WIKA DI35 User Manual

Operating instructions
Digital indicator model DI35-M GB
14053538.01 11/2012
Digital indicator model DI35
Operating instructions model DI35-M
GB
page 1 - 52
© 2010 WIKA Alexander Wiegand SE & Co. KG All rights reserved. WIKA® is a registered trademark in various countries.
Prior to starting any work, read the o perating instr uc tions ! Keep for later use!
2 WIKA operating instructions digital indicator DI35-M
Contents
1 General information ................................................................................ 4
2 Safety ....................................................................................................... 5
2.1 Intended use ........................................................................................ 5
2.2 Personnel qualification......................................................................... 7
2.3 Special hazards ................................................................................... 7
2.4 Labelling / Safety marks ...................................................................... 8
3 Specifications .......................................................................................... 9
4 Design and function .............................................................................. 13
4.1 Short description ................................................................................ 13
4.2 Scope of delivery ............................................................................... 13
5 Transport, packaging and st orage ....................................................... 13
5.1 Transport ........................................................................................... 13
5.2 Packaging .......................................................................................... 13
5.3 Storage .............................................................................................. 14
6 Commissoning, operat ion .................................................................... 14
6.1 Mounting ............................................................................................ 14
6.2 Elec trical connection .......................................................................... 15
6.3 Function and operation description .................................................... 20
6.4 Configuration of the indicator ............................................................. 27
6.5 D escription of the measuring input .................................................... 29
6.6 Description oft he program numbers .................................................. 32
6.7 Program number ta ble ....................................................................... 40
6.8 Default values .................................................................................... 47
7 Maintenance and cleaning .................................................................... 47
7.1 Maintenance ...................................................................................... 47
7.2 Cleaning ............................................................................................ 47
8 Faults ..................................................................................................... 48
9 Dismounting, return and disposal ....................................................... 50
9.1 Dismounting ...................................................................................... 50
9.2 Return ............................................................................................... 50
9.3 Disposal ............................................................................................. 50
10 Appendix: Declaration of conformity ................................................... 51
Declarations of conformi ty can be found online at www.wika.com. WIKA operating instructions digital indicator model DI35-M 3

1 General information

1 General information
The instrument described in the operating instructions has been
designed and manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during production. Our management systems are certified to ISO 9001.
These operating instructions contain important information on handling
the instrument. Working safely requires that all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general
safety regulations for the instrument's range of use.
The operating instructions are part of the instrument and must be kept
in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time.
Skilled personnel must have carefully read and understood the
operating instructions, prior to beginning any work.
The manufacturer's liability is void in the case of any damage caused by
using the product contrary to its intended use, non-compliance with these operating instructions, assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument.
The general terms and conditions, contained in the sales
documentation, shall apply.
Subject to technical modifications. Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: AC 80.03
- Application consultant: Tel.: (+49) 9372/132-0 Fax: (+49) 9372/132-406 E-Mail: info@wika.de
4 WIKA operating instructions digital indicator DI35-M

2 Safety

WARNING!
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
Information
... points out useful tips, recommendations and information for efficient and trouble-free operation.
DANGER!
...identifies hazards caused by electric power. Should the safety instructions not be observed, there is a risk of serious or fatal injury.
2 Safety
Before installation, commissioning and operation, ensure that the appropriate instrument has been selected in terms of measuring range, design and specific measuring conditions. Non-observance can result in serious injury and/or damage to equipment.
Further important safety instructions can be found in the individual chapters of these operating instructions.

2.1 Intended use

The digital indicator DI35-M is used for measurement and indication of sensor signals, thermocouples and RTDs. Signals can be put out via an analogue output for further processing.
The instrument has been designed and built solely for the intended use described here, and may only be used accordingly.
WIKA operating instructions digital indicator model DI35-M 5
2 Safety
Please read the following safety advice and the assembly before installation and keep it for future reference.
If the instrument is transported from a cold into a warm environment, the formation of condensation may result in the instrument malfunctioning. Before putting it back into operation, wait for the instrument temperature and the room temperature to equalise.
Notes on installation
There must be no magnetic or electric fields in the vicinity of the device,
e.g. due to transformers, mobile phones or electrostatic discharge.
Do not install inductive consumers (relays, solenoid valves etc.) near
the device and suppress any interference with the aid of RC spark extinguishing combinations or free-wheeling diodes.
Keep input, output and supply lines separate from one another and do
not lay them parallel with each other. Position “go” and “return lines” next to one another. Where possible use twisted pair. So, you receive best measuring results.
Screen off and twist sensor lines. Do not lay current-carrying lines in the
vicinity. Connect the screening on one side on a suitable potential equaliser (normally signal ground).
Do not install several devices immediately above one another or in an
extremely thermal isolated housing. Due to the internal heat dissipation of the devices, the recommended ambient temperature can be excessed.
The device is not suitable for installation in areas where there is a risk
of explosion.
Any electrical connection deviating from the connection diagram can
endanger human life and/or can destroy the equipment.
The terminal area of the devices is part of the service. Here electrostatic
discharge needs to be avoided. Attention! High voltages can cause dangerous body currents.
Galvanic insulated potentials within one complex need to be placed on
a appropriate point (normally earth or machines ground). So, a lower disturbance sensibility against impacted energy can be reached and dangerous potentials, that can occur on long lines or due to faulty wiring, can be avoided.
The fuse rating of the supply voltage should not exceed a value of 6A
N.B. fuse.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
6 WIKA operating instructions digital indicator DI35-M
2 Safety
WARNING!
Keep unqualified personnel away from hazardous areas.
DANGER!
WARNING!
death or serious injury and material damage.

2.2 Personnel qualification

Risk of injury should qualification be insufficient!
Improper handling can result in considerable injury and damage to equipment.
Skilled electrical personnel
Skilled electrical personnel are understood to be personnel who, based on their technical training, knowledge of measurement and control technology and on their experience and knowledge of country-specific regulations, current standards and directives, are capable of carrying out work on electrical systems and independently recognising and avoiding potential hazards. The skilled electrical personnel have been specifically trained for the work environment they are working in and know the relevant standards and regulations. The skilled electrical personnel must comply with current legal accident prevention regulations.
The activities described in these operating instructions
may only be carried out by skilled personnel who have the qualifications described below.

2.3 Special hazards

Danger of death caused by electric current. Upon contact with live parts, there is a direct danger of death.
Electrical instruments may only be installed and mounted
by skilled electrical personnel.
Operation using a defective power supply unit (e.g. short
circuit from the mains voltage to the output voltage) can result in life-threatening voltages at the instrument!
Do NOT use this product as safety or emergency stopping device, or in any other application where failure of the product could result in personal injury or material damage. Failure to comply with these instructions could result in
WIKA operating instructions digital indicator model DI35-M 7
2 Safety

2.4 Labelling / Safety marks

Product label
Explanation of symbols
Before mounting and commissioning the instrument, ensure you read the operating instructions!
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
8 WIKA operating instructions digital indicator DI35-M

3 Specifications

Principle
7-segment LED, red, 5-digit, brightness adjustable in 10 steps
Character size
14 mm
Indication range
-9999 … +99999
Indication time
0.1…10.0 seconds
Memory
EEPROM (independent of power supply), data retension > 100 years
Input
Number and type
1 multi-function input
Input configuration
Selectable via terminal configuration and programming
Accuracy
see following table
Temperature error
50 ppm/K, at ambient temperature T < 20 °C or > 40 °C
Measuring principle
Sigma/Delta
Resolution
24 bit, (at measuring tim e 1 second )
Measuring time
0.02…10.0 sec
Totalizator time-error
max. 0.1% of totalizator value at integration time > 1 min
{Transmitter supply}
DC 24 V, 50 mA
Power supply
AC 230 V, 50 / 60 Hz, ± 10 % or
Power supply galvanic insulated
Power consumption
max. 15 VA
Electrical connection
plug-in terminal, wire cross-section up to 2.5 mm²
{Analogue output}
Number and type
1 analogue output (galvanic insulated):
0 ... 10 V (12-bit), load ≥ 10 kΩ
Error
0.1% in the range 20 °C ≤ Tu ≤ 40 °C, beyond this value temperature error 50 ppm/K
Internal resistance
100 Ω (at measuring input 0…10 V)
3 Specifications
Specifications
Display
{AC 115 V, 50 / 60 Hz, ± 10 %} or {AC 115 / 230 V, 50 / 60 Hz, ± 10 % switchable} or {DC 24 V, ± 10%}
4 ... 20 mA (12-bit), load ≤ 500 Ω or 0 ... 20 mA (12-bit), load ≤ 500 Ω or
WIKA operating instructions digital indicator model DI35-M 9
3 Specifications
{Switching outputs}
number and type
2 or 4 change-over contacts (relays), fully programmable
Load
AC 230 V, 5 A (ohmic load) or DC 30 V, 2 A (oh mic load)
Switching cycles
0.5 * 105 at max contact rating
Characteristic data as per DIN EN 60255
{Serial Interface}
RS 232, selectable with or without galvanic
selectable with or without galvanic isolation
Protocol
manufacturer-specific ASCII
communication
9600 Baud, no parity, 8 data bits, 1 stop bit
Lead length
RS 232: max. 3 m RS 485: max. 1000 m
Material
PC polycarbonate, ABS Blend, UL 94V-0, black
Ingress protection
Front: IP 54, {IP 65}; Back: IP 00 (per IEC 60529 / EN 60529)
Weight
Approx. 450 g
Dimensions
96 x 48 x 148 mm (w x h x d) including plug-in terminals
Mounting
snap-in screw element for wall thickness up to 50 mm
Operating temperature
0…60 °C
Storage temperature
-20…80 °C
Humidity
0…75 % relative humidity, non-condensing
EMC directive
2004/108/EC, EN 61326 emission (group 1, application)
Low voltage directive
2006/95/EG, EN 61010-1
5 * 106 mechanically Separation as per DIN EN 50178
isolation or RS 485 (only for point-to-point connection),
Case
Permissible ambient conditions
CE conformity
class B ) and interference immunity (industrial
{ } Items in curved brackets are optional extras for additional price.
10 WIKA operating instructions digital indicator DI35-M
3 Specifications
Input signals
Measuring span
Measuring error in % of the span
Inner resistance
Current signals
0…20 mA
± 0.02 % ± 1 Digit
50 Ω
4…20 mA
± 0.02 % ± 1 Digit
50 Ω 0…5 mA
± 0.02 % ± 1 Digit
50 Ω 0…2 mA
± 0.02 % ± 1 Digit
50 Ω
Voltage signals
-1…10 V
± 0.01 % ± 1 Digit
150 kΩ -1…5 V
± 0.02 % ± 1 Digit
150 kΩ
-500…2500 mV
± 0.03 % ± 1 Digit
1 MΩ
-500…1250 mV
± 0.03 % ± 1 Digit
1 MΩ
-500…600 mV
± 0.03 % ± 1 Digit
1 MΩ
-300…300 mV
± 0.03 % ± 1 Digit
1 MΩ
-150…150 mV
± 0.03 % ± 1 Digit
1 MΩ
-75…75 mV
± 0.04 % ± 1 Digit
1 MΩ
-35…35 mV
± 0.06 % ± 1 Digit
1 MΩ
-18…18 mV
± 0.03 % ± 1 Digit
1 MΩ
PT100 (2-/3-/4-wire)
-200,0…850,0 °C
± 0.04 % ± 1 Digit
1 MΩ
Thermocouple
Typ L
-200…900 °C
± 0.06 % ± 1 K
1 MΩ
Typ J
-210…1200 °C
± 0.05 % ± 1 K
1 MΩ
Typ K
-250…1271 °C
± 0.05 % ± 1 K
1 MΩ
Typ B
-100…1810 °C
± 0.10 % ± 1 K
1 MΩ
Typ S
0…1767 °C
± 0.06 % ± 1 K
1 MΩ
Typ N
-250…1300 °C
± 0.06 % ± 1 K
1 MΩ
Typ E
-260…1000 °C
± 0.06 % ± 1 K
1 MΩ
Typ R
0…1767 °C
± 0.07 % ± 1 K
1 MΩ
Typ T
-240…400 °C
± 0.07 % ± 1 K
1 MΩ
Resistance (2-/3-/4-wire)
100 Ω
± 0.04 % ± 1 Digit
1 MΩ 1 kΩ
± 0.04 % ± 1 Digit
1 MΩ 10 kΩ
± 0.04 % ± 1 Digit
1 MΩ
Accuracy of input signals
The measuring errors are valid for ambient temperatures of 20…40 °C and a measuring time of 1 second.
The datas for PT100 3-/4-wire are valid for a max. resistance of wire of 10 Ω.
WIKA operating instructions digital indicator model DI35-M 11
3 Specifications
Input signal
Measuring time in seconds
Current signals
0.02…10.00
Voltage signals
0.02…10.00
PT100 (2-/4-wire)
0.04…10.00
PT100 (3-wire)
0.06…10.00
Thermocouple
0.04…10.00
Resistance (2-/4-wire)
0.04…10.00
Resistance (3-wire)
0.06…10.00
1: Program key 3: UP key
4: LEDs for alarm output 6: 7 segment display
Adjustable measuring times
For further specifications see WIKA data sheet AC 80.03 and the order documentation.
Operating elements
2: DOWN key
5: Multi-function key
12 WIKA operating instructions digital indicator DI35-M

5 Transport, packa ging and storage

4 Design and function

4.1 Short description

The digital indicator DI35-M is a multi-function and highly accurate digital indicator. It has a multi-function input with 29 different calibrated input configurations, which can be selected via the terminal configuration and by the selection of the input signal in the instrument configuration. Furthermore the possibility of sensor calibration and linearisation with up to 30 points is offered. The standard features are completed by the adjustable sampling rate and display time as well as the input offset for the correction of zero offsets or sensor drifts and TARA and HOLD function. The measured value or one of the functions can be indicated and used as output signal.
As an option up to 4 fully programmable alarm outputs, an analogue output signal, a serial interface and a transmitter power supply are available.

4.2 Scope of delivery

The scope of delivery is:
Indicator 2 fixing elements Seal Operating instructions
Cross-check scope of delivery with delivery note.
5 Transport, packaging and storage

5.1 Transport

Check instrument for any damage that may have been caused by transport. Obvious damage must be reported immediately.

5.2 Packaging

Do not remove packaging until just before mounting. Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).
WIKA operating instructions digital indicator model DI35-M 13

6 Commissoning, ope ration

WARNING!

5.3 Storage

Permissible conditions at the place of storage:
Storage temperature: -20 ... +80 °C Humidity: 0 ... 75 % relative humidity (no condensation)
Avoid exposure to the following factors:
Direct sunlight or proximity to hot objects Mechanical vibration, mechanical shock (putting it down hard) Soot, vapour, dust and corrosive gases Potentially explosive environments, flammable atmospheres
Store the instrument in its original packaging in a location that fulfils the conditions listed above. If the original packaging is not available, pack and store the instrument as described below:
1. Wrap the instrument in an antistatic plastic film.
2. Place the instrument, along with shock-absorbent material, in the packaging.
3. If stored for a prolonged period of time (more than 30 days), place a bag, containing a desiccant, inside the packaging.
Before storing the instrument (following operation), remove any residual media. This is of particular importance if the medium is hazardous to health, e.g. caustic, toxic, carcinogenic, radioactive, etc.
6 Commissoning, operation
Please read the safety instructions and installation instructions in chapter 2 before installation and keep this user manual for future reference.

6.1 Mounting

Panel cut out: 92,0 Assembly grid: 120 mm horizontal, 96 mm vertical (recommended)
14 WIKA operating instructions digital indicator DI35-M
+0,8
mm x 45,0
+0,6
mm
6 Commissoning, ope ration
1. After removing the fixing elements, insert the device.
2. Check the seal to make sure it fits securely.
3. Click the fixing elements back into place and tighten the clamping screws by hand.
Information
The dimension symbols can be exchanged before installation via a channel on the side!

6.2 Electrical connection

All the necessary signals for operation are connected to the rear terminals. The connecting terminals are designed as removable screw-type terminals with a grid pitch of 5.08 mm. This makes it possible to connect wires of up to
2.5 mm².
WIKA operating instructions digital indicator model DI35-M 15
6 Commissoning, ope ration
Relay 1 (S1)
Relay 2 (S2)
Relay 3 (S3)
Relay 4 (S4)
Normally closed
21
24
27
30
Normally open
22
25
28
31
Com
23
26
29
32

6.2.1 Terminal c onfi gura t ion Lower terminal connector

The power supply, the input signal, the transmitter supply and the analogue output signal have to be connected to the lower terminal connector. The mounting screws for the transmitter supply and the analogue output signal are only available if these options have been chosen.
Upper terminal connector
The switching contacts (relays) and the serial interface have to be connected to the upper terminal connector. The mounting screws for the switching contacts and the interface are only available if these options have been choosen.
16 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Serial interface RS 232:
The lines for the RS 232 interface must be connected 1:1, TxD to TxD and RxD to RxD.
RS 485:
The RS 485 interface is connected via a shielded data line with a twisted pair. At each end of the bus, a termination of the bus lines must be connected. This is necessary to guarantee reliable data transmission on the bus. For this, a resistance of 120 Ohm is inserted between the lines Data B(+) and Data A(–).
CAUTION!
The potential reference can lead to a compensating current (interface ⇔ measuring input) with a non-galvanic insulated interface and can thus affect the measuring signals
WIKA operating instructions digital indicator model DI35-M 17
6 Commissoning, ope ration

6.2.2 Connection examples

This section gives a few examples of practical connections. The different examples can be combined.
a) 4…20 mA signal, 2-wire transmitter
b) 0…5 V/0…10 V signal, 3-wire tran smitter
The voltage drop on the transmitter supply wire is irrelevant, which is why this can also be bridged directly on the indicator.
c) Voltage signal ≤ 2,5 V, 3 wire transmitt er
18 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
d) Resistance thermometer (eg. Pt100) or resistance, 2 wire
e) Resistance thermometer (eg. Pt100) or resistance, 3 wire
f) Resistance thermometer (eg. Pt100) or resistance, 4 wire
g) Thermocouple & digital input
WIKA operating instructions digital indicator model DI35-M 19
6 Commissoning, ope ration
Name
Description
Program key [P]
With the program key, you can call up the programming mode.
DOWN key []
With the DOWN (de crease ) key, you can call up the mode.
UP key []
With the UP (increase) key, you can call up the MAX memory or alter parameters in the programming mode.
Multi-function [O]
Multi-function for activating TARA function and HOLD function; reset for MIN/MAX permanent

6.3 Function and operation description

6.3.1 Operation

The DI35-M has 4 keys ([P], [], [], [O]), with which you can parameterise and call up various functions during operation.
programming mode or perform various functions in the
MIN memory or alter parameters in the programming

6.3.2 Switching on

Before switching on, check all the electrical connections to make sure they are correct. On completion of the installation, the device can be switched on by applying the supply voltage.
During the switching-on process, a segment test is performed for approx. 1 second, whereby all LED on the front (including setpoint LED) are triggered. After this, th e type of software is indicated for approx. 1 second and then, also for 1 second, the software version. After the starting procedure, the unit changes to operation/display mode.
20 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Parameter
Description
Alarm / Relay x
De-activiated, instananeaous value, MIN value, MAX value
Threshold
Threshold / Switch-over threshold
Hysteresis
Width of window between switching threshold
Working principle
Operating current / quiescent current
Switch-on delay
Time between reaching the threshold and the resultant switching on of the relay.
Switch-off delay
Time between reaching the threshold and the resultant switching off of the relay.
Alarm confirmation
Switch-on or switch-off interlock and rejection at activated digital input or multi-function key

6.3.3 General functi ons MIN/MAX memory

The measured minimum and maximum values are saved in a volatile memory in the unit and get lost when the unit is switched off. You can call up the contents of the memory by pushing (less than 1 second) the [▲] or [▼] key. The relevant value is indicated for approx. 7 seconds. By briefly pressing the same key again, you will return immediately to the display mode.
[▲] dis playing of MAX value [▼] dis playing of MIN value
You can erase the value shown in the display by simultaneously operating the [▲] and [▼] keys. The erasure is acknowledged by horizontal bars.
Information
The content of the memory will be lost with switching-off of the device.

6.3.4 Descripti on of t he al ar m output s

With the aid of the LED next to the 7‑segment display, you can view the switching state of the relays. An active relay is indicated by the relevant LED lighting up.
Working principle
The alarm outputs have the following properties with regard to their switching properties:
value, Hold value, sliding average value, totalizator
WIKA operating instructions digital indicator model DI35-M 21
6 Commissoning, ope ration
Operating current
The alarm is off below the threshold and on when reaching the threshold.
Quiescent current
The alarm is on below the threshold and switched off on reaching the threshold.
Switch-on delay
The relay is on e.g. 10 seconds after reaching the threshold. Briefly exceeding the threshold does not lead to the relay being switched on.
The switch-off delay functions in a similar manner, in other words it keeps the alarm output switched on until the parameterised time has elapsed.
22 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Modus
Actuate value
0
none
1
Instaneaous value
2
Minimal value
3
Maximal value
4
HOLD value
5
Sliding average value
6
Totalizator value
Allocation of the alarms to a certain actuate value
As it is not always desired that alarms follow the operating mode, the outputs can be assigned to the minimal-/maximal value or any other value. Therefor the adjustable value range is assigned to the according program number (PN60, PN70, PN80 and PN90).
Alarm confirmation
If one wants to display interim occured alarms, the self-acting switching-on or switching-off can be blocked. Therefore the confirmation of the according setpoints 1-4 must be assigned to the digital input or the multi-function key under program numbers 67, 77, 87 and 97.
Information
Alarm status will get lost by voltage drop!
Optical response, flashing display
If one or some thresholds are broken, the flashing of the alarm LED can amplify the optical response by assignment of the threshold (PN59) to the 7 segment display.
Example: The threshold for flashing of the display is set at setpoint 2. If
setpoint 1 is exceeded and set point 2 is not, the set point LED 1 lights up permanently. If setpoint 2 exceeds the threshold, the 7-segment displ a y will star t to flash, setp o i nt 1 will light up permanently and set point LED 2 will flash. The flashing enhances the optical response and the operator sees immediately that an important threshold has been exceeded with this unit.
WIKA operating instructions digital indicator model DI35-M 23
6 Commissoning, ope ration

6.3.5 Analog output

The optional analogue output is used for the transduction of a measuring value, supported by a standard signal of 0…10 V or 0/4…20 mA. The analogue output is parameterised via the two program numbers PN20 “final value (fullscale)” and PN21 “initial value (offset)”. At the initial value, the value is set at which the analogue output transmits the minimal value (0 V or 0/4 mA), and with "Full scale", the value at which the output transmits its maximum (10 V or 20 mA). By this means it is possible to re-scale the input signal of a transducer or even to convert it into another standard signal. The analogue output can be de-activated via the actuate value PN22, as well as set on the active measuring value, MIN value, MAX value, HOLD value, sliding average value or totalizator value. The analogue output is updated within the cycle of the measuring time. At a high measuring rate, smaller cycle fluctuations of some milli-seconds are possible.

6.3.6 Digital input / multi-function key

In combination with the digital input (via terminal) and/or the multi-function key at the front, functions like e.g. HOLD, TARA, MIN/MAX permanent or totalizator function, can be actuated respectively set back. The digital input is available in combination with the option sensor supply or via an external DC 24 V-signal. The multi-function key at the front of the device can be activated by keypress.
HOLD function
The HOLD function is a static signal and will be activated via the digital input or the multi-function key. With activated HOLD the lastly given measuring value remains and is by deactivation permanently overwritten by the measuring value recording. With this function a test state can be recorded beyond a specific period, so that this device can be used for control in run production, too.
Information
HOLD value gets lost with re-start!
24 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
TARA function
The TARA-Function can be activated by multi-function key, digital input or with boot-up, the display value is then on the tare value. This function is only done once, after actuation of the desired trigger and has to be taken back before a new alignment.
MIN/MAX permanent
To measure a MIN-/MAX-value the display can be set back by the display mode (PN15) in a way, that it only shows the minimal or maximal measured value. The value can be reset by the multi-function key and/or the digital input.
Information
MIN/MAX value get lost with re -start!
Totalizator functi ons
With the totalizator, the measured display value can be integrated or accumulated over a time. The accumulated time-frame depends on the preset measuring time (PN14). With this function e.g. a volume over the current discharge can be recorded. So this function is qualified for the dose of fill-up quantities in conjunction with relays. The mileage section can be detected by the measured speed. The cumulative value:
can be parameterized on different time bases and dimensions (e.g. for
volume, liter, m³, km³, …).
can be directed to the display and outputs as a default display value. can be reset by a parameterized signal as counter reset (PN185) or by
the counter value (PN184).
is saved in the device even beyond a voltage drop by long-lasting
memory. A data loss of max. 30 minutes can occur in case of a voltage drop.
WIKA operating instructions digital indicator model DI35-M 25
6 Commissoning, ope ration
Parameter
Description
PN34 = 0
Standard mode in which the unit only replies if called on to do current measuring value can be recalled via commando “A ↵ “.
PN34 = 1
Transmission mode in which the measurements are measuring time.

6.3.7 Serial interface RS232 / RS485

If the DI35-M has an serial interface, the device can be programmed via this interface. The interface is available as an option, the basic version is without an interface.
Operating mode:
The interface can be operated in various modes which can be parameterized via the PN34 (interface behavior).
so. This mode is used only for configuration. Furthermore the
transmitted via the serial interface cyclically with the set
The transmission mode is interrupted on receipt of “> “ and the unit changes to standard mode. To change back to transmission mode, the display must be restarted, either by entering the command “S “ or by switching the device off and on.
With the transmission mode, the display value is transmitted via the interface in ASCII format. Minus signs and decimal points are also transmitted so that the output can be displayed directly on a terminal or processed by a SPS. Zeros at the front are suppressed during transmission. With an over or underflow, the display transmits horizontal bars (hyphens) "- - - - - ".
If there is a broken wire detected at temperature measurement "Lbr ↵ " will be sended. A choosen dimension ("°C" / "°F") will be ignored at transmission.
Examples: "0.00 " ; "-9.99 " ; "999.99 ↵" ; "-123.45" ; "- - - - - “ ; "Lbr " With the aid of this simple protocol structure, the display data can be
transferred very easily to a PC etc. and further processed there. In the simplest case, a terminal program from the operating system is sufficient to store the received data in a file .
Configuration of the devic e vi a inte rf a c e
For configuration the set-up tool PM-Tool can be used. As the communication is a straight point-to-point connection. The baud rate is set to 9600 baud, with 8 databits, without parity and one stopbit. Configuration is performed by transmitting ASCII symbols.
26 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Example:

6.4 Configuration of the indicator

Functional diagram of programming via key pad:
Description of the progr a m numbers
In the display, the program numbers (PN) are shown, right-justified, as a 3­digit number with a P in front of them:
Programming procedure
The entire programming of the DI35 is done by the steps described below.
Change to programming mode
Push the [P] key to change into programming mode. The unit goes to the lowest available program number. If the programming lock is activated, the key must be pushed for at least 1 second.
Displaying of program number 0, after pushing the [P] key.
Change between program numbe rs
To change between individual program numbers, hold the [P] key down and push the [▲] key for changing to a higher program number or the [▼] key for changing to a lower number. By keeping the keys pushed, e.g. [P] & [▲], the display will begin, after approx. 1 second, to automatically run through the program numbers.
WIKA operating instructions digital indicator model DI35-M 27
6 Commissoning, ope ration
Example:
and 7 do not need to be changed.
Change to the parameter
Once the program number appears in the display, you can push the [▼] or [▲] key to get to the parameters set for this program number. Es erscheint
für einen kurzen Moment „SCALE“ in der Anzeige. The currently stored parameters are displayed.
Changing a parameter
After changing to the parameter, the lowest digit of the respective parameter flashes on the display. The value can be changed with the [▲] or [▼] key. To move to the next digit, the [P] key must be briefly pushed. Once the highest digit has been set and confirmed with [P], the lowest digit will begin to flash again.
Saving of parameters
All parameters must be acknowledged by the user by pushing the [P] key for one second. The changed parameters are then taken over as the current operating parameters and saved in the EEPROM. This is confirmed by horizontal bars lighting up in the display. All the newly entered data are confirmed by the unit. If no confirmation is received, the relevant parameters have not been saved, e.g. confirmation of parameters:
The 0 is flashing this is the lowest digit and asks
if you want to change it. Let us assume the figure
is to be changed from 75,640 to 75,000. Briefly push the [P] key to move to the next digit. The 4 begins to flash. Change the figure by pushing [▲] or [▼] to change the digit from 4 to
0. Briefly push the [P] key to move on to the next digit. The 6 begins to flash. Change the digit by pushing [▲] or [▼] to move the 6 to a 0. Briefly push the [P] key to move to the next digit. The 5
Information
If a minus shall be displayed for negative values, the leftest digit of the 7 segment display has to be activated (it blinks). The minus can be activated with the [▼] key.
28 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
CAUTION!
Changing from programming to operating mode
If no key is pushed in the programming mode for about 7 seconds, the unit will return automatically to operating mode. Before „SAVE“ will be displayed until the next measuring value is displayed.

6.5 Description of the measuring input

Universal measuring input
The DI35-M is equipped with a universal measuring input that enables the signals from all kinds of different sensors to be measured direct. So that the unit can work according to the signal generated by the sensor, the input must be configured. The basic parameter is always set under PN0.
Setting / Calibration of the meas uring input
All the units are calibrated in the factory, whereby offset and full scale have been saved for the various measuring ranges. Via terminal connections and the choice of the measuring input under PN0, different types of input signals can be worked up.
Factory calibration c urrent / voltage under PN0 = 1…12
For these parameters, new scaled display values can be allocated which are used for scaling the measurement on the display. For the offset, an input signal of 0 is assumed and for full scale, the specific full scale of the parameterized measuring range. For parameterization, no sensor signal has to be applied because stored values are used. Because of the differing input signals, the corresponding input configuration must be parameterized via PN0. For the sensor signal with 4...20 mA, for example, PN0 = 3 has to be parameterized.
For the unit to function correctly, it is absolutely essential that
the right sensor is parameterized under program number 0. If a wrong sensor is parameterized there, the operating behavior may be impaired.
WIKA operating instructions digital indicator model DI35-M 29
6 Commissoning, ope ration
Temperature measurement PN0 = 13…29
For the temperature measurement, the scaling cannot be changed by the user and is only determined from the standardized sensor range. Sensor­caused variations can be balanced by offset shift (PN5) on the characteristic line.
Sensor calibration for resistance / current / voltage PN0 ≥ 30
With the sensor calibration, the unit can be calibrated or set up directly via the sensor signal or via a calibrator. For this, the measuring signal must be connected to the input of the unit. The respective display value (SCALE) must then be saved under the program number PN1 (full scale) and PN2 (offset). The sensor signal is measured via the factory parameter and displayed as current or voltage. A measurement must be started by shortly pushing the [P] key. Through this process with two calibration points, the unit is matched up with the measuring section. For more far-reaching adjustments to the characteristic line of the sensor, a linearization can be activated. At the resistance measurement, only the display value (SCALE) is parameterised. The adjoining sensor signal (INPUT) will not be displayed, but directly absorbed unit-intern. For linearization of the parameter at least PN1 (final value) or PN2 (zero point) must be preset.
Linearization PN100
The DI35-M offers the possibility to linearize, with up to 30 additional setpoints, non-linear sensors for the display of the measuring values and their subsequent processing (analog output). The number of the desired setpoints is determined under PN100. Be aware of choosing the one that makes th e m ost sens e, as it ca n lead to a ma lfunction of the device in case of no adjustment.
Approach to sensor calibrat ion PN0 ≥ 33
To program e.g. 5 additional calibration points, 5 must be entered under PN100. Subsequently, for each of the calibration points, the voltage/current must be applied to the unit and the respective display value programmed under the following program numbers PN101 – PN105. The sensor signal must be consistently parameterized. A gap of at least +1 digit to the previous display value must be adhered to, otherwise the input will be refused and no confirmation of the saving will be given.
Example: Linearization of a pressure transducer for 0...100 mbar with an
output of 0...20 mA. The display value before correction can be either calculated from the known characteristic line of the transducer or be determined empirically.
30 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Calibration
Pressure
Output (mA)
display before (IN)
Desired (OUT)
2 0 0.5
2.5
0.0
101
15
3.3
16.5
15.0
102
30
6.2
31.0
30.0
103
40
9.2
46.0
40.0
104
60
11.4
57.0
60.0
105
75
14.7
73.5
75.0
1
100
20
100.0
100.0
The non-linear range is between 0...75 mbar. For calibration point 101, this means: A pressure of 15 mbar, the transducer delivers 3.3 mbar instead of the optimum value of 3.0 mbar. As 20 mA in the display corresponds to 100.0 mbar, 3.3 mA in the display corresponds to 16.5 mA before the correction. To correct this error, enter “15.0“ at PN101.
point (PN)
(mbar)
transmitter
correction
display
WIKA operating instructions digital indicator model DI35-M 31
6 Commissoning, ope ration
Proceeding with factory calibration PN0 ≤12
With adjusted factory calibration a linearization without connection of the sensor signal can be presetted. Therefore the number of the desired setpoints needs to be filled in under PN100, to subsequently relate the display values to a certain measuring signal. Starting on setpoint (PN101) the display value (SCALE) and subsequently the according measuring signal (INPUT) need to be programmed. Both inputs are saved by pushing the [P]-key (for approx. 1 sec).

6.6 Description of the program numbers

The DI35-M device has a default configuration ex factory, where a 0…10 V input signal is changed into a display value of 0…10000. For devices, where the pre-configuration is unknown, a reset on the default parameter should be done (see chapter “6.8 Default values”). Otherwise unwanted reactions of the device can occur due to foreign settings. The devices do have a digital input, with which some functions like e.g. HOLD, TARA, or MIN/MAX can be actuated.
PN0: Measuring input
For the basic configuration of the unit, you must parameterize the right measuring input for your application under PN0. There is a choice of various inputs in the program number table (chapter „6.7 Program number table“).
PN1 and PN2: Scaling
The two program numbers 1 and 2 serve to scale the display; with these two parameters, the offset and full scale are parameterized . For each setpoint there is a SCALE–value and a INPUT–value. The SCALE–value indicates the desired display value. The according measuring signal is determined by the INPUT–value. In case of factory calibration the desired current or voltage value is preset. If a sensor calibration is demanded, a measurement can be actuated by a short pushing of the [P]-key. Before the saved current / voltage value is visible. All inputs need to be confirmed by pushing the [P]-key for approx. 1 second; the device confirms the correct take-over with 5 vertically bars in the display.
PN3: Decimal point
By changing this parameter, the position of the decimal point in the display is changed. With temperature measurements, the physical unit °C or °F can also be added.
32 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
PN5: Offset shift / Zero point shift
With this parameter it is possible to carry out a parallel shift of the parameterized characteristic line. This may be necessary if, for example, a pressure sensor ages over the course of time and a shift in the zero point occurs. With the parallel shift, the sensor can be adjusted back to the zero point. Another application would be to parameterize a certain tank level to zero and have any deviation from this level displayed. With the offset it does not matter whether the original characteristic line has been programmed by the user with PN1, PN2 or PN101...130 or whether it is the characteristic line of a temperature sensor. The value parameterized under PN5 is added to the original display value.
Example: If, for example, a temperature sensor shows approx. 3°C
instead of 0°C, you can compensate for this deviation by changing the value under PN 5 from 0 to 3.
If the comparison metering point is turned off for the thermocouple, the comparison metering temperature can be preset manually. This parameter can be changed directly by taring, if it has been actuated by a configurated incident (see PN8).
PN6: Thermocouple reference junction
The thermocouple reference junction is only available for thermocouples and can be activated or deactivated under PN6. Deactivation may be useful where the interchange point is kept at a very constant level or the temperature constitutes the direct relationship to the process. In this case the wiring to the measuring device can be conducted in simple wiring copper.
PN7: Setpoint value f or taring
By actuation of the taring, the display value is set on the taring value. This means the offset / zero point is shifted in a way that the display value is equivalent to the taring value.
PN8: Actuation f or taring
During taring, the instantaneaus value is set on a demanded setpoint value, which is configurated under PN7. The difference between setpoint value and actual value is safed as Offset PN5 in the device. The following operating modes, which are adjustable at PN8, are available:
WIKA operating instructions digital indicator model DI35-M 33
6 Commissoning, ope ration
PN8 =
Actuation for taring
0
none
1
Digital input active, longer than 3 seconds
2
Multi-function key actuated for longer than 3 seconds
3
Digital input or multi-function key active for longer than 3 seconds
4
Taring at boot-up
5
Taring at boot-up and with digital input
6
Taring at boot-up and with multi-function key
7
Taring at boot-up, digital input and multi-function key
8
Taring with activated digital input for activation period
9
Fast taring on digital input
10
Fast taring on multi-function key
11
Fast taring on digital input or multi-function key
The taring can be called off by programming of the PN5 offset shift on the value zero. A special form is taring PN8 = 8: the taring is not saved in PN5 offset shift, but charged temporarily for the duration of the activated digital input. The old tara value gets lost by a boot-up. The display shows „ooooo“ for approx. 1 second to confirm the taring. Taring is done only one time after actuation of the desired activator. For a anew calibration the signal for the activation of the taring must be cancelled. If the MIN/MAX value reset is programmed on the same activator as the taring, then after taring a MIN- / MAX value reset takes place, too. Furthermore the taring can be watched very well as the instantaneous value is shown directly before and after taring.
PN12: Sliding average value
The complete average time is a results of the product or a multiplication of time and recorded average value PN14 x PN12. If one wants to see this result in the display, the display mode PN15 needs to be programmed parallel on this result. This must be pointed out with an optional analogue output or with the relays, too.
PN13: Display time
The display time is the interval at which the display is updated. The longer the time between two display cycles, the calmer the display. The eye perceives a display time of 1 second as very pleasant.
PN14: Measuring time
The DI35-M performs an averaging process by calculating an average from several measurements taken during the measuring time (1/measuring time = Samples/s). For most applications, a measuring time of 0.20 to 1.00 seconds is suitable .
34 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
CAUTION!
short measuring time.
PN15=
Description
1
Instantaneous value: Operational mode „instantaneous value“ is displayed.
2
Minimal value display: In this operational mode, the smallest
(switching-on) or by the digital input/ multi-function key.
3
Maximal value display:
digital input/ multi-function key.
5
Sliding average value: The complete average time is a results
analogue output or with the relays, too.
6
Totalisator value: In operation mode „Totalisator value“, the
to be displayed in a individual adjustable dimension.
7
Absolute value: In operation mode „absolute value“ the display connection, without consideration of a previous taring.
8
Trigger mode: In operation mode „trigger mode“ the
The updating of other functional components (analogue output and relay) is carried out cyclically with the set measuring time. If the measuring time is set very short, it is possible that there will be jumps in the analogue output in the case of a noisy signal or a brief switching of the relay. When selecting the measuring time, it should be borne in mind that the MIN / MAX memory receives its values on the basis of the set measuring time. Should the peaks of a turbulent signal be recorded, it may certainly be worthwhile to choose a very
PN15: Display mode
The device supports several operational modes, which are selectable under PN15.
is equal to the standard display, where the last measured value
occurred display value, since the last minimal value reset, is displayed. The minimal value reset is actuated by boot-up
In this operational mode, the largest occurred display value, since the last maximal value reset, is displayed. The maximal value reset is actuated by boot-up (switching-on) or by the
of the product or a multiplication of time and recorded average value PN14 x PN12. If one wants to see this result in the display, the display mode PN15 needs to be programmed parallel on this result. This must be pointed out with an optional
totalisator- / sum value is displayed. With this value by means of an active flow rate, a volume about the time can be collected. As this time can be very long (approx. 1 year), the value needs
shows the value that has been measured since voltage
WIKA operating instructions digital indicator model DI35-M 35
6 Commissoning, ope ration
instantaneous value is only transmitted on the display by a multi-function key.
PN16 =
Activator for MIN / MAX value reset
0
None
1
Digital input active, for longer than 50 ms
2
Multi-function key pressed for longer than 50 ms
3
Digital input or multi-function key active, for longer than 50 ms
4
Taring function
increasing shoulder via the digital input or by activating of the
PN16: Activator for MIN / MAX value reset
After boot-up the MIN / MAX values are automatically set back on the instantaneous value. To set back minimal- /maximal values even during operation, 3 additional escapements are available.
The value reset is only shown shortly after actuation of the digital input or multi-function key by 5 horizontal bars (“ - - - - - “) for 0.5 se co n ds. After that the instantaneous value is shown as long in operating mode MIN / MAX value display, as the activator is taken back. This way the instantaneous value can be watched for a longer time. If the value reset ought to be done during taring, then there is no report in the display. During value reset only the MIN/MAX value that presently shown in the display is set back!
PN18: Zero point suppression
The zero point suppression offers the possibility of masking an area around zero for displaying a value of zero. In the program number the amount is parameterized which is then effective in both the positive and the negative directions. This may be necessary if, for example, a number of revolutions is being measured by an analogue sensor and has a drift around zero. If the signal changes slightly when the motor comes to a standstill, a speed of zero is still indicated. In addition, slightly negative rpms are suppressed.
PN20, PN21 and PN22: Analogue out put
The parameters of the analogue output refer to the scaling of the display and are cyclically updated with the measuring time. With PN22 = 0 the analogue output can be de-activated, whereas it remains on its initial value after a re­start of the device. The analogue output can be related to all possible values that are recorded in the device. For further information please see chapter „6.3.5 Analogue output“ or chapter “6.7 program number table”.
36 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
Userlevel PN 52 =
0 1 2 3 4 5 6 7 8
Access to
PN
Display brightness
19
Programming lock
50
Serial number
200
Setpoint threshold values
61, 71, 81, 91
• • • • • • •
Setpoint parameters
59…95
Interface parameters (option)
32…34
Analog output parameter (option)
20…22
Measuring input parameters
0…18
Linearization para met e r s for measuring input
100…130
Authorization code
51 •
Userlevel
52
The inital and final value is always displayed without comma. The demonstration of the measuring value in the display is taken as base, so with a demonstration of e.g. 6.400 the final value can be parameterized by 6400 on this display value.
PN34: Interface behavior
The current display value can be sent by the optional interface. In standard mode PN34 = 0 the display stays passive and expects data from the bus. This operation is used for the configuration of the display. For slower actions the instantaneous measuring value can be actively asked for by command. In sending mode PN34 = 1 the displays sends actively in cycle of the measuring time the current measuring value. For further information please see chapter „6.3.7 Serial Interface RS232/ RS485“.
PN50 to PN52: Security setting , user level
With the parameters in the security settings, access to the program numbers is regulated through the setting of various user levels. The user levels divide the access into various levels. The user is only given access to the settings authorized by the system operator, such as the setting of thresholds. The lower the figure for the user level given under PN52, the lower the level of security of the unit parameters against user intervention .
Userlevel contains program number x
The user level 1,3, and 5 are reserved. With rising userlevel, the number of for the user unlocked parameters decreases, according to the above shown table.
The parameterized user level PN52 is active as long as the authorization code PN51 and programming lock PN50 are different. On delivery both parameters are set to 0000, so that the programming lock is deactivated.
WIKA operating instructions digital indicator model DI35-M 37
6 Commissoning, ope ration
PN180 =
Activator for MIN/MAX value reset
0
Without summation function, the sum value is pre-allocated with „0“ and does not change any more.
1
Without permanent storage e.g. for dose procedures < 30 min
all data get lost.
2
Permanent storage e.g. for the survey of quantities or distances power failure is avoided.
To activate the set user level, you must enter a four-digit number under PN51 as a "locking code" and confirm it by pressing the [P] key for approx. 1 second.
On changing to programming mode, the unit jumps to the first authorized program number. If user level PN52 = 3, then, for example, the parameters of the set points can be changed, but changing the parameter of the measuring input (PN0) is not possible at this user level. In order to obtain access to all program numbers later (equivalent to user level 0), you have to enter under PN50 the same code you used before under PN51. You must then acknowledge this by pressing the [P] key for approx. 1 second. After this you have access to all program numbers.
Information
If the authorization code becomes lost, the unit can be set t o the default value 0000 at the manufacturer's without any data loss.
PN59 to PN97: Setpoints / Relays
You can influence the behavior of the setpoints with various program numbers. The figures refer to the scaled measurement and are updated with the set measuring time. A description of the various parameters is given in chapter „6.3.4 Description of the alarm outputs”.
PN100 to PN130: Linearization
Through the linearization, the user has the possibility to linearize a non-linear sensor signal. A detailed description can be found in chapter „6.5 Description of the measuring input“, part „Linearization“ PN100 ≥ 0.
PN180: Totalizer / summati on f unction
For the add of measuring values, 3 operation types are available:
the sum value is not stored in the devices memory, it could be damaged by being set back too often. In case of power failure
or for longer spaces of time > 1h. Here a data loss in case of a
38 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
PN181, PN182 and PN183: Totaliser calculation
To calculate a totaliser / sum value the time base and the unit are very important. The discharge is stated in amount per time and the speed in distance per time. By parameterization of the time base PN181 to s, min or h the device adds up the die totalisor value.
If e.g. a sensor collects 1.200l/h, you only have to add up the 3.600th part of the total amount of liter at a measuring time of 1 second; in this case it would be 0.333 liter per measuring cycle. Despite of this small value, the totaliser value can add up itself to a quite high value during a period of one year. In this example it would be approx. 10,512,000 liter in a year. Here, a declaration in cubic meters would be reasonable. For the realization of this, you have to preset a factor, in this example PN182=3 (10³), so the value can be divided and liters become cubic meters. If you want to integrate the amount for only one month, the demonstration in cubic meters can be provided with a decimal place under PN183. If you parameterize now factor PN182=2 and the decimal place PN183=1, it would lead to a demonstration of 864.0 cubic meters at the end of the month.
PN184, PN185: Totaliser-Reset
According to the demanded application the totaliser- / sum value needs to be set back to a special point of time. This can be done directly by a parameterization of the initial value PN184 on multi-function or by the under PN185 parameterized actuators (see program number table chapter 6.7). The most reasonable way is by the digital input, as it is not easy accessible for the operating personal.
PN186: Recall of the totalisator values
The totaliser- / sum value can be permanently or displayed by an actuator (multi-function key / digital input). Often the sum value has not the first priority, so its demonstration occurs as a coproduct.
PN200: Serial number
Under PN200 you can call up the 5-digit serial number that allows allocation to the production process and the manufacturing procedure.
WIKA operating instructions digital indicator model DI35-M 39
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
0
Measuring input
Current, voltage
40 = ± 150 mV
3
2

6.7 Program number table

The program table lists all the program numbers (PN) with their function, range of values, default values and user level.
Parameters 1 to 29 make use of the factory calibration. At PN0 = 1…12 set points can be changed in the measuring range. The parameters ≥ 30 need
sensor calibration.
01 = 0…20 mA 02 = 4…20 mA 03 = 0…10 V 04 = 0…5 V 05 = 0…2500 mV 06 = 0…1250 mV 07 = 0…600 mV 08 = 0…300 mV 09 = 0…150 mV 10 = 0…75 mV 11 = 0…35 mV 12 = 0…18 mV Temperature measurement 13 = PT100 (4/2 wire) 14 = PT100 (3 wire) 15 = PT200 (4/2 wire) 16 = PT200 (3 wire) 17 = PT500 (4/2 wire) 18 = PT500 (3 wire) 19 = PT1000 (4/2 wire) 20 = PT1000 (3 wire) 21 = L 22 = J 23 = K 24 = B 25 = S 26 = N 27 = E 28 = T 29 = R Resistance / Potentiometer
30 = ≤ 100 Ω (4/2 wire) 31 = ≤ 1 kΩ (4/2 wire) 32 = ≤ 10 kΩ (4/2 wire)
Sensor calibration 33 = 0/4…20 mA 34 = -1…10 V 35 = -1…5 V 36 = -500…2500 mV 37 = -500…1250 mV 38 = -500…600 mV 39 = ± 300 mV
40 WIKA operating instructions digital indicator DI35-M
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
41 = ± 75 mV
45 = 0…2 mA
1
Final value / Fullscale
PN20 ≤ 12 or PN0 ≥ 30
-9999…99999
10000
2 2 Zero point / Offset
PN0 ≤ 12 and PN0 ≥ 30
-9999…99999
0
2
3
Decimal point
shown in the display
5
Offset shift
PN0 = 13 to 29
6
thermocouple reference
thermocouples)
0 = inactive
1
2
7
Setpoint for taring
-9999…99999
0
2
8
Activator for taring
0 = none
7 = combination 3 with 4
0
2
42 = ± 35 mV 43 = ± 18 mV 44 = 0…5 mA
Voltage, current
With PN0 ≤ 12 and PN0 ≥ 30
PTxxx resistance thermometer
Physical unit and number after the decimal point; with PN0 = 13 to 20 0 or 1: the physical unit is not shown in the display 2 to 5: the unit is shown after the figure Thermocouple Physical unit and number after the decimal point; PN0 = 21 to 29 0 or 1: the physical unit is not
At analogue or resistance measurements and sensor calibration PN0 = 1 to 12 or 30 to 45, with temperature sens or s,
00000…0,0000
0 = 8888.8 [°C] 1 = 8888.8 [°F] 2 = 8888°C [°C] 3 = 8888°F [°F] 4 = 888.8°C [°C] (-99.9…999.9) 5 = 888.8°F [°F] (-99.9…999.9)
0 = 8888.8 [°C] 1 = 8888.8 [°F] 2 = 8888°C [°C] 3 = 8888°F [°F]
-9999…99999
Measuring range
none
2
0
0 / 0,0
2
2
2
2
junction
With PN0 = 21 to 29 (can only be parameterised with
WIKA operating instructions digital indicator model DI35-M 41
1 = active
1 = digital input 2 = multi-function key 3 = digital input without key 4 = boot-up 5 = combination 1 with 4 6 = combination 2 with 4
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
8 = temporarily taring via
or multi-function key
General settings
12
Sliding average value
0 = off 1…100 measuring values
0
2 13
Display time
0,1…10,0
1,0
2
14
Measuring time
Resistance 3-Leiter
0,06…10,00
1,00
2
15
Display mode
1 = instantaneous value
8 = trigger mode
1
2 16
Activator for MIN- / MAX
0 = no reset activator
4 = with taring function
2
2
18
Zero point suppression
0…99999
10000
4
19
Display brightness
0…9 (0 = bright / 9 = dark)
3 8 Analogue output (Option)
20
Final value / Fullscale
-9999….99999
1000
4
21
Inital value / Offset
-9999…99999
0
4
22
Analog output
0 = de-activated
7 = absolute value
1
4
Interface
34
Interface behaviour
0 = standard operation
0
4
digital input 9 = fast taring on digital input 10 = fast taring on multi-
function key 11 = fast taring on digital input
Voltage, current (PN0 = 1…12; 33…45) PTxxxx 2- / 4-wire PTxxxx 3-wire Temperature measurement thermocouple Resistance 2- / 4-Leiter
value reset
0,02…10,00 0,04…10,00
0,06…10,00 0,04…10,00
0,04…10,00
2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizer value 7 = absolute value
1 = digital input 2 = multi-function key 3 = digital input or multi-
function key
1,0 1,0
1,0 1,0
1,00
2 2
2 2
2
42 WIKA operating instructions digital indicator DI35-M
1 = instantaneous value 2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizator value
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
1 = transmission operation
Security settings
50
Programming lock
0000…9999
0000
8
51
Authorization code
0000…9999
0000
0
52
Userlevel
0…8
8 0 Flashing of the LED display
59
Display flashing (approx.
and 4
0
6
Setpoint 1
60
Setpoint 1 (Source / Trigger
0 = not activated
7 = absolute value
1
6
61
Threshold
-9999…99999
1000
6
62
Hysteresis
1…99999
1
6
63
Active above / below SP value
0 = active below SP 1 = active above SP
1
6 64
Switch delay
0.0…10.0 seconds
0,0
6
65
Delay type
0 = none
digital input
1
6
67
Setpoint confirmation
0 = no locking
7 = switch-on locking by both
0
6
0.5 seconds) No flashing Flashing at set point 1 Flashing at set point 2 Flashing at set point 3 Flashing at set point 4 Flashing at set point 1 and 2 Flashing at set point 3 and 4 Flashing at set point 1, 2, 3
value)
0 = no flashing 1 = flashes at 1 2 = flashes at 2 3 = flashes at 3 4 = flashes at 4 5 = flashes at 1 and 2 6 = flashes at 3 and 4 7 = flashes at 1, 2, 3 and 4
1 = instantaneous value 2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizer value
WIKA operating instructions digital indicator model DI35-M 43
1 = switch-on delay 2 = switch-off delay 3 = switch-on/-off delay 4 = suppression with activated
1 = switch-off locking by multi-
function key 2 = switch-off locking by
external input 3 = switch-off locking by both 4 = no locking 5 = switch-on locking by multi-
function key 6 = switch-on locking by digital
input
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
Setpoint 2
70
Setpoint 2 (Source / Trigger
0 = not activated
7 = absolute value
1
6
71
Threshold
-9999…99999
1000
6
72
Hysteresis
1…99999
1
6
73
Active above / below SP value
0 = active below SP 1 = active above SP
1
6 74
Switch delay
0.0…10.0 seconds
0,0
6
75
Delay type
0 = none
digital input
1
6
77
Setpoint confirmation
0 = no locking
7 = switch-on locking by both
0
6
Setpoint 3
80
Setpoint 3 (Source / Trigger
0 = not activated
7 = absolute value
1
6
81
Threshold
-9999…99999
1000
6
82
Hysteresis
1…99999
1
6
83
Active above / below SP value
0 = active below SP 1 = active above SP
1
6 84
Switch delay
0.0…10.0 seconds
0,0
6
value)
1 = instantaneous value 2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizator value
1 = switch-on delay 2 = switch-off delay 3 = switch-on / -off delay 4 = suppression with activated
1 = switch-off locking by multi-
function key 2 = switch-off locking by
external input 3 = switch-off locking by both 4 = no locking 5 = switch-on locking by multi-
function key 6 = switch-on locking by digital
input
value)
44 WIKA operating instructions digital indicator DI35-M
1 = instantaneous value 2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizator value
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
85
Delay type
0 = none
digital input
1
6
87
Setpoint confirmation
0 = no locking
7 = switch-on locking by both
0
6
Setpoint 4
90
Setpoint 4 (Source / Trigger
0 = not activated
7 = absolute value
1
6
91
Threshold
-9999…99999
1000
6
92
Hysteresis
1…99999
1
6
93
Active above / below SP value
0 = active below SP 1 = active above SP
1
6 94
Switch delay
0.0…10.0 seconds
0,0
6
95
Delay type
0 = none
digital input
1
6
97
Setpoint confirmation
0 = no locking
input
0
6
1 = switch-on delay 2 = switch-off delay 3 = switch-on / -off delay 4 = suppression with activated
1 = switch-off locking by multi-
function key 2 = switch-off locking by
external input 3 = switch-off locking by both 4 = no locking 5 = switch-on locking by multi-
function key 6 = switch-on locking by digital
input
value)
1 = instantaneous value 2 = MIN value 3 = MAX value 4 = HOLD value 5 = sliding average value 6 = totalizator value
1 = switch-on delay 2 = switch-off delay 3 = switch-on / -off delay 4 = suppression with activated
1 = switch-off locking by multi-
function key 2 = switch-off locking by
external input 3 = switch-off locking by both 4 = no locking 5 = switch-on locking by multi-
function key 6 = switch-on locking by digital
WIKA operating instructions digital indicator model DI35-M 45
6 Commissoning, ope ration
PN
Function
Range of values
De­fault
User­level
7 = switch-on locking by both
Linearization
100
Number of additional setpoints
0…30
0
2
101 130
Setpoints 1…30
-9999…99999
2
180
Totalizer function
0 = off
saving
0
3
181
Time base of display value
0 = second 2 = hour
0
3 182
Factor for totalizer value
(in powers of 10)
0 = 1…6 = 1.000.000
0 3 183
Decimal point for totalizer value
00000…0,0000
0
3
184
Counter value in digit (for value aswell
0…99999
0
3
185
Activator for counter reset
0 = no reset source
showing totalisator value
0
3
186
Change display on
0 = no change 2 = by digital input
0
3
Information
200
Serial number
0…99999
0
8
1 = Totalizer without
permanent saving (Reset
by boot-up) 2 = Totalizer with permant
for totalizator functi o n
Reset through 0, too), inital
on 0
(multi-function key or digital input: push for at least 50 ms)
totalizator value
1 = minute
1 = by multi-function key 2 = by external input 3 = by multi-function key and
digital input 4 = UP and DOWN while
1 = by multi-function key
46 WIKA operating instructions digital indicator DI35-M

7 Maintenance and clea ning

CAUTION!
moisture.

6.8 Default values

Reset to default values
To return the unit to a defined basic state, a reset can be carried out to the default values.
The following procedure should be used:
Switch off the power supply Press button [P] Switch on the power supply and press [P] for further approx. 2 seconds
until „- - - - -“ is shown in the display.
With reset, the default values of the program table are loaded and used for subsequent operation. This puts the unit back to the state in which it was supplied.
Caution! This is only possible when the programming lock PN50 allows
access to all PNs or “HELP” is shown in the display.
Caution! All application-related data are lost
7 Maintenance and cleaning

7.1 Maintenance

This instrument is maintenance-free. Repairs must only be carried out by the manufacturer.

7.2 Cleaning

Before cleaning, correctly disconnect the instrument from
the mains.
Clean the instrument with a moist cloth. Electrical connections must not come into contact with
For information on returning the instrument see chapter "9.2 Return".
WIKA operating instructions digital indicator model DI35-M 47

8 Faults

Error description
Measures/Solutions
The unit permanently indicates
The input has a very high
correctly.
The unit permanently shows
The input has a very low
correctly.
The word "HELP " lights up in the 7-
The unit has found an error in the
your application.
Program numbers for parameterising
The programming lock is set at a
be parameterised.
"Err1" lights up in the 7-segment display
Please contact the manufaturer if
errors of thi s ki n d occur.
The addressed digital input does not
Meas ure the current of the digital
be between 1 mA and 3 mA.
Program numbers for the analog output PN20…PN22 are not
The anal og output is an option of
this device type. If it is not
8 Faults
overflow „ ¯ ¯ ¯ ¯ ¯ “. (5 bars at the top of the 7 segment display)
measurement, check the measuring circuit.
With a selected input with a low
voltage signal, it is only connected on one side or the input is open.
Not all of the activated setpoints
are parameterised. Check if the relevant parameter PN1, PN2, PN100…PN130 are adjusted
underflow „ _ _ _ _ _ “. (5 bars at the bottom of the 7 segment display)
segment display.
of the input are not accessible.
measurement, check the measuring circuit .
With a selected input with a low
voltage signal, it is only connected on one side or the input is open.
Not all of the activated setpoints
are parameterised. Check if the relevant parameter PN1, PN2, PN100…PN130 are adjusted
configuration memory. Perform a reset on the default values and reconfigure the unit according to
user level that does not allow access.
Under PN1, a different sensor type
was parameterised so that the desired program number cannot
react.
48 WIKA operating instructions digital indicator DI35-M
input with a multimeter. It should
8 Faults
accessible.
assembled, then the program numbers are not shown.
The device does not react as
If you are not sure if the device has
delivery status.
CAUTION!
In this case, contact the manufacturer.
expected.
If faults cannot be eliminated by means of the measures listed above, the instrument must be shut down immediately, and it must be ensured that pressure and/or signal are no longer present, and it must be prevented from being inadvertently put back into service.
If a return is needed, please follow the instructions given in chapter "9.2 Return".
been parameterised before, then follow the steps as written in the next chapter and set it back to its
WIKA operating instructions digital indicator model DI35-M 49

9 Dismounting, retur n a nd disposal

9 Dismounting, return and disposal
WARNING!
Residual media in dismounted instruments can result in a risk to persons, the environment and equipment. Take sufficient precautionary measures.

9.1 Dismounting

To dismount the instrument, do the following steps:
1. Open the clamping screws and remove the fixing elements.
2. Remove the instrument and seal from panel cutout.

9.2 Return

WARNING! Strictly observe when shi pping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous substances (acids, bases, solut ion s, etc.).
When returning the instrument, use the original packaging or a suitable transport package.
Enclose the completed return form with the instrument.
The return form is available on the internet:
www.wika.de / Service / Return

9.3 Disposal

Incorrect disposal can put the environment at risk. Dispose of instrument components and packaging materials in an
environmentally compatible way and in accordance with the country-specific waste disposal regulations.
50 WIKA operating instructions digital indicator DI35-M

10 Appendix: Declara t ion of conformity

10 Appendix: Declaration of conformity
WIKA operating instructions digital indicator model DI35-M 51
WIKA global
www.wika.de
WIKA subsidiaries worldwide can be found online at www.wika.com.
52 WIKA operating instructions digital indicator DI35-M
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg • Germany Tel. (+49) 9372/132-0 Fax (+49) 9372/132-406 E-Mail info@wika.de
Loading...