WILKINS 375XL, 375 Installation, Testing, Operation And Maintenance Manual

a company
®
a ® company
FLOOR DRAIN
INLET SHUT OFF
DIRECTION OF FLOW
12" MIN.
30” MAX.
AIR GAP
OPTIONAL WATER METER
175 PSIG 180ß F
3/4" 375 RP
ZURN
WILKINS
2” PIPE (DRAIN LINE CAN BE ANY STANDARD PIPING MATERIAL)
PROTECTIVE
ENCLOSURE
Model 375, 375XL
Reduced Pressure Principle (3/4"-1")
Installation Testing Maintenance Instructions
CAUTION: Installation of Backow Pre­venters must be performed by qualied, licensed personnel. The installer should be sure the proper device has been selected for the particular installation. Faulty installation could result in an
improperly functioning device.
Proper performance is dependent upon following these installation instructions and prevailing governmental and industry standards and codes. Failure to do so, according to WILKINS Limited Warranty "...releases WILKINS of any liability that it might otherwise have with respect to that device." Such failure could also result in an improperly functioning device.
Damage to the device could result wherever water hammer and/or water thermal expan­sion could create excessive line pressure. Where this could occur, shock arresters and/or pressure relief valves should be installed downstream of the device.
1. Before installing a Model 375 Backow Preventer, ush the line thoroughly to remove all debris, chips and other foreign matter. If re­quired, a strainer should be placed upstream of the Backow Preventer.
CAUTION: Do not use a strainer in sel­dom used emergency waterlines such as re lines.
3. WARNING: If installation of a Model
375 is in a building, a suitable drain ar­rangement MUST be provided to drain off spillage from the relief valve. An air gap at least two times the pipe diameter must be provided between the relief valve and the drain piping to prevent a cross­connection. Air Gap AG-11 not intended to support weight of drain pipe.
CAUTION: Do not pipe the relief valve solidly to a oor drain, sewer or sump.
CAUTION: An adequately sized drain is required to prevent possible water dam­age due to relief valve discharge.
4. Install valve at least 12 inches above surrounding ood level.
5. Always consult local codes for installa­tion methods, approvals and guidance.
OUTDOOR INSTALLATION
Model 375 Backow Preventers may be installed outdoors only if the device is protected against freezing conditions. Exposure to freezing conditions will result in improper function or damage to the device. The installation location must be kept above 32°F. All the basic installation instructions apply.
If installation is in a pit or vault, the Back­ow Preventer must never be submerged in water because this will cause a cross­connection. Make sure that the pit or vault always remains dry by providing ample drainage.
INDOOR INSTALLATION
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply to such installations.
PARALLEL INSTALLATION
PLACING THE DEVICE IN SERVICE
After the installation of a Model 375 has been completed, place the unit in service as follows:
375 REDUCED PRESSURE PRINCIPLE
3. Slowly open the downstream shut-off valve. The Model 375 Reduced Pressure Principle Backow Preventer is now in service.
4. If "spitting" or intermittent discharges from the relief valve are noted, it could be a result of pressure uctuation and/or a water hammer condition in the system. If such conditions exist, install a WILKINS water pressure reducing valve, a WILKINS Model 40XL check valve, or a WILKINS Model 1250 water hammer shock arrest­ers in compliance with industry standards as needed.
5. After the Model 375 has been prop­erly installed, test the device (see "TEST PROCEDURES"). If the device fails the test, remove the rst and second check valves and thoroughly ush the device. If the relief valve fails to operate properly, inspect the sensing passage for clogging (see "MAINTENANCE INSTRUCTIONS"). Clean rubber seals of all debris and place unit back in service.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
1
Testing Procedures
#1 TEST COCK
#2 TEST COCK
#3 TEST COCK
#4 TEST COCK
#1 SHUT-OFF VALVE
VENT HOSE
LOW SIDE HOSE
HIGH SIDE HOSE
BY-PASS VALVE "B"
BY-PASS VALVE "C"
BY-PASS
VALVE "A"
#2 SHUT-OFF
VALVE
175 PSIG 180ß F
3/4" 375 RP
ZURN
WILKINS
a ® company
MODEL 375 REDUCED PRESSURE PRINCIPLE
ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1
Purpose: Test #2 check valve for tightness against reverse ow. Requirement: The valve must close tight against reverse ow under all pressure differentials.
Procedure:
1. Attach the "HIGH" hose to test cock #2 and the "LOW" hose to test cock #3.
2. Close #2 shut-off valve.
3. Open test cocks #2 and #3.
4. Open by-pass valves "C" and "A" and bleed to atmosphere until all air is expelled.
5. Close by-pass valve "A". Open by-pass valve "B" and bleed to atmosphere until all air is expelled. Close by-pass valves "B" and "C".
6. Attach the "VENT" hose to test cock #4.
7. Slowly open by-pass valves "A" and "C" and keep by-pass valve "B" closed.
8. Open test cock #4.
9. Indicated pressure differential will drop slightly. If pressure differential does not continue to decrease, the #2 check valve is considered tight.
TEST NO. 2
Purpose: Test #1 check valve for tightness and record pressure drop across #1 check valve.
Requirement:
The static pressure drop across the #1 check valve should be at least 3.0 PSID greater than the relief valve opening point (TEST NO. 3).
Procedure:
1. Close by-pass valve "A"
2. Close test cock #4, and disconnect "VENT" hose from test cock #4.
3. Open by-pass valves "B" and "C" bleeding to atmosphere, then close by-pass valve "B" restoring the system to normal static condition.
4. Observe the pressure differential gauge and note this as the #1 check valve psid.
Maintenance Instructions
All Model 375 Reduced Pressure Principle Backow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specied by local codes. Replace­ment of worn or damaged parts must only be made with genuine "WILKINS" parts. The WILKINS Certicate of Limited Warranty provides that failure to do so "...releases WILKINS of any liability that it might otherwise have with respect to that device." Such failure could also result in an improperly functioning device.
The Model 375 Reduced Pressure Principle Assemblies should be thoroughly ushed after backow conditions occur to prevent any type of corrosive deterioration to its components. Failure to
do so could result in malfunction of the device.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2
TEST NO. 3 Purpose:
To test operation of the differential relief valve.
Requirement:
The pressure differential relief valve must operate to maintain the "ZONE" between the two check valves at least 2 PSID less than the supply pressure.
Procedure:
1. Close by-pass valve "C" and open by-pass valve "A".
2. Open by-pass valve "B" very slowly until differential gauge needle starts to drop. Hold the valve at this position and observe the gauge reading at the moment the rst dis­ charge is noted from the relief valve. Record this as the opening differential pressure of the relief valve.
WARRANTY: WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended. If in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight prepaid, to WILKINS within 12 months from date of purchase, it will be repaired or replaced free of charge. WILKINS liability shall be limited to our agreement to repair or replace the valve only.
2. Carefully inspect rubber seal rings, diaphragms and o-rings for damage.
3. Test unit after reassembly for proper operation (see "Testing Procedures").
SERVICING CHECK VALVES
1. Close inlet and outlet shut-off valves.
2. Open No. 2, No. 3 and No. 4 test cocks to release pressure from valve.
3. Unscrew clamp screws, and remove clamp. (inserting screw in center hole can remove stuck clamp). Slide sleeve toward inlet pipe. Slide valve body toward inlet and lift upward.
4. Using nger or blunt object, push in outlet end of body, both checks should slide out the body inlet. (A phillips screw driver will work in a 3/4" valve. The closed ball valve handle will work in a 1" valve).
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
WILKINS, a ZURN company
Loading...
+ 2 hidden pages