Read and understand all instructions in the manual
before starting and operating the generator set.
USING THIS MANUAL
Congratulations on your choice of a Winco generator set.
You have selected a high-quality, precision-engineered
generator set designed and tested to give you years of
satisfactory portable service.
To get the best performance from your new engine
generator set, it is important that you carefully read and follow
the operating instructions in this manual.
Should you experience a problem please follow the
“Things To Check” near the end of this manual. The warranty
listed in this manual describes what you can expect from
WINCO should you need service assistance in the future.
You must be sure your new engine generator set is:
*Properly serviced before starting
*Operated in a well ventilated area
*Exhaust gases are dispersed safely
*Wired by a qualified electrician
*Operated only for its designed purposes
*Used only by operators who understand its operation
*Properly maintained
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as
yours. It is important that you record the number and other
vital information here, if you should ever need to contact us
on this unit it will help us to respond to your needs faster.
MODEL____________________________________
TABLE OF CONTENTS
INTRODUCTIONi
FEATURES BY MODEL TABLE1
GUIDE TO PRODUCT SAFETY2
BASIC INFORMATION
Intended Uses3
Restricted Uses3
Unit Capabilities3
PREPARING THE UNIT4
Unpacking the unit4
Unit Preparation4
LP/NG Installation4
Battery Installation6
Low Oil Shutdown6
Automatic Idle7
BASIC OPERATION7
Starting7
Starting Hints8
Stopping And Storage8
Operating Speed8
Connecting The Load9
INSTALLATION GUIDELINES9
Wiring9
OPERATOR CARE AND MAINTENANCE10
Engine Care10
Generator Care10
Cleaning11
Things To Check BEFORE
You Call For Service11
24 MONTH WARRANTY13
SERIAL NUMBER____________________________
PURCHASE DATE____________________________
DEALER___________________________________
PROPER USE AND INSTALLATION
Page 3
HD15000KEKOHLERGASOLINE1 YEAR12 GAL YES NO NO NONO
This engine generator set has been designed and
manufactured to allow safe, reliable performance. Poor
maintenance, improper or careless use can result in
potential deadly hazards; from electrical shock, exhaust gas
asphyxiation, or fire. Please read all safety instructions
carefully before installation or use. Keep these instructions
handy for future reference. Take special note and follow all
warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
______________________________________________________
DANGER:
DANGER indicates an imminently hazardous situation which,
if not avoided, will result in death or serious injury. This signal
word is to be limited to the most extreme situations.
______________________________________________________
______________________________________________________
WARNING:
WARNING indicates a potentially hazardous situation which,
if not avoided, could result in death or serious injury.
______________________________________________________
______________________________________________________
CAUTION:
CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
______________________________________________________
NOTE:
CAUTION is also used on the unit labels and in this
manual to indicate a situation that could result in serious
damage or destruction of the equipment and possible
personal injury.
______________________________________________________
1.ELECTRIC SHOCK- The output voltage present in this
equipment can cause a fatal electric shock. This equipment
must be operated by a responsible person.
a.Do not allow anyone to operate the generator
without proper instruction.
b.Guard against electric shock.
c.Avoid contact with live terminals or receptacles.
d.Use extreme care if operating this unit in rain or
snow.
e.Use only three-prong grounded plugs and
extension cords.
f.Be sure the unit is properly grounded to an
external ground rod driven into the earth.
2.FIRE HAZARD- Gasoline and other fuels always present a
hazard of possible explosion and/or fire.
a.Do not refuel when the engine is running or hot.
Allow the engine to cool at least two minutes before
refueling.
b.Keep fuel containers out of reach of children.
c.Do not smoke or use open flame near the
generator set or fuel tank.
d.Keep a fire extinguisher nearby and know its
proper use. Fire extinguishers rated ABC by
NFPA are appropriate.
e.Store fuel only in an approved container, and
only in a well-ventilated area.
3.DEADLY EXHAUST GAS - Exhaust fumes from any
gasoline engine contain carbon monoxide, an invisible,
odorless and deadly gas that must be mixed with fresh air.
a.Operate only in well ventilated areas.
b.Never operate indoors.
c.Never operate the unit in such a way as to
allow exhaust gases to seep back into closed
rooms (i.e. through windows, walls or floors).
4.NOISE HAZARD - Excessive noise is not only tiring, but
continual exposure can lead to loss of hearing.
a.Use hearing protection equipment when
working around this equipment for long periods
of time.
b.Keep your neighbors in mind when
permanently installing this equipment.
5.CLEANLINESS- Keep the generator and surrounding
area clean.
a.Remove all grease, ice, snow or materials that
create slippery conditions around the unit.
b.Remove any rags or other material that could
create potential fire hazards.
c.Carefully wipe up any gas or oil spills before
starting the unit.
d.Never allow leaves or other flammable
material tobuild up around the engine exhaust
area.
6.SERVICING EQUIPMENT- All service, including the
installation or replacement of service parts, should be
performed only by a qualified technician.
a.Use only factory approved repair parts.
b.Do not work on this equipment when
fatigued.
c.Never remove the protective guards, cover, or
receptacle panels while the engine is running.
d.Use extreme caution when working on
electrical components. High output voltages from
this equipment can cause serious injury or death.
e.Always avoid hot mufflers, exhaust manifolds,
and engine parts. They all can cause severe
burns instantly.
f.Installing a home-standby generator is not a
“do-it-yourself” project. Consult a qualified,
licensed electrician or contractor. The
installation must comply with all national, state,
and local codes.
INTENDED USES
These engine generator sets have been designed primarily
for portable use. Both 120 and 240 volt AC receptacles are
provided in the 'control panel' to plug in your loads (lights,
portable tools, and small appliances). These units are
dual wound generators, therefore the 120 Volt loads must
be equally split with 1/2 of the rated capacity available on
each of the two 120 Volt circuits. See unit capabilities for
further explanation.
WINCO PORTABLE SERIES
Page 260706-113
Page 5
BASIC INFORMATION
These portable units require large quantities of fresh air for
cooling of both the engine and the generator. Fresh air is
drawn from both the engine end and the generator end and
is exhausted at the center of the unit. For safety, long life
and adequate performance, these units should never be
run in small compartments without positive fresh air flow.
RESTRICTED USES
DO NOT remove from the cradle assembly. Removal of the
generator from the cradle assembly may cause excessive
vibration and damage to the engine generator set.
DO NOT install and operate these portable generators in a
small compartment., i.e. generator compartment of
vehicles, motor homes or travel trailers. These
compartments will not allow enough free flow fresh air to
reach the engine generator set for cooling and will cause
the unit to overheat, damaging both the engine and the
generator. Small compartments will also develop hot
spots where there is very little air flow and may cause a fire.
DO NOT attempt to operate at 50 cycles. These units are
designed and governed to operate at 60 Cycles only.
UNIT CAPABILITIES
Generator Connections
The diagram below represents a typical 4000 watt
generator. Receptacles A and B are the two 120 Volt
duplex receptacles. Up to 2000 watts at 120 volts (16.6
Amps) can be taken from the generator at each of the
receptacles. This generator produces 120 and 240 volt, 60
Hz (Hertz), AC (Alternating Current).
The WINCO High Performance series generators have the
EXTRA Heavy FULL POWER winding to allow the use of all
the power available from the engine at either 120 Volts, 240
Volts or any combination of the 120 or 240 volts. You are
not restricted to splitting up your large 120 Volt loads or
choosing to power them OR a 240 Volt load. There are no
switches or connectors to change. Simply plug in and use
the power without being concerned about overloading the
generator winding as long as the load doesn't exceed the
size of the generator.
Check the appliance or tool nameplates for the current and
voltage to insure compatibility. Remember that power
taken from receptacle C reduces the power available at
both A and B and vice versa.
Starting Electric Motors
Electric motors require much more current (amps) to start
them than to run them. Some motors, particularly low cost
split-phase motors, are very hard to start and require 5 to 7
times as much current to start them as to run them.
Capacitor motors are easier to start and usually require 2 to 4
times as much current to start them as to run them.
Repulsion Induction motors are the easiest to start and
usually require 1 1/2 to 2 1/2 times as much to start them as
to run them.
Most fractional horsepower motors take about the same
amount of current to run them whether they are of RepulsionInduction (RI), Capacitor (Cap), or Split-Phase (SP) type. The
chart below shows the approximate current required to start
and run various types and sizes of 120 volt 60 cycle electric
motors under average load conditions.
RUNNING STARTING AMPS
HP AMPS SPCAPRI
1/6 3.2 16 TO 22 6 TO 13 5 TO 8
1/4 4.5 22 TO 32 9 TO 18 7 TO 12
1/3 5.2 26 TO 3510 TO 21 8 TO 17
1/2 7.2 NOT MADE14 TO 2911 TO 18
113.0 NOT MADE26 TO 5220 TO 33
The figures given above are for an average load such as a
blower or fan. If the electric motor is connected to a hard
starting load such as an air compressor, it will require more
starting current. If it is connected to a light load, or no load
such as a power saw, it will require less starting current. The
exact requirement will also vary with the brand or design of
the motor.
Self-excited generators respond to severe overloading
differently than the power line. When overloaded, the engine
is not able to supply enough power to bring the electric motor
up to operating speed. The generator responds with high
initial starting current, but the engine speed drops sharply.
The overload may stall the engine. If allowed to operate at
very low speeds, the electric motor starting winding will burn
out in a short time. The generator winding might also be
damaged.
CAUTION: EQUIPMENT DAMAGE
RUNNING THE GENERATOR SET UNDER THESE
CONDITIONS MAY RESULT IN DAMAGING THE
GENERATOR STA TOR AS WELL AS THE MOTOR WINDING.
Because the heavy surge of current required for starting
motors is required for only an instant, the generator will not
be damaged if it can bring the motor up to speed in a few
seconds of time. If difficulty is experienced in starting motors,
turn all other electrical loads off and if possible reduce the
load on the electric motor.
UNPACKING
CAUTION: EQUIPMENT DAMAGE
THIS UNIT HAS BEEN SHIPPED WITHOUT OIL. Failure to
maintain the engine oil at the proper level will result in serious
engine damage.
When you unpack your new ENGINE GENERATOR be sure to
remove all the information sheets and manuals from the
carton.
Page 360706-113
WINCO PORTABLE SERIES
Page 6
PREPARING THE UNIT
1.This generator set was in good order when shipped.
Inspect the power plant promptly after receiving it. If
damage is noted, notify the transportation company
immediately, request proper procedures for filing a
“concealed damage” claim. Title to the equipment and
responsibility for filing a claim rests with you when a
generator is sent F.O.B. shipping point. Only you can
legally file a claim.
2.Before proceeding with the preparation of your new
engine generator set for operation, take a couple of
minutes to insure that the unit you have received is the
correct model and review the specification pages in this
manual to insure that this unit fits your job requirements.
3.After removing the engine generator from the carton
locate and remove the shipping strap attached to the
generator shock mount. See attached tag for removal
instructions.
UNIT PREPARATION
Before your engine generator was shipped from our factory it
was fully checked for performance. The generator was load
tested to its full capacity, and the voltage and frequency were
carefully checked and adjusted.
LUBRICATION
Before starting the engine, fill the crankcase to the proper
level with a good quality oil. The recommended grade of oil
and quantity of oil required is listed in the engine operator's
manual shipped with our unit. The necessity of using the
correct oil, and keeping the crankcase full cannot be
overemphasized. Engine failures resulting from inadequate
or improper lubricant are considered abuse and are not
covered by the generator or the engine manufacturer's
warranty.
GASOLINE FUEL
Always use a good grade of unleaded fuel. Leaded gasoline
may be used if unleaded is not available. Gasoline
containing alcohol, such as gasohol is not recommended.
However, if gasoline with alcohol is used, it must not contain
more than 10 percent Ethanol and must be removed from the
engine during storage. DO NOT use gasoline containing
methanol. Always insure that the fuel is clean and free of all
impurities.
burn properly. The use of a fuel additive, such as STA-BIL,
or an equivalent will minimize the formation of fuel gum
deposits. If a unit has been out of operation for an
extended period of time it is best to drain old fuel from the
fuel tank and replace with fresh fuel before attempting to
start.
LP/NG FUEL INSTALLATION
The information in this instruction is offered to assist you in
providing the proper vapor fuel supply for your engine. This
information is only provided to advise you of the engine’s
requirements and the decisions you must make. In no
case should this information be interpreted to conflict with
any local, state or national code. If in doubt, always follow
local codes.
DANGER: FIRE - PERSONAL INJURY -
All fuel lines must be installed by qualified fuel
supplier.
LOCATION
The engine-generator models covered in this manual were
designed for portable use. DO NOT INSTALL OR OPERATETHESE UNITS INDOORS. The unit should be stored in a dry
location. During a power outage move the unit outdoors to
a flat dry location such as a driveway, concrete pad or
sidewalk for use. We recommend installing the optional
dolly kit or equivalent for ease of handling.
The fuel source should be as close as possible to the
outdoor operating location. This will reduce the installation
cost of fuel runs. Connect the fuel supply line to the inlet of
the fuel demand regulator on the unit using a locally
approved flexible fuel line (see table for recommended line
size). The pressure supplied to the demand regulator
MUST BE FOUR TO SIX OUNCES or 7 to 11 INCHES
W.C.(water column). The primary regulator at the fuel
supply must be capable of delivering the proper volume of
fuel at this pressure.
Have your local fuel supplier install a protected fuel
connection at the outside operating location. He should
also install a lockable fuel shutoff valve at the connection
point. Have your fuel supplier permanently install a flexible
fuel line to the demand regulator on the engine generator
set.
INSTALLING THE FUEL LINE
DIESEL FUEL
ASTM No.2 diesel fuel is recommended for these engines.
The use of No. 2 diesel fuel will result in optimum engine
performance. The use of a lighter fuel will reduce fuel
economy. See your engine operators manual for complete
fuel information.
WARNING: FIRE DANGER
Gasoline, diesel fuel and its fumes are VERY explosive
when proper precautions are not taken.
Never use fuel that has been stored for an extended
period of time as the fuel will lose it's volatile properties and
you will be left with only the varnish residue. This varnish like
substance will clog the carburetor or injectors and will not
WINCO PORTABLE SERIES
DANGER: PERSONAL INJURY
Units that are intended to be run unattended MUST have an
electric fuel solenoid installed. This solenoid MUST be
wired to AUTOMATICALLY turn off the fuel whenever the
engine stops. Request instruction sheet 60714-009 from
your dealer for additional information.
Unit location will determine the size of fuel line that is
required to supply the engine with a constant fuel pressure.
Refer to the tables below for fuel line size, and
recommended tank size. For distances of 100 feet and
over, a two regulator fuel system consisting of a primary 1015# regulator at the tank and a 6 ounce secondary
regulator installed close to the engine-generator set. When
a two (2) stage regulator system is used, a fuel line size of
3/8 inch is generally adequate for distances up to 300 feet.
Page 460706-113
Page 7
PREPARING THE UNIT
The line size from the table below applies to the distance
from the second regulator to the demand regulator. A
positive fuel shut-off device must be installed in the fuel line
close to the engine generator set. This may be either a
lockable manual shut-off valve available from your local fuel
installer, or a 12 volt DC fuel solenoid valve. This optional
12 volt DC valve is available through your local Winco dealer
as part number 42942-000.
The fuel line used to connect the supply line to the demand
regulator must be a locally approved flexible fuel line.
Products used will vary in different regions depending on
availability and local codes. Consult with your local fuel
supplier to insure complete compliance with ALL codes.
1. Remove the pipe plug from the demand
regulator.
2. Connect the flex fuel line to the demand
regulator.
Remember that whichever fuel delivery system or type of
vapor fuel used, the fuel pressure at the demand regulator
installed on the engine generator must be between 4 and 6
oz (7-11 inches of water column). Any lower pressure and
the unit will starve for fuel under load. Any higher and the
unit will ‘flood’ when attempting to start.
LP TANK SIZING
Once above the minimum acceptable size, the size of L.P.
tank used will generally depend on how long you want the
unit to run without re-filling. The tank sizes shown below are
the smallest recommended tank sizes based on the outside
temperature. Keep in mind the colder it gets the slower L.P.
will vaporize. This is the reason for the larger tanks at low
temperature. Minimum sizing is not based on running time.
DANGER: PERSONAL INJURY
Do not use galvanized pipe in the fuel line runs. The
galvanized coating will become eroded and flake off,
causing possible obstruction or damage to the regulator or
fuel valve. The obstruction could cause an inoperative
engine or an explosive fuel leak.
Size of pipe required for generators operating on natural
gas/LP gas.
*allow an additional 3 feet for each standard elbow. Do not
use ‘street ells’ (restrictive)
DANGER! - FIRE - PERSONAL INJURY -
Be careful when sealing gas joints. Excessive sealing
compound can be drawn into the solenoid, regulator or
carburetor causing an engine malfunction or dangerous fuel
leak.
FUEL PRESSURE
Correct fuel pressure cannot be stressed enough. The
most common cause for inoperative systems is an
inadequate or incorrect fuel pressure. Power and
performance of the engine is in direct relation to the
correctness of the fuel system. Shown below is a block
diagram of a typical L.P. or N.G. installation.
Reference numbers 1 through 4 in the block diagrams
above are fuel lines supplied by customer.
Reference number 5 is already installed on your engine
generator set.
CHANGING FUEL TYPES
These engine generator sets are designed to run on
three different fuels; gasoline, natural gas or LP vapor.
They may be easily changed from one fuel to another.
FROM GASOLINE TO LP/NG
1.With the engine running turn off the gasoline
fuel valve.
2.Run the engine until it runs out of fuel.
3.Remove the pipe plug from the demand
regulator.
4.Install locally approved flexible fuel line.
5.Connect the LP/NG vapor fuel line.
6.Turn on the vapor fuel.
7.Start the engine.
8.Apply the load to the generator.
9.Adjust the fuel mixture valve to smooth the
engine out.
Note: Operating on LP/NG vapor fuel for an extended period
of time without liquid fuel in the carburetor may damage the
carburetor float, and the needle seat assembly. If you plan
to convert back to gasoline, we recommend the float and
needle seat assembly be removed from the carburetor.
(Consult a local engine supplier for assistance.)
FROM LP/NG TO GASOLINE
1.With the engine running turn off the LP/NG fuel
supply.
2.Run the engine until it runs out of fuel.
3.Remove the flexible fuel line from the demand
regulator.
4.Reinstall the pipe plug in the regulator. (use
thread sealant sparingly)
5.Check to be sure the gasoline fuel valve is off.
6.Fill the gasoline fuel tank.
7.Turn on the gasoline fuel valve.
8.Start the engine.
9.Adjust the load jet on the carburetor as
required to smooth the engine out.
Page 560706-113
WINCO PORTABLE SERIES
Page 8
PREPARING THE UNIT
BATTERY INSTALLATION
All electric start engine generator sets are shipped with a
battery kit for customer installation. This kit consists of a
battery rack, battery tie down, battery cables, and instruction
sheet for installation. After installing the battery rack, file the
instruction sheet in the back of this manual for future
reference.
If you intend to use the power plant’s electric start system, you
will need to purchase and install a battery to operate it. Units
equipped with a recoil or rope start will operate satisfactorily
without a battery. A twelve volt battery, group U1 rated at 235
CCA or larger is recommended for this electric start engine
generator set. Follow the battery manufacturers
recommendations for servicing and charging prior to use.
Connect the battery to the electric start system using the
cables provided.
CAUTION: EQUIPMENT DAMAGE
feature is designed to prevent costly repairs and downtime.
This system uses a float in the engine crankcase to sense
the oil level. If a low oil level condition should occur during
operation, the float will ground out the magneto impulse,
“killing” the engine. In addition, there is an indicator light
mounted on the engine shroud near the recoil starter. This
light will blink on and off to indicate a low oil level condition
when you are attempting to start the unit. To get the engine
started, you must add the required amount of oil to the
engine crankcase.
Use of the float system on applications that are subject to
shock, bumping or severe angles of operation (in excess of
15 degrees) should be avoided. This is especially true if
an unexpected shutdown would cause a safety hazard or
serious inconvenience for the operator. To disable the
OILGARD, remove the wire attached to the sensor unit
mounted on the engine crankcase. The wire should be
insulated with a connector or tape.
These electric start engines are NEGATIVE GROUND. Use
extreme caution when connecting the battery. Connect the
NEGATIVE battery terminal to GROUND.
For your safety always connect the positive battery cable to the
“bat+” terminal first. Then connect the negative battery cable
to the “bat-” terminal. Make sure all connections are clean
and tight. Reverse the sequence when disconnecting,
disconnect the negative cable first. These engines produce
enough direct current to keep a battery charged under normal
operating conditions, but were not intended to be used as a
battery charger.
WARNING: PERSONAL INJURY
Lead acid batteries produce explosive hydrogen gas when
charging. Keep sparks, flames, and burning cigarettes away
from the battery. Ventilate the area when charging or using
the battery in an enclosed space. Lead acid batteries contain
sulfuric acid, which causes severe burns. If acid contacts
eyes, skin or clothing, flush well with water. For contact with
eyes, get immediate medical attention
Battery Charging
Units equipped with electric start have a small flywheel
charger built into the engine flywheel assembly for recharging
the starting battery. This flywheel charger generates a small
AC current that passes through a diode at the end of the
charging lead to produce a DC charging current of about 1
AMP. This circuit is not designed to be used as a battery
charging circuit to recharge dead batteries.
OPTIONAL DOLLY KIT
An optional dolly kit is available for most of these engine
generator sets. The dolly kit comes with instructions and
parts list. After installing the dolly kit, file the instructions and
parts list in the back of this manual for future reference.
LOW OIL LEVEL SHUTDOWN SYSTEM
All Winco Industrial generators are equipped standard with
low oil shutdown systems. The Honda, Kawasaki and Briggs
& Stratton IC engines all use a float switch system. This low
oil warning system will automatically stop the engine before
the oil level reaches an operational danger point. This
WINCO PORTABLE SERIES
The Yanmar diesel, Kohler Commander and the Briggs &
Stratton Vanguard all use a pressurized oil system. The oil
pressure is monitored by an oil pressure sensor mounted
on the engine. If the oil pressure gets low during operation
the engine ignition is grounded out and the engine will
shutdown. On the Yanmar the oil pressure sensor opens
the power feed to the run solenoid, allowing the fuel rack to
close shutting the engine down. If during starting the oil
system doesn’t build sufficient pressure to close the oil
sensor switch the engine will not continue to run. This can
be caused by a low oil level or by using the wrong grade of
oil for the ambient air temperature.
AUTOMATIC IDLE CONTROL
(HP Series Only)
The automatic idle control is a gas saving, solid state
system, designed to reduce engine speed whenever the
electrical load is removed from the generator. Without a
slow down control, the engine would run at full speed at all
times, regardless of the electrical load. With the automatic
idle control switch in the 'Auto' position, the throttle control
lever is electrically released when the load is turned on so
it in no way interferes with the normal governor operation.
When the load is turned off, the idle magnet energizes and
reduces the engine speed. It does not cause incorrect
operation of the carburetor or governor, but neither does it
correct them.
The automatic idle control consists of a solid state module
mounted in the generator end cover, a switch, resistor and
transformer located in the generator control box, and an
electromagnet mounted on the engine near the throttle
lever. The automatic idle control is only offered as a factory
installed feature. It is not available for field installation.
With the automatic idle switch in the “automatic”
position,the system operates as follows:
1. After the engine has been started, and no electrical
load is applied, the transformer senses and signals
the solid state module to turn ON the electromagnet.
This will pull and hold the throttle lever, closing the
throttle on the carburetor reducing the engine speed.
2. When a load is applied to the generator, the
transformer senses it and sends a signal to the solid
state module to turn off the electromagnet. This allows
Page 660706-113
Page 9
BASIC OPERATION
the throttle to release and allows the governor spring to
open the throttle. The engine will respond and come up
to the governed speed (3600 rpm).
3. When the electrical load is turned off, no power will
flow through the transformer, and as a result, the
automatic idle control will once again energize the
magnet, pulling and holding the throttle.
When the automatic idle switch is in the “off” position, the
engine will run at full governed speed regardless of the
generator load.
INITIAL START UP
Use the following checklist to verify the correct preparation of
the engine generator before starting.
Before Starting always Check:
1. Engine oil, fill as required with correct grade and
quantity.
2. Fuel level, fill as required with clean fresh fuel.
3. Automatic Idle is in the 'Off' position
4. Visually check for loose or broken parts.
STARTING
The throttle control on these generators is preset and locked
to operate at 3600 RPM (nominal) with no load speed set at
3690 RPM. Only a trained service technician should be
allowed to adjust this speed setting. See “Operating Speed”
section for additional information.
NOTICE: ENGINE
Theses units will not start if it is low on oil. The lubricating oil
level must be at the full mark before the engine will start.
MANUAL STARTING
Refer to the engine manual for additional starting, operating,
and stopping instructions.
NOTICE: TRI-FUEL STARTING
Tri-Fuel generators operating on vapor fuel, (either L.P. or
NG) must be started using the electric start system provided.
You cannot hand crank the unit fast enough to develop the
proper vacuum to make the vapor fuel system work. In
addition when starting on VAPOR FUEL NEVER USE THECHOKE. Use of the choke will prevent the air and fuel from
properly mixing.
1. Turn on the fuel supply.
2.For gasoline move the choke to the full "on"
position. A warm engine will require less choking
than a cold engine.
3. Grasp starter grip and pull slowly until starter
engages, then pull cord rapidly to overcome
compression, prevent kickback and start the
engine. Repeat if necessary.
4. When the engine starts, open the choke
gradually.
5. The engine should promptly come up to
operating speed.
ELECTRIC STARTING
If the engine is cold and stiff or if the battery is not fully
charged, starting can be made easier by slowly hand
cranking the engine through the compression stroke before
pushing the starter switch. This permits the starter to gain
momentum before the heavy load of the compression stroke
occurs. This minimizes the drain on the battery and
improves the possibility of starting under such adverse
conditions. Always keep the battery charged, especially
during cold weather operation.
1.Turn on the fuel supply.
2.For gasoline move the choke to the full "on"
position. A warm engine will require less choking
than a cold engine.
3.Engage the engine start switch briefly to the
START position. The starter life is improved by
using shorter starting cycles with time to cool off
between cranking cycles. Do not operate the starter
more than 15 seconds during each minute. Repeat
if necessary.
4.When the engine starts, open the choke
gradually.
5.The engine should promptly come up to
operating speed.
CAUTION: EQUIPMENT DAMAGE
Never permit the choke to remain on after the engine has
run for a short time. It is not necessary to choke the engine
when it is warm. Avoid over-choking.
STARTING HINTS
1.Cold weather
a.Use the proper oil for the temperature
expected.
b.Use fresh winter grade fuel. Winter grade
gasoline is blended to improve starting. Do
not use summer gasoline.
c.A slightly richer fuel mixture will usually
improve cold starting.
2.Hot weather
a.Use the proper oil for the temperature
expected.
b.Use only summer blended gasoline. Using
gasoline left over from winter may cause the
unit to vapor lock.
c.DO NOT over-choke the unit.
STOPPING AND STORAGE
1.Depress the stop switch.
2.Close the fuel shut-off valve. Always shut the
fuel off whenever the engine is stopped to prevent
fuel leakage from carburetor.
3.Before extended storage (over 30 days) certain
precautions must be taken to ensure the fuel
doesn’t deteriorate and clog the fuel system.
a.Remove the remaining fuel from the fuel
tank.
b.Start the engine and allow it to run until all
the fuel in the carburetor and the fuel lines
has been used up and the engine stops.
c.While the engine is warm, drain the oil and
refill with fresh oil.
d.Remove the spark plug, pour approximately
1/2 ounce (15 cc) of engine oil into the
cylinder and crank slowly to distribute oil.
Replace spark plug.
e.Clean dirt and chaff from cylinder,
cylinder head fins, blower housing, rotating
Page 760706-113
WINCO PORTABLE SERIES
Page 10
BASIC OPERATION
screen and muffler areas.
f.Store in a clean and dry area.
Note: The use of a fuel additive, such as STA-BIL, or an
equivalent, will minimize the formationof gum deposits
during storage. Such an additive may be added to gasoline
in theengine’s fuel tank or to gasoline in a storage
container.
OPERATING SPEED
The engine-generator must be run at the correct speed in
order to produce the proper electrical voltage and frequency.
CAUTION: EQUIPMENT DAMAGE
The output voltage should be checked to insure the generator
is working properly prior to connecting a load to the generator.
Failure to do so could result in damage to equipment plugged
into the unit and possible injury to the individual.
All engines have a tendency to slow down when a load is
applied. When the electrical load is connected to the
generator,the engine is more heavily loaded, and as a result
the speed drops slightly. This slight decrease in speed,
together with the voltage drop within the generator itself,
results in a slightly lower voltage when the generator is
loaded to its full capacity than when running no load. The
slight variation in speed also affects the frequency of the
output current. This frequency variation has no appreciable
effect in the operation of motors, lights and most appliances.
However, electronic equipment and clocks will be affected if
correct RPM is not maintained. See Load vs. Output chart.
Although individual units and models may vary slightly, the
normal voltage and frequency of the engine-generators
described in this book are approximately as follows, under
varying loads:
The speed of the engine was carefully adjusted at the factory
so that the generator produces the proper voltage and
frequency. For normal usage, the speed setting should not
be changed. If the generator is being run continuously on a
very light load, it is often advisable to lower the operating
speed slightly. Whenever making any speed adjustments
check the unit with a voltmeter or tachometer and be sure the
speed is correct.
Lower voltage may damage both the generator and any load
connected to it. Running the engine at excessively high
speeds results in high voltage, which may significantly
shorten the life of appliances being used.
Output voltage should be checked periodically to ensure
continued proper operation of the generating plant and
appliances. If the generator is not equipped with a voltmeter,
it can be checked with a portable meter. Frequency can be
checked by using an electric clock with a sweep second
hand. Timed against a wrist watch or a stop watch the clock
LOAD vs. OUTPUT
should be correct within +/- 2 seconds per minute.
CONNECTING THE LOADS
Applying The Load
Allow the engine to warm up for two or three minutes before
applying any load. This will allow the engine to reach
normal operating temperature and oil to circulate
throughout the engine. A short warm-up time will permit
the engine to work more efficiently when the load is applied
and will reduce the wear in the engine, extending its life.
Receptacles have been provided to allow loads to be
connected to the generator. The loads should be added
one at a time. If a large motor is being started or multiple
motors are being started, they should be started
individually and the largest should be started first.
CAUTION: EQUIPMENT OVERLOAD
Keep the generator load within the generator and
receptacle nameplate rating. Overloading may cause
damage to the generator and/or the loads .
Most electric tools and appliances will have the voltage and
amperage requirements on their individual nameplates.
When in doubt consult the manufacturer or a local
electrician. The nameplate amperage rating for electric
motors can be misleading. See “Starting Electric Motors” in
Unit Capabilities (page 3).
These engine generator sets are inherently self regulating
based on engine speed. The engine governor will
automatically adjust itself to the load. No harm to the
generator will result if it is operated with no load connected.
Proper utilization of the receptacles located on the control
panel is necessary to prevent damage to either the
receptacles or the generator. The generator is a limited
source of electrical power, therefore pay special attention to
the receptacle and generator ratings. The nameplate rating
can be obtained through a single receptacle as long as the
receptacle amperage rating is not exceeded.
Grounding
All units must be grounded. Drive a 3/4 or 1" copper pipe
or rod into the ground close to the engine-generator set.
The pipe must penetrate moist earth. Connect an
approved ground clamp, to the pipe. Run a no. 10 Awg wire
from clamp to the generator ground lug on the “receptacle
panel”. Do not connect to a water pipe or to a ground used
by a radio system.
The engine-generators covered in this manual were
designed for portable use. DO NOT OPERATE INDOORS.
The unit should be stored in a warm dry location. Move the
unit outdoors to a flat dry location for use.
WIRING
Plug your tools such as drills, saws, blowers, sump pump
and other items to be powered directly into the generator
receptacles. Before plugging in all the tools and cord sets,
recheck the rating of the generator set. Be sure it can
handle the intended load and is compatible with the
voltage, phase, and current ratings.
WINCO PORTABLE SERIES
Page 860706-113
Page 11
BASIC OPERATION
‘Hard Wiring’ this unit directly into a temporary construction
site electrical system is NOT A SIMPLE DO-IT-YOURSELF
JOB. For your safety all wiring must be done by a qualified
electrician and conform to the National Electric Code and
comply with all state and local codes and regulations.
Check with local authorities before proceeding.
during the outage to the emergency panel. Keep in
mind only a limited amount of amperage is available
from the generator set. Some circuit breakers may still
have to be turned off to prevent an overload on the
generator during the initial start up. See the nameplate
on your generator for the amperage capabilities of your
unit.
WARNING: PERSONAL DANGER
A fully isolated, double pole double throw manual transfer
switch must be installed any time a generator is being
connected to an existing distribution system.
1. These engine generator sets are designed for
portable heavy duty commercial use. Receptacles are
provided on the control panel to permit 120 and 240 volt
portable appliances and tools to be plugged directly into
them. Please note that the 3 wire 240 volt receptacle(s)
on these units are designed to power only 240 volt
tools. There are 2 hot and a ground wire, but no neutral
connection in the 3 wire 240 volt receptacle. Split 120/
240 volt ‘TemPower’ service requires the installation of
a 4 wire receptacle (2 hot, 1 ground, and 1 neutral).
Consult a licensed electrician for wiring the TemPower
plug and connecting it as temporary service.
To connect these units directly to an un-powered,
isolated construction site TemPower panel, have your
electrician select one of the following methods:
a.Wire the distribution panel directly to the
generator output using a fine strand (flexible) motor
lead wire. DO NOT by-pass the generator control
panel mainline circuit breakers.
b.Wire a 120/240 volt, four wire twist-lock
receptacle. (Hubbel Spec. #CS 6365) The use of
locking receptacles and locking plugs provides the
convenience of quickly disconnecting the wiring for
moving the unit and security on the job site. The
plug also allows non electrical workers to safely
reconnect the power after moving the unit and
prevents the plug from being accidentally removed
by bumping or vibration.
2. If the generator set is connected to existing (electrical)
wiring circuits (NOT RECOMMENDED with the HP
series), it is permitted only through a fully isolated
manual transfer switch. The transfer switch prevents
damage to the generator and other circuit components if
main line power is restored while the generator is
connected. Installing a transfer switch also permits the
use of normal fusing.
3. Many homes and construction sites are wired for at
least 60 to 100 Amp entrance service, much greater
than the capacity of these portable generators. When
installing the generator at these sites, a secondary
emergency distribution panel may have to be installed,
such as the Emergency Transfer/Service (ET/S) system
available through your Winco dealer. The emergency
distribution panel must be installed by a licensed
electrician according to all applicable codes. The
electrician will move the critical circuits to be powered
CAUTION: EQUIPMENT DAMAGE
Failure to properly limit and balance the load applied to the
generator will cause the generator to produce low voltage
and may damage the engine generator set. It may also
cause severe damage to the loads connected to the
generator at that time. Improper loading of the generator set
constitutes abuse and will not be covered by warranty.
ENGINE CARE
If major engine service or repair is required contact an
authorized engine service center. The manufacturer of these
engines has established an excellent world-wide engine
service organization. Engine service is very likely available
from a nearby authorized dealer or distributor. Check the
yellow pages of your local telephone directory under
“Engines-Gasoline” for the closest engine repair center or
ask the dealer from whom you purchased the power plant.
Change the oil
After the first five hours of operation and every 25 hours (50
hours for engines with oil filters) thereafter under normal
operating conditions. Change engine oil more often if the
engine is operated under heavy load, or in high ambient
temperatures.
a. Remove oil drain plug at base of the engine and
drain the oil with the engine warm.
b. Replace oil drain plug.
c. Change the oil filter if applicable
d. Remove oil filler plug and refill with new oil.
Refer to the table in the engine manual for the
proper grade of oil based on your operating
temperature.
e. Replace filler plug.
Checking the Oil Level
The oil level must always be checked before the engine is
started. Take care to remove any dirt or debris from around
the oil fill plug before removing. Be sure the oil level is
maintained. FILL TO POINT OF OVERFLOWING or on units
with the extended oil fill to the “FULL” mark on the dipstick.
Cartridge Air Cleaner
Remove and clean cartridge yearly or after every 25 hours,
whichever occurs first. Service more often if necessary.
Clean by tapping gently on flat surface. If very dirty, replace
the cartridge using only original equipment parts available at
any engine service center.
Do not use petroleum solvents, such as kerosene, to
attempt to clean the cartridge. They may cause deterioration
of the cartridge. DO NOT OIL CARTRIDGE, DO NOT USE
PRESSURIZED AIR TO CLEAN OR DRY CARTRIDGE.
Dual Element Air Cleaner
Clean and re-oil foam pre-cleaner at three month intervals or
every 25 hours, whichever occurs first. Service more often
Page 960706-113
WINCO PORTABLE SERIES
Page 12
OPERATOR CARE AND MAINTENANCE
under dusty conditions.
a.Remove knob and cover.
b.Remove foam pre-cleaner by sliding it off the
paper cartridge.
c.Wash foam pre-cleaner in kerosene orliquid
detergent and water
d.Wrap foam pre-cleaner in cloth and squeeze
dry.
e.Saturate foam pre-cleaner in engine oil.
Squeeze to remove excess oil.
f.Install foam pre-cleaner over paper cartridge.
Reassemble cover and screw down tight.
Replace the cartridge included with Dual Element Air Cleaner
yearly or every 100 hours. Service more often if necessary.
Spark Plug
Clean and reset gap at .030" every 100 hours of operation.
Do not blast clean spark plug. Clean by scraping or wire
brushing and washing with a commercial solvent. Poor
spark will occur if terminal does not fit firmly on spark plug. If
this happens reform the terminal to fit firmly on spark plug tip.
GENERATOR CARE
Proper care and maintenance of the generator is
necessary to insure a long trouble free life.
Exercising The Generator
The generator should be operated every three to four weeks.
It should be operated for a period of time sufficient to warm
the unit up and to dry out any moisture that has accumulated
in the windings (15 to 20 minutes). If left, this moisture can
cause corrosion in the winding. Frequent operation of the
engine generator set will also insure that the set is operating
properly should it be needed in an emergency.
Generator Maintenance
Any major generator service including the installation or
replacement of parts should be performed only by a qualified
electrical service technician. USE ONLY FACTORY
APPROVED REPLACEMENT PARTS.
a.Bearing - The bearing used in these generators
is a heavy duty double sealed ball bearing. They
require no maintenance or lubrication.
b.Receptacles - Quality receptacles have been
utilized. If a receptacle should become cracked or
otherwise damaged, replace it. Using damaged or
cracked receptacles can be both dangerous to the
operator and destructive to the equipment.
dirt and combustible debris to prevent a fire.
3.On engine mufflers equipped with spark arresters,
the spark arrester must be removed every 50 hours for
cleaning and inspection. Replace if damaged.
TROUBLESHOOTING HINTS
PROBLEM (SYMPTOMS) POSSIBLE CAUSES
——————————————————————————
Won’t Start*Low Oil Level.
*Fouled spark plug.
*Out of fuel.
*Stop switch in stop
position.
*Engine won't turn over.
*Fuel supply turned off.
*Plugged air cleaner
Remove dirt and debris with a cloth or brush. DO NOT use
high pressure spray to clean either the engine or the
generator. This high pressure spray could contaminate the
fuel system and the generator components.
1.Keep the air inlet screen on both the engine and
generator free of any dirt or debris to insure proper
cooling. At least yearly remove the blower housing on the
engine and clean the chaff and dirt out of the engine
cooling fins and flywheel. Clean more often if necessary.
Failure to keep these areas clean may cause
overheating and permanent damage to the unit.
2.Periodically clean muffler area to remove all grass,
WINCO PORTABLE SERIES
Page 1060706-113
Page 13
WINCO, Inc.
Limited Warranty
WINCO, Incorporated warrants to the original purchaser for the warranty period that goods
manufactured or supplied by it will be free from defects in workmanship and material, provided such
goods are installed, operated and maintained in accordance with Winco written instructions.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited
to the repair of the product. At WINCO’s option, material found to be defective in material or
workmanship under normal use and service will be repaired or replaced. For warranty service, return
the product within the warranty period from the date of purchase, transportation charges prepaid, to
your nearest WINCO Authorized Service Center or to WINCO, Inc. at Le Center Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY.
To the extent permitted by law, any and all warranties, including those of merchantability and fitness
for a particular purpose, are limited to the warranty period from date of purchase. In no event is
WINCO liable for incidental or consequential damages.
Note: Some states do not allow limitation on the duration of implied warranty and some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above limitations may
not apply in every instance. This warranty gives you specific legal rights which may vary from state to
state.
WINCO reserves the right to change or improve its products without incurring any obligations to make
such changes or improvement on products purchased previously.
EXCLUSIONS:
WINCO does not warrant engines, batteries, receptacles, or other component parts that are
warranted by their respective manufacturers.
WINCO does not warrant modifications or alterations which were not made by WINCO, Inc.
WINCO does not warrant products which have been subjected to misuse and/or negligence or have
been involved in an accident.
This warranty does not include travel time, mileage, or labor for removal or reinstallation of WINCO
product from its application.
225 S. Cordova Ave.
Le Center MN 56057
612-357-6831
Page 1160706-113
WINCO PORTABLE SERIES
Page 14
P/N 60706-113
225 South Cordova Avenue
Le Center MN 56057
612-357-6831
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.