WILKINS 375XL, 375 Installation, Testing, Operation And Maintenance Manual

Page 1
a company
®
a ® company
FLOOR DRAIN
INLET SHUT OFF
DIRECTION OF FLOW
12" MIN.
30” MAX.
AIR GAP
OPTIONAL WATER METER
175 PSIG 180ß F
3/4" 375 RP
ZURN
WILKINS
2” PIPE (DRAIN LINE CAN BE ANY STANDARD PIPING MATERIAL)
PROTECTIVE
ENCLOSURE
Model 375, 375XL
Reduced Pressure Principle (3/4"-1")
Installation Testing Maintenance Instructions
CAUTION: Installation of Backow Pre­venters must be performed by qualied, licensed personnel. The installer should be sure the proper device has been selected for the particular installation. Faulty installation could result in an
improperly functioning device.
Proper performance is dependent upon following these installation instructions and prevailing governmental and industry standards and codes. Failure to do so, according to WILKINS Limited Warranty "...releases WILKINS of any liability that it might otherwise have with respect to that device." Such failure could also result in an improperly functioning device.
Damage to the device could result wherever water hammer and/or water thermal expan­sion could create excessive line pressure. Where this could occur, shock arresters and/or pressure relief valves should be installed downstream of the device.
1. Before installing a Model 375 Backow Preventer, ush the line thoroughly to remove all debris, chips and other foreign matter. If re­quired, a strainer should be placed upstream of the Backow Preventer.
CAUTION: Do not use a strainer in sel­dom used emergency waterlines such as re lines.
3. WARNING: If installation of a Model
375 is in a building, a suitable drain ar­rangement MUST be provided to drain off spillage from the relief valve. An air gap at least two times the pipe diameter must be provided between the relief valve and the drain piping to prevent a cross­connection. Air Gap AG-11 not intended to support weight of drain pipe.
CAUTION: Do not pipe the relief valve solidly to a oor drain, sewer or sump.
CAUTION: An adequately sized drain is required to prevent possible water dam­age due to relief valve discharge.
4. Install valve at least 12 inches above surrounding ood level.
5. Always consult local codes for installa­tion methods, approvals and guidance.
OUTDOOR INSTALLATION
Model 375 Backow Preventers may be installed outdoors only if the device is protected against freezing conditions. Exposure to freezing conditions will result in improper function or damage to the device. The installation location must be kept above 32°F. All the basic installation instructions apply.
If installation is in a pit or vault, the Back­ow Preventer must never be submerged in water because this will cause a cross­connection. Make sure that the pit or vault always remains dry by providing ample drainage.
INDOOR INSTALLATION
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply to such installations.
PARALLEL INSTALLATION
PLACING THE DEVICE IN SERVICE
After the installation of a Model 375 has been completed, place the unit in service as follows:
375 REDUCED PRESSURE PRINCIPLE
3. Slowly open the downstream shut-off valve. The Model 375 Reduced Pressure Principle Backow Preventer is now in service.
4. If "spitting" or intermittent discharges from the relief valve are noted, it could be a result of pressure uctuation and/or a water hammer condition in the system. If such conditions exist, install a WILKINS water pressure reducing valve, a WILKINS Model 40XL check valve, or a WILKINS Model 1250 water hammer shock arrest­ers in compliance with industry standards as needed.
5. After the Model 375 has been prop­erly installed, test the device (see "TEST PROCEDURES"). If the device fails the test, remove the rst and second check valves and thoroughly ush the device. If the relief valve fails to operate properly, inspect the sensing passage for clogging (see "MAINTENANCE INSTRUCTIONS"). Clean rubber seals of all debris and place unit back in service.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
1
Page 2
Testing Procedures
#1 TEST COCK
#2 TEST COCK
#3 TEST COCK
#4 TEST COCK
#1 SHUT-OFF VALVE
VENT HOSE
LOW SIDE HOSE
HIGH SIDE HOSE
BY-PASS VALVE "B"
BY-PASS VALVE "C"
BY-PASS
VALVE "A"
#2 SHUT-OFF
VALVE
175 PSIG 180ß F
3/4" 375 RP
ZURN
WILKINS
a ® company
MODEL 375 REDUCED PRESSURE PRINCIPLE
ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1
Purpose: Test #2 check valve for tightness against reverse ow. Requirement: The valve must close tight against reverse ow under all pressure differentials.
Procedure:
1. Attach the "HIGH" hose to test cock #2 and the "LOW" hose to test cock #3.
2. Close #2 shut-off valve.
3. Open test cocks #2 and #3.
4. Open by-pass valves "C" and "A" and bleed to atmosphere until all air is expelled.
5. Close by-pass valve "A". Open by-pass valve "B" and bleed to atmosphere until all air is expelled. Close by-pass valves "B" and "C".
6. Attach the "VENT" hose to test cock #4.
7. Slowly open by-pass valves "A" and "C" and keep by-pass valve "B" closed.
8. Open test cock #4.
9. Indicated pressure differential will drop slightly. If pressure differential does not continue to decrease, the #2 check valve is considered tight.
TEST NO. 2
Purpose: Test #1 check valve for tightness and record pressure drop across #1 check valve.
Requirement:
The static pressure drop across the #1 check valve should be at least 3.0 PSID greater than the relief valve opening point (TEST NO. 3).
Procedure:
1. Close by-pass valve "A"
2. Close test cock #4, and disconnect "VENT" hose from test cock #4.
3. Open by-pass valves "B" and "C" bleeding to atmosphere, then close by-pass valve "B" restoring the system to normal static condition.
4. Observe the pressure differential gauge and note this as the #1 check valve psid.
Maintenance Instructions
All Model 375 Reduced Pressure Principle Backow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specied by local codes. Replace­ment of worn or damaged parts must only be made with genuine "WILKINS" parts. The WILKINS Certicate of Limited Warranty provides that failure to do so "...releases WILKINS of any liability that it might otherwise have with respect to that device." Such failure could also result in an improperly functioning device.
The Model 375 Reduced Pressure Principle Assemblies should be thoroughly ushed after backow conditions occur to prevent any type of corrosive deterioration to its components. Failure to
do so could result in malfunction of the device.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2
TEST NO. 3 Purpose:
To test operation of the differential relief valve.
Requirement:
The pressure differential relief valve must operate to maintain the "ZONE" between the two check valves at least 2 PSID less than the supply pressure.
Procedure:
1. Close by-pass valve "C" and open by-pass valve "A".
2. Open by-pass valve "B" very slowly until differential gauge needle starts to drop. Hold the valve at this position and observe the gauge reading at the moment the rst dis­ charge is noted from the relief valve. Record this as the opening differential pressure of the relief valve.
WARRANTY: WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended. If in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight prepaid, to WILKINS within 12 months from date of purchase, it will be repaired or replaced free of charge. WILKINS liability shall be limited to our agreement to repair or replace the valve only.
2. Carefully inspect rubber seal rings, diaphragms and o-rings for damage.
3. Test unit after reassembly for proper operation (see "Testing Procedures").
SERVICING CHECK VALVES
1. Close inlet and outlet shut-off valves.
2. Open No. 2, No. 3 and No. 4 test cocks to release pressure from valve.
3. Unscrew clamp screws, and remove clamp. (inserting screw in center hole can remove stuck clamp). Slide sleeve toward inlet pipe. Slide valve body toward inlet and lift upward.
4. Using nger or blunt object, push in outlet end of body, both checks should slide out the body inlet. (A phillips screw driver will work in a 3/4" valve. The closed ball valve handle will work in a 1" valve).
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
WILKINS, a ZURN company
Page 3
a ® company
Maintenance Instructions
SEAT O-RING #1 CHECK SEAT POPPET SCREW SEAL RING RETAINER
POPPET SEAL RING
POPPET
#1 CHECK SPRING
#1 CHECK SPRING RETAINER
#2 CHECK ASSY.
BODY INLET O-RING
BODY
BODY OUTLET O-RING
RV COVER O-RING
RV DIAPHRAGM
RV UPPER PLUNGER
RV COVER BOLT S
RV COVER
RV PLUNGER O-RING
RV LOWER PLUNGER
RV SEAL RING
RV SCREW
RV SPRING
RV SEAT
RV SEAT O-RING
SLEEVE
SLEEVE O-RING
CLAMP
CLAMP BOLT S
MODEL 375 3/4” - 1”
5. Twist spring retainers counter-clockwise to remove from seat and access poppets.
6. Inspect the rubber seal ring for cuts or embedded debris. To remove seal ring, remove screw and seal ring retainer. If the reverse side of the seal ring is unused, it is possible to invert the seal ring. This would be considered a temporary solution to xing a fouled check and should be replaced with a new seal ring as soon as possible.
7. Inspect seat surface for nicks or dings and replace if necessary. Use ngernail to check for dings. Re-grease seat o-rings.
8. Inspect seat o-ring sealing areas in body and wipe clean.
9. Reverse the above procedures to reinstall check valve assembly. (Drop #2 check assembly in body. Then drop #1 check assembly in and turn until #1 spring retainer lines up with #2 seat. Then push both assemblies into body.) Care should be taken to make sure the heavy spring is installed in the No. 1 check valve. Do not overtighten clamp screws as this can cause leak at the sleeve o-ring.
SERVICING RELIEF VALVE
1. Remove relief valve cover screws and cover. Gently pull on diaphragm to remove the cartridge assembly.
2. Inspect seal ring for cuts and embedded debris. Turn over or replace if required.
3. Disassemble cartridge by unscrewing relief valve retaining screw.
4. Inspect diaphragm and o-ring for damage. Replace required parts and apply a light coat of grease to plunger o-ring, and place on plunger.
5. Carefully reassemble cartridge assembly.
6. Inspect relief valve seat for wear on seating surface. If damaged, replace seat and seat o-ring. (Twist seat and o-ring while inserting to keep it from popping out.
7. Insert cartridge assembly into relief valve cover.
8. Check cover o-ring in groove on body. Clean or replace as necessary.
9. Replace relief valve cover and cover screws.
10. Place device in service and test per "TESTING PROCEDURES".
Troubleshooting
When the relief valve discharges intermittently it can be almost always assumed that the device is functioning correctly and that the discharge is caused
by systems problem such as inlet pressure uctuations or water hammer due to quick closing valves.
1. SUDDEN OR RAPID SPITTING
2. LIGHT INTERMITTENT DRIP
Continuous discharge of the relief valve signies a failure of some part of the device. To help determine the specic area of failure, close the #2 shut­off valve. If the discharge stops, the #2 check requires service. If the discharge continues, the #1 check requires service.
1. CONTINUOUS DISCHARGE 1. Fouled #1 check.
In summation, the amount of discharge is proportional to degree of fouling. Most problems occur in the #1 check which is where debris enters the backow preventer rst.
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to WILKINS' specica­tions and prevailing governmental & industry standards and codes and upon following these installation instructions. Failure to do so releases WILKINS of any liability that it might otherwise have with respect to that device. Such failure could also result in an improperly functioning device.
PROBLEM
1. Drop in inlet pressure.
2. Sudden increase in downstream pressure due to water hammer from quick closing shut-off valve installed downstream.
1. Slightly fouled #1 check
2. Fouled relief valve seat.
3. Fouled #2 check.
POSSIBLE CAUSES
SPECIFICATIONS
Maximum working water pressure 175 PSI Maximum working water temp. 180◦°F Hydrostatic 350 PSI End connections Threaded NPT ANSI B1.20.1
A. Install an in-line spring loaded check valve upstream of backow. (WILKINS
Model 40XL)
B. Install pressure reducing valve up stream of backow unit. (WILKINS Model
BR4 or NR3XL)
C. Install in-line spring loaded check valve downstream of backow as close to source as possible, but not closer than 4 feet. (WILKINS Model 40XL)
A. Clean #1 check and turn check valve seal ring over or replace.
A. Clean check valves and turn check valve seal rings over or replace. B. Clean relief valve seat and turn relief valve seal ring over or replace.
CORRECTIVE ACTION
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
3
Page 4
MODEL 375, 475 & 975 RP & RPDA
0
50
100
150
200
0 200 400 600 800
FLOW RATE (U.S. GPM)
ZONE PRESSURE (U.S. PSIG)
Blow Out / Flush Procedure for Freeze Protection
FLUSH OUT HOSE
HOSE TO AIR COMPRESSOR
AIR INLET BLOW OUT CONNECTION (6)
BLOW OUT/ FLUSH FITTING
FLUSH OUT PORT (7)
(ADAPTERS AND HOSES PROVIDED BY OTHERS)
OUTLET SHUT-OFF VA LVE (5)
AIR INLET BLOW OUT CONNECTION (6) 3/4” NPT
BLOW OUT/ FLUSH FITTING
FLUSH OUT PORT (7) 3/4” NPT
CHECK HOUSING
MAIN SHUT-OFF VA LVE (1)
DRAIN
INLET DRAIN VA LVE (2)
DIRECTION OF FLOW
DRAIN
TEST COCK (4)
MODEL 375
INLET SHUT-OFF VA LVE (3)
LEAVE BALL VA LVES AND TEST COCKS 1/2 OPEN TO PREVENT FREEZE DAMAGE
(RK34-375BOF, RK1-375BOF)
To Blow Out System for freeze protection, use the following procedure:
1. Turn off main shut-off valve (1) that supplies water to the system.
2. Open inlet drain valve in the system (2). Open inlet and outlet shut-off valves on the backow preventer (3 & 5) and all of the test cocks (4). Leave all valves and test cocks in the half open/half closed (45°) position to allow full drainage of the ball valves and test cocks.
3. Remove black backow preventer housing. Replace with orange Blow Out / Flush tting. Store backow preventer housing in a safe location for winter. Orange Blow Out / Flush tting may remain in valve body during winter. Place plugs in ports to keep debris from entering housing.
4. A hose and adapter can be connected to ush out port (7) to drain water to a safe drain.
5. Connect an air hose and adapter to the air inlet connection (6). Inject an adequate volume of air to remove all water from the downstream portion of the system. Do not allow the tting to overheat.
6. Leave drain valve (2), shut-off valves (3 & 5) and test cocks (4) in the half open/half closed position (45°) for the duration of the winter to prevent freezing.
7. Store valve housing/check assemblies, clamp/sleeve and o-rings in sealed plastic bag during winter to prevent weathering.
To Flush System during installation, use the following procedures:
1. Install backow device in pipe system, leave water off.
2. Remove the black backow preventer housing from the bronze body.
3. Install the orange Blow Out / Flush tting into the bronze body.
4. Thread a garden hose adapter into Flush-Out port (7). Connect a hose to the adapter and run to a safe drain. Shut-off valves (3) and (4) should be open.
5. Turn on water supply at main shut-off valve (1) to ush out any debris in the pipe. Turn water off.
6. Remove orange Blow-Out / Flush tting and replace black check housing back into the line. Close shut-off valves (3) and (4). Turn water on at main shut-off (1).
7. Slowly open shut-off valve (3) to pressurize backow preventer. Once fully open, pressurize system by slowly opening shut-off valve (4).
CAUTION: For freeze protection be certain that main shut-off valve (1) remains tightly closed to prevent relling of the system. Also, the main shut-off valve must be resilient seated to insure no leakage of water into the system.
Performance Characteristics
(Worst case condition- If 1st check or relief valve is lodged wide open)
4
IS375-34-1 (REV. 3/09)
Relief Valve Discharge Rates
BACKFLOW PREVENTERS
3/4" - 1"
1-1/4" - 2"
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/2" 5 7 9 14 3/4" 8 12 17 25
1" 13 20 27 40
2-1/4" - 6"
8" - 10"
1 1/4" 23 35 47 70 1 1/2" 32 48 63 95
2" 52 78 105 167
REPAIR KITS FOR 375's
BLOW OUT/FLUSH FITTING VESSEL
3/4" RK34-375BOF 3/4" RK34-375V
1" RK1-375BOF 1" RK1-375V
COMPLETE INTERNALS WEDGE/CLAMP
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
3/4" RK34-375 3/4" RK34-375W
1" RK1-375 1" RK1-375W
RUBBER PARTS
3/4" RK34-375R
BLOW OUT/ FLUSH FITTING
1" RK1-375R
WILKINS, a ZURN company
Loading...