WIKA TXA2CL, TXS2CL, TXA4CL, TXS4CL, TXA2QL Instruction Manual

...
INSTRUCTION MANUAL
TEMPERATURE SWITCHES SERIE TXS, TXA
NI-492WE
Rev. 4 05/18
WEATHERPROOF AND INTRINSICALLY SAFE:MODELS TXS; FLAMEPROOF: MODELS TXA
CORD CABLE INSTRUMENT INSTRUMENT WITH JUNCTION BOX
Stem Type C-Q-R Stem Type B
WEIGHT 0,4kg Dimension in mm WEIGHT 1kg Dimension in mm
Stem Type B: Y = 125mm ; X = 50mm Stem Type C: K = 2m ; Y max. = 350mm Stem Type R: K = 10m ; Y max. = 1800mm
For surface mounting use two screws M6 (not supplied with the instrument)
NOTE: dimensions and weights are not binding unless released on certified drawings.
CAUTION
Before installing, using or carrying out maintenance on the instrument it is necessary to read and understand the indications given
in the attached Instruction Manual.
The instrument must only be installed and maintained by qualified personnel in relation to working with instruments for hazardous
areas.
INSTALLATION IS TO BE CARRIED OUT ONLY AFTER CHECKING THAT INSTRUMENT CHARACTERISTICS ARE
CONSISTENT WITH PROCESS AND PLANT REQUIREMENTS.
The functional features of the instrument and its degree of protection are shown on the identification plate fixed to the case.
CONTENTS:
GENERAL
1 ­2 -OPERATING PRINCIPLE 3 -MODEL CODE 4 -NAMEPLATE AND MARKINGS 5 -SPECIAL CONDITIONS FOR SAFE USE (X) 6 -SET POINT ADJUSTMENT 7 -SET POINT CALIBRATION 8 -INSTRUMENT PLUMBING 9 -MOUNTING AND CONNECTIONS 10 -PUTTING INTO OPERATION 11 -VISUAL INSPECTION 12 -FUNCTIONAL VERIFICATION 13 -STOPPING AND DISMOUNTING 14 -DISPOSAL 15 -TROUBLE SHOOTING
SAFETY INSTRUCTIONS FOR USE IN EXPLOSIVE ATMOSPHERES
RECOMMENDATIONS FOR THE SAFE USE OF THE INSTRUMENT
  
Stem Type Q: K = 5m ; Y max. = 900mm
DOCUMENT CORRELATED
to document authenticated with certificates
N° IECEx PRE 16.0073X N° IECEx PRE 16.0074X
All data, statements and recommendations supplied with this manual are based on information believed by us to be reliable. As the conditions of effective
use are beyond our control, our products are sold under the condition that the user himself evaluates such conditions before following our recommendations for the purpose or use foreseen by him.
This document is the property of ALEXANDER WIEGAND SE &Co and may not be reproduced in any form, nor used for any purpose other than for which it is supplied.
INSTRUCTION MANUAL
range
Max working temperature
(T max.) Shall not exceed the maximum temperature specified on the nameplate (see fig.1 item 5).
Max electrical rating
(resistive load)
5A@24V d.c.; 5A@250V a.c.
See nameplate of the instrument
(electrical rating)
Max electrical
rating
(resistive load)
5A@24V d.c.;
5A@250V a.c.
See nameplate of
the instrument
(electrical rating)
1 - GENERAL
1.1 FOREWORD
The wrong choice of a models or a version, as well as the incorrect installation, lead to malfunction and reduce instrument life. Failure to follow the indications given in this manual can cause damage to the instrument, the environment and persons.
1.2 ALLOWED OVERRANGES
Temperature exceeding the working range can be allowed only for testing proposal up to the proof temperature. Continuous
temperature exceeding the (adjustable) “RANGE* (see fig 1) can be applied to the instrument, provided they are clearly stated in the instrument features (see fig.1, “MAX TEMPERATURE”). The current and voltage values stated in the technical specifications and data plate must not be exceeded: transitory overranges can have a destructive effect on the switch.
1.3 TEMPERATURES
The temperature of the instrument is influenced by the environmental and process temperature. Special attention must be taken to avoid the exceeding of the limits specified in table 1 and 2.
For the instrument version TX**B* (stem for direct mounting) the following table is applicable Table 1 – Temperature conditions
Temp. Classification
T6 T5 T4 T3 T2 T1
Ambient temperature range (Tamb)
-50 … +60 °C
-50 … +85 °C
For the instrument versions TX**C*, TX**Q*, TX**R* (stem for remote mounting) and TX**S* (helical bulb for ambient temperature) the following table is applicable Table 2 – Temperature conditions
Temperature Classification
T6 T5 T4 T3 T2 T1
Ambient
temperature
(Tamb)
-50..+60 °C
-50..+85 °C
2 - OPERATING PRINCIPLE
The operating principle is based on a pressure measuring element, connected via a capillary tube to a bulb. This system is partially filled with a volatile liquid, the residual free volume being filled by its saturated vapour. In this system a pressure is generated which is a non-linear function of bulb temperature; this pressure acts on a stainless steel diaphragm which applies a force to a stiff disc; this force is directly proportional to the temperature value to which the bulb is submitted and is contrasted by an compression spring charged by a suitable bush. When the force balance point is exceeded, the stiff disc shifts and, by means of a rigid rod, activates one or two simultaneous release electric microswitches. The microswitches are of the rapid release type with automatic rearm. When the temperature moves away from the set values, returning towards the normal values, the switch is rearmed.
3 - MODEL CODE
See Annex 1
4 - NAMEPLATE AND MARKINGS
The i nstru ment is f itted wit h a metal plate beari ng al l its functional characteristics and in case of flameproof or intrinsic safety execution, also the markings prescribed by standard IEC/EN 60079-0. Fig.1 shows the plate mounted on flameproof instruments.
NI-492WE
Rev.4 05/18
Fig. 1 - Flameproof instruments plate
1 Notified body that issued the type certificate and number of said
certificate.
2 CE marking and identification number of the notified body
responsible for production surveillance.
3 Apparatus classification according to ATEX 2014/34/EU
directive. 4 Type of protection and ambient temperature limits of operation. 5 Max working temperature The following table gives the relationship between hazardous areas, ATEX Categories and Equipment Protection Level (EPL) listed on the flameproof instrument nameplate.
Hazardous area
Gas, vapours, fog Gas, vapours, fog Gas, vapours, fog
Zone 0 1G Ga
Zone 1 2G or 1G Gb or Ga
Zone 2 3G, 2G or 1G Gc, Gb or Ga
Dust Zone 20 1D Da
Dust Zone 21 2D or 1D Db or Da
Dust Zone 22 3D, 2D or 1D Dc, Db or Da
5 - SPECIAL CONDITIONS FOR SAFE USE (X)
The instrument cannot be repaired (see also throubleshooting). Should the instrument be installed without a junction box require an electric connection suitable for the mode of protection chosen at the free end of the cable. Should the instrument be installed in mines (Group I) the elettrical connection has require to be protected by chemical agents. Therefore a mounting with cable protected by tubing is mandatory.
6 - SET POINT ADJUSTMENT
The compression of the spring can be regulated by means of the bush (for adjustment) in such a way that the switch is released when the temperature reaches (either increasing or decreasing) the desired value (set point). The instrument is usually supplied with the switches set at 0°C or at the lowest setting range value if this is higher than 0°C (factory calibration).
The instrument is supplied with an adhesive label showing the set point calibration value. With factory calibration the values are not indicated on the label as these are temporary and will be modified with the definitive values. Prior to installation the instrument must be calibrated and the definitive calibration values written on the label.
If the instrument has been ordered with a specific calibration, it is a good rule to check the calibration values marked on the relevant adhesive label, prior to installation.
Categories
according to
2014/34/EU
Directive (ATEX)
EPL
2 of 7
The position of the adjusting bush is given in Fig. 2.
Fig. 2 - Adjusting bush and plumbing
Adjustment slot cover
Sealing lead
Stainless steel wire
Adjusting bush The effect of the sense of rotation of the adjusting bush is shown on the slot cover. Rotate the bush by inserting a 3mm dia. rod or drill into the holes on the bush itself (It recommends using a drill bit on the side of the shank).
7 - SET POINT CALIBRATION
In order to proceed with the calibration and the periodical functional verification of the instrument a suitable calibration circuit (Fig. 3) and of an adequate source of heat are required. The test instrument should have a measurement range approximately equal to or slightly wider than the pressure switch range and should have an accuracy consistent with the accuracy required to calibrate the set point.
Fig. 3 – Calibration circuit
TS - Temperature switch TT - Test thermometer TB - Thermostatic bath
7.1 PRELIMINARY OPERATIONS
Slide up the adjustment cover (Fig. 2 item 1).
7.2 CALIBRATION CIRCUIT AND OPERATIONS
Prepare the control circuit as indicated in Fig.3 If the instrument is equipped with two contacts, remember that
they are released simultaneously but within the specification tolerance.
The warning lamps should be connected to the terminals NA or NC according to the required contact action.
Fig. 4 – Color of wires and function
GDN-Internal grounding connection: color jellow/green
C-Common: color brown NO-Normally open: color blue NC-Normally closed: color black
C-Common: color gray NO-Normally open: color red NC-Normally closed: color white
.
INSTRUCTION MANUAL
NI-492WE
Rev.4 05/18
Contacts status at atmospheric pressure.
C - Common NA - Normally open NC - Normally closed
Connection between C and NA
• If the circuit is open at the workin temperature, the instrument closes the circuit when the set point is reached with temperature on rise (closure on rise).
• If the circuit is closed at the working temperature, the instrument opens the circuit when the set point is reached with temperature on fall (opening on fall). Connection between C and NC
• If the circuit is closed at the working temperature, the instrument opens the circuit when the set point is reached with temperature on rise (opening on rise).
• If the circuit is open at the working temperature, the instrument
closes the circuit when the set point is reached with temperature on fall (closure on fall).
The temperature switch must be kept in the normal installation position, i.e. with the temperature connection downwards. Modify the temperature in the circuit up to the desired microswitch set point value. Using a 3mm dia. rod drill into the holes on the bush (It recommends using a drill bit on the side of the shank). Adjust its position until the relative lamp turns on (or turns off); then turn it in the opposite direction until the lamp turns off (or on). Slowly turn the bush again until the lamp turns on (or off)
7.3 SET POINT VERIFICATION
Increase the temperature up to the normal working temperature (Tw), wait the stabilization of the temperature. Modify, slowly the temperature up to the set value (Ti) and record the set point value. Write the set point value on the adhesive label. Note: the verification of the repeatability have to be tested checking the set point (Ti) three times approaching the set point from the same starting point (Tw). The temperature cycles have to be performed slowly.
7.4 FINAL OPERATIONS
Disconnect the instrument from the calibration circuit. Close the adjustment slot by sliding down the slot cover (Fig. 2,
1), then seal with lead the instrument. Mount on pressure connection the protecting cap supplied with
the instrument. It should be definitively removed only during the connection steps.
8 - INSTRUMENT PLUMBING
The plumbing (see Fig. 2), aimed as a guarantee against possible tampering of the calibration, can be carried out using a flexible steel wire (2), 1 mm case in the groove purposely provided.
9 - MOUNTING AND CONNECTIONS
9.1 MOUNTING
Mount instruments with capillary either on pipe or surface by means of the proper bracket (see Fig. 9 and 10) or direct on plant. Select a location where possible shocks and temperature variations remain within tolerable limits. For the instrument with capillary the difference in height between bulb and case have not exceeding two meters (fig 11 and 12 distance h).
9.2 INSTALLATION OF TEMPERATURE SWITCH WITH DIFFERENCE IN HEIGHT BETWEEN BULB AND INSTRUMENT ENCLOSURE GREATER THAN 2 METERS
Micro 1
9.2.1 TEMPERATURE SWITCHES CLASS SAMA II A
Difference in height between bulb and instrument enclosure causes a systematic error of set point calibrated value (“bulb elevation error”). This error can be corrected during calibration using the table attached to our technical instruction IS-TC.401E, available on request.
Micro 2
2
in section, wound up around the
3 of 7
Loading...
+ 4 hidden pages