WIKORA WIKOSOL TWIN TRIVALENT Installation Manual Operating Instructions

© Wikora GmbH Page 1 As of November 2013 Errors excepted.
WIKORA GmbH
89568 Hermaringen
Phone: (07322) 9605-0
Fax: (07322) 9605-30
email: contact@wikora.de
Installation manual Operating instructions
Solar combi tank with DHW heat exchanger
WIKOSOL TWIN TRIVALENT
Installation and commissioning must be undertaken by a specialist.
General terms and conditions of warranty state that all installations must be carried out by a suitably trained and qualified plumber who observes the local norms and regulations.
The installation and maintenance record must be entirely completed and the user has to be instructed accordingly.
Efficient operation can only be guaranteed if the instructions of this manual are followed. Warranty does not cover any damage caused due to non-observance of this manual and the technical rules in force. The system is to be checked annually by a specialized company. In addition, occurring defects must be repaired immediately.
This document should be handed over to the client on completion of the installation.
.
Index
1 General ................................................................................................................................................................................... 2
2 Transport and installation ....................................................................................................................................................... 2
3 Dimensions and connections .................................................................................................................................................. 3
4 Technical data ........................................................................................................................................................................ 4
5 Installation .............................................................................................................................................................................. 5
6 Commissioning ....................................................................................................................................................................... 6
7 Maintenance and wear parts .................................................................................................................................................. 6
8 Warranties and guarantee ...................................................................................................................................................... 7
9 Installation record ................................................................................................................................................................... 8
© Wikora GmbH Page 2 As of November 2013 Errors excepted.
1 General
Depending on the type and design, W IKORA tanks are suitable for heating and / or storing DHW and / or heating water. The heating is achieved indirectly via heat generators, if applicable, from different heat sources. The maximum working pressure and working temperature can be found in the technical data.
Set-up, installation and commissioning must be undertaken by a qualified specialist, who must observe these instructions.
The site of installation must be frost-protected according to DIN 4753 and should be in direct proximity to the heat generator.
When setting-up and installing the tank, the following regulations should be considered: In addition to the technical rules in force DIN 1988, DIN 18160, DIN 4753, DIN 4109, DIN 4708, DIN 4751 section 2-4 energy conservation law and VDE regulations are to be observed. Moreover, the relevant regulations of the suppliers as well as legal building regulations are to be considered.
Important: The exhaust pipe must be at least as big as the safety valve outlet in width. It may not have more than 2 bends and should not be longer than 2 m. If for any compelling reasons 3 bends or a length up to 4 m are required, then the entire exhaust line must be designed one nominal size larger. More than 3 bends, or a length exceeding 4 m is prohibited. The exhaust pipe must be installed with downward gradient. The drain line behind the funnel must feature at least the double width of the valve entrance. A sign is to be attached close to the exhaust pipe of the safety valve or on the safety valve itself. „For safety reasons water may leak from the exhaust pipe during the heating process! Do not lock! "The operability of the safety valve is to be checked at regular intervals by means of de-ventilation.
2 Transport and installation
In order to prevent damage during transport, the packaging should only be removed at the site of installation. During shipment, it should be ensured that the tank does not come in contact with any spiky or sharp items, nor is damaged through dropping or knocks. During installation, the tank must be disconnected from any humidity carrying components. Moreover, sufficient space for maintenance and cleaning purposes should be kept free in front of, beside, above and behind the tank.
Please note that the insulation provided should be kept in a dry place at least 24 hours at a minimum temperature of 20°C before installation.
© Wikora GmbH Page 3 As of November 2013 Errors excepted.
3 Dimensions and connections
Illustration 1
Dimensions:
Type
d D
E F H
K
(K) L (L1)
M N U V W R O
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
[mm] [mm]
[mm]
[mm] [mm]
Wikosol Twin Trivalent 600
790 990 957 1397 1623
1562 (832)
282
(842)
732 282 1082 552 1630 832 157
Wikosol Twin Trivalent 800
790 990 1357 1797 2023
1962
(1032)
282
(1107)
832 282 1382 602 2030 977 157
Chart 1
W = Tilting dimension
Connections:
Type Wikosol Twin
Trivalent
600
Wikoso Twin Trivalent 800
Cold water / hot water 1/2 R 5/4 5/4 Coaxial flow / return 1.1/2.1 R ¾ ¾ Aux boiler flow / return 4/5 R 1 1 Drain (5) R
1 1
Solar flow / return 6 / 7 Rp
1 1
Heating flow / return 10 / 11 Rp
1 1
Plug for electric heater 12 Rp
6/4 6/4
Chart 2
R = male thread
Rp = female thread