Winchester B2332496, B2332493, B2332491, B2332492, B2332490 User Manual

INSTALLATION MANUAL
SINGLE STAGE ECM RESIDENTIAL GAS FURNACES
MODELS: TM8E, TMLE (80% Multi-Position/Standard & Low NOx)
LIST OF SECTIONS
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LIST OF FIGURES
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Furnace and Coil Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Horizontal Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . 16
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . 25
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . 25
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Thermostat Chart - Single Stage AC with
Single Stage Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Thermostat Chart - Single Stage HP with
Single Stage Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Combustion Air Inducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Combustion Airflow Path Through The Furnace Casing to the Burner
Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . 15
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
LIST OF TABLES
Unit Clearances to Combustibles (All Dimensions in Inches and cm, and All Surfaces Identified with the
Unit in an Upflow Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Recommended Filter Sizes (High Velocity 600 FPM) . . . . . . . . . 8
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . 11
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
These high efficiency, compact units employ induced combustion, reli­able hot surface ignition and high heat transfer aluminized tubular heat exchangers. The units are factory shipped for installation in upflow or horizontal applications and may be converted for downflow applica­tions.
These furnaces are designed for residential installation in a basement, closet, alcove, attic, recreation room or garage and are also ideal for commercial applications. All units are factory assembled, wired and tested to assure safe dependable and economical installation and oper­ation.
These units are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code.

SECTION I: SAFETY

This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER, WARNING, or CAUTION.
Unconfined Space Minimum Area . . . . . . . . . . . . . . . . . . . . . . . 14
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Gas Rate (CU FT/HR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Default Blower Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Blower Performance CFM - Any Position (without filter) . . . . . . 21
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property dam­age.
!
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal­function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this product.
Johnson Controls Ducted Systems 5594752-UIM-B-0419
5594752-UIM-B-0419
SPECIFIC SAFETY RULES AND PRECAUTIONS
1. Only Natural gas or Propane (LP) gas are approved for use with this furnace.
2. Install this furnace only in a location and position as specified in these instructions.
3. A gas-fired furnace for installation in a residential garage must be installed as specified in these instructions.
4. Provide adequate combustion and ventilation air to the furnace space as specified in these instructions.
5. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SECTION VI of these instructions.
6. Test for gas leaks as specified in these instructions.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
7. Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.
8. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
9. It is permitted to use the furnace for heating of buildings or struc­tures under construction where the application and use must com­ply with all manufacturer’s installation instructions including:
• Proper vent installation;
• Furnace operating under thermostatic control;
• Return air duct sealed to the furnace;
• Air filters in place;
• Set furnace input rate and temperature rise per rating plate mark-
ing;
• Means for providing outdoor air required for combustion;
• Return air temperature maintained between 55ºF (13ºC) and
80ºF (27ºC);
• The air filter must be replaced upon substantial completion of
the construction process;
• Clean furnace, duct work and components upon substantial com-
pletion of the construction process, and verify furnace-operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
10. When installed in a non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from occu­pied spaces.
11. The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
12. When moving or handling this furnace prior to installation it is rec­ommended to leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace by the cabinet, support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings (bottom or sides) or supply air opening.
13. When lifting the furnace, it is acceptable to use the primary heat exchanger tubes as a lifting point provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel. Do not use the top return bend of the heat exchangers as lift­ing points as the tubes may shift out of position or their location brackets/baffles.
IMPORTANT: During installation, doors should remain on the furnace when moving or lifting.
SAFETY REQUIREMENTS
!
CAUTION
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
• Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple­num dimensions in Figure 7. The plenum must be installed according to the instructions.
• Provide clearances from combustible materials as listed under Clearances to Combustibles.
• Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.
• These models ARE NOT CSA listed or approved for installation into a HUD Approved Modular Home or a Manufactured (Mobile) Home.
• This furnace is not approved for installation in trailers or recre­ational vehicles.
• Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
• Check the rating plate and power supply to be sure that the elec­trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60 Hz power supply. DO NOT CONNECT THIS APPLI­ANCE TO A 50 Hz POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.
• Furnace shall be installed so the electrical components are pro­tected from water.
• Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service gas heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau­tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
2 Johnson Controls Ducted Systems
5594752-UIM-B-0419
COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)
The furnace requires OUTDOOR AIR for combustion when the furnace is located in any of the following environments.
• Restricted Environments
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces installed in hobby or craft rooms
• Furnaces installed near chemical storage areas
• Chemical exposure
The furnace requires OUTDOOR AIR for combustion when the furnace is located in an area where the furnace is being exposed to the follow­ing substances and / or chemicals.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above.
!
WARNING
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean­ers or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds;
plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
CODES AND STANDARDS
Follow all national, local codes and standards in addition to this installa­tion manual. The installation must comply with regulations of the serv­ing gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following, using the latest edition available:
STEP 1 -Safety
• US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: CAN/CGA-B149.1 National Standard of Canada. Natu­ral Gas and Propane Installation Codes (NSCNGPIC)
STEP 2 -General Installation
• US: Current edition of the NFGC and NFPA 90B. For copies, con­tact the
National Fire Protection Association Inc. Batterymarch Park Quincy, MA 02269
or for only the NFGC, contact the
American Gas Association, 400 N. Capital, N.W. Washington DC 20001
or www.NFPA.org
• CANADA: NSCNGPIC. For a copy contact:
Standard Sales, CSA International 178 Rexdale Boulevard Etobicoke, (Toronto) Ontario Canada M9W 1RS
STEP 3 -Combustion and Ventilation Air
• US: Section 5.3 of the NFGC, air for Combustion and Ventilation
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply for Appliances
STEP 4 -Duct Systems
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors Association National Association (SMACNA), or American Soci­ety of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 1997 Fundamentals Handbook Chapter 32.
STEP 5 -Acoustical Lining and Fibrous Glass Duct
• US and CANADA: Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
STEP 6 -Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 2, 3, 4, & 9 and National Plumbing Codes
• CANADA: NSCNGPIC Part 5
STEP 7 -Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
These instructions cover minimum requirements and conform to exist­ing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
Johnson Controls Ducted Systems 3
5594752-UIM-B-0419
FOR FURNACES INSTALLED IN THE COMMON­WEALTH OF MASSACHUSETTS ONLY
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for resi­dential purposes, including those owned or operated by the Com­monwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following require­ments shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At
the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back­up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon
monoxide detector as required in accordance with the above pro­visions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be perma-
nently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heat­ing appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes car­bon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation, the unit should be checked for screws or bolts which may have loosened in transit. There are no shipping or spacer brackets which need to be removed from the interior of this unit.
FURNACE LOCATION AND CLEARANCES
The furnace shall be located using the following guidelines:
1. Where a minimum amount of air intake/vent piping and elbows will be required.
2. As centralized with the air distribution as possible.
3. Where adequate combustion air will be available (particularly when the appliance is not using outdoor combustion air).
4. Where it will not interfere with proper air circulation in the confined space.
Installation in freezing temperatures:
1. Furnace shall be installed in an area where ventilation facilities pro­vide for safe limits of ambient temperature under normal operating conditions.
!
WARNING
Improper installation in an ambient below 32ºF (0ºC) could create a hazard, resulting in damage, injury or death.
2. Do not allow return air temperature to be below 55ºF (13ºC) for extended periods. To do so may cause condensation to occur in the main heat exchanger, leading to premature heat exchanger failure.
Clearances for access/service:
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recommended:
1. Twenty-four (24) inches (61 cm) between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches (46 cm) at the side where access is required for passage to the front when servicing or for inspection or replace­ment of flue/vent connections.
In all cases, accessibility clearances shall take precedence over clear­ances for combustible materials where accessibility clearances are greater.
Installation in a residential garage:
A gas-fired furnace for installation in a residential garage must be installed so the burner(s) and the ignition source are located not less than 18” (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles.
Table 1: Unit Clearances to Combustibles (All Dimensions in Inches and cm, and All Surfaces Identified with the Unit in an Upflow Configuration)
Application
Upflow 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 6 (15.2) Combustible Yes Yes Yes No
Upflow B-Vent 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 1 (2.5) Combustible Yes Yes Yes No
Downflow 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 6 (15.2)
Downflow B-Vent 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 1 (2.5)
Horizontal 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 6 (15.2) Combustible No Yes Yes
Horizontal B-Vent 1 (2.5) 1 (2.5) 0 (0.0) 0 (0.0) 0 (0.0) 1 (2.5) Combustible No Yes Yes
1. Special floor base or air conditioning coil required for use on combustible floor.
2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
Top Front Rear
In. (cm) In. (cm) In. (cm) In. (cm) In. (cm) In. (cm)
Left
Side
Right
Side
Flue
Floor/
Bottom
1 (25.4)
1 (25.4)
Closet Alcove Attic
1
Yes Ye s Ye s No
1
Yes Ye s Ye s No
Line
Contact
2
Yes
2
Yes
4 Johnson Controls Ducted Systems
5594752-UIM-B-0419

SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION
The duct system’s design and installation must:
1. Handle an air volume appropriate for the served space and within
the operating parameters of the furnace specifications.
2. Be installed in accordance of National Fire Protection Association
as outlined in NFPA standard 90B (latest editions) or applicable national, provincial, state, and local fire and safety codes.
3. Create a closed duct system. For residential and non-HUD Modular
Home installations, when a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
4. Complete a path for heated or cooled air to circulate through the air
conditioning and heating equipment and to and from the condi­tioned space.
!
CAUTION
The indoor coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.
When the furnace is used with an indoor coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensa­tion in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be ade­quate to prevent chilled air from entering the furnace. If manually oper­ated, the damper must be equipped with means to prevent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.
When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con­trols may not operate at all.
The duct system is a very important part of the installation. If the duct
system is improperly sized the furnace will not operate properly.
The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.
IMPORTANT: The minimum plenum height is 12” (30.5 cm). The fur­nace will not operate properly on a shorter plenum height. The mini­mum recommended rectangular duct height is 4” (10.1 cm) attached to the plenum.
!
WARNING
The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.
Refer to Table 5 or the furnace rating plate for the correct rise range and static pressures.
If the ducts are undersized, the result will be high duct static pres­sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.
If a matching cased indoor coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. If an uncased indoor coil with a thermoplastic drain pan is to be installed in the upflow/horizontal­configuration, then extra 2” minimum spacing may be needed to ensure
against drain pan distortion.
On all installations without an indoor coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.
DUCT FLANGES
Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges.
If the flanges are not used, they must remain in the rotated down posi­tion as shipped.
)RUGXFWDWWDFKPHQW LIQHHGHG
FIGURE 1: Duct Attachment
)DFWRU\ LQVWDOOHG
$
DUCTWORK INSTALLATION AND SUPPLY PLENUM CONNECTION - UPFLOW/HORIZONTAL
Attach the supply plenum to the furnace outlet. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.
FLOOR BASE AND DUCTWORK INSTALLATION ­DOWNFLOW
Installations on combustible material or directly on any floors must use a combustible floor base shown in Figure 3. Follow the instructions supplied with the combustible floor base accessory. This combustible floor base can be replaced with a matching indoor coil, properly sealed to pre­vent leaks. Follow the instructions supplied with the indoor coil cabinet for installing the cabinet to the duct connector. Plug intake and vent pipe holes in bottom panel and move grommet to desired vent side exit.
Downflow Air Conditioning Coil Cabinet
The furnace should be installed with coil cabinet part number specifi­cally intended for downflow application. If a matching indoor coil is used, it may be placed directly on the furnace outlet and sealed to pre­vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil cabinet.
Attach the indoor coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the furnace, indoor coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage.
Johnson Controls Ducted Systems 5
5594752-UIM-B-0419
COIL INSTALLATION
IMPORTANT: On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.
'2:1)/2:
$33/,&$7,21
127( 9HULI\WKDWDOOGUDLQV DUHWUDSSHGRUSOXJJHG
)851$&(
&2,/
&2,/
)851$&(
'5$,13/8* )25+25,=217$/ 6(&21'$5<'5$,1
83)/2:
$33/,&$7,21
The indoor coil must be mounted on the supply side of the furnace as shown in Figure 2. Refer to the Installation Instructions provided with each indoor coil.
)851$&(
/()7)/2: $33/,&$7,21
&2,/
&2,/
5,*+7)/2: $33/,&$7,21
'5$,13/8* )259(57,&$/ 6(&21'$5<'5$,1
)851$&(
35,0$5<'5$,1 75$3&211(&7,21
6(&21'$5<'5$,1 75$3&211(&7,21
FIGURE 2: Furnace and Coil Attachment
DOWNFLOW DUCT CONNECTORS
All downflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace. The duct connec­tors are designed to be connected to the rectangular duct under the floor and sealed. Refer to the instructions supplied with the duct con­nector for proper installation.
)851$&(
&20%867,%/()/225 %$6($&&(6625<
FIGURE 3: Combustible Floor Base Accessory

:$50$,53/(180 :,7+´)/$1*(6
),%(5*/$66 ,168/$7,21
),%(5*/$667$3( 81'(5)/$1*(

$
35,0$5<'5$,1 75$3&211(&7,21
$
RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION
Return air may enter the furnace through the side(s) or bottom depend­ing on the type of application. Return air may not be connected into the rear panel of the unit.
SIDE RETURN APPLICATION
Side return applications pull return air through an opening cut in the side of the furnace casing. This furnace is supplied with a bottom block­off panel that should be left in place if a side return is to be used. If the furnace is to be installed on a flat, solid surface, this bottom panel will provide an adequate seal to prevent air leakage through the unused bottom opening. However, if the furnace is to be installed on a surface that is uneven, or if it is to be installed on blocks or otherwise raised off the floor, it will be necessary to seal the edges of the bottom panel
to the casing using tape or other appropriate gasket material to prevent air leakage.
BOTTOM RETURN AND ATTIC INSTALLATIONS
Bottom return applications normally pull return air through a base plat­form or return air plenum. Be sure the return platform structure or return air plenum is suitable to support the weight of the furnace.
The internal bottom panel must be removed for this application.
Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
6 Johnson Controls Ducted Systems
5594752-UIM-B-0419
DOWNFLOW APPLICATION
For downflow applications, the furnace must be turned upside-down so that the circulating air enters at the top and exits the furnace at the bot­tom. The combustion air inducer must be rotated 90° as shown in Fig­ure 14. DO NOT BLOCK COMBUSTION AIR INLET OPENINGS.
HORIZONTAL APPLICATION
$
FIGURE 4: Horizontal Application
IMPORTANT: This furnace may be installed in a horizontal position on either side as shown above. It must not be installed on its back.
ATTIC INSTALLATION
´
6833/<$,5
9(170DLQWDLQ UHTXLUHGFOHDUDQFHV WRFRPEXVWLEOHV
6+((70(7$/ ,1)52172) )851$&( &20%867,21$,5 23(1,1*6,6 5(&200(1'('
$
/,1(&217$&721/<3(50,66,%/( %(7:((1/,1(6)250('%<7+( ,17(56(&7,212))851$&(723 $1'7:26,'(6$1'%8,/',1*
-2,676678'625)5$0,1*
),/7(55$&. 0867%($0,1,080 ',67$1&(
2)´FP )5207+( )851$&(
5(7851$,5
*$63,3,1*
   
6(',0(17
75$3
´
´0,1 :25.$5($
FIGURE 5: Typical Attic Installation
This appliance is certified for line contact when the furnace is installed in the horizontal left or right position. The line contact is only permissible between lines that are formed by the intersection of the top and two sides of the furnace and the building joists, studs or framing. This line may be in contact with combustible material. Refer to Figure 5.
When moving or handling this furnace prior to installation, always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace, support the ends of the furnace rather than lifting by the cabinet flanges at the return air open­ings (bottom or sides) or supply air opening.
It is acceptable to use the primary heat exchanger tubes as a lifting point provided that the tubes are lifted at the front of the heat exchang­ers where attached to the vestibule panel. Do not use the top return bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets/baffles.
SUSPENDED FURNACE / CRAWL SPACE INSTALLATION
The furnace can be hung from floor joists or installed on suitable blocks or pads. Blocks or pad installations shall provide adequate height to ensure that the unit will not be subject to water damage.
Units may also be suspended from rafters or floor joists using rods, pipe angle supports or straps. In all cases, the furnace should be supported with rods, straps, or angle supports at three locations to properly sup­port the furnace. Place one support at the supply end of the furnace, one support located approximately in the center of the furnace near the blower shelf, and the third support should be at the return end of the fur­nace. Maintain a 6” (15.2 cm) minimum clearance between the front of the furnace and the support rods or straps.
All six suspension points must be level to ensure proper and quiet fur­nace operation. When suspending the furnace, use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists. Refer to Figure 6 for details and additional information.
6XSSRUW 5RG
6XSSRUW $QJOH[
$
FIGURE 6: Typical Suspended Furnace / Crawl Space Installation
0DLQWDLQ´PLQLPXP FOHDUDQFHEHWZHHQVXSSRUW URGVDQGIURQWRIIXUQDFH
IMPORTANT: During installation, doors should remain on the furnace when moving or lifting.
IMPORTANT: During installation, doors should remain on the furnace when moving or lifting.
When moving or handling this furnace prior to installation it is recom-
!
WARNING
When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12 inches (30.5 cm) away from furnace and burner combustion air openings.
mended to leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace, support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings (bottom or sides) or supply air opening.
It is acceptable to use the primary heat exchanger tubes as a lifting point provided that the tubes are lifted at the front of the heat exchang­ers where attached to the vestibule panel. Do not use the top return bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets/baffles.
Johnson Controls Ducted Systems 7
5594752-UIM-B-0419
5,*+76,'(
´
´
5(7851(1'
´
´
/()76,'(
´ ´
´
%
´
9HQW&RQQHFWLRQ 2XWOHW
(OHFWULFDO (QWU\
*DV3LSH (QWU\
7KHUPRVWDW :LULQJ
´'LDPHWHU 9HQW&RQQHFWLRQ 2XWOHW
&
)5217
$
´
(OHFWULFDO (QWU\
9HQW &RQQHFWLRQ 2XWOHW
*DV3LSH (QWU\
7KHUPRVWDW :LULQJ
%
6833/<(1'
FIGURE 7: Dimensions Table 2: Cabinet and Duct Dimensions
BTUH (kW)
Input
Nominal
CFM (m
3
/min)
Cabinet
Size
A A (cm) B B (cm) C C (cm) Lbs
Cabinet Dimensions (Inches)
40 (11.7) 1200 (34.0) A 14 1/2 36.8 13 3/8 34.0 10.3 26.2 89
60 (17.6) 1200 (34.0) A 14 1/2 36.8 13 3/8 34.0 10.3 26.2 94
80 (23.4) 1200 (34.0) B 17 1/2 44.4 16 3/8 41.6 11.8 29.9 103
80 (23.4) 1600 (45.3) C 21 53.3 19 7/8 50.5 13.6 34.5 116
80 (23.4) 2000 (56.6) C 21 53.3 19 7/8 50.5 13.6 34.5 121
100 (29.3) 1200 (34.0) B 17 1/2 44.4 16 3/8 41.6 11.8 29.9 108
100 (29.3) 1600 (45.3) C 21 53.3 19 7/8 50.5 13.6 34.5 120
100 (29.3) 2000 (56.6) C 21 53.3 19 7/8 50.5 13.6 34.5 124
120 (35.1) 1600 (45.3) C 21 53.3 19 7/8 50.5 15.8 40.1 125
120 (35.1) 2000 (56.6) C 21 53.3 19 7/8 50.5 15.8 40.1 131
130 (38.1) 2000 (56.6) D 24.5 62.2 23 3/8 59.4 17.5 44.4 137
´
´
´
´
´
$
Approximate
Operating Weights

SECTION III: FILTERS

FILTER INSTALLATION
!
CAUTION
All filters and mounting provision must be field supplied. All installa­tions must have a filter installed.
All applications require the use of a field installed filter. All filters and mounting provision must be field supplied.
Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.
NOTICE
Single side return above 1800 CFM is approved as long as the filter
Table 3: Recommended Filter Sizes (High Velocity 600 FPM)
CFM
(m³/min)
Cabinet
Size
Side
(in)
Bottom
(in)
1200 (34.0) A 16 x 25 14 x 25
1200 (34.0) B 16 x 25 16 x 25
1600 (45.3) C 16 x 25 20 x 25
2000 (56.6) C (2) 16 x 25 20 x 25
2000 (56.6) D (2) 16 x 25 22 x 25
1. Air velocity through throwaway type filters may not exceed 300 feet per minute (91.4 m/min). All velocities over this require the use of high velocity filters.
2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For
CFM greater than 1800, you may use two side returns or one side and the bottom or one return with a transition to allow use of a 20x25 filter.
velocity does not exceed filter manufacturer’s recommendation.
8 Johnson Controls Ducted Systems
5594752-UIM-B-0419
SIDE RETURN
Locate the “L” shaped corner locators. These indicate the size of the cut­out to be made in the furnace side panel. Refer to Figure 8.
)52172) )851$&(
6,'(2) )851$&(
&251(5 0$5.,1*6
$
FIGURE 8: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another location in the return air system, the ductwork may be directly attached to the furnace side panel.
IMPORTANT: Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instruc­tions supplied with that accessory for side opening requirements. Do not cut the opening larger than the dimensions shown in Figure 7.
HORIZONTAL FILTERS
Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum before the filter. Use of straps and/or supports is required to support the weight of the external filter box.
DOWNFLOW FILTERS
!
CAUTION
In downflow furnace arrangement, the filter must be located a mini­mum of 12” from the return air inlet of furnace.
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum above the filter height.
Filter(s) may be located in the duct system external to the furnace using an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and/or supports is required to support the weight of the external filter box.

SECTION IV: GAS PIPING

GAS SAFETY
!
DANGER
An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 PSI (14" w.c., 3.48 kPa). Pressures exceeding
0.5 PSI (14” w.c., 3.48 kPa) at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the fur­nace or some of its components that will result in property damage and loss of life.
OUTLET PRESSURE PORT
INLET
WRENCH BOSS
INLET PRESSURE PORT
ON/OFF SWITCH (Shown in ON position)
OFF
ON
FIGURE 9: Gas Valve
IMPORTANT: Plan your gas supply before determining the correct
gas pipe entry. Use 90-degree service elbow(s), or short nipples and conventional 90-degree elbow(s) to enter through the cabinet access holes.
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con­nector. Do not use a connector that has previously serviced another gas appliance.
Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal­lation of a drip leg and ground union is required. Refer to Figure 10.
VENT PORT
OUTLET
MAIN REGULATOR ADJUSTMENT
A0226-001
NOTE: Ground Union maybe installed inside or outside unit.
Ground Union
To Gas Supply
Drip
Leg
External Manual Shut-off Valve
Upflow
Configuration
To Gas Supply
Drip
Leg
Ground Union
Gas Pipe
Gas Valve
To Gas Supply
Drip
Leg
External Manual Shut-off Valve
Downflow
Configuration
To Gas Supply
Drip
Leg
Ground Union
Gas Valve
Horizontal
Configuration
Gas Pipe
Gas Valve
Ground Union
Drip Leg
Drip Leg
Ground Union
External Manual Shut-off Valve
To Gas Supp
To Gas Supply
ly
FIGURE 10: Gas Piping
Johnson Controls Ducted Systems 9
Loading...
+ 19 hidden pages