CAUTION: Installation of Backow Preventers must be performed by qualied, licensed
personnel. The installer should be sure the proper device has been selected for the particular
installation. Faulty installation could result in an improperly functioning device.
WILKINS Model 450 Double Check Valve assemblies are for use on potable water lines
where a health hazard does not exist in the event of a backow situation.
Damage to the device could result wherever water hammer and/or water thermal expansion could create excessive line pressure. Where this could occur, shock arrestors, check
valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backow Preventer must never be submerged in
water because this could cause a cross-connection. Make sure that the pit or vault always
remains dry by providing ample drainage.
1. Before installing a Model 450 Backow Preventer, ush the line thoroughly to
remove all debris, chips and other foreign matter. If required, a strainer should be
placed upstream of the Backow Preventer. CAUTION: Do not use a strainer in
seldom used emergency waterlines such as re lines.
2. Provide adequate space around the installed unit so that the test cocks will be
accessible for testing and servicing.
3. Install valve at least 6 inches above surrounding ood level.
PLACING THE DEVICE IN SERVICE
1. Start with both shut-off valves closed.
Slowly open the inlet shut-off valve until the
backow preventer is completely pressurized.
2. When the unit has been pressurized,
vent any trapped air by slightly opening
each of the four test cocks.
3. Slowly open the downstream shut-off
valve. The Model 450 Double Check Valve
assembly is now in service.
4. After the Model 450 has been properly installed, test the device (see “TEST
PROCEDURES”). If the device fails the
test, remove the rst and second check
valves and thoroughly ush the device.
Clean rubber and seats of all debris and
place unit back in service.
4. Always consult local codes for installation methods, approvals and guidance.
TYPICAL HORIZONTAL ORIENTATION
OUTDOOR INSTALLATION
The Model 450 Backow Preventer may be installed outdoors only if the device is
protected against freezing conditions. Exposure to freezing conditions will result in
improper function or damage to the device. The installation location must be kept above
32°F. All the basic installation instructions apply.
INDOOR INSTALLATION
Indoor installation is preferred in areas
that are subject to freezing conditions. All
the basic installation instructions apply to
such installations.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects
or other reproductive harm.
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
Page 2
Testing Procedures
a company
®
®
HIGH SIDE HOSE
LOW SIDE HOSE
BY PASS HOSE
LOW SIDE BLEED
NEEDLE VALVE
(behind body)
HIGH SIDE BLEED
NEEDLE VALVE
(behind body)
BLEED TUBE
FILTERS
#1 TEST COCK
#2 TEST COCK
#2 SHUT-OFF
VALVE
#1 SHUT-OFF
VALVE
#4 TEST COCK
#3 TEST COCK
MODEL 450 DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #1 shall be at least
1.0 psid. If test cock #3 is not at the highest point of the check
valve body, then a vertical tube must be installed on test cock #3
so that it rises to the top of the check valve body.
PROCEDURE:
1. Slowly open all 4 test cocks to remove any foreign material
and attach ttings.
2. Attach hose from the high side of the test kit to the #2 test
cock.
3. Open test cock #2 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high side
bleed needle valve. If a tube is attached to test cock #3,
open test cock #3 to ll the tube. Close test cock #3.
Close #2 shut-off valve then close the #1 shut-off valve.
4. Hold gauge at same level as test cock #3 or water level in
tube. Slowly open test cock #3. Record the static pressure
drop across check valve #1 after gauge reading stabilizesand water stops running out of test cock #3.
5. Close all test cocks, open shut-off valve #1 and remove test
equipment.
TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least
1.0 psid. If test cock #4 is not at the highest point of the check
valve body, then a vertical tube must be installed on test cock #4
so that it rises to the top of the check valve body.
PROCEDURE:
1. Attach hose from the high side of the test kit to the #3 test cock.
2. Open test cock #3 and bleed all air from the hose and gauge
by opening the high side bleed needle valve. Close high
side bleed needle valve. If a tube is attached to test cock
#4, open test cock #4 to ll the tube. Close test cock #4.
Close #1 shut-off valve.
3. Hold gauge at same level as test cock #4 or water level in
tube. Slowly open test cock #4. Record the static pressure
drop across check valve #2 after gauge reading stabilizes
and water stops running out of test cock #4.
4. Close all test cocks, slowly open shut-off valve #1 & #2 and
remove test equipment.
2
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
Page 3
SEAT ASSEMBLY
SEAL RING
O-RING
(BOLT)
SEAL RETAINER
WASHER
BOLT
CHECK HANDLE
O-RING (SEAT)
Maintenance Instructions
a company
®
®
WIRE RETAINER
#1 CHECK ASSEMBLY
ACCESS COVER
GROOVED COUPLING
ASSEMBLY
#1 CHECK
ASSEMBLY
STEM
PLATE RETAINER
#2 CHECK ASSEMBLY
CHECK ASSEMBLY
All Model 450 Double Check Valve Backow Preventers must be
inspected and maintained by licensed personnel at least once
a year or more frequently as specied by local codes. Replacement of worn or damaged parts must only be made with genuine
“WILKINS” parts.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2. Carefully inspect rubber seal rings and o-rings for damage.
3. Test unit after reassembly for proper operation (refer to
“TESTING PROCEDURES”).
SERVICING CHECK VALVES
1. Close the outlet and then the inlet shut-off valves.
2. Open No. 2, 3 and 4 test cocks to release internal pressure.
Leave them open during check removal and reinstallation.
3. Loosen and remove the two nuts, bolts, gasket and grooved
coupling from around the access cover.
4. If the valve has a wire retainer on the #1 check assembly,
pinch together the exposed ends, pull toward the #2 check
and remove from valve.
5. If the valve has a plastic retainer on the #1 check, grasp one
of the exposed ends, push down and then pull toward the #2
check. The retainer should “spiral” out of the groove around
the check.
6. Remove the #2 check by locating one of the two spring-loaded
plate retainers around the face of the check. Pinch the sides
of the spring together and rotate the plates out of the body
groove one at a time. Remove the 2nd retainer the same way.
7. Always service the checks one at a time to avoid mixing parts. Start by removing the hardware and o-rings from the
back of the check assembly (See “Check Assembly” illustra-
tion). Separate the seal retainer from the assembly to expose
the seal ring.
8. Inspect the seal ring for cuts or embedded debris. If the reverse
side of the seal is unused, the seal ring can be inverted and
used temporarily until a new seal is obtained. Inspect seat
o-ring and replace if cut or damaged in any way.
9. Inspect valve cavity and seating areas. Flush with water to
remove any debris.
10.Reassembly: Lubricate the #2 check o-ring, install in the body
and close the #4 test cock. Install the #2 check retainers
into the body groove one plate at a time, squeezing the
spring ends together to clear the stops on the face of the seat.
Lubricate and install the #1 check, close the #2 test cock and
install:
(A) wire retainer by pinching the ends together, placing the
lower edge of the ring into the body groove below the check
and rotating the top of the ring into the notch above the check.
(B) plastic retainer by inserting the end with short tab into the
notch above the check, sliding your hand around the face of
the retainer pushing it into the groove as you go. Retainer
should “snap” into place.
11.Lubricate the outside surface of the grooved coupling gasket
Reassemble access cover and grooved coupling, making
sure the ends of the coupling touch each other. Close any
remaining open test cocks and place valve back in service.
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
SPECIFICATIONS
Maximum working water pressure: 175 PSI
Maximum working water temperature: 140°F
Hydrostatic test pressure: 350 PSI
End connections: Grooved AWWA C606
WILKINS, a ZURN company
3
Page 4
MODEL 450DA 4" & 6" (STANDARD & METRIC)
0
5
10
15
040080012001600
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.025.250.575.7100.9
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MODEL 450 4" & 6" (ST ANDARD & METRIC)
0
5
10
15
040080012001600
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.025.250.575.7100.9
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MODEL 450 2 1/2" & 3" (STAND AR D & METRIC)
0
5
10
15
0200400600800
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.012.625.237.950.5
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
a company
®
®
Troubleshooting
PROBLEMPOSSIBLE CAUSESCORRECTIVE ACTION
1. LEAKING CHECK VALVES1. Debris on seat or seal ring.1. Clean seat area
2. Damaged seat area2. Replace check assembly
3. Damaged seat o-ring 3. Replace seat o-ring
4. Damaged bolt o-ring(s) on check retainer4. Replace o-ring(s)
2. LOW OR NO FLOW1. Device installed backwards1. Verify ow direction arrow
2. Gate valves not fully open2. Turn handles counterclockwise
3. Low supply pressure3. Attach pressure gauge to test cock #1 and verify pressure
Performance Characteristics
2 1/2" (65mm)
4" (100mm)
3" (80mm)
6" (150mm)
4" (100mm)
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to WILKINS' specications and
Rated Flow (Established by approval agencies)
prevailing governmental & industry standards and codes and upon following these installation instructions. Failure to do so releases WILKINS of
any liability that it might otherwise have with respect to that device. Such failure could also result in an improperly functioning device.
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IS450 (REV. 11/10)