Williams 7691, 7687, 7690, 7688, 7685 Instructions Manual

Page 1
.................................................................................................
=_ INSTRUCTIONS _OR WILLIAMS GAS APPLIANCE
CONVERSION KITS 7685, 7687, 7688, 7690 & 7691
iil=Jl_' i=,t;tl=_;,},]il'ii n_!l NATURAL G_S TO LIQUID PROPANE GAS
THIS KIT IS FOR USE WITH MODEL NUMBERS:
This conversion kit shall be installed by a qualified service agency in accordance manufacturer's instructions and all
applicable
codes and requirements of the authority having
jurisdiction. If the information in these instructions
is not followed exactly, a fire, explosion or production of carbon monoxide may result, causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit, The installation is not proper and complete until the operation of the converted appliance is checked as specified in the
manufacturer's instructions supplied with the kit,.
3508332; 3508732; 5008732;
5508332; 6_08732; 6008532
PPL!CATION: THESE CONVERSION KITS ARE USED ON
E FORSAIRE TOP VENT WALL FURNACES WHEN
I_QUIPPED WiTH NATURAL GAS VALVES;
P323209 (STANDING PILOT MODELS)
i P3232t0 (ELECTRONIC IGNITION MODELS)
with the WITHhOmm STAINLESS STEEL BURNER 12956
dONVERTtNG TO L P GAS
THIS K_ CONTAINS:
(1} CAP SCREW (t) PRESSURE REGULATOR ADJUSTMENT SCREW
(t) SPR_NG (RED) (3) CONVERSION LABELS (1 OR 2) PILOT ORIRCES (LP. GAS')
(1 OR 2) BURNER ORIRCES (LP GAS)
{1) LPG. TAG {1) "O" RING
_AUTION:THE GAS SUPPLY MUST BE
SHUTOFF PRIOR TO DISCONNECTING THE
ELECTRICAL POWER BEFORE PROCEEDING
WITH THE CONVERSION,
I,,
2.,
3.,
4_
5_
,.
7,,
8_,
9,,
10o 11_
12.
13
I4. !5 16,
17.,
18. 19,
2&
CONVERSION INSTRUCTIONS - NATURAL GAS TO LP. GAS Shut off gas to the furnace, Shut off electric power to the furnace, Disconnect gas supply linefrom control valve Remove electronic ignition module (ifequipped).
CAUTION: Label all wires prior to disconnection for'proper reconnection,
STANDING PILOT MQDELS ONLY_ Disconnect (2) tw$ wires from terminal block on thermocouple and (2) two wires from control valve.
Use a 7/16" open end wrench to remove outer end nuts rom burner wire hangers and swing them up to drop burner down. '_
NOTE: On single burner models, (2) two sheet metal ;crews are used instead of end nuts° Pull the burner and control assembly forward to free itfrom he rear burner support bracket, Once removed, all work can be performed on work bench. Use a 7/16" boxed end wrench and remove the burner orifice(s) from the manifold and replace with the orifice(s) provided in thiskit. Refer to Figure 1 on page 2 Remove pilot orifice from pilot and replace with orifice prov_ed in this kit, Refer to Figure 2A or B on page 2.
Remove regulator cap screw and pressure regulator adjust!ng screw Refer to Figure 3 on page 2. Remove the existing spring, i insertthe replacement red spring. Refer to Figure 4 on pa{e 2_
Install the new plastic pressure regulator adjustment screw !Assure that the screw top is flush with the regulator
top. I Turn pressure regulator adjustment screw clockwise efever_complete turns. The preliminary pressure setting
isapproximately I0.,5 in, w.c. for LP gas regulator and 4,0 i_. w,,c.,for natural gas regulator
J
Check the regulator setting using a manometer or by ctock_nnthe gas meter°
installthe new cap screw and O ring, Reassemble the furnace by following the steps above in re{,erse order° Use information from chart on page 3 to fill in blanks on sepplemental data label_ A_ach label permanently
adjacent to the rating plate on a cteer surface area° i Leave these instructionswith the homeowner.
REV 6/00 P323213_A917 74 SHT 1 OF
Page 2
,. I'_T NO.
7685
7657
7688
7690
769t
MODEL NOoON RATINGPLATE
3508332 3508732
5008732 55O8332 6508332
6508732
6OO8532
FIGURE 5
CHART
TO BE USI_ ON CONVICTION LABEL
NEW MOD_
NO.
3508331
3508731 50(38731
5508331 6508331
6508731
6008531
PEW INPUT
BI'UtHR
35,(X)0
35,000
5O,000
55,000
65,000
65,000
7/8
- (_8)
_ DURNg_I
NEWHEATING
DAPACITY BTLt91R
2B,000 28,000 37,500 44,000 52,000 52,000
60,000 49,200
.r- 3/_2 (lo)
HONEYWELLP322.954(Q314}
(AFTER
CONVERSION)
i
OFJRCE
SIZE
#52
#52 #54 #54 #52
#52
#53
IMPORTANT: LABEL PLACEMENT
After conversion is completed, the large conversion label provided in this kit must be filled out completely (using chart information). Attach small conversion label
to gas valve, and attach large data conversion label to inside of casing door next to rating plate° Remove "Natural Gas"
tag from burner and replace with "Liquid
Propane Gas" tag provided with this kit. This is necessary to provide information for future servicing. Failure to do so could
result in property damage, personal injury or death.,
t
(,,25) (I S
ROBERTSHAW "_L-__._=
! P3226B0 _ I (AFTER
dONVERSION)
BURNER
,
Refer to the Lighting and Operating Instruction Plate located in _ontrol area of furnace for instructions on lighting the burner°
I
Any adjustments must be performed by a qualified service techr dcian only. Improper adjustments could result in property damage, personal injuryor death., t
!
The following information is provided for use by a qualified servic_ technician. With main burner in 0peration, check aii"pipe connections, pilot _jas tubin'g"and around pressure regulator for gas leaks with a rich soap and water solution. Bubbles indicate gas t_akage. Never use a match or open flame totest
for leaks. Correct even the slightest leak at once before using fu!nace.
ADJUST PILOT BURNER
NOTE: Pilot gas may need adjustment depending on inlet
pressure, increase or decrease to obtain proper setting,.
Pilot flame should surround 3f8 inch to 1/2 inch of the therrnocouple or generator tip, To adjust, if needed, remove
pilot adjustment cap (do not lose gasket).
i. Remove screw cover over pilot adjusting screw,
2 insert small screwdriver. Adjust flame as needed°
Turn screw counterclockwise _ to increase flame or clockwise _ to _ecrease flame
3o Turn thermostat to-highest setting. Main burner
should light quickly and smoothly. Turn thermostat to lowest setting,. Main burner should go out. Pilot should remain liL
4 Replace screw cover over pilot adjusting screw.
t
D[ANGER OF PROPERTY DAMAGE, BODILY iNJURY OR DEATH,
L_uid Petroleum (L,P,) is heavier than air and it will
s_)ttle in any low area, including open depressions, a_d it will remain there unless area is ventilated°
Nbver attempt startup of unit before thoroughly
v+ntilating area,
children, clothing, furniture and flammable
t
P323213,.'LA_l 7_74 SHT. 3 OF 4
Page 3
CHECK GAS PRESSURE
J w
The minimum inlet pressure in the gas supply pipe should be 111,0 w,c, for Propane Gas., The maximum inlet
pressure should never exceed 13" w_c- This should be checked at the 1/8 inch N.,PT, plugged tapping in the supply line with a manometer,
The manifold pressure for this appliance is !0,5" w,c, for Propane!Gas, Check with a manometer at the pressure tap on the control valve,, To adjust pressure, remove ca_from! regulator and turn regulator adjustment screw
clockwise _ to increase and counterclockwise _ X, _ decrease pressure,
RATE VERIFICATION
Refer to the Lighting and Operating Instruction Plate located in cdntrol area of furnace for instructionson lighting the
burner.
I_ Make certainthereisno gas flowthroughthemeterothertha41otheappliancebeingchecked,Otherappliances
must remainoffand thepilotsextinguished(ortheirconsum#tiondeductedfromthemeterreading),
2. With gas control knob in "ON" position, cycle main burner o_ and off several times by means of thermostat to stabilize PRV diaphragm,, i
3, With second hand on watch, carefully clock gas meter to detet'mine exact rate of gas flow to main burner in cubic
feet per hour (see CONVERSION TABLE below)° ,,
4. Compare actual input with manufacturer's recommended houily input stamped on rating platen Convert BTU per hour input rating to cubic feet of gas per hour (cfh) by using _e following formula.
Whereas: Input Rating in BTUperHouJr = Cubic Feet of
PRV= Pressure BTU Content of Gas per cu tt Gas per Hour
RegulatorValve
MJ = Megajoule Input Rating in MJ/hr = m3ihr m3 = MetricCube MJ of Gas per m3
5. If actual gas flow (cfh) does not conform to manufacturer's r_commended input rating (cfh or_U converted to cfh), a limited adjustmen_tof the PRV may be made. Turn PI_V adjusting screw clockwise [ % to increase or counterclockwise / "\ to decrease gas flow. Burne_ input must not exceed nameplate rating.
6. Replace cap screw in PRV adjustment stack. Turn gas suppl,/to other appliances back on and re4ight all pilots.
7o Place furnace in operation and observe through at least one €omplete cycle to be sure all controls are operating
satisfactorily., i
co"w"s'o"
This table shows the gas flow rate for measured time per revolution of the ONE CUBIC Foot
DIAL in cubic feet per hour (=th) and m3/hr.
,i ,,,,,,i ,H,, ,
TIM_ FLOW
sec cfh
40 90
......... ,,, ,,,
41 88 42 86 43 84 44 82 45 80 46 78 47 77
....... | ,,,,,,
75 73 72
FLOW TIME
m3/hr sec
2.55 56
2.50 57 5B
FLOW
cfh
64
63 62
2.44
2.38
2,32
2.21
.... , =
2.18
2,12
2.07
2,04
59 6O 62 64 66 68 70
6t i 1.73
60 _ 1.70 5B I 1.64
5s !1,59
54 ,,i,,,1.53 53 _ 1.50
51 il 1.44
FLOW TIME
m3/hr sec
}1.81 88
11.78 g2
= ................. __ ....
I 1,76 96
48 49 5O 51 71 2.01 52 69 1.95 53 68 1.93
54 67 1.90 80 _ 45
e5 ...........
For 1/2 cu froper revolution of meter dial, multiply For 2 cu, ft. per revolution of meter dial, diTde flow
74 49 76 47 78 46
..........72 ...... i,50 _} 1.42-'
I 1_39 ! 1.33
! !.3o
1.27
I 1.22
FLOW
cfh
41 39 38
36
34 33
31
30 29
I00 105 110
115 120 125 130 28 135 27 140 26 150 24 160 23 170 21 180 20
rate by 2.
by 2,
FLOW
m3/hr
1.16
1.10
1.o8
1.02 .96 .93
.88
.85 .82
.79 .76
,74 .68 .65
.59 .57
REV 6-'00
P3232134LA917..74
SH'f 4 OF 4
|
Page 4
FIGURE 1
BRACKET
OTEMI)
SCREWJ_
CONTROL ASSEMBLY
FOR MODELS
3508332; 3508732 (shown) 50087'32; 5508332 (not shown) 6508732; 60DB532 (not shown)
PILOT
BURNER
2)
I
_'- SCREW
FIGURE 2
A
INTERMITTENT JGNITJDN SYSTEMS PILOT BURNER
STAMPED 3S24F
i /FORIFICE (LP SHOWN)
/STAMPED 11LP
#
/
B
HIGH BTU
BUILT-fN THERMOSTAT MODELS PILOT BURNER
STAMPED Q314AFK
ORIFIC{ (UP, SHOWN) (RED MARKING ON L.,P ORIFICE)
STAMPED BBRIO
t
i /r_PilO T
tlJ ,u==o
,/,/ PILOT HOOD
FIGURE 3
I_RESSURE REGULATOR CONVENIENCE (,_NNNDU_TMEN'T TERMINALS [2) / WIRING
ER CAP SCREW)\\ (OPI3ONAL) i " / TERMINALS (2)
! _R_SURE TAP, _ _ _'I/IUET_uRE
dO.N=CTiON,! A/.1 '_s \_ILOTADJUSTMENT
.ES_ COBOL(UNOE.CAPS_
BUTTON KI_K_B
A THERMOGOUPLE CONNECTION AND RED RESET
BUTTON ON STANDING PILOT MODELS ONLY
I FIGURE 4
PRESSURE REGULATOR HOUS1NG
!
1
P323213/L.A_17_74 SHT 2 OF ,_
Loading...