97017 Rev B.1 10/18 Page 20 of 23
Note: Alarm will be on or off based on current state of alarm (allowing scroll-through
programming without changing state). Alarm will be left on or off until the end of programmingmode
2.t. Alarm#2, Type of alarm
L.o. Alarm activates when 4-20mA signal is lower than trip-point
H.i. Alarm activates when 4-20mA signal is higher than trip-point
b.o. Alarm activates when BOV is outside of hysteresis range
o.F. Alarm has no function (always off except for error setting)
Note: b.o. only displays if S.i. (source) is set for TBUS data
2.P. Alarm#2, trip-Point (%)
00 Minimum programmable setting, 0% or 0V
99 Maximum programmable setting, 99%
24 Maximum programmable setting, 24V
Programmable to any percentage between 00 and 99 for H.i. or L.o.
Programmable to any integer voltage between 00 and 24 for b.o.
2.H. Alarm#2, Hysteresis (allowable operation span from trip-point)
00 Minimum programmable setting, 0% or 0V
99 Maximum programmable setting, 99%
24 Maximum programmable setting, 24V
Programmable to any percentage between 00 and 99 for H.i. or L.o.
Programmable to any integer voltage between 00 and 24 for b.o.
2.n. Alarm#2, Alarm turn-on delay (fault must exist for this time to activate)
00 Minimum programmable setting, 0-seconds
99 Maximum programmable setting, 99-seconds
Programmable to any integer second between 00 and 99
Note: Internal signal interrogation takes 1-second, so actual delay is 01-second to 100-seconds
after fault
2.F. Alarm#2, Alarm turn-off delay (fault must clear for this time to reset)
00 Minimum programmable setting, 0-seconds
99 Maximum programmable setting, 99-seconds
Programmable to any integer second between 00 and 99
Note: Internal signal interrogation takes 1-second, so actual delay is 01-second to 100-seconds
after no-fault condition
2.A. Alarm#2, manually activate alarm
o.n. Alarm#1 is manually-activated
o.F. Alarm#1 is not manually-activated
Note: Alarm will be on or off based on current state of alarm (allowing scroll-through programming
without changing state). Alarm will be left on or off until the end of programming-mode
3.t. Alarm#3, Type of alarm
L.o. Alarm activates when 4-20mA signal is lower than trip-point
H.i. Alarm activates when 4-20mA signal is higher than trip-point
b.o. Alarm activates when BOV is outside of hysteresis range
o.F. Alarm has no function (always off except for error setting)