WILKINS 450, 450DA Instructions Manual

Page 1
Model 450 & 450DA
a company
®
PROTECTIVE ENCLOSURE
6" MIN.
WILKINS VALVE SETTER MJFS
DIRECTION OF FLOW
Double Check Valve Assembly (4” & 6”) Double Check Detector Assembly (4” & 6”)
Installation Testing Maintenance Instructions
(Patent No. 5,913,331)
INSTALLATION INSTRUCTIONS
CAUTION: Installation of Backow Preventers must be performed by qualied, licensed personnel. The installer should be sure the proper device has been selected for the particular installation. Faulty installation could result in an improperly functioning device.
WILKINS Model 450 Double Check Valve assemblies are for use on potable water lines where a health hazard does not exist in the event of a backow situation.
Damage to the device could result wherever water hammer and/or water thermal expan­sion could create excessive line pressure. Where this could occur, shock arrestors, check valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backow Preventer must never be submerged in water because this could cause a cross-connection. Make sure that the pit or vault always remains dry by providing ample drainage.
1. Before installing a Model 450 Backow Preventer, ush the line thoroughly to remove all debris, chips and other foreign matter. If required, a strainer should be placed upstream of the Backow Preventer. CAUTION: Do not use a strainer in seldom used emergency waterlines such as re lines.
2. Provide adequate space around the installed unit so that the test cocks will be accessible for testing and servicing.
3. Install valve at least 6 inches above surrounding ood level.
PLACING THE DEVICE IN SERVICE
1. Start with both shut-off valves closed. Slowly open the inlet shut-off valve until the backow preventer is completely pressur­ized.
2. When the unit has been pressurized, vent any trapped air by slightly opening each of the four test cocks.
3. Slowly open the downstream shut-off valve. The Model 450 Double Check Valve assembly is now in service.
4. After the Model 450 has been prop­erly installed, test the device (see “TEST PROCEDURES”). If the device fails the test, remove the rst and second check valves and thoroughly ush the device. Clean rubber and seats of all debris and place unit back in service.
4. Always consult local codes for installation methods, approvals and guidance.
TYPICAL HORIZONTAL ORIENTATION
OUTDOOR INSTALLATION
The Model 450 Backow Preventer may be installed outdoors only if the device is protected against freezing conditions. Exposure to freezing conditions will result in improper function or damage to the device. The installation location must be kept above 32°F. All the basic installation instructions apply.
INDOOR INSTALLATION
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply to such installations.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
Page 2
Testing Procedures
a company
®
®
HIGH SIDE HOSE
LOW SIDE HOSE
BY PASS HOSE
LOW SIDE BLEED NEEDLE VALVE (behind body)
HIGH SIDE BLEED
NEEDLE VALVE
(behind body)
BLEED TUBE
FILTERS
#1 TEST COCK
#2 TEST COCK
#2 SHUT-OFF
VALVE
#1 SHUT-OFF
VALVE
#4 TEST COCK
#3 TEST COCK
MODEL 450 DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #1 shall be at least
1.0 psid. If test cock #3 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #3 so that it rises to the top of the check valve body.
PROCEDURE:
1. Slowly open all 4 test cocks to remove any foreign material and attach ttings.
2. Attach hose from the high side of the test kit to the #2 test cock.
3. Open test cock #2 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. If a tube is attached to test cock #3, open test cock #3 to ll the tube. Close test cock #3. Close #2 shut-off valve then close the #1 shut-off valve.
4. Hold gauge at same level as test cock #3 or water level in tube. Slowly open test cock #3. Record the static pressure
drop across check valve #1 after gauge reading stabilizes and water stops running out of test cock #3.
5. Close all test cocks, open shut-off valve #1 and remove test equipment.
TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least
1.0 psid. If test cock #4 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #4 so that it rises to the top of the check valve body.
PROCEDURE:
1. Attach hose from the high side of the test kit to the #3 test cock.
2. Open test cock #3 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. If a tube is attached to test cock #4, open test cock #4 to ll the tube. Close test cock #4. Close #1 shut-off valve.
3. Hold gauge at same level as test cock #4 or water level in tube. Slowly open test cock #4. Record the static pressure drop across check valve #2 after gauge reading stabilizes and water stops running out of test cock #4.
4. Close all test cocks, slowly open shut-off valve #1 & #2 and remove test equipment.
2
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
Page 3
SEAT ASSEMBLY
SEAL RING
O-RING
(BOLT)
SEAL RETAINER
WASHER
BOLT
CHECK HANDLE
O-RING (SEAT)
Maintenance Instructions
a company
®
®
WIRE RETAINER
#1 CHECK ASSEMBLY
ACCESS COVER
GROOVED COUPLING ASSEMBLY
#1 CHECK ASSEMBLY
STEM
PLATE RETAINER #2 CHECK ASSEMBLY
CHECK ASSEMBLY
All Model 450 Double Check Valve Backow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specied by local codes. Replace­ment of worn or damaged parts must only be made with genuine “WILKINS” parts.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2. Carefully inspect rubber seal rings and o-rings for damage.
3. Test unit after reassembly for proper operation (refer to “TESTING PROCEDURES”).
SERVICING CHECK VALVES
1. Close the outlet and then the inlet shut-off valves.
2. Open No. 2, 3 and 4 test cocks to release internal pressure. Leave them open during check removal and reinstallation.
3. Loosen and remove the two nuts, bolts, gasket and grooved coupling from around the access cover.
4. If the valve has a wire retainer on the #1 check assembly, pinch together the exposed ends, pull toward the #2 check and remove from valve.
5. If the valve has a plastic retainer on the #1 check, grasp one of the exposed ends, push down and then pull toward the #2 check. The retainer should “spiral” out of the groove around the check.
6. Remove the #2 check by locating one of the two spring-loaded plate retainers around the face of the check. Pinch the sides of the spring together and rotate the plates out of the body groove one at a time. Remove the 2nd retainer the same way.
7. Always service the checks one at a time to avoid mixing parts. Start by removing the hardware and o-rings from the back of the check assembly (See “Check Assembly” illustra- tion). Separate the seal retainer from the assembly to expose the seal ring.
8. Inspect the seal ring for cuts or embedded debris. If the reverse side of the seal is unused, the seal ring can be inverted and used temporarily until a new seal is obtained. Inspect seat o-ring and replace if cut or damaged in any way.
9. Inspect valve cavity and seating areas. Flush with water to remove any debris.
10.Reassembly: Lubricate the #2 check o-ring, install in the body and close the #4 test cock. Install the #2 check retainers into the body groove one plate at a time, squeezing the spring ends together to clear the stops on the face of the seat. Lubricate and install the #1 check, close the #2 test cock and
install:
(A) wire retainer by pinching the ends together, placing the lower edge of the ring into the body groove below the check and rotating the top of the ring into the notch above the check. (B) plastic retainer by inserting the end with short tab into the notch above the check, sliding your hand around the face of the retainer pushing it into the groove as you go. Retainer should “snap” into place.
11.Lubricate the outside surface of the grooved coupling gasket Reassemble access cover and grooved coupling, making sure the ends of the coupling touch each other. Close any
remaining open test cocks and place valve back in service.
FIGURE 1 FIGURE 2 FIGURE 3
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
2 1/2" 75 112 149 224
3" 115 173 230 346 4" 198 298 397 595 6" 450 675 900 1351 8" 780 1169 1559 2339
10" 1229 1843 2458 3687
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
SPECIFICATIONS
Maximum working water pressure: 175 PSI
Maximum working water temperature: 140°F
Hydrostatic test pressure: 350 PSI
End connections: Grooved AWWA C606
WILKINS, a ZURN company
3
Page 4
MODEL 450DA 4" & 6" (STANDARD & METRIC)
0
5
10
15
0 400 800 1200 1600
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.0 25.2 50.5 75.7 100.9
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MODEL 450 4" & 6" (ST ANDARD & METRIC)
0
5
10
15
0 400 800 1200 1600
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.0 25.2 50.5 75.7 100.9
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MODEL 450 2 1/2" & 3" (STAND AR D & METRIC)
0
5
10
15
0 200 400 600 800
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.0 12.6 25.2 37.9 50.5
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
a company
®
®
Troubleshooting
PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION
1. LEAKING CHECK VALVES 1. Debris on seat or seal ring. 1. Clean seat area
2. Damaged seat area 2. Replace check assembly
3. Damaged seat o-ring 3. Replace seat o-ring
4. Damaged bolt o-ring(s) on check retainer 4. Replace o-ring(s)
2. LOW OR NO FLOW 1. Device installed backwards 1. Verify ow direction arrow
2. Gate valves not fully open 2. Turn handles counterclockwise
3. Low supply pressure 3. Attach pressure gauge to test cock #1 and verify pressure
Performance Characteristics
2 1/2" (65mm)
4" (100mm)
3" (80mm)
6" (150mm)
4" (100mm)
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to WILKINS' specications and
Rated Flow (Established by approval agencies)
prevailing governmental & industry standards and codes and upon following these installation instructions. Failure to do so releases WILKINS of any liability that it might otherwise have with respect to that device. Such failure could also result in an improperly functioning device.
WILKINS, a ZURN company