated warrants to the original purchaser for 12 months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such
goods are installed, operated and maintained in accordance with Winco written instructions.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall
be limited to the repair of the product. At WINCO’s option, material found to be defective in
material or workmanship under normal use and service will be repaired or replaced. For
warranty service, return the product within 12 months from the date of purchase, transportation charges prepaid, to your nearest WINCO Authorized Service Center or to WINCO, Inc.
at Le Center Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY.
To the extent permitted by law, any and all warranties, including those of merchantability and
fitness for a particular purpose, are limited to 12 months from date of purchase. In no event
is WINCO liable for incidental or consequential damages.
Note: Some states do not allow limitation on the duration of implied warranty and some
states do no allow the exclusion or limitation of incidental or consequential damages, so the
above limitations may not apply in every instance. This warranty gives you specific legal
rights which may vary from state to state.
WINCO reserves the right to change or improve its products without incurring any obligations
to make such changes or improvement on products purchased previously.
EXCLUSIONS:
WINCO does not warrant engines, batteries, or other component parts that are warranted by
their respective manufacturers.
WINCO does not warrant modifications or alterations which were not made by the WINCO,
Inc.
WINCO does not warrant products which have been subjected to misuse and/or negligence
or have been involved in an accident.
Page 9
DC ELECTRICAL SCHEMATIC
Page 10
RECEPTACLE PANEL WIRING
CIRCUIT BREAKER PANEL
Page 11
AC SCHEMATIC
Page 12
AC WIRING DIAGRAM
Page 13
P/N 60706-137
225 South Cordova Avenue
Le Center, Minnesota 56057
1-507-357-6821
8300-10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.