Winchester B2332484, B2332487, B2332488, B2332489, B2332486 User Manual

INSTALLATION MANUAL
SINGLE STAGE ECM RESIDENTIAL GAS FURNACES
MODELS: TM9E Series (95% AFUE Multi-position)
LIST OF SECTIONS
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
CONDENSATE PIPING AND FURNACE
VENTING CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LIST OF FIGURES
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Furnace and Coil Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Left Side Supply Gas Pipe Arrangement . . . . . . . . . . . . . . . . . . . . . . 9
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermostat Chart - 1H/1C - Single Stage Furnace
(STD-ECM) - Single Stage Air Conditioner . . . . . . . . . . . . . . . . . . . 12
Thermostat Chart - 1H/2C - Single Stage Furnace
(STD-ECM) - Single Stage Air Conditioner . . . . . . . . . . . . . . . . . . . 12
Typical. Condensate drain, vertical installation . . . . . . . . . . . . . . . . 13
Upflow Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COMBUSTION AIR and VENT SYSTEM . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . .27
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
NORMAL OPERATION AND DIAGNOSTICS . . . . . . . . . . . . . . . . .33
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Downflow Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Horizontal Left Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Horizontal Right Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Termination Configuration - 1 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .23
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .23
Termination Configuration - 2 Pipe Basement . . . . . . . . . . . . . . . . .23
Double Horizontal Combustion Air Intake and Vent Termination . . .24
Double Vertical Combustion Air Intake and Vent Termination . . . . . 24
Downward Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Direct Vent Air Intake Connection and Vent Connection . . . . . . . . .24
Combustion Airflow Path Through The Furnace Casing . . . . . . . . .25
Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Attic and Crawl Space Combustion Air Termination . . . . . . . . . . . . .27
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
LIST OF TABLES
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Recommended Filter Sizes (High Velocity 600 FPM) . . . . . . . . . . . . 8
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . 10
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . 11
Maximum Equivalent Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . . 20
High Altitude Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Equivalent Length of Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
These high efficiency, compact units employ induced combustion, reli­able hot surface ignition and high heat transfer aluminized tubular heat exchangers. The units are factory shipped for installation in upflow or horizontal applications and may be converted for downflow applica­tions.
Johnson Controls Unitary Products 1083163-UIM-J-0918
Combustion Air Intake and Vent Connection
Size at Furnace (All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Unconfined Space Minimum Area . . . . . . . . . . . . . . . . . . . . . . . . . .25
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Gas Rate (CU FT/HR) at Full Input . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Blower Performance CFM - Any Position (without filter) . . . . . . . . . . 32
These furnaces are designed for residential installation in a basement, closet, alcove, attic, recreation room or garage and are also ideal for commercial applications. All units are factory assembled, wired and tested to assure safe dependable and economical installation and oper­ation.
These units are Category IV listed and may not be common vented with another gas appliance as allowed by the National Fuel Gas Code.
1083163-UIM-J-0918

SECTION I: SAFETY

This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property dam­age.
!
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal­function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this product.
SPECIFIC SAFETY RULES AND PRECAUTIONS
1. Only Natural gas or Propane (LP) gas are approved for use with this furnace.
2. Install this furnace only in a location and position as specified in these instructions.
3. A gas-fired furnace for installation in a residential garage must be installed as specified in these instructions.
4. Provide adequate combustion and ventilation air to the furnace space as specified in these instructions.
5. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SECTION VII, "COMBUSTION AIR and VENT SYSTEM" of these instruc­tions.
6. Test for gas leaks as specified in these instructions.
9. It is permitted to use the furnace for heating of buildings or struc­tures under construction where the application and use must com­ply with all manufacturer’s installation instructions including:
• Proper vent installation;
• Furnace operating under thermostatic control;
• Return air duct sealed to the furnace;
• Air filters in place;
• Set furnace input rate and temperature rise per rating plate mark-
ing;
• Means for providing outdoor air required for combustion;
• Return air temperature maintained between 55ºF (13ºC) and
80ºF (27ºC);
• The air filter must be replaced upon substantial completion of
the construction process;
• Clean furnace, duct work and components upon substantial com-
pletion of the construction process, and verify furnace-operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
10. When installed in a non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from occu­pied spaces.
11. The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
12. When moving or handling this furnace prior to installation, always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace by the cabinet, support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings (bottom or sides) or sup­ply air opening.
13. When lifting the furnace, it is acceptable to use the primary heat exchanger tubes as a lifting point provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel. Do not use the top return bend of the heat exchangers as lift­ing points as the tubes may shift out of position or their location brackets/baffles.
IMPORTANT
During installation, doors should remain on the furnace when moving or lifting.
SAFETY REQUIREMENTS
!
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
7. Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.
8. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
• Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple­num dimensions in Figure 13. The plenum must be installed according to the instructions.
• Provide clearances from combustible materials as listed under Clearances to Combustibles.
• Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.
• These models ARE NOT CSA listed or approved for installation into a HUD Approved Modular Home or a Manufactured (Mobile) Home.
• This furnace is not approved for installation in trailers or recre­ational vehicles.
!
CAUTION
2 Johnson Controls Unitary Products
1083163-UIM-J-0918
• Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
• Check the rating plate and power supply to be sure that the electri­cal characteristics match. All models use nominal 115 VAC, 1 Phase, 60-Hz power supply. DO NOT CONNECT THIS APPLI­ANCE TO A 50-Hz POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.
• Furnace shall be installed so the electrical components are pro­tected from water.
• Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service gas heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau­tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)
!
WARNING
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning com­pounds; plastic items or containers; gasoline, kerosene, ciga­rette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
The furnace requires OUTDOOR AIR for combustion when the furnace is located in any of the following environments.
• Buildings with indoor pools
• Chemical exposure
• Commercial buildings
• Furnaces installed in hobby or craft rooms
• Furnaces installed in laundry rooms
• Furnaces installed near chemical storage areas
• Restricted Environments
The furnace requires OUTDOOR AIR for combustion when the furnace is located in an area where the furnace is being exposed to the follow­ing substances and / or chemicals.
• Antistatic fabric softeners for clothes dryers
• Carbon tetrachloride
• Cements and glues
• Chlorine based swimming pool chemicals
• Chlorinated waxes and cleaners
• Cleaning solvents (such as perchloroethylene)
• De-icing salts or chemicals
• Halogen type refrigerants
• Hydrochloric acid
• Masonry acid washing materials
• Permanent wave solutions
• Printing inks, paint removers, varnishes, etc.
• Water softening chemicals
When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above.
CODES AND STANDARDS
Follow all national, local codes and standards in addition to this installa­tion manual. The installation must comply with regulations of the serv­ing gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following, using the latest edition available:
STEP 1 - Safety
• US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: CAN/CGA-B149.1 National Standard of Canada. Natu­ral Gas and Propane Installation Codes (NSCNGPIC)
STEP 2 - General Installation
• US: Current edition of the NFGC and NFPA 90B. For copies, con­tact the
National Fire Protection Association Inc. Batterymarch Park Quincy, MA 02269
or for only the NFGC, contact the
American Gas Association, 400 N. Capital, N.W. Washington DC 20001
or www.NFPA.org
• CANADA: NSCNGPIC. For a copy contact:
Standard Sales, CSA International 178 Rexdale Boulevard Etobicoke, (Toronto) Ontario Canada M9W 1RS
STEP 3 - Combustion and Ventilation Air
• US: Section 5.3 of the NFGC, air for Combustion and Ventilation
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply for Appliances
STEP 4 - Duct Systems
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors Association National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 1997 Fundamentals Handbook Chapter 32.
STEP 5 - Acoustical Lining and Fibrous Glass Duct
• US and CANADA: Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
STEP 6 - Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 2, 3, 4, & 9 and National Plumbing Codes
• CANADA: NSCNGPIC Part 5
STEP 7 - Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
These instructions cover minimum requirements and conform to exist­ing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
Johnson Controls Unitary Products 3
1083163-UIM-J-0918
FOR FURNACES INSTALLED IN THE COMMON­WEALTH OF MASSACHUSETTS ONLY
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for resi­dential purposes, including those owned or operated by the Com­monwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following require­ments shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon mon­oxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above pro­visions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be perma­nently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heat­ing appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes car­bon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation, the unit should be checked for screws or bolts which may have loosened in transit. There are no shipping or spacer brackets which need to be removed from the interior of this unit.
FURNACE LOCATION AND CLEARANCES
The furnace shall be located using the following guidelines:
1. Where a minimum amount of air intake/vent piping and elbows will be required.
2. As centralized with the air distribution as possible.
3. Where adequate combustion air will be available (particularly when the appliance is not using outdoor combustion air).
4. Where it will not interfere with proper air circulation in the confined space.
5. Where the outdoor vent terminal will not be blocked or restricted. Refer to “VENT CLEARANCES” located in SECTION VII of these instructions. These minimum clearances must be maintained in the installation.
6. Where the unit will be installed in a level position with no more than 1/4” (6.4 mm) slope side-to-side and front-to-back to provide proper condensate drainage.
Installation in freezing temperatures:
1. Furnace shall be installed in an area where ventilation facilities pro­vide for safe limits of ambient temperature under normal operating conditions. Ambient temperatures must not fall below 32°F (0°C) unless the condensate system is protected from freezing.
!
WARNING
Improper installation in an ambient below 32ºF (0.0° C) could create a hazard, resulting in damage, injury or death.
2. Do not allow return air temperature to be below 55ºF (13°C) for extended periods. To do so may cause condensation to occur in the main heat exchanger, leading to premature heat exchanger failure.
3. If this furnace is installed in an unconditioned space and an extended power failure occurs, there will be potential damage to the internal components. Following a power failure situation, do not operate the unit until inspection and repairs are performed.
!
WARNING
Liquid anti-freeze will cause damage to internal plastic parts of this furnace. DO NOT attempt to winterize the furnace using liquid
anti-freeze.
Clearances for access/service:
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recommended:
1. Twenty-four (24) inches (61 cm) between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches (46 cm) at the side where access is required for passage to the front when servicing or for inspection or replace­ment of flue/vent connections.
In all cases, accessibility clearances shall take precedence over clear­ances for combustible materials where accessibility clearances are greater.
Installation in a residential garage:
A gas-fired furnace for installation in a residential garage must be installed so the burner(s) and the ignition source are located not less than 18” (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles.
Table 1:
Unit Clearances to Combustibles
Application Upflow Downflow Horizontal
Top 1" 0" 0"
Vent 0" 0" 0"
Rear 0" 0" 0"
Side 0" 0" 1"
Front* 0" 0" 0"
Floor Combustible
Closet Yes Yes Yes
Line Contact No No Yes
1. For combustible floors only when used with special sub-base. * 24" clearance in front and 18" on side recommended for service access. All furnaces approved for alcove and attic installation.
Combustible
1
Combustible
4 Johnson Controls Unitary Products

SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION
The duct system’s design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
2. Be installed in accordance of National Fire Protection Association as outlined in NFPA standard 90B (latest editions) or applicable national, provincial, state, and local fire and safety codes.
3. Create a closed duct system. For residential and non-HUD Modular Home installations, when a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
4. Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the condi­tioned space.
!
CAUTION
The indoor coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.
When the furnace is used with an indoor coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensa­tion in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be ade­quate to prevent chilled air from entering the furnace. If manually oper­ated, the damper must be equipped with means to prevent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.
When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con­trols may not operate at all.
The duct system is a very important part of the installation. If the duct
system is improperly sized the furnace will not operate properly.
The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.
IMPORTANT
The minimum plenum height is 12” (30.5 cm). The furnace will not operate properly on a shorter plenum height. The minimum recom­mended rectangular duct height is 4” (10.1 cm) attached to the ple­num.
If a matching cased indoor coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. If an uncased indoor coil with a thermoplastic drain pan is to be installed in the upflow/horizontal configuration, then extra 2” minimum spacing may be needed to ensure against drain pan distortion.
On all installations without a coil, a removable access panel is recom­mended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.
1083163-UIM-J-0918
!
WARNING
The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.
Refer to the furnace rating plate for the correct rise range and static pressures or to Table 6 for the correct rise range.
If the ducts are undersized, the result will be high duct static pres­sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.
DUCT FLANGES
Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges.
If the flanges are not used, they must remain in the rotated down posi­tion as shipped.
For duct attachment, if needed.
FIGURE 1: Duct Attachment
Factory installed
DUCTWORK INSTALLATION AND SUPPLY PLENUM CONNECTION - UPFLOW/HORIZONTAL
Attach the supply plenum to the furnace outlet. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.
FLOOR BASE AND DUCTWORK INSTALLATION ­DOWNFLOW
Installations on combustible material or directly on any floors must use a combustible floor base shown in Figure 8. Follow the instructions supplied with the combustible floor base accessory. This combustible floor base can be replaced with a matching indoor coil, properly sealed to pre­vent leaks. Follow the instructions supplied with the indoor coil cabinet for installing the cabinet to the duct connector. Plug intake and vent pipe holes in bottom panel and move grommet to desired vent side exit.
Downflow Air - Indoor Coil Cabinet
The furnace should be installed with coil cabinet part number specifi­cally intended for downflow application. If a matching indoor coil is used, it may be placed directly on the furnace outlet and sealed to pre­vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil cabinet.
Attach the indoor coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the furnace, indoor coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage.
Johnson Controls Unitary Products 5
1083163-UIM-J-0918
COIL INSTALLATION
IMPORTANT
On all installations without a coil, a removable access panel is recom­mended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a man­ner as to prevent leaks.
'2:1)/2:
$33/,&$7,21
127( 9HULI\WKDWDOOGUDLQV DUHWUDSSHGRUSOXJJHG
)851$&(
&2,/
&2,/
)851$&(
'5$,13/8* )25+25,=217$/ 6(&21'$5<'5$,1
83)/2:
$33/,&$7,21
The indoor coil must be mounted on the supply side of the furnace as shown in Figure 2. Refer to the Installation Instructions provided with each indoor coil.
)851$&(
/()7)/2: $33/,&$7,21
&2,/
&2,/
5,*+7)/2: $33/,&$7,21
'5$,13/8* )259(57,&$/ 6(&21'$5<'5$,1
)851$&(
35,0$5<'5$,1 75$3&211(&7,21
6(&21'$5<'5$,1 75$3&211(&7,21
FIGURE 2: Furnace and Coil Attachment
DOWNFLOW DUCT CONNECTORS
All downflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace. The duct connec­tors are designed to be connected to the rectangular duct under the floor and sealed. Refer to the instructions supplied with the duct con­nector for proper installation. Refer to the separate accessory parts list at the end of these instructions for the approved accessory duct con­nectors.
FURNACE
WARM AIR PLENUM WITH 1” FLANGES
FIBERGLASS INSULATION
FIBERGLASS TAPE UNDER FLANGE
COMBUSTIBLE FLOOR BASE ACCESSORY
35,0$5<'5$,1 75$3&211(&7,21
$
RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION
Return air may enter the furnace through the side(s) or bottom depend­ing on the type of application. Return air may not be connected into the rear panel of the unit.
SIDE RETURN APPLICATION
Side return applications pull return air through an opening cut in the side of the furnace casing. This furnace is supplied with a bottom block­off panel that should be left in place if a side return is to be used. If the furnace is to be installed on a flat, solid surface, this bottom panel will provide an adequate seal to prevent air leakage through the unused bottom opening. However, if the furnace is to be installed on a surface that is uneven, or if it is to be installed on blocks or otherwise raised off the floor, it will be necessary to seal the edges of the bottom panel
to the casing using tape or other appropriate gasket material to prevent air leakage.
BOTTOM RETURN AND ATTIC INSTALLATIONS
Bottom return applications normally pull return air through a base plat­form or return air plenum. Be sure the return platform structure or return air plenum is suitable to support the weight of the furnace.
The internal bottom panel must be removed for this application.
Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
FIGURE 3: Combustible Floor Base Accessory
6 Johnson Controls Unitary Products
1083163-UIM-J-0918
HORIZONTAL APPLICATION
FIGURE 4: Horizontal Application
IMPORTANT
This furnace may be installed in a horizontal position on either side as shown above. It must not be installed on its back.
ATTIC INSTALLATION
Line contact only permissible between lines formed by the intersection of furnace top and two sides and building joists, studs or framing
Filter rack must be a minimum distance of 18” (45.7 cm) from the furnace
Gas Piping
30” MIN. Work Area
12”
12”
Supply Air
Vent (Maintain required clearances to combustibles)
Sheet metal in front of furnace combustion air Openings is Recommended
bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets/baffles.
SUSPENDED FURNACE / CRAWL SPACE INSTALLATION
The furnace can be hung from floor joists or installed on suitable blocks or pads. Blocks or pad installations shall provide adequate height to ensure that the unit will not be subject to water damage.
Units may also be suspended from rafters or floor joists using rods, pipe angle supports or straps. In all cases, the furnace should be supported with rods, straps, or angle supports at three locations to properly sup­port the furnace. Place one support at the supply end of the furnace, one support located approximately in the center of the furnace near the blower shelf, and the third support should be at the return end of the fur­nace. Maintain a 6” (15.2 cm) minimum clearance between the front of the furnace and the support rods or straps.
All six suspension points must be level to ensure proper and quiet fur­nace operation. When suspending the furnace, use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists. Refer to Figure 6 for details and additional information.
Support Rod
Return Air
FIGURE 5: Typical Attic Installation
This appliance is certified for line contact when the furnace is installed in the horizontal left or right position. The line contact is only permissible between lines that are formed by the intersection of the top and two sides of the furnace and the building joists, studs or framing. This line may be in contact with combustible material. Refer to Figure 5.
When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12” (30.5 cm) away from furnace and burner combustion air openings.
Sediment
Trap
!
WARNING
IMPORTANT
During installation, doors should remain on the furnace when moving or lifting.
When moving or handling this furnace prior to installation, always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace, support the ends of the furnace rather than lifting by the cabinet flanges at the return air open­ings (bottom or sides) or supply air opening.
It is acceptable to use the primary heat exchanger tubes as a lifting point provided that the tubes are lifted at the front of the heat exchang­ers where attached to the vestibule panel. Do not use the top return
Support Angle (x3)
FIGURE 6: Typical Suspended Furnace / Crawl Space Installation
Maintain 6” minimum clearance between support rods and front of furnace
DOWNFLOW APPLICATION
To apply the furnace in a downflow position, it will be necessary to rotate the vent blower 90° left or right so that the vent pipe passes through the side of the furnace casing. See Figure 7.
Rotate vent blower 90° either way
LEFT SIDE VENT
FIGURE 7: Downflow Venting
RIGHT SIDE VENT
Johnson Controls Unitary Products 7
1083163-UIM-J-0918
&RPEXVWLRQ$LU,QOHW
&RQGHQVDWH'UDLQ 'RZQIORZ
´
%
´
´
/()76,'(
´9HQW &RQQHFWLRQ 2XWOHW
´
´
´
&RPEXVWLRQ $LU,QOHW
´
6833/<(1'
´
*DV3LSH (QWU\
(OHFWULFDO (QWU\
&RQGHQVDWH 'UDLQ
7KHUPRVWDW :LULQJ
´9HQW &RQQHFWLRQ 2XWOHW
&
)5217
$

*DV3LSH (QWU\
(OHFWULFDO (QWU\
&RQGHQVDWH 'UDLQ
7KHUPRVWDW :LULQJ
5,*+76,'(
&RPEXVWLRQ$LU,QOHW
&RQGHQVDWH'UDLQ 'RZQIORZ
´9HQW &RQQHFWLRQ 2XWOHW
´
2SWLRQDO5HWXUQ$LU &XWRXW(LWKHUVLGH
´
´
5(7851(1'
FIGURE 8: Dimensions
Table 2: Cabinet and Duct Dimensions
BTUH (kW)
Input
Nominal
CFM (m3/min)
Cabinet
Size
A (in) A (cm) B (in) B (cm) C (in) C (cm) Lbs (kg)
Cabinet Dimensions (Illustrated in Figure 13)
40 (11.7) 1000 (28.3) A 14 1/2 36.8 13 3/8 34.0 11 3/4 29.8 113 60 (17.6) 1200 (34.0) B 17 1/2 44.4 16 3/8 41.6 13 1/4 33.7 122 80 (23.4) 1200 (34.0) B 17 1/2 44.4 16 3/8 41.6 14 3/4 37.5 126
80 (23.4) 1600 (45.3) C 21 53.3 19 7/8 50.5 16 1/2 41.9 136 100 (29.3) 1600 (45.3) C 21 53.3 19 7/8 50.5 18 1/4 46.4 142 100 (29.3) 2000 (56.6) C 21 53.3 19 7/8 50.5 18 1/4 46.4 145 120 (35.1) 2000 (56.6) D 24 1/2 62.2 23 3/8 59.4 21 3/4 55.2 156
´
´
%
$
Approximate
Operating Weights

SECTION III: FILTERS

FILTER INSTALLATION
!
CAUTION
All filters and mounting provision must be field supplied. All installa­tions must have a filter installed.
All applications require the use of a field installed filter. All filters and mounting provision must be field supplied.
Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.
NOTICE
Single side return above 1800 CFM is approved as long as the filter velocity does not exceed filter manufacturer’s recommendation and a transition is used to allow use on a 20x25 filter.
Table 3: Recommended Filter Sizes (High Velocity 600 FPM)
CFM (m³/min) Cabinet Size Side (in) Bottom (in)
1000 (28.3) A 16 x 25 14 x 25 1200 (34.0) B 16 x 25 16 x 25 1600 (45.3) C 16 x 25 20 x 25 2000 (56.6) C (2) 16 x 25 20 x 25 2000 (56.6) D (2) 16 x 25 22 x 25
1. Air velocity through throwaway type filters may not exceed 300 feet per min­ute (91.4 m/min). All velocities over this require the use of high velocity fil­ters.
2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For CFM greater than 1800, you may use two side returns or one side and the bottom or one side return with a transition to allow use of a 20x25 filter.
SIDE RETURN
Locate the “L” shaped corner locators. These indicate the size of the cut­out to be made in the furnace side panel. Refer to Figure 9.
Front of Furnace
Side of Furnace
Corner Markings
FIGURE 9: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another location in the return air system, the ductwork may be directly attached to the furnace side panel.
IMPORTANT
Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instructions supplied with that accessory for side opening requirements. Do not cut the opening larger than the dimensions for the “Optional Return Air Cut­out” shown in Figure 8.
8 Johnson Controls Unitary Products
HORIZONTAL FILTERS
Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum before the filter. The use of straps and/or supports is required to support the weight of the external filter box.
DOWNFLOW FILTERS
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum above the filter height.
Filter(s) may be located in the duct system external to the furnace using an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and/or supports is required to support the weight of the external filter box.

SECTION IV: GAS PIPING

GAS SAFETY
!
DANGER
An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 psig (14" w.c., 3.48 kPa). Pressures exceeding
0.5 PSI (14” w.c., 3.48 kPa) at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the fur­nace or some of its components that will result in property damage and loss of life.
1083163-UIM-J-0918
IMPORTANT
Plan the gas supply routing before determining the correct gas pipe entry. Use 90° conventional elbow(s) and short pipe nipples to enter through the cabinet access holes.
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con­nector. Do not use a connector that has previously serviced another gas appliance.
Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal­lation of a drip leg and ground union is required. Refer to Figure 11.
For left side supply gas pipe arrangement, two 1/2” elbows and two 1/2” x 1-1/2” pipe nipples must be used. The arrangement shown in Figure 11 aligns entrance hole in furnace casing with supply gas pipe. Furnace casing does not support installations completed using street-elbows.
´[´
*$6 9$/9 (
3,3(1,33/(

(/%2:
´[´ 3,3(1,33/(
Outlet Pressure Port
Inlet
Wrench Boss
Inlet Pressure Port
FIGURE 10: Gas Valve
To Gas Supply
Ground Union
Drip Leg
Configuration
FIGURE 12: Gas Piping
OFF
ON
On/Off Switch (Shown in ON position)
To Gas Supply
External Manual Shut-off Valve
Drip Leg
Upflow
72*$6
Vent Port
Outlet
Main Regulator Adjustment
NOTE: Ground Union maybe installed inside or outside unit.
External Manual
Ground Union
Gas Valve
Gas Pipe
Ground Union
Gas Pipe
To Gas Supply
Drip Leg
Shut-off Valve
Downflow
6833/<
FIGURE 11: Left Side Supply Gas Pipe Arrangement
To Gas Supply
Ground Union
Gas Valve
Drip Leg
Configuration
Ground Union
Gas Pipe
Horizontal
Configuration
Drip Leg
(/%2:

To Gas Supply
Drip Leg
External Manual Shut-off Valve
Gas Valve
To Gas
Ground Union
Supply
$
Johnson Controls Unitary Products 9
1083163-UIM-J-0918
GAS ORIFICE CONVERSION FOR PROPANE (LP)
IMPORTANT
An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet (1.8 m) of the furnace.
The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 0.5 psig (3.5 kPa).
!
CAUTION
The gas valve body is a very thin casting that cannot take any exter­nal pressure. Never apply a pipe wrench to the body of the gas valve when installing piping. A wrench must be placed on the octagon hub located on the gas inlet side of the valve. Placing a wrench to the body of the gas valve will damage the valve causing improper opera­tion and/or the valve to leak.
Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace. Refer to Figures 8 and 11.
Table 4: Nominal Manifold Pressure - High Fire
Gas Heating
Value
(BTU/cu ft.)
800 3.5 3.5 3.5 29.8 0.87 0.87 0.87
850 3.5 3.5 3.5 31.7 0.87 0.87 0.87
900 3.5 3.5 3.5 33.5 0.87 0.87 0.87
950 3.5 3.5 3.3 35.4 0.87 0.87 0.81
1000 3.5 3.2 2.9 37.3 0.87 0.80 0.73
1050 3.5 2.9 2.7 39.1 0.87 0.73 0.67
1100 3.2 2.7 2.4 41.0 0.80 0.66 0.61
2500 (LP) 9.8 8.2 7.5 93.2 (LP) 2.44 2.03 1.86
0-7999 8000-8999 9000-9999 0-2437 2438-2742 2743-3048
in. w.c. in. w.c. in. w.c. kPa kPa kPa
Manifold Pressures
Altitude (feet) Altitude (m)
This furnace is constructed at the factory for natural gas-fired operation, but may be converted to operate on propane (LP) gas by using a fac­tory-supplied LP conversion kit. Follow the instructions supplied with the LP kit.
HIGH ALTITUDE GAS ORIFICE CONVERSION
This furnace is constructed at the factory for natural gas-fired operation at 0 – 7,999 feet (0 – 2,438 m) above sea level.
The manifold pressure must be changed in order to maintain proper and safe operation when the furnace is installed in a location where the altitude is greater than 7,999 feet (2,438 m) above sea level. Refer to Table 4 for proper manifold pressure settings.
HIGH ALTITUDE PRESSURE SWITCH CONVERSION
For installation where the altitude is less than 5,000 feet (1,524m), it is not required that the pressure switch be changed unless you are in an area subject to low pressure inversions.
Manifold Pressures
Gas Heating
Value
(MJ/cu m)
!
DANGER
PROPANE AND HIGH ALTITUDE CONVERSION KITS
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed. Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-
pane (LP) gas. Do not use this furnace with butane gas. Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death. High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application. An authorized distributor or dealer must make all gas conversions. In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed. Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames, caus­ing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage and/or death.

SECTION V: ELECTRICAL POWER

!
ELECTRICAL POWER CONNECTIONS
Field wiring to the unit must be grounded. Electric wires that are field installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 5 in these instructions for specific furnace electrical data.
Use copper conductors only.
CAUTION
10 Johnson Controls Unitary Products
1083163-UIM-J-0918
Table 5: Ratings & Physical / Electrical Data
Input Output
MBH kW MBH kW CFM
40 11.7 38 11.1 1000 28.3 95.5 30-60 17-33 190 88 1/2 6.8 11x8 15 10.6 1/2"
60 17.6 57 16.7 1200 34.0 95.5 30-60 17-33 190 88 1/2 6.8 11x8 15 10.6 1/2"
80 23.4 76 22.3 1200 34.0 95.5 40-70 22-39 190 88 1/2 6.8 11x8 15 10.6 1/2"
80 23.4 76 22.3 1600 45.3 95.5 35-65 19-36 190 88 1/2 6.8 11x10 15 10.6 1/2"
100 29.3 95 27.8 1600 45.3 95.5 40-70 22-39 190 88 1/2 6.8 11x10 15 10.6 1/2"
100 29.3 95 27.8 2000 56.6 95.5 35-65 19-36 190 88 3/4 8.4 11x11 15 12.2 1/2"
120 35.1 114 33.4 2000 56.6 95.5 45-75 25-42 190 88 3/4 8.4 11x11 15 12.2 1/2"
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures. Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water.
Nominal
Airflow
m3/min
AFUE
Air Temp.
Rise
% °F °C °F °C HP Amps
Max. Outlet
Air Temp
Blower
Blower
Size
Fuse or
Circuit
Breaker
Total Unit
Amps
Gas Pipe
Connection,
SUPPLY VOLTAGE CONNECTIONS
IMPORTANT
The power connection leads and wiring box may be relocated to the opposite side of the furnace. Remove the screws and cut wire tie
Junction Box
Connect ground lead to screw
Electrical Entry
BLK
L1-Hot
WHT
Neutral
FIGURE 13: Electrical Wiring
1. Provide a power supply separate from all other circuits. Install over-
current protection and disconnect switch per local/national electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect or fused switch in the OFF position, check all wiring against the unit wiring label. Refer to the wiring dia­gram in this instruction.
2. Remove the wiring box cover screws. Route all power wiring
through a conduit connector or other proper bushing that is field installed into the unit opening and the junction box. In the junction box there is a black wire, a white wire and a green ground screw. Connect the power supply as shown on the unit’s wiring label located on the inside of the blower compartment door, or the wiring schematic in this section. Connect the black wire to L1 (hot) from the power supply. Connect the white wire to neutral. Connect the ground wire (installer-supplied) to the green (equipment ground) screw. An alternate wiring method is to use a field-provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the outside of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring connections, replace the wiring box cover and screws. Refer to Figure 12.
3. The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 12.
holding excess wiring. Reposition on the opposite side of the furnace and fasten using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied thermostat by following the instructions that come with the thermostat. With the thermostat set in the OFF position and the main electrical source disconnected, connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module, as shown in Figures 13 & 14. Electronic thermostats require the common wire to be connected. Apply strain relief to thermostat wires passing through cabinet. If air conditioning equipment is installed, use thermostat wiring to connect the Y and C terminals on the furnace control board to the proper wires on the out­door unit.
IMPORTANT
Set the heat anticipator in the room thermostat to 0.4 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.
IMPORTANT
Some electronic thermostats do not have adjustable heat anticipa­tors. They should be set to six cycles per hour. Follow the thermostat manufacturer's instructions.
The 24-volt, 40 VA transformer is sized for the furnace components only, and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.
NPT
Johnson Controls Unitary Products 11
1083163-UIM-J-0918
+&7KHUPRVWDW6LQJOH6WDJH)XUQDFH67'(&06LQJOH6WDJH$LU&RQGLWLRQHU
7+(50267$7
&
±9ROW&RPPRQ
5
±9ROW+RW
*
)DQ
<
)LUVW6WDJH
&RPSUHVVRU
:
)LUVW6WDJH+HDW
<
6HFRQG6WDJH
&RPSUHVVRU
:
6HFRQG6WDJH+HDW
RU2
5HYHUVLQJ9DOYH
6,1*/(67$*(
)XUQDFH
67'(&0
&
±9ROW&RPPRQ
5
±9ROW+RW
*
)DQ
<<
)XOO6WDJH&RPSUHVVRU
:
)XOO6WDJH+HDW
<
)LUVW6WDJH&RPSUHVVRU
([WHUQDO+XPLGLVWDW
2SWLRQDO2SHQRQ
+XPLGLW\5LVH
9$&+XPLGL¿HU
2SWLRQDO
FIGURE 14: Thermostat Chart - 1H/1C - Single Stage Furnace (STD-ECM) - Single Stage Air Conditioner
6,1*/(67$*(
$,5
&21',7,21(5
&
±9ROW&RPPRQ
5
±9ROW+RW
<
)LUVW6WDJH
&RPSUHVVRU
$
+&7KHUPRVWDW6LQJOH6WDJH)XUQDFH67'(&07ZR6WDJH$LU&RQGLWLRQHU
7+(50267$7
&
±9ROW&RPPRQ
5
±9ROW+RW
*
)DQ
<
)LUVW6WDJH
&RPSUHVVRU
:
)LUVW6WDJH+HDW
<
6HFRQG6WDJH
&RPSUHVVRU
:
6HFRQG6WDJH+HDW
RU2
5HYHUVLQJ9DOYH
([WHUQDO+XPLGLVWDW
2SWLRQDO2SHQRQ
+XPLGLW\5LVH
9$&+XPLGL¿HU
2SWLRQDO
FIGURE 15: Thermostat Chart - 1H/2C - Single Stage Furnace (STD-ECM) - Single Stage Air Conditioner
6,1*/(67$*(
)XUQDFH
67'(&0
&
±9ROW&RPPRQ
5
±9ROW+RW
*
)DQ
<
)LUVW6WDJH&RPSUHVVRU
:
)XOO6WDJH+HDW
<<
)XOO6WDJH&RPSUHVVRU
7:267$*(
$,5
&21',7,21(5
&
±9ROW&RPPRQ
5
±9ROW+RW
<
)LUVW6WDJH
&RPSUHVVRU
<
6HFRQG6WDJH
&RPSUHVVRU
$
12 Johnson Controls Unitary Products
ACCESSORY CONNECTIONS
The furnace control will allow power-switching control of various acces­sories.
ELECTRONIC AIR CLEANER CONNECTION
Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during circulating blower opera­tion.
HUMIDIFIER CONNECTION
Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.
A mounting hole is provided on the control panel next to the furnace control board for mounting a humidifier transformer if required.
TWINNING
These furnaces are not to be twinned. If more than one furnace is needed in an application, each furnace must have its own complete duct system and its own wall thermostat.

SECTION VI: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION
As shipped from the factory:
• For all 040, 060 & 080K input furnaces the main drain is plumbed through the casing right-side opening when viewed from the front of the furnace.
• For all 100 & 120 input furnaces the main drain is plumbed through the casing left-side opening when viewed from the front of the fur­nace.
1083163-UIM-J-0918
IMPORTANT
Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4” per foot (20 mm/m) downward slope to the drain.
IMPORTANT
If an external vent tee is being installed, then it must have its own condensate trap before it is disposed into an open or vented drain.
This is not to be considered as a second trap as referenced else­where in this document.
23(167$1'3,3( $QWLVLSKRQDLUYHQW
´0D[
7((
NOTICE
The Figures 16 - 19 show the condensate drain arrangement for the various possible furnace and vent blower positions.
The condensate hoses must slope downwards at all points.
!
CAUTION
The furnace condensate pan is self priming and contains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.
When drain hose routing changes are required (shown in Figures 16-
19), be sure to cap all unused openings.
If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.
No hose clamps are needed for connecting to the condensate pan.
IMPORTANT
The furnace, indoor coil, and humidifier drains may be combined and drained together. The evaporator coil drain may have an external, field-supplied trap prior to the furnace drain connection to prevent conditioned air leakage. All drain connections (furnace, indoor coil, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible. Regular maintenance is required on condensate drainage system.
7223(125 9(17(''5$,1
$
FIGURE 16: Typical. Condensate drain, vertical installation
The condensate will flow to the drain better if an open stand pipe is installed in the drain line. See Figure 15.
If indoor coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher, above the 5” minimum.
Do not drain other devices (humidifier, indoor coil, etc.) into the top opening of the vent stand pipe. Instead, install a second tee in the vented drain tube below the furnace drain tee and route additional drainage through the new tee.
NOTICE
A loop has been added to the pressure switch vacuum hose. How­ever, ensure that all pressure switch hoses are routed such that they prevent any condensate from entering the pressure switch.
Johnson Controls Unitary Products 13
Loading...
+ 28 hidden pages