WILKINS 350, 350ADA, 350DA, 350A Installation And Testing Instructions

Page 1
a company
®
®
Model 350, 350A, 350ADA & 350DA
DIRECTION OF FLOW
12" MIN.
30" MAX.
DIRECTION OF FLOW
Double Check Valve Assembly (8”, 10” & 12”) and Double Check Valve Detector Assembly (8”, 10” & 12”)
Installation Testing  Maintenance Instructions
(Patent No. 5,913,331)
CAUTION: Installation of Backow Preventers must be performed by qualied, licensed personnel. The installer should be sure the proper device has been selected for the particular installation. Faulty installation could result in an improperly functioning device.
WILKINS Model 350 Double Check Valve assemblies are for use on potable water lines where a health hazard does not exist in the event of a backow situation.
Damage to the device could result wherever water hammer and/or water thermal expan­sion could create excessive line pressure. Where this could occur, shock arrestors, check valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backow Preventer must never be submerged in water because this could cause a cross-connection. Make sure that the pit or vault always remains dry by providing ample drainage.
1. Before installing a Model 350 Backow Preventer, ush the line thoroughly to remove all debris, chips and other foreign matter. If required, a strainer should be placed upstream of the Backow Preventer. CAUTION: Do not use a strainer in seldom used emergency waterlines such as re lines.
2. Provide adequate space around the installed unit so that the test cocks will be accessible for testing and servicing.
3. Install valve at least 12 inches above surrounding ood level.
PLACING THE DEVICE IN SERVICE
1. Start with both shut-off valves closed. Slowly open the inlet shut-off valve until the backow preventer is completely pressur­ized.
2. When the unit has been pressurized, vent any trapped air by slightly opening each of the four test cocks.
3. Slowly open the downstream shut-off valve. The Model 350 Double Check Valve assembly is now in service.
4. After the Model 350 has been properly installed, test the device (see “TEST PRO­CEDURES”). If the device fails the test, remove the rst and second check valves and thoroughly ush the device. Clean rub­ber and seats of all debris and place unit back in service.
4. Always consult local codes for installation methods, approvals and guidance.
OUTDOOR INSTALLATION
The Model 350 Backow Preventer may be installed outdoors only if the device is protected against freezing conditions. Exposure to freezing conditions will result in improper function or damage to the device. The installation location must be kept above 32°F. All the basic installation instructions apply.
INDOOR INSTALLATION
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply to such installations.
VERTICAL INSTALLATION
Vertical installation is acceptable in ap­plications where inlet and outlet piping are flowing vertically upwards. All the basic installation instructions apply to such installations. Consult factory for approval status.
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
1
Page 2
VENT HOSE
LOW SIDE HOSE
HIGH SIDE HOSE
LOW SIDE BLEED NEEDLE VALVE
#1 TEST COCK
#4 TEST COCK
#3 TEST COCK
#2 TEST COCK
#2 SHUT-OFF VALVE
#1 SHUT-OFF
VALVE
HIGH SIDE BLEED
NEEDLE VALVE
Testing Procedures
a company
®
®
MODEL 350 DOUBLE CHECK VALVE ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #1 shall be at least
1.0 psid. If test cock #3 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #3 so that it rises to the top of the check valve body.
PROCEDURE:
1. Slowly open all 4 test cocks to remove any foreign material and attach ttings.
2. Attach hose from the high side of the test kit to the #2 test cock.
3. Open test cock #2 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. If a tube is attached to test cock #3, open test cock #3 to ll the tube. Close test cock #3. Close #2 shut-off valve then close the #1 shut-off valve.
4. Hold gauge at same level as test cock #3 or water level in tube. Slowly open test cock #3. Record the static pressure drop across check valve #1 after gauge reading stabilizes and water stops running out of test cock #3.
5. Close all test cocks, open shut-off valve #1 and remove test equipment.
TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE
REQUIREMENT:
The static pressure drop across check valve #2 shall be at least
1.0 psid. If test cock #4 is not at the highest point of the check valve body, then a vertical tube must be installed on test cock #4 so that it rises to the top of the check valve body.
PROCEDURE:
1. Attach hose from the high side of the test kit to the #3 test cock.
2. Open test cock #3 and bleed all air from the hose and gauge by opening the high side bleed needle valve. Close high side bleed needle valve. If a tube is attached to test cock #4, open test cock #4 to ll the tube. Close test cock #4. Close #1 shut-off valve.
3. Hold gauge at same level as test cock #4 or water level in tube. Slowly open test cock #4. Record the static pressure drop across check valve #2 after gauge reading stabilizes and water stops running out of test cock #4.
4. Close all test cocks, slowly open shut-off valve #1 & #2 and remove test equipment.
WILKINS, a ZURN company
2
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
Page 3
#1 CHECK ASSEMBLY
#2 CHECK ASSEMBL
Y
Maintenance Instructions
a company
®
®
SEAT ASSEMBLY
SEAL RING
O-RING (BOLT)
RETAINER
WASHER
BOLT
CHECK ASSEMBLY
SERVICING CHECK VALVES
A ratchet wrench, 11/16” deep socket, and a 4” long extension are recommended for removing check assemblies.
1. Close inlet and outlet shut-off valves.
2. Open No. 2, No. 3 and No. 4 test cocks to release pressure from valve.
3. Loosen & remove the grooved coupling around the access cover. Remove cover.
4. To service only the #1 check assembly, remove the 6 bolts, washers and o-rings from the back of the #1 check assembly. Separate the retainer and the seal ring from the check assembly and proceed to step #8.
5. To service both checks or the #2 check, the #1 check assembly must rst be removed. Remove the 4 nuts and washers retaining the #1 check assembly. Remove the #1 check assembly from the body.
All Model 350 Double Check Valve Backow Preventers must be inspected and maintained by licensed personnel at least once a year or more frequently as specied by local codes. Replace­ment of worn or damaged parts must only be made with genuine “WILKINS” parts.
GENERAL MAINTENANCE
1. Clean all parts thoroughly with water after disassembly.
2. Carefully inspect rubber seal rings and o-rings for damage.
3. Test unit after reassembly for proper operation (refer to “TESTING PROCEDURES”).
6. To remove the #2 check assembly, remove the 7 nuts, washers and the #2 check retaining ring. Grasp the check assembly by the stem and remove from valve.
7. Remove all 6 bolts, washers and o-rings from the check assembly (See “Check Assembly” illustration). Separate retainer from check assembly to expose seal ring for inspection.
8. Inspect the rubber seal ring for cuts or embedded debris. If the reverse side of the seal ring is unused, it is possible to invert the seal ring. This would be considered a temporary solution to xing a fouled check and should be replaced with a new seal ring as soon as possible.
9. Inspect valve cavity and seating areas. Remove any debris.
10. Reverse the above procedures to reinstall check assemblies. Lubricate seat o-rings to hold them in place while reinstalling seat. Place washers on studs and tighten retaining nuts evenly.
11. Reinstall access cover and grooved coupling.
NOTE: If any portion of the seat assembly is damaged or missing or if the seat sealing rib is damaged in any way, do not attempt to eld repair it. Contact your local WILKINS representative for assistance.
WILKINS, a ZURN company
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
3
Page 4
MOD EL 35 0D A 8 ", 10" & 12 " (ST AND AR D & M ETR IC )
0
5
10
15
0 1000 2000 3000 4000
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
34
69
103
0.0 63.1 126.2 189.3 252.4
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MOD EL 35 0AD A 8 " & 1 0" (S TA ND ARD & ME TR IC)
0
5
10
15
0 1000 2000 3000 4000
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
35
69
104
0.0 63.1 126.2 189.3 252.4
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MOD EL 35 0A 8 " & 1 0" (ST AND AR D & ME TR IC)
0
5
10
15
0 1000 2 000 30 00 400 0
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
0
35
69
104
0.0 6 3.1 12 6.2 189. 3 25 2.4
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
MOD EL 35 0 8 ", 10 " & 12 " (ST AND AR D & ME TR IC)
0
5
10
15
0 1000 2000 3000 40 00
FLOW RATES (GPM)
PRESSURELOSS (PSIG)
0
35
69
104
0.0 63.0 12 6.0 189. 0 252.0
FLOW RATES (l/s)
PRESSURE LOSS (kpa)
Troubleshooting
PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION
1. LEAKING CHECK VALVES 1. Debris on seat or seal ring. 1. Clean seat area
2. Damaged seat area 2. Replace check assembly
3. Damaged seat o-ring 3. Replace seat o-ring
4. Damaged bolt o-ring(s) on check retainer 4. Replace o-ring(s)
2. LOW OR NO FLOW 1. Device installed backwards 1. Verify ow direction arrow
2. Gate valves not fully open 2. Turn handles counterclockwise
3. Low supply pressure 3. Attach pressure gauge to test cock #1 and verify pressure
Repair Kits
SIZE MODEL 350 CHECKS ONLY
8" RK8-350
10" RK8-350
Performance Characteristics
12" (300mm)
8" (200mm)
10" (250mm)
8" (200mm)
Rated Flow (Established by approval agencies)
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
2 1/2" 75 112 149 224
3" 115 173 230 346 4" 198 298 397 595 6" 450 675 900 1351
8" 780 1169 1559 2339 10" 1229 1843 2458 3687
12" 1763 2644 3525 5288
10" (250mm)
10" (250mm)
8" (200mm)
8" (200mm)
10" (250mm)
12" (300mm)
SPECIFICATIONS
Maximum working water pressure: 175 PSI Maximum working water temperature: 140°F Hydrostatic test pressure: 350 PSI
End connections: Flanged ANSI B16.1 Class 125
Proper performance is dependent upon licensed, qualied personnel performing regular, periodic testing according to WILKINS' specications and prevailing governmental & industry standards and codes and upon following these installation instructions. Failure to do so releases WILKINS of any liability that it might otherwise have with respect to that device. Such failure could also result in an improperly functioning device.
IS350-8 (REV. 10/11)
1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
WILKINS, a ZURN company
4
Loading...