Wilkerson ER2 User Manual

Richland, MI 49083 Tel: (269) 629-5000
Installation & Service Instructions 83-130-000
Electronic Regulator Model ER1 / ER2
ISSUED: February, 2005 Supersedes: July, 2004
Doc. #83-130-000, ECN # 050149, Rev. 4
WARNING
!
To avoid unpredictable system behavior that can cause personal injury and property damage:
• Disconnect electrical supply (when necessary) before installation, servicing, or conversion.
• Disconnect air supply and depressurize all air lines connected to this product before installation, servicing, or conversion.
• Operate within the manufacturer’s specified pressure, temperature, and other conditions listed in these instructions.
• Medium must be moisture-free if ambient temperature is below freezing.
• Service according to procedures listed in these instructions.
• Installation, service, and conversion of these products must be performed by knowledgeable personnel who understand how pneumatic products are to be applied.
• After installation, servicing, or conversion, air and electrical supplies (when necessary) should be connected and the product tested for proper function and leakage. If audible leakage is present, or the product does not operate properly, do not put into use.
• Warnings and specifications on the product should not be covered by paint, etc. If masking is not possible, contact your local representative for replacement labels.
! WARNING
Product rupture can cause serious injury.
Do not connect regulator to bottled gas.
Do not exceed maximum primary pressure rating.
Control
Board
Housing
Intake / Exhaust
Valve
(2 Required)
Housing
Gasket
Filter
Upper
Diaphragm
Filter
Screw (2 Required) For LCD Housing
LCD Housing
LCD Cover
Standard
Housing
Screw (3 Required) For Control Board Housing
Strain Relief
Standard or LCD Control Board
O-Ring
Body Cap
Restrictor
Mid-Plate
WARNING
!
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from The Company, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure and review the information concerning the product or systems in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by The Company and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
Lower
Diaphragm
Inlet Port
Valve Stem
and Base
Bottom
Plug
Body
Outlet Port
O-Ring
Insert
Spring
O-Ring
Description
The ERl and ER2 are high flow electro-pneumatic regulators capable of delivering accurate pressures over a wide range of flows. The units have a variety of port sizes, ranging from 1/4 inch to 3/4 inch NPT and “G” series threads and use the convenient Wilkerson 18/28 series modular mounting. The ER series consists of an integral system of two control valves and feedback transducer to provide closed-loop control. In addition the units come with an optional LCD display that displays the outlet pressure in psig or bar.
The ER series regulators are controlled by either a 0–10 VDC or 4–20 mA external input signal, or by internal adjustment for stand- alone operation. The control signal is compared to the output signal of the internal pressure sensor and the regulator adjusts the pressure accordingly. The pressure sensor signal is also an output of 0–10 VDC for external monitoring.
Powe r Supply 12–28 VDC
+–
Comparator / Controller
Command Signal 0–10 VDC 4–20 mA
E
P
Sensor
IN
OUT
Installation
Mechanical Installation
!
1. Refer to the WARNING above.
2. Do not install until you have read the entire product information sheet.
3. Minimum inlet pressure ............................. 20 psig (1.4 bar)
Maximum inlet pressure ........................ 150 psig (10.3 bar)
Minimum temperature ..................................... 40°F (4.4°C)
Maximum temperature ................................ 125°F (51.6°C)
4. Prior to installation, ensure that the pressure in the line where this product is to be connected is at atmospheric pressure 0 psig (0 bar).
5. Install a quality Wilkerson filter upstream of the unit for maximum trouble free operation.
6. Install with the air flow in the same direction as the arrow on the unit. DO NOT restrict the air flow with undersize piping or fittings, unless maximum flow is not required.
Electrical Connection
Since the same control board is used for all control signal options
(Figure 3A)
board must be configured for each particular application by positioning the jumpers correctly and wiring correctly. This is a
very important step to ensure optimum performance.
Determine what signal you will be using to control the regulator and follow the instructions for that application. The control board must be configured and wired accordingly.
to provide maximum flexibility at minimum cost, the
!
Caution: Improper wiring may result in damage to the unit.
To configure the unit for the desired option, and to connect the external wires to unit, remove the housing by removing the two screws on top of the unit off and lay it to one side, making sure not to damage the ribbon cable that connects the control board to the LCD board.
The jumpers should be configured correctly from the factory for the configuration ordered and will only need to be
changed if once the unit is received, the user decides on different control signal, pressure display or pressure range.
(Refer to Figure 2)
Option #1 Sensor feedback signal
Internal sensor ................................. Jumper on position #5
Option #2 LCD display mode
a. psig............................................... Jumper on position #4
b. bar ................................................ Jumper off position #4
NOTE: If using bar option, be careful not to lose jumper.
Option #3 Control signal
a. 0–10 VDC .................................... Jumper on position #1
b. Internal control ............................. Jumper on position #2
c. 4–20 mA ....................................... Jumper on position #3
NOTE: Only one control signal at a time can be used.
Option #4 Pressure Range
Each control board has two pressure ranges available and can be selected by the Jumper on position #7
The high range board can be configured for either:
a. 0–90 psig (0–6 bar) .....................Jumper on position #7
b. 0–125 psig (0–8,6 bar) ................Jumper off position #7
The low range board can be configured for either:
a. 0–30 psig (0–2 bar) .....................Jumper on position #7
b. 0–60 psig (0–4 bar) .....................Jumper off position #7
First feed the cable through the strain relief provided and remove the retaining nut for the strain relief. Now feed the wires through the hole in the control board housing, slide the retaining nut over the wires and secure the strain relief to the housing making sure to have the required amount of wire to connect them to the terminal block. Once this is completed you can connect the wires to the terminal block as the following describes.
Now, with the unit configured to the desired options, the external electrical connection of the unit can be done. This is accomplished by securing the wires directly to the control board terminal block on the upper right hand side of the unit
(Figure 3)
required number of wires for your application be used to connect the unit if using an external control and monitor signal. The shield should be connected to the supply ground and not to the unit. If using the internal control, only a supply voltage will be required, although the monitor signal can be used.
. It is recommended that a shielded cable with the
(Figure 4)
. Carefully lift the housing
or
or
or
or
Loading...
+ 4 hidden pages