This manual provides an overview of the functionalities of the modular samos safety
system as a safety processing unit for plant and machines. It describes the individual
modules and the way they function together in the system as a whole with safety sensors,
switches and actuators.. As well as the specific configurations of switches and terminals,
the fundamental methods by which the functions work are also explained in detail.
Relevant application examples help you to use samos in practice, especially in hierarchical
safety zones. The manual also includes installation information, instructions and rules that
must be observed, technical data and interface descriptions, error information, error
handling and instructions for risk analysis.
This manual contains the information required for proper use of the devices described in it.
The system and its modules must only be installed by properly qualified personnel. The
applicable national norms and regulations must be observed (in Germany VDE). For that
reason this manual is aimed at technically qualified personnel such as mechanical and
electrical engineers, safety reps, PLC programmers, enclosure makers, electrical fitters,
machine and plant operators, setup staff, and service and maintenance personnel.
The “Caution” symbol is used at various places in this manual.
“Caution” indicates a potentially dangerous situation or state that could – if not avoided –
lead to minor or medium injury. “Caution” is also used to warn against uncertain
operation and potential misuse. “Caution” is also used to indicate situations where
property damage could occur without causing personal injury.
Please observe the following safety rules:
Only trained professional electricians may install, startup, modify, and retrofit this
equipment!
Disconnect supply voltage to the equipment / system prior to starting any work! If
installation or system errors occur, line voltage may be present at the control circuit in
devices without DC isolation!
Observe all electrical safety regulations issued by the appropriate technical authorities or
the trade association.
Opening the housing or any other manipulation will void the warranty.
If the device has been subjected to improper or incorrect use it must no longer be used,
and the guarantee loses its validity. Impermissible conditions include: strong mechanical
stress, for example through a fall, or voltages, currents, temperatures or humidity
outside of the specifications.
Before starting up your machine/plant for the first time, please be sure to check all the
safety functions according to valid regulations, and observe the specified test cycles for
safety equipment.
Take the following safety measures prior to installation, assembly, or disassembly:
Disconnect supply voltage to the equipment / system prior to starting any work!
Lockout/tag the equipment/system to prevent accidental activation!
Confirm that no voltage is present!
Ground the phases and short to ground!
Protect against adjacent live components using guards and barriers!
The samos safety system described in this manual serves to protect people, the
environment, the machine and the material according to the valid EU occupational health
and safety directive 89/391/EEC, the machinery directive 2006/42/EC, the use of work
equipment directive 89/655/EEC as well as the statutory regulations and standards
applicable in other countries (e.g. USA with OSHA 29 CFR 1910.xxx safety standards,
OSHA 3067 concepts and technologies for machine safety and NPFA 70, NFPA 79, ANSI
B11 product liability).
If the safety system is properly maintained and used for its intended purpose it will not
normally cause damage to property or present health hazards. However, improper
configuration, installation, maintenance or operation of the system or machine, ignoring the
instructions in this manual, or intervention by insufficiently qualified personnel may result
in connected actuators (such as motors, hydraulic units, etc.) becoming a source of
danger.
The safety system is a state-of-the-art product and is manufactured to recognized safety
requirements. All the same, its use can cause danger to the health and safety of operators
and others, or damage machines, systems or other property.
The safety system must only be used in perfect technical condition for its intended
purpose, with attention given to safety and danger, and observing the information and
instructions given in this manual and the operating instructions supplied with the devices.
Correct transport, storage, installation, operation and maintenance of the system are all
prerequisites for smooth and safe operation of the control system. Malfunctions, in
particular those which may affect safety, must be immediately resolved.
The devices must be installed in an enclosure with at least IP54 protection.
The devices must be installed on a mounting rail (EN 50022-35).
The mounting rail must be connected to protective earth (PE).
The system and the system inputs must always be powered by a common power supply
unit.
The external power supply unit must comply with the regulations for safety and
protection extra low voltage systems (SELV, PELV acc. to IEC 60536) and DIN EN 50178
(Electronic Equipment for Use in Power Installations).
The application examples and circuitry suggestions have been developed to the state of
the art and our best knowledge. Nonetheless, Wieland cannot accept liability for the
correctness and completeness of the information. The information does not have the legal
status of guarantees or guaranteed qualities.
safety system consists of a small number of multifunctional modules and an
optional field bus coupler. This
you add modules as the safety task grows. Sensibly coordinated, combinable function
blocks take the place of singular solutions and isolated specialists.
samos
combines all the safety sensors that monitor your machine/plant safety singly, in
combination or all together.
replaces special devices for monitoring – for example – emergency stop, position
switches, two-hand switches and light barriers.
allows you to create dependent/independent safety zones.
sa
fety modular system is, as the name suggests, modular –
Even a single 22.5 mm base module can operate independently and replace two safety
switching devices. Two
samos
modules replace up to 6 safety switching devices. In the
maximum configuration you can monitor up to 50 dual-channel safety sensors – up to EN
ISO 13849-1 PL e / category 4 or EN 61508/EN 62061 SIL 3.
Handling and function will be familiar from conventional safety switching devices. You
can set all the safety functions simply using a screwdriver – no programming software –
and read them off on the device. If required, you can expand the inputs or outputs using
additional modules.
Emergency stop, with or without cross-circuit monitoring
Safety door monitoring, also with coded electromagnetic switches
Controlled stopping with settable off delay up to 5 minutes, with or without retriggering
Light barrier monitoring with testable/self-testing sensors (non-contact safety device type 2
and 4)
Position monitoring with testable inductive sensors (PDF)
Static valve monitoring
Two-hand applications to EN 574, type IIIA and IIIC
Jog mode
4-wire switching mat monitoring
Muting and bypass
Enabling function for cascading and grouping
Automatic or manual Reset, starting and restarting inhibit
The samos modular safety system is a programmable electronics PE) element of an
electrical/ electronic/programmable electronic system (E/E/PES) as described in IEC/EN
61508/EN 62061. The system comprises base modules, input and output modules, and
bus coupler modules.
The minimum configuration is one SA-BM master base module. You can connect other
active safety modules, passive safety modules and bus coupler modules to the master to
create a system.
Up to 12 active safety modules (SA-IN input modules)
Additionally up to 4 SA-OR passive relay output modules
Additionally 1 bus coupler module
All SA-BM base modules can be expanded with SA-IN inputs and SA-OR relay outputs.
The system groups formed in this way are functionally autonomous and can be wired
together as required.
Structure
In a system the master base module is at the left-hand end, the optional bus coupler
module at the right-hand end. The modules are connected by means of a connector with
proper coding, integrated in the housing. The 24 V power supply is fed in through the
master base module.
Accordingly to the applications in a samos overall system hard-coded system groups can
be assembled, whose codings are different and whose logical functions are independent
from each other. Every system group of the overall system consists of a distinctly coded
basic module, which can be amended with input modules of the same coding.
Example of one system group
Basic module
Master (SA-BM-S1)
Input module
(SA-IN-S1)
Input module
(SA-IN-S1)
Output module
Bus interconnection
System group 1
More safety via coding
In our enhanced
samos
IN) is hard-coded according to its system group (1-3) and cannot be applied in other
system groups. Equally coded basic modules cannot be stuck together. Modules SA-BM,
and/or SA-IN in combination with
Germany in an overall system with two or more basic modules of the same coding and at
least one input module, prior to the 17th of April in 2012 (till construction level E-01)
mustn't be applied without approval of the patentee of the German patent 100 20 075.
(more information at http://register.dpma.de/DPMAregister/pat/einsteiger?lang=en)
module
system, every basic module (SA-BM) and every input module (SA-
The master base module is the obligatory basic element of the samos system. On its own
it functions as a complete safety switching device for monitoring up to 2 safety circuits. It
offers 8 function blocks for inputs and logic functions (set on rotary switch on front), 8
inputs and 4 wear-free semiconductor safety outputs. The system configuration is saved in
the master. Errors and unauthorized alterations cause safety shutdown of the whole
system.
The input module adds additional input circuits or logic functions to a base module on its
left. The module has two function groups, A and B, each with 4 inputs. You have to set
one of 10 functions for each group using the rotary switch.
The output module adds potential-free output safety circuits with positively driven relay
contacts to expand the base module outputs. The module does not function as a slave on
the internal safety bus of the samos system. Instead it is integrated in the functions via
external wiring. It can therefore be positioned anywhere between the master base module
and the (optional) bus coupler module.
The bus coupler module for the Profibus-DP field bus allows system information for
diagnosis purposes (input levels, error and status information) to be sent to other bus
stations (e.g. higher-order controller). There is a separate manual for the bus coupler
modules (see page 70).
Risk assessment and risk minimization for plant and machines
This simplified description outlines the basics of risk analysis for planners and designers.
For more detailed information please consult the relevant norms.
Determining the limits of a machine
Proper use
Spatial limits (transport, assembly, installation, power supply, material feed)
Temporal limits (working life, servicing intervals, ...)
Identifying dangers
Crushing, shearing, electric shock, poisoning, burns, ...
You can find examples
for logic functions on
page 53ff.
You can find an overview
of applications on page
19 and 36.
You can find descriptions
of input modules on page
32ff.
You can find descriptions
of base modules on page
13ff,
relay output modules on
page 42ff.
You can find examples
for logic functions on
page 53ff.
You can find the
descriptions of reset
behavior on page 24ff.
Bus coupler modules are
described in a separate
manual. You can find the
order numbers on page
70.
samos
Guide
The technical measures for reducing the risk of dangerous states and damage to the
machine or material include the electrical equipment. The required level of risk
minimization and consequently the requirements of the safety-related parts on the
controller are determined for example according to EN ISO 13849-1 (here controller
category.
Creating safety zones
In risk analysis the machine is often divided into different safety
zones, which may have different risk potentials. The zones are
linked by safety logic functions so that only the necessary parts
of the machine are shut down when a safety event occurs.
Selecting safety devices and safety functions
for monitoring the safety equipment and safety zones. Selection
of stop category 0 and/or 1 (EN 60204-1).
Select function blocks and input circuit functions for the application on the samos
base module.
How many safety sensors and safety circuits
must also be monitored?
Select input expansions.
How many additional safety outputs are needed?
Select outputs on base module (semiconductor)
or output expansion (relay contacts)
Link safety zones
and function blocks in the samos system.
Select Reset behavior
for powering up and after safety event.
Select optional field bus function
as diagnosis function.
The samos safety system is for monitoring sensors as part of the safety equipment of
machines. The safety function (e.g. an emergency stop function) is implemented by
switching outputs Q on or off safely in relation to the state of the sensors on inputs I, EN
(enable) and S (Reset condition). Switching these outputs on/off prevents dangerous states
occurring in the plant/ machine.
The safety function is made up of a chain of logically linked functions. The input
modules communicate with the associated base module (on the left) via the internal safety
bus (SBus). The relay output modules are not integrated directly via the SBus in the samos
safety communication system. However, indirect monitoring is possible via the feedback
circuits.
Input circuit function
The input circuit function logically links input signals for further processing. There are
different methods for activation:
Input circuit function single-channel via NC contact
Input circuit function with dual-channel equivalent activation,
with/without cross-circuit monitoring, with/without synchronous time monitoring
Input circuit function with dual-channel non-equivalent activation,
with/without cross-circuit monitoring, with/without synchronous time monitoring
Two-hand function with activation by one NO contact per hand (EN 574, IIIA)
Two-hand function with activation by NO/NC combination for each hand (EN 574, IIIC)
Dual-channel equivalent activation by semiconductor
The off signal of an input function can be bridged with an OR signal. For example, in setup
mode a safety function can be bridged using an enabling button; an OR operation can also
link two safety functions.
The muting function is a special case of the OR function. For example, muting sensors
allow a conveyor belt to transport material through a light curtain by briefly bridging the
light curtain function.
With a bypass signal the OFF signal of a Reset function (see page 47) can be changed into
an ON signal in the base module. Bypass is used when the system is to be switched on
after a power shutdown but a light barrier is obstructed by material. Bypass cancels the
safety function of the safety device, allowing the blockage to be cleared. In normal
operation the muting function bridges automatically (see above).
The Reset function defines which (Reset) conditions must be fulfilled if, for example, an
ON signal is to be passed on to the Reset function output. All input and muting signals
from the base module and the associated input modules, and the bypass/OR signals from
the input modules are logically linked (AND/OR). The terminal configuration with bridges
and feedback circuits is also evaluated.
The enable function enables the ON signal in the Reset function if there is H-level on the
EN input. The H-level for enabling can be generated, for example, by a semiconductor
output Q
applications (EN ISO 13849-1) the module that generates the enabling signal must be in the
same enclosure. If the EN input is open or on L-level the following Q
outputs are locked.
on the base module for logic operations or a PLC output. For category 4
The time behavior of the safety ON/OFF signal is defined in the output function. Depending
on the function, you can set a off delay for outputs Q3 or Q3/Q4 between 0 and 5 minutes
(depending on module version).
The controller category (EN ISO 13849-1) or SIL (EN 61508/EN 62061) depends on the
external circuitry, the wiring, the choice of control devices and their location on the
machine.
In the event of single-channel control of a contact extension (e.g. SA-OR) through a base
module (SA-BM), category 4 according to EN ISO 13849-1 can be achieved if both
devices are installed in the same enclosure.
The SA-BM must be protected with a 6 A fuse of utilization category gG or a 6 A (4 A)
circuit-breaker (tripping characteristic B or C).
The rotary switches for selecting function and time must only be adjusted when power is
off.
Never connect or disconnect modules while the operating voltage is switched on.
If external contactors or relays are connected, the feedback circuits (NC contacts) must
be connected to the base module.
When inductive loads are connected (e.g. valves, contactors) a suppressor circuit must
be set up (e.g. RC combination).
Internal samos module addresses are assigned automatically when the system starts up.
Manual addressing is unnecessary (and not possible).
The safety system must be installed in an enclosure with at least IP 54 protection.
Each base module forms a system group within the overall system (sometimes together
with associated input expansion modules; see diagram on page 8).
Master base module
The SA-BM master base module is the obligatory
module of the samos system. On its own it functions
as a complete safety switching device for monitoring
up to 2 safety circuits.
* For the times, see the
function diagram at the
end of the table
The sum of currents,
which are drained from
the outputs X1, X2 of all
Base modules to supply
external sensors, may not
exceed 600 mA!
-BM-S1
Function
Function display 11 green LEDs, 1 red LED
Controls 2 10-position switches, 1 1-position button
Terminals Plug-in terminals with screws / spring force
Max. number of modules / status in system 1 / SBus master
Max. number of parallel-connected module inputs
Input circuit (I1..I4, EN, S1..S3) Min. Typical Max.
Input voltage, U
(LOW)
Input current, I
(LOW)
Cyclical peak input current, I
Input capacitance, C
Input resistance, R
ON period* t
OFF period* t
Break time of U
Break time period
Synchronous time t
Synchronous time t
Duration of operation Reset inuts S1, S2
Output voltage
Output current
Wire capacitance, C
Wire resistance, R
Type of outputs / short-circuit behavior Semiconductor / absolutely short-circuit-proof
Response time*** t
Functions 3.1, 7, 8
Function 3.2 (BWS type 2)
Function 3.2 (PDF sensors)
Functions 1 (except safety mat), 2, 4, 5.1, 6, 9
Function 1 (safety mat)
Function 5.2
DISABLE (via EN input)
OR off to Qx off
Function 3 (MUTING off to Qx off)
EN off to Qx off
Enter button ON period
Isolation
Power circuitry – input circuit
Power circuitry – output circuit
Input circuit – output circuit
Weight 0.16 kg
General technical data See page 65.
Order numbers See page 69.
3 s
no
no
no
* Signal changes are not
detected during the test
pulse.
** Signal changes from
HIGH to LOW are not
detected during the test
pulse.
For the times see the
function diagrams at the
end of the table.
*** The response time tAN
is the time between the
OFF signal arriving at the
input terminals and the
outputs actually being shut
down (in normal
operation).
The response times of
any assigned input
modules must also be
taken into consideration.
See input module data,
page 33.
For information on
safety-related
parameters, see glossary
p. 49
Voltage supply of the basic module and the
corresponding extension module (Plus
voltage at A1)
Outputs only for voltage supply of inputs of
the module or rather the control of the
sensors
Input for enabling the outputs
Control inputs for the configuration of mode
of operation and the connection of reset
buttons / feedback circuits
Inputs for the connection of signal
transmitters / sensors
Outputs for the controlling of actuators
10-pin connector for safety bus
- SA-BM: just nut (coded)
Push-buttons
FUNCTION
Q3/4 DELAY
ENTER
S1, S2, S3
LEDs
EN, S1 .. S3, I1.. I4
(green)
PWR (green)
Q1/2, Q3/4 (green)
FLT (red)
8-staged torque switch for adjustment of an
input circuit function
10-staged torque switch for adjustment of
the fall-back delay time
Button for the assumption of system
configuration (just SA-BM)
Indicators of according inputs
Voltage supply
Switching status of the semiconductor
outputs
Indicator of flawed operating modes
(see FLT error codes page 63)
Power supply to module electronics is on
H-level on corresponding input
Cross-circuit between I1 and I2
Cross-circuit between I3 and I4
Sequence error on I1, I2
Sequence error on I3, I4
Synchronous time error. The input that flashes is the one
that achieves good state too late.
Synchronous time error. The input that flashes is the one
that achieves good state too late.
H-level on corresponding input
Feedback circuit open
H-level on corresponding outputs, Q3/4 flashes during off
delay time
No fault states
Manipulation, handling errors and operating errors during operation
Configurations can only be set or altered using the switches
and terminals when the whole system is switched off, i.e.
when there is no operating voltage on terminals A1/A2 on
any base module. After the required functions and control
circuit functions have been set on all the modules in the
system (using the rotary switches and external circuitry on
terminals S1, S2, S3 respectively), operating voltage must
be connected while the ENTER button on the SA-BM base
module is pressed and held. As soon as the FLT indicator
starts blinking the ENTER button must be released within 3
seconds. Then the selected mode is saved in non-volatile
form and active. If the ENTER button is pressed for longer
than 5 seconds after the LED has started blinking, the FLT
display will indicate a fault (blinking light).
Terminals S1, S2, S3 serve not only to set the mode; they
can also be used for feedback-circuit monitoring of
connected relays and contactors. This means that the
terminal signals change during operation (opened
contact). The set mode remains unaffected because it is
only detected, checked and saved when the system is
switched on or restarted.
Because the relay expansion modules are not directly inte-
grated in the communication or diagnosis of the samos
system via the internal safety bus, changes in their
input/output circuitry are registered only indirectly via the
feedback circuits.
Manipulating the system configuration (e.g. operating a
rotary switch or adding or removing modules causes
immediate canceling of enabling. To assist in setting the
valid configuration the green PWR LED on the module
changes from blinking to continuous when the respective
switch position has been restored. A restart (switch off
and on again) under the set Reset condition is possible
when the former configuration has been restored. The
ENTER key has no effect during operation.
If the new configuration is to be adopted you have to go
through the “accept configuration” procedure described
above.
We recommend keeping a record of the configuration
with the documentation or in a clearly visible place in the
enclosure. One way to check the system configuration is to
output a checksum of the configuration data via a connected
bus coupler module.
There is a separate manual for the bus coupler modules
(see page 70).
Using the rotary FUNCTION switch on the front you can set 8 function blocks as single,
combination or dual functions. On their own or in appropriate combinations these function
blocks cover the main fields of safety application. Using terminal combinations you can set
Reset behavior for manual/automatic Reset (page 24), off delay retriggering (page 25) and
special functions (page 23). Switch positions 0 and 9 are without function and must not be
used.
Single functions 1 to 4
The input circuits of function groups A and B act jointly on output circuits Q1 to Q4
(exception: function 3 with Q3 as muting lamp / Reset required output). In functions 1
and 2 settable off delay and retriggering act jointly on outputs Q3 and Q4; in function 3
only on Q4; in function 4 no off delay can be set.
Combination functions 5 to 7
The input circuits of function group A act directly on all output circuits Q1 to Q4; the input
circuits of function group B act on output circuits Q3 and Q4.
They are AND-linked via the internal logic with input circuits A. This allows the safety
concept found on many machines (two safety zones, one group subordinate) to be
reproduced within the device. With the exception of function 5 (for which no off delay is
settable) the settable off delay and retriggering act only on output Q4.
Dual function
The input circuits of function groups A and B act separately on output circuits Q1, Q2 or
Q3, Q4. This means that with one base module you can monitor two independent safety
groups on a machine or system. Settable off delay and retriggering act only on output
Q4.
Evaluating input circuits / function blocks
The diagram shows three different types of evaluation and the signal flows between inputs
and outputs for single function 1, combination function 6 and dual function 8. The diagram
is an excerpt from the function overview (see page 30).
The off signal of an input function can be bridged with a OR
signal, for example with an enabling button for setup mode.
All the function blocks offer the possibility to link OR
function signals on the SA-IN input modules (function 7, see
page 39) with base module input signals by logical OR via
the SBus.
Additionally, the single function blocks 1 and 2 offer use of
the OR function on the base module itself via the two inputs
I3 and I4. U
+
is expected as the signal. Generation of an ON
x
signal (H-level) depends on several functions (see "System
Functions", page 46).
The OR function corresponds to an input circuit function
with dual-channel equivalent activation without cross-circuit
monitoring.
With a constant Ux signal+ on I3 and I4 and outputs Q1 to
Q4 switched on, the outputs remain switched on regardless
of the condition of the monitored safety sensors.
The muting function is a conditional OR function, with
which for example muting sensors can briefly bridge a light
curtain function to allow material to be transported through a
light curtain.
Muting is only possible on base modules with single
function block 3, via inputs I3 and I4. U
+
is expected as the
x
signal. Generation of an ON signal (H-level) depends on
several functions (see “System Functions”, page 46).
Output Q3 controls the corresponding muting lamp. If
manual Reset is configured, the Q3 output additionally
indicates via periodical ON/OFF (0.5 s/0.5 s) that Reset is
expected at input S1 (Reset-Required).
The muting function in the base device corresponds to
an input circuit function with dual-channel equivalent
activation without cross-circuit monitoring.
With a constant Ux signal+ on I3 and I4 and outputs Q1, Q2
and Q4 switched on, the outputs remain switched on
regardless of the condition of the monitored safety sensors.
Muting of a safety function must not be dependent on a
single signal!
+
The Ux signal can come from
supply voltage +UB,
the Qx semiconductor outputs on the base modules,
the OSSD outputs of muting light barriers (muting
function only).
Single function 3 and combination function 5 allow the use of special functions that are
activated via a corresponding configuration on control circuit terminal S2.
Single function 3
This function block offers the possibility of monitoring with an external test not only
emergency stop, safety door and non-contact safety device type 4 applications (acc. to EN
61496-x) but also sensors (e.g. non-contact safety device type 2) and potential-free
contacts. When the inputs are activated in this way the test function is activated by
leaving terminal S2 unactivated. Otherwise S2 is bridged with the supply voltage
(functions 3.1 and 3.2, see the “Control circuit functions” table on page 26 and the
“Function blocks” table on page 28).
Testable sensors on X1-I1 (terminal S2 open):
If time conditions are observed several sensors can be cascaded. Testable sensors
such as non-contact safety device type 2 light barriers (EN 61496-x) have separate
activation inputs on the transmitters. The activation inputs are used to test the sensor
function with a low signal; the base module analyses the response signal generated by
the receiver.
Testable sensors on X2-I2 (terminal S2 open):
If time conditions are observed up to four sensors can be cascaded. The time
conditions are matched specially for the GM 504S and GM 505S non-contact inductive
sensors (PDF acc. to EN 60947-5-3) made by ifm. The connection is only available on base
modules, not on input modules.
If one of the inputs I1 or I2 in not used a bridge must be installed to the respective
control output.
Inputs I3/I4 can be used as muting inputs specially for use with light curtains. They
are AND-linked to one another and OR-linked to the other inputs. The muting inputs only
act if the corresponding internal output signals of the Reset function Q
module were previously high (see also pages 22 and 46).
Output Q3 functions as a muting lamp output and as sigalling output „ResetRequired“. In this single function off delay for controlled stopping and retriggering act
only on output Q4.
Function group B can be used to monitor normal two-hand operation (synchronous
operation of two buttons within 0.5 s, function 5.1*) or two-hand operation in jog mode
(function 5.2*), e.g. for clearing a system. Here an output signal is only generated while
the controls are being pressed. Jog mode is restricted to 5 s. Releasing both controls
resets the time; repeated Reset is possible.
To activate jog mode terminal S2 remains unactivated. For other two-hand and safety
door applications S2 is bridged with the supply voltage +U
The two-hand function with two NO contacts cannot be used for operating presses,
because the safety level usually required (category 4) is not achieved. Function block 4
should be selected for press operation (EN 574 Type IIIC).
.
B
on the base
START
Special function
type 2
Special function
Testable PDF
Special function
two-hand
* For the functions see
also the "Control circuit
function" table on page
26 and the "Function
block overview" table on
page 30).
You can set the Reset behavior of the base modules by configuring terminals S1/S2 and
connecting Reset buttons, bridges or feedback circuits from external contactors/relays.
When power is switched on and the inputs are in safe state the base module expects a
Reset (if restarting inhibit ON) or actuation on at least one input circuit (if restarting
inhibit OFF).
NOTE
Restarting lockout
NOTE
NOTE
Reset function
The enabling input does not act as an input circuit on the monitored sensors, i.e. the
starting inhibit is not canceled by switching the EN signal off and on again. In combination
functions 5, 6, 7 the starting inhibit in group B is not canceled by a signal change on the
Reset function in group A; the signal change must occur in group B.
OFF
The outputs switch on immediately after power is switched on and the inputs are in safe
state.
For resetting the safety function after a safety event the base module expects the Reset
button to be operated. This realizes the required manual Reset after emergency stop (or
switching back on after the safety zone has been entered and left again).
The Reset button must be operated for between 50 ms and 5 s. In combination functions
5, 6, 7 the restarting inhibit in group B must always be canceled by the Reset button.
In function 3, the expected Reset signal is indicated via blinking output Q3 (ResetRequired).
OFF
Automatic Reset after safety event and restoration of safe state of inputs.
Elimination of a cross circuit is also immediately defined as restoration of safe state of
inputs.
The Reset function of manual and automatic Reset is defined by connecting terminals
S1/S2 with supply voltage +U
or the module’s own clock output X1. (Here terminal S1 is
B
shown; in functions with separate evaluation of function groups A and B terminal S2 and
clock output X2 are used equivalently for group B; see the table on page 26).
Starting inhibit Restarting inhibit Manual reset
Reset button and feedback
circuit between S1 and
supply voltage
Bridge or feedback circuit
between S1 and clock
output
NOTE
24
During the configuration phase (after power on) of manual Reset (with Reset button) the
corresponding S output must be open or connected to a high-ohm output (e.g. a PLC).
High or low potential will result in incorrect configuration.
On the front of the base modules you can set a off delay of 0..5 s, 0..50 s or 0..5 min,
depending on the device version. In position 0 release time = t
Technical Data, page 15). Depending on the selected function block, the off delay acts on
outputs Q3 and Q4, only on Q4, or on none of the outputs.
for undelayed outputs (see
R
Release delay
In functions without off delay (4 and 5) the delay switch must be set to 0 s, otherwise a
fault will be indicated. Contactors and/or relay output modules connected to the delayed
outputs are monitored separately via the feedback circuits (see “Control Circuit Functions”,
The behavior of off delay (retriggering) can be influenced by configuring terminal S3.
Bridge or feedback
circuit between S3 and
clock output X1
Auto mode (restarting inhibit OFF)
Manual mode (restarting inhibit ON)
Bridge or feedback
circuit between S3 and
supply voltage
Manual mode (restarting inhibit ON)
).
Auto mode (restarting inhibit OFF)
Auto mode (restarting inhibit OFF)
ON
If the safe input state (“good state”) of
the input circuits is reached again
before the delay has expired, the
delayed output circuits do not alter and
the delay time is reset (
In restarting inhibit mode the Reset
button has to be actuated additionally
during retriggering time (
Example: In automatic mode the safety
door is opened and the off delay starts
for the corresponding enabling paths. If
the door is closed again before the time
has expired the enabling paths do not
shut down and the machine continues to
operate without interruption.
OFF
Regardless of the state of the input
circuits, the delayed output circuits open
after expiry of the off delay time
(
and ).
With automatic Reset and “good state”
before expiry of the off delay time, the
delayed output circuits shut down for
400 ms and then switch on again (
Example: In manual mode the
emergency stop button is operated and
the off delay starts for the corresponding
enabling paths. If the emergency stop
button is released before the time has
expired and the Reset button operated,
the enabling paths shut down anyway.
The delay time must expire before
enabling via the Reset input is possible
again.
Retrigger and feedback – activation of control input
Retrigger OFF
Without
FEEDBACK
S3
With
FEEDBACK
Bridge or
feedback circuit
Q1/Q2 resp. Q4
S3
Feedback
via
S3
Retrigger ON
In functions without cross-circuit monitoring (see “Function Blocks – Overview”, page 30)
dynamic signals on outputs X1 and X2 are generated only during the configuring phase after
power on.
During the configuration phase (after power on) of manual Reset (with Reset button)
the corresponding S output must be open or connected to a high-ohm output (e.g. a PLC).
High or low potential will result in incorrect configuration.
In order to monitor external contactors (FEEDBACK) that may be connected to outputs Q1 Q4 the NC contacts of the respective contactors or output expansions must be connected
in series with the associated control inputs (see the tables here and page 47).
by I3/ I4,
Output Q3 for indicator
Muting/ Reset required
OR**
by I3/I4 or
input
expansion
INPUT A
INPUT B
7
I4
I3
+
>
1
AND
Input
expansion
RESETFB Q1/2AB,
RESET
switch
or
INPUT A
INPUT B
*K1/2
+U
B
*K1/2
X1
1-6
S1
S1
Startup
inhibit
ON
OFF
&
Restart
inhibit
ON
OFF
AND
Internal logic
Special function
S2
+U
B
or
S2
+U
BYPASS****
Input
expansion
ENABLE***
B
INPUT A
INPUT B
8
Q
START
SBus AB
>
1
EN
&
Off-delay
Retriggering, FB Q3/4
*K3/4
X2
S3
or
*K3/4
+UB
S3
Outputs
SAFE
Q1
Internal safety bus for function group
A or B or AB
*K1/2 Bridge or feedback circuit Q1/2
*K3/4 Bridge or feedback circuit Q3/4
*K3 Bridge or feedback circuit Q3
*K4 Bridge or feedback circuit Q4
OFF-DELAY
ON
OFF
SAFE
SAFE
SAFE
Q2
Q4
Q3
SINGLE
SINGLE
2
X1
X2
X1
X2
AB
n
t
I1
I2
CH1
t
sync
CH2
I1
I2
CROSSMON
3
AB
SAFE
POSITION
TYPE 4
n
t
I1
X1
I2
I1
Ux
Ux
X2
I2
I1
I2
I4
I3
+
>
1
I4
I3
SBus ABSBus ABSBusABSBus AB
+
>
1
SBus ABSBus ABSBusABSBus AB
&
Restart
Startup
inhibit
inhibit
ON
ON
OFF
OFF
Q
START
SBus ABSBus ABSBusAB
>
1
EN
&
OFF-DELAY
ON
SAFE
SAFE
Q1
OFF
SAFE
SAFE
Q2
Q4
Q3
>
1
&
Restart
Startup
inhibit
inhibit
ON
OFF
OFF
TEST
3.2
3.1
OFF
Q
START
>
1
EN
&
SAFE
Q1
MUTING
SAFE
Q2
**For signal supply to MUTING and OR
inputs I3/I4 see page 22.
**For signal supply to ENABLE input EN
see page 48.
SINGLE
4
AB
TEST
TYPE 2
n
t
TEST
or
TEST
ER
or
I1
I2
I1
X1
I2
I3
X2
I4
>
1
CH1
t
sync
CH2
CROSSMON
X1
X2
&
Startup
inhibit
ON
OFF
Q
ON
ON
Restart
Startup
inhibit
inhibit
OFF
ON
fixfix
*K1/2
+U
B
S1
Q
START
>
1
EN
&
OFF-DELAY
ON
OFF
SAFE
SAFE
Q4
Q3
SAFE
Q1
****BYPASS limited to max. 60 s.
Signal Ux from supply voltage +UB or the Qx
semiconductor outputs on the base module or the
OSSD of light barriers/light
Starting inhibit ON: Manual Reset after supply ON.
Starting inhibit OFF: Automatic Reset after supply ON.
Restarting inhibit ON: Manual Reset after safety event.
Restarting inhibit OFF: Automatic Reset after safety event (see page 24).
Retriggering ON: Delayed outputs remain in ON condition if safe
state of inputs has been restored when the delay has expired.
Retriggering OFF: Unconditional time delay period (see page 25).
31
Page 32
SA-IN Input Module
Y
5 SA-IN Input Module
Input Module Data
SA-IN-S1,
SA-IN-S1
Input Module
The input module adds additional input circuits or logic
functions to a base module on its left (SA-BM master).
ou can operate several input modules on one base
module.
There are two function groups, A and B, each with
four inputs and four sensor supplies. You can set one of
10 functions for each group independently, using the
rotary switches on the front. The configuration will be
permanently saved in the master base module. The
device operates as a slave on the internal safety bus.
Connection
diagram
Notes
Accepting
configuration
SA-IN
The controller category (EN ISO 13849-1) or SIL (EN 61508/EN 62061) depends on the
external circuitry, the wiring, the choice of control devices and their location on the
machine.
The rotary switches for selecting function must only be adjusted when power is off.
Never connect or disconnect modules while the operating voltage is switched on.
Internal samos module addresses are assigned automatically when the system starts up.
Manual addressing is unnecessary (and not possible).
The safety system must be installed in an enclosure with at least IP 54 protection.
Input modules are always assigned functionally to the next connected base module to
the left. Each base module forms a system group within the overall system (sometimes
together with associated input expansion modules; see diagram on page 8).
Base modules and input modules are uniquely coded depending on their system system
group (see diagram on page 8).
Accepting the system configuration
For accepting the system configuration see page 18.
Function
Function display 11 green LEDs, 1 red LED
Controls 2 10-position switches
Terminals Plug-in terminals with screws / spring force
Max. number of modules / status in system 12 / slave on SBus
Response time*** t
Function 1
Functions 6, 7
Functions 2 (without safety mat), 3, 4, 5, 8
Function 2 (safety mat)
(normal operation)
AN
Input module in the samos system
1.2 W
–5.0 V 5.0 V
–2.5 mA 2.1 mA
15 mA
200 nF
8 k
70 ms
> tAN
20 ms
18.0 V 30.0 V
150 mA
1000 nF
12 ms
20 ms
100
40 ms
33 ms
16 ms
24 ms
42 ms
Technical data
SA-IN
* For the times see the
function diagrams at the
end of the table.
The sum of currents,
which are drained from
all input modules of one
system to supply external
sensors, may not exceed
600 mA!
* Signal changes are not
detected during the test
pulse.
** Signal changes from
HIGH to LOW are not
detected during the test.
For the times see the
function diagrams at the
end of the table.
*** The response time tAN
is the time between the
output signal arriving at the
input terminals and the
semiconductor outputs of
the associated base
module actually being shut
down. The time is
independent of the
number of input modules
connected to the base
module.
Isolation
Power circuitry – input circuit
Power circuitry – output circuit
Input circuit – output circuit
Connection diagram KS 260-1-3
Weight 0.13 kg
General technical data See page 65
Order numbers See page 69
Power supply to module electronics is on
H-level on corresponding input
Cross-circuit between I1 and I2
Cross-circuit between I3 and I4
Cross-circuit between I5 and I6
Cross-circuit between I7 and I8
Sequence error on I1, I2
Sequence error on I3, I4
Sequence error on I5, I6
Sequence error on I7, I8
Synchronous time error. The input that flashes is the one
that achieves good state too late.
Synchronous time error. The input that flashes is the one
that achieves good state too late.
Synchronous time error. The input that flashes is the one
that achieves good state too late.
Synchronous time error. The input that flashes is the one
that achieves good state too late.
Good state of AND-linked input pairs I1/I2 and I3/I4
(function group A)
Good state of AND-linked input pairs I5/I6 and I7/I8
(function group B)
No fault states
sensors (functional group A)
rather control sensors of the module
(functional group A)
Inputs for connection of signal transmitters /
sensors (functional group B)
rather control sensors of the module
(functional group B)
nut)
10-staged torque switch for adjustment of an
input circuit function (functional group A or
rather B)
Indicators of according inputs
Voltage supply
Overall indicator of inputs I1..I4 (functional
group A)
Overall indicator of inputs I5..I8 (functional
group )
Indicator of flawed operating modes
(see FLT error codes page 63)
You can set one of 10 input functions (0–9) for each function group using the INPUT A and
INPUT B rotary switches on the front. The input signals are evaluated internally (depending
on switch position, for example for cross-circuit and simultaneity) and passed in groups on
the safety bus to the base module to the left. There they are linked logically with the
corresponding function group A or B. Several input modules can be assigned to one base
module. The effect of the input module groups on the associated base module depends on
the function block set there.
Function blocks 1 - 4: the inputs of both function groups on the input module (A + B) will
act together on the selected base module function (AND operation).
Function blocks 5 - 8: the inputs of both function groups on the input module A resp. B
will act separately on the respective group on the base module function.
* Maximum control
category (depends on
sensor, wiring and
installation). Please also
note the information on
page 13.
** Pairs of inputs
Group A:
I1/I2 and I3/I4,
Group B:
I5/I6 and I7/I8.
Sensor
connection
Evaluation Application
Single-channel
All four inputs of each function group (A, B) are
single-channel and linked by a logical AND. The
inputs In expect test pulses, which are generated
on the associated outputs Xn.
Single-channel testable sensors
Type 2 non-contact safety devices (light
barriers)
Testable sensors (e.g. type 2 non-contact
safety devices) are monitored. All four inputs of
each function group (A, B) are single-channel
and linked by a logical AND. The inputs I
n
expect test pulses, which are generated on the
associated outputs X
. You can also cascade
n
several light barriers. Also observe the test
pulse data for the sensors (non-contact safety
device, PDF, ...) and the samos module!
Two pairs are formed from the four inputs of a
function group (e.g. group A: I1/I2 and I3/I4)**.
A valid ON signal is only generated if ON state
is present at both inputs of a pair and both
were previously in OFF state (L-level) (flipflop).
Both pairs are then linked by a logical AND.
Two pairs are formed from the four inputs of a
function group (e.g. group A: I1/I2 and
I3/I4)**.
A valid ON signal is only generated if ON state
(H/L-level) is present at both inputs of a pair
and both were previously in OFF state (L/Hlevel) (flipflop). Both pairs are then linked by a
logical AND.
Two pairs are formed from the four inputs of a
function group (e.g. group A: I1/I2 and
I3/I4)**.
A valid ON signal is only generated if ON state
is present at both inputs of a pair and both
were previously in OFF state (L-level) (flipflop).
Both pairs are then linked by a logical AND.
OR
(without cross-circuit monitoring)
Two pairs are formed from the four inputs of a
function group (e.g. group A: I1/I2 and
I3/I4)**.
A valid ON signal is only generated if ON state
(H-level) is present at both inputs of a pair and
both were previously in OFF state (L-level)
(flipflop). Both pairs are then linked by a logical
OR. The result of this function is used in the
base module to suppress an OFF signal.
For the OR function see page 46.
BYPASS
(with cross-circuit monitoring)
A pair is formed from the first two inputs of a
function group (e.g. group A: I1/I2)**. A valid
ON signal is only generated if ON state (Hlevel) is present at both inputs of the pair and
both were previously in OFF state (L-level)
(flipflop). The result of this function is used in
the base module to force an ON signal of
duration limited to 60 s. For the BYPASS
function see page 46.
pplication
e.g.
INPUT A
INPUT B
5 / 4 4
6 4
7 3
8 4
SA-IN Input Module
Cat.
up to*
When cross-circuit is detected the whole group (A or B) is shut down.
Functions 1 to 6 allow input expansion for standard functions such as emergency stop,
light curtain, valve position monitoring, etc. The signals are AND-linked with the base
module function blocks. The configuration of input terminals I1 to I4 (function group A)
and I5 to I8 (function group B) can be set separately. In switch position 0 unused inputs do
not need to be connected. In all other switch positions any unused inputs must be
connected in such a way as to correspond to the indicated good state of the selected input
circuit function of the respective function group on the input module.
The output signal Q
linked inputs. The exception is function 1, where all inputs are AND-linked. See also
"Evaluating inputs", page 36.
Output signal
Output signal
Connection
* & : AND-linked input pairs
+ : Combination of flipflop + AND link; see "Evaluating inputs", page 36.
Terminal assignment see page 41.
or QB from function group A or B is generated from paired AND-
In functions 7 and 8 the signals from the input expansion are OR-linked with the base
module function blocks. This makes it possible to create safety functions, e.g. for setup
mode, for clearing parts of a system or for safe position monitoring. The configuration of
input terminals I1 to I4 (function group A) and I5 to I8 (function group B) can be set
separately.
OR function 7 overwrites the input circuit of the associated base module. The function
prevents switching off (e.g. setup mode with enabling button for temporary bridging of
safety door functions) or is used alternative to good state of the safety sensor.
Bypass function 8 switches the outputs on regardless of their previous control state.
The function is restricted to max. 60 s. Input pairs I3/I4 and I7/I8 are inactive; they do
not have to be connected.
Logic functions
The bypass signal should be generated only by a particularly deliberate action by a person
with a view into the system (e.g. by using a lockswitch). The bypass instruction is canceled
by the deactivated EN enabling input of the associated base module. For the OR and
bypass functions see page 46.
Output signal
Output signal
Connection
* 1 : OR-linked input pairs
+ : Combination of flipflop + AND operation; see "Evaluating inputs", page 36.
Function 9 assigns the inputs of the function group to the respective other group and takes
on their input circuit function. Thus with one input module you can expand function block
A or B in the base module by 8 single-channel or 4 dual-channel sensors with the same
input circuit function (e.g. 8x emergency stop or 4x NC/NO electromagnetic switch.
Function 9 must only be selected for one of the two function groups. Otherwise a device
error will be detected and the FLT LED will flash.
Settings: Input module INPUT A Function 9 (input expansion) INPUT B Function 3 (dual-channel with cross-circuit
Base module FUNCTION 6
Result: Function 6B on the base module is expanded by the 4 dual-channel inputs
With switch positions 0 to 6 there is an AND link in the base module; for switch positions
7 (OR) and 8 (BYPASS) there is an OR link.
A and B on the associated base module see page 36.
Example for the interaction of base and input modules
on the input module
monitoring and simultaneity monitoring)
For the effects of input module function groups
Input modules act only on the next base
module to the left, with which they form a
coded system group. The blue digits
designate the set functions.
System 1: INPUT A and INPUT B of the
input module act together with base module
function group AB on the four outputs
(green).
System 2: INPUT A of the input module
acts together with base module function
group A on output group A (blue); INPUT B
acts together with function group B on
out
The assignment of outputs X1 to X8 to inputs I1 to I8 depends on the selected input circuit
function. The functions of groups A and B can be set independently.
Unused inputs must be bridged according to the illustrated good state.
Relay output module with 2 relay groups K1, K2
Relay output module with 1 relay group K1
Relay output modules expand an existing base
module with potential-free output circuits. Each
potential-free output circuit comprises the seriesconnected relay contacts of two redundantly
operating positively driven relays and can be used up
to category 4 (EN ISO 13849-1).
The passive relay output expansions do not
operate as slaves on the internal safety bus. Instead
they are integrated in the functions by wiring.
Connection
diagram
SA-OR-S1
SA-OR-S2
SA-OR-S1 SA-OR-S2
Notes
Accepting
configuration
42
SA-OR-S1 SA-OR-S2
The controller category (EN ISO 13849-1) or SIL (EN 61508/EN 62061) depends on the
external circuitry, the wiring, the choice of control devices and their location on the
machine.
In the event of single-channel control of a contact extension (e.g. SA-OR) through a base
module (SA-BM/BS), category 4 according to EN ISO 13849-1 can be achieved if both
devices are installed in the same enclosure and the samos system is separated from the
power supply at least once a day.
The voltage supply of each output circuit must be protected with a 6 A fuse (utilization
category gG) or a 6 A circuit-breaker (tripping characteristic B or C).
Never connect or disconnect modules while the operating voltage is switched on.
The safety system must be installed in an enclosure with at least IP 54 protection.
Because the relay output modules are not directly integrated in the
communication/diagnosis of the samos system via the internal safety bus, errors are
registered indirectly via the base module feedback circuits.
Accepting the system configuration
For accepting the system configuration see page 18.
Function
Function display 3 LEDs green
Controls –
Terminals Plug-in terminals with screws / spring force
Max. number of modules / status in system 4 / passive module
Type of outputs positively-driven relay
Contact type SA-OR-S1
SA-OR-S2
Contact material AgSnO
Output circuit protection per current path 6 (gG)
Utilization category (EN 60947-1) AC 15: 3 A, 230 V
Input circuit – output circuit
Rated voltage AC 230 V
Connection diagram SA-OR-S1
SA-OR-S2
Weight SA-OR-S1
SA-OR-S2
General technical data See page 65
Order numbers See page 69
The input circuit function logically links input signals for further processing. In order to
detect faults (e.g. in the external circuitry of safety inputs) the inputs are tested periodically in
relation to function (external input dynamization).
Input circuit function single-channel via NC contact
One input is monitored (e.g. the NC contact of an emergency stop button). A
valid input signal is only generated if ON state (H-level) is present at the input
and it was previously in OFF state (L-level).
Input circuit function single-channel with testable sensors
Testable sensors (e.g. type 2 non-contact safety devices) are
monitored. A valid input signal is only generated if ON state (H-level)
is present at the input and it was previously in OFF state (L-level).
Input circuit function with dual-channel equivalent activation
Two equivalent inputs (e.g. the opening contacts of an
emergency stop button or actuated N/O contact / N/C contact
of two safety-door position switches)
are monitored.
A valid input signal is only generated if ON state (H-level) is
present at both inputs and both were previously in OFF state
(L-level). The function can be used with/without cross-circuit
monitoring and with/without synchronous time monitoring.
Input circuit function with dual-channel non-equivalent activation
Two non-equivalent inputs are monitored. A valid input signal
is only generated if ON state (H/L-level) is present at both
inputs and both were previously in OFF state (L/H-level). The
function can be used with/without cross-circuit monitoring
and with/without synchronous time monitoring.
Two-hand function with activation by one NO contact per hand (EN 574, IIIA)
Two equivalent inputs are monitored (e.g. the NO contacts of the two twohand buttons). A valid input signal is only generated if ON state (H-level) is
present at both inputs within 0.5 s (synchronous change, both two-hand
buttons actuated) and both were previously in OFF state (L-level). For jog
mode the ON signal can be temporarily restricted to 5 s if required.
Two-hand function with activation by NO/NC combination for
each hand (EN 574, IIIC)
Two pairs of non-equivalent inputs are monitored (the NO/NC contact pairs of
the two two-hand buttons). A valid input signal is only generated if ON state
(H/L-level) is present at both inputs within 0.5 s (synchronous change, both
two-hand buttons actuated) and both were previously in OFF state (L/H-level).
Dual-channel equivalent activation by semiconductor
Two equivalent inputs are monitored (e.g. the signals from a light barrier). A
valid input signal is only generated if ON state (H-level) is present at both
inputs and both were previously in OFF state (L-level).
The off signal of an input function can be bridged with an OR signal. For example, in setup
mode a safety function can be bridged using an enabling button; an OR operation can also
link two safety functions.
The OR function can be implemented by the base module (depending on the function)
or by an input module. It corresponds to an input circuit function with dual-channel
equivalent activation without cross-circuit monitoring.
The muting function is a special case of the OR function (conditional OR). For example,
muting sensors allow a conveyor belt to transport material through a light curtain by briefly
bridging the light curtain function. An ON signal (H-level) is generated only if the internal
output signal of the Reset function Q
function
The muting function in the samos base device corresponds to an input circuit function
with dual-channel equivalent activation without cross-circuit monitoring. Muting of a safety
function must not be dependent on a single signal! An output controls the corresponding
muting lamp. This lamp additionally indicates by blinking that the Reset signal is expected at
input S1.
has H-level at the beginning of the Muting
START
Bypass
EXAMPLE
For the input circuit
functions of the input
modules see page 36.
The deactivated enabling input of the associated base module shuts down the outputs
(Q1..Q4) switched on by OR or MUTING. The Muting lamp output Q3 stays on during the
Muting function, if function block 3 is selected. When they are subsequently activated, OR
or MUTING mode continues.
With a bypass signal an internal OFF signal (L-level) of the Reset function Q
overwritten in the base module. The bypass function is generated by a high-level (see also
the “Reset Function” figure on page 47). It corresponds to an input function with dualchannel equivalent activation with cross-circuit monitoring.
Bypass is used when the system is to be switched on after a power shutdown but a light
barrier is obstructed by material. Bypass cancels the safety function of the light barrier and
the blockage can be cleared. In normal operation the muting function bridges automatically
(see above).
The bypass signal is limited to 60 s. After the time has expired bypass mode can be
reactivated. After the bypass signal has been cancelled and respectively after 60 s the
enabling outputs are switched off, if the restarting inhibit function is on and the light
curtain was inerrupted. However, any set release time will run in full.
Bypass can be aborted by canceling the bypass instruction on the input module or by a
low signal on the EN enabling input on the associated base module. This means, for
example, that a higher-priority emergency stop can shut the machine down during bypass
mode.
After the bypass signal has been cancelled, the internal signal Q
Start
determines the
state of the outputs (see Reset Function on page 47).
START
can be
NOTE
46
The bypass signal should be generated only by a particularly deliberate action by a person
with a view into the system (e.g. by using a lockswitch that automatically returns to off
position or a combination of lockswitch and enabling button).
The starting inhibit on the associated base module is never on when bypass inputs are
active. This means that when voltage is switched on with high potential on the EN
ENABLE input, the outputs are enabled immediately without additional manual
intervention.
The Reset function defines which (reset) conditions must be fulfilled if, for example, an ON
signal is to be passed on to output Q
. All input and muting signals from the base
START
module and the associated input modules (i.e. of a system group within the samos
system), and the bypass/OR signals from the input modules are logically linked (AND/OR).
The terminal configuration with bridges and feedback circuits is also evaluated (see
below).
An ON signal from the Reset function can only be canceled by an OFF signal from an
input circuit function (i.e. changed into an OFF signal), and is not influenced by enabling,
muting or bypass functions or by feedback circuit monitoring.
& : AND blink ≥1 : OR link
+ : Combination of flipflop + AND link.
Muting : An ON signal is generated only if the output signal of the Reset function Q
Start
has
good state at the beginning of the muting function.
Reset condition / evaluation of feedback circuits
On the base modules there are three control inputs S1, S2, S3 for configuring the control
circuit functions. They can be used, depending on the function, to set starting inhibit,
restarting inhibit, retriggering and off delay (see page 24). Depending on the application,
the configuration is realized using bridges or by connecting the NC contacts of connected
relays/contactors. Together with the module outputs this creates feedback circuits which
allow evaluation of the control states of the respective connected relays/contactors with
positively driven contacts. Evaluation uses one of two different methods depending on the
function (see also page 26).
The NC contact is connected directly with the respective control input. As soon as the
contact closes the Reset function is activated and it is possible to switch on the outputs.
The configuration is evaluated when the system is switched on. The configuration is
verified before each Reset following a safety event. If a change is detected (e.g.
feedback circuit not closed) the system generates an error message and cannot be
switched back on until the malfunction has been rectified.
In operation with restarting inhibit the NC contact is connected to the respective input
via a Reset button. The required Reset condition for canceling the restarting inhibit is
only fulfilled if the feedback circuit is also closed.
Glossary
Reset
Feedback circuit
monitoring
The feedback circuits that belong to the safety system must be housed in the same
enclosure as the samos system in order to exclude the “Short-circuit to +24 V”.
The enable function enables an ON signal in the Reset function if there is H-level on the EN
input. The H-level for enabling can be generated, for example, by a semiconductor output
Q
on the base module for logic operations or a PLC output. For category 4 applications
n
(EN ISO 13849-1) the module that generates the enabling signal must be in the same
enclosure. If the EN input is open or on L-level the following Q
semiconductor outputs are
n
locked.
The enable function makes it easy, for example, to cascade safety circuits or form
dependent safety zones. Unused EN inputs are connected to supply voltage +U
enabling input is open or on L-level all safety outputs on the base module shut down. Any
set off delay will run in full. The enable function has priority over all other input signals
(safety sensors, bypass, etc.).
. If the
B
NOTE
NOTE
Diagnosis
When voltage is switched on the starting inhibit on/off Reset condition is integrated in the
enable function. During operation the Reset conditions are not checked. I.e., Reset can be
prepared in disabled condition. ENABLE enables the outputs.
Output function
The time behavior of the safety ON/OFF signal is defined in the output function. In order to
detect faults in the safety outputs the outputs are tested periodically (output
dynamization).
Depending on the function, you can use the rotary switch to set a off delay for outputs Q4
or Q3/Q4 between 0 and 5 minutes (depending on module version). This does not influence
switching on procedures.
Safety shutdown of drives according to stop category 1 (controlled stopping) is possible
with each base module.
Note that the delayed outputs shut down immediately if operating voltage is switched off
during the off delay.
Communication
With the communication function system data is exchanged between the different
modules in a system via the internal safety bus (SBus).
Diagnosis and display function
The diagnosis function allows internal system data to be provided to external systems via a
diagnosis module or bus coupler module. The SBus is used as the internal system
communication channel.
With the display function voltage levels on terminals and particular operating states of
the system are displayed via LEDs. The diagnosis and display functions are decoupled and
are not safety functions. In other words, no data from external systems can enter the
system via a diagnosis or bus coupler module.
The international norm IEC/EN 61508/EN 62061 is the new standard for the specification,
design and operation of safety systems.
The norm takes the whole system into consideration. It expands the safety
requirements of single complex devices to cover the whole safety installation from sensor
through control electronics and communications systems to actuators, and also includes
possible errors by operators. The norm provides the framework for future developments
and is decisive for manufacturers and users alike, especially as it also touches on questions
of product liability.
The safety considerations concentrate on analyzing dangers and defining risks. The goal
of the assessment is to reduce the risk involved in a safety system to an acceptable level of
residual risk by calculating failure probabilities for components, system and design from
development right through to disposal.
The safety function of the samos system is shutting down or preventing a dangerous
process. All the system functions described in this manual are safety functions.
A safety integrity level defines the range for failure probability of a safety function in
relation to operating mode and request frequency. IEC/EN 61508/EN 62061 describes two
modes for safety functions:
A safety function in demand mode is only executed on demand. It brings the
monitored system into a defined safe state and has no influence on the system in normal
operation (example: emergency stop monitoring).
A safety function in continuous mode continuously maintains the monitored system in
its normal safe state (example: speed monitoring).
This division means there are two different demand rates for safety functions:
Mode with low demand rate when the demand rate is less than once per year;
Mode with high demand rate or continuous demand when the demand rate is more
than once per year.
The demand rates are considered in relation to failure probabilities:
Low demand rate in relation to probability of failure on demand (PFD),
High demand rate or continuous demand in relation to probability of failure per hour
(PFH).
According to IEC/EN 61508/EN 62061, the samos safety function can be used in modes
with low and high demand rates.
With low demand rates the PFD for SIL 3 is
-4
10
to <10-3 (e.g. emergency stop components) for the whole safety chain.
With high or continuous demand rates the PFD is
-8
10
to <10-7 (e.g. two-hand application) for the whole safety chain.
In the following, you will find the results of calculations of the MTTFd, PFD and PFH values
of different system configurations. They apply under following conditions:
Units are permanently in operation: 24 h per day, 365 days per year
Service life (PFH – applications): 20 years
Proof test interval (PFD – applications): 1 year
Average ambient temperature: 40°C
The emergency stop function is used to protect persons and machines by directly
disconnecting the power supply.
Safety door monitoring
Safety door monitors with sensors (e.g. position switches, coded electromagnetic
switches) are used for monitoring separating safety devices.
Static valve monitoring
Position monitoring with position switches.
Switching mat monitoring
Short-circuiting switching mats are access monitoring sensors that alter their
control state when stood upon.
Two-hand function
Two-hand functions as per EN574 protect the operator of presses, cutting and
bending machines, machining centers, etc. The two controls (two-hand buttons)
must be actuated at the same time to initiate the dangerous operation. If one or
both of the buttons is released the enable is canceled.
On press control systems the function must only be used in accordance with EN
574 Typ IIIC.
Two-hand operation in jog mode
In jog mode an output signal is only generated while the controls are being
pressed, e.g. for motions in setup mode. Jog mode on the base modules is
restricted to 5 s.
Light barrier / light curtain monitoring
Access monitoring with self-testing sensors (e.g. type 4 non-contact safety devices).
A non-contact safety device is a setup of devices and/or components that work
together for safety shutdown and detection of persons. The non-contact safety
device has at least a sensor function (e.g. safety light barrier or other secure
sensors), a monitoring function (e.g. cyclical self-tests) and an output switching
element (OSSD). The function is matched for modulated self-test signals or
overcurrent limitation of sensor semiconductor outputs.
Light barrier / light curtain monitoring
Access monitoring with testable sensors (e.g. type 2 non-contact safety devices). The
sensors have separate activation inputs that are used to test the sensor function
with a low signal; the base module analyses the response signal generated by the
receiver. Several sensors can be cascaded.
Controlled stopping
With the settable off delay a drive can be switched off after expiry of the time
according to stop category 1 and EN 60204, and if required a brake can be
applied.
Safe Position
Safe position, e.g. of a robot, is detected by a sensor. Zone protection is lifted and
an operator can enter the robot zone. If the robot leaves the position it is switched
off safely.
E.g. emergency stop button, position switch, electromagnetic switch, light curtain, ...
All emergency stop buttons and light curtains with FUNCTION 1 from
the SA-BM-S1 and the SA-IN-S1 input expansion are AND-linked.
AND-linked safety inputs (sensor inputs)
The non-contact inductive safety sensor S1 with test input (e.g. GM 504S, GM505S from
ifm) and the testable light barrier LC1 are AND-linked. Both sensors must be actuated
before a new Reset can be initiated. The emergency stop button ES1 at SA-BM-S1 has
priority over the enabling input on the right SA-BM-S1 by AND operation.
SA-IN-S1
SA-BM-S1
+ Combination
of flipflop + AND
operation
+ Combination
of flipflop + AND
operation
1* MUTING
the conditional ORcombination is valid only if
the result of the Reset
function before was =1
(see pages 46/47).
The safety door switch on the base module SA-BM-S1 and the light curtain on the input
expansion SA-IN-S1 in function group B of the function block (FUNCTION 6) are AND-
linked in the function block to function group A (emergency stop circuits of base module
and input expansion). Function group A has priority over function group B. Via Q8 on the
PLC Q3 and Q4 on the SA-BM-S1 can also be enabled or shut down.
+ Combination
of flipflop + AND
operation
SA-IN-S1
AND-linked
samos
function blocks
The SA-BM-S1 function block for two-hand function (FUNCTION 4) is subordinate to the
SA-BM-S1 emergency stop function block (FUNCTION 1). The AND link is made by output
Q2 on the SA-BM-S1 and the EN enabling input on the right SA-BM-S1.
The safety door circuitry of SG1 shuts down output Q3,Q4 on the SA-BM-S1. SG2 and SG3
shut down the independent Q1 and Q2 / Q3, Q4 of the right SA-BM-S1. When ES1
(emergency stop) is actuated the internal AND link in the SA-BM-S1 function block and
the connection of output Q2 on the SA-BM-S1 with the EN enabling input on the right SABM-S1 ensure complete shutdown of all outputs.
samos
function blocks
SA-BM-S1
+ Combination
of flipflop + AND
operation
OR-linked safety inputs (sensor inputs)
Actuation of lockswitch S1 bridges the safety door function with an OR link; i.e. all outputs
Q1 to Q4 remain on. Lockswitch takes effect even with safety door opened and switches
1* MUTING
the conditional ORcombination is valid only
if the result of the Reset
function before was =1
(see pages 46/47).
OR-linked safety inputs (sensor inputs)
Actuation of muting sensors MU1 and MU2 automatically bridges the safety function of
light curtain LC1 by OR operation (MUTING); i.e. outputs Q1, Q2, Q4 remain on. Light
curtain LC1 must not be interrupted when the two muting sensors are actuated. Output Q3
controls the muting lamp.
+ Combination
of flipflop + AND
operation
1* MUTING
the conditional ORcombination is valid only
if the result of the Reset
function before was =1
(see pages 46/47).
OR-linked safety inputs (sensor inputs)
Actuation of muting sensors MU1 and MU2 automatically bridges the safety function of
light curtain LC1 by OR operation (MUTING); i.e. outputs Q1, Q2, Q4 remain on. Light
curtain LC1 must not be interrupted when the two muting sensors are actuated. Output Q3
controls the muting lamp. Actuating lockswitch S4 on the SA-IN-S1 activates the BYPASS
function for clearing the light curtain when power is switched on. BYPASS operates as an
OR operation on the base module SA-BM-S1 outputs via input module SA-IN-S1.
The safety door switches of SG2 in function group B of the function block (FUNCTION 6)
are AND-linked in the function block with SG1 of function group A. Function group A has
priority over function group B. An additional safety door circuit with an electromagnetic
switch MS1 is assigned to function group A via the input expansion. The sensor input of
function group B of the SA-BM-S1 is OR-linked via function INPUT 7 of the SA-IN-S1 input
expansion and enabling button SET1. If enabling button SET1 is actuated, outputs Q3 and
Q4 do not shut down when door SG2 is opened.
Two-channel emergency stop and safety door monitoring. Emergency stop has priority
over the safety door function. In case of emergency stop contactors K1, K2 and output Q3
shut down immediately. The drive shuts down immediately via the enable signal. After the
preset time power to the drive is switched off via K4, K5 and a brake applied (safe stopping
as per stop category 1).
Reset after emergency stop and after power on is with RESET. When the safety door is
opened only the drive is stopped safely. K1 and K2 remain switched on. After the safety
door has been closed and the feedback circuits checked, the safety device is reset
automatically. The machine is ready to switch on.
+ Combination
of flipflop + AND
operation
e
58
amos module K6
Type
SA-BM-S1
FUNCTION 7
Function group AB A B
External circuitry category (EN ISO 13849-1)
up to
3 3
Cross-circuit monitoring – –
Synchronous time monitoring –
Stop category (EN 60204-1) 0 1
OFF delay
Retriggering ON –
AUTO-RESET after POWER ON
MANUAL RESET after POWER ON X X
AUTO-RESET X
MANUAL RESET X
Comment
The safety light curtain LC1 monitors the access to the machine zone. The optical muting
sensors LM1 and LM2 are OR-linked with light curtain LC1 (muting function).
Both muting sensors are pulse controlled and must be active to carry out the muting
function (light curtain bypass).
The muting function requires that outputs Q1, Q2, Q4 have previously been switched
on. This means that the vision of LC1 has to be uninterrupted for power on.
Lamp L1 indicates the active muting state (static on). The expected Reset signal at S1 is
indicated by blinking of L1. L1 control complies with EN 60496-1.
Restart is possible after exiting the danger zone and pushing Reset button S3.
pplications
Application example
A267
Machine zone
protection with light
curtain
Muting function
Category 4
Stop category 0
samos
module
Type
K3
SA-BM-S1
FUNCTION 3.1
Function group AB
External circuitry category (EN ISO 13849-1)
up to
4
Cross-circuit monitoring X
Synchronous time monitoring --
Stop category (EN 60204-1) 0
OFF delay
Q4
0 s
Retriggering ON --
AUTO-RESET after POWER ON
MANUAL RESET after POWER ON X
AUTO-RESET
MANUAL RESET X
Comment Crossmonitoring by safety sensors
1* MUTING
the conditional ORcombination is valid only if
the result of the Reset
function before was =1
(see pages 46/47).
59
Page 60
A
pplications
Application example
A 258_B
Two independent safety
zones
Monitoring with coded
electromagnetic
switches
Higher-order emergency
stop
Category 3/4
Stop category 0
When the safety door monitored with MS1 is opened K1 and K2 shut down. When the
safety door monitored with MS2 is opened K3 and K4 shut down.
In case of emergency stop via S1, all contactors K1 to K2 shut down. With button S2
you can reset the safety system while the safety devices are closed. Reset button S2 is
monitored for errors.
+ Combination
of flipflop + AND
operation
SA-IN-S1
samos
module
Type
K6 K6A
SA-BM-S1 SA-IN-S1
FUNCTION 8 4 4
Function group AB A B A B
External circuitry category (EN ISO 13849-1)
up to
3 3 4 4
Cross-circuit monitoring – – X X
Synchronous time monitoring – – – –
Stop category (EN 60204-1) 0 0
OFF delay
Q4
0 s
Retriggering ON –
AUTO-RESET after POWER ON
MANUAL RESET after POWER ON X X
AUTO-RESET
MANUAL RESET X X
Comment
samos modules and contactors in the same enclosure
Robot zone access is monitored by light curtain LC1. The machine zone is further
protected by a safety door and an emergency stop circuit.
Sensor S3 is OR-linked with LC1 and detects the safe position of the robot.
This enables e.g. equipping through an opening in the processing area without
switching off the robot power supply. If the robot is not in the safe position when the light
curtain is interrupted, the entire machine and the robot are switched off.
Opening the safety door or actuating the emergency stop button also result in a safe
switch off. The robot control receives the command to switch off (returning to the safe
position) from Q1.
K1 and K2 immediately interrupt the power supply to other consumers. The power
supply of the robot is switched off safely via K4 and K5 after 1 s.
Restart is possible after exiting the danger zone and pushing Reset button S4.
+ Combination
of flipflop + AND
operation
1* MUTING
the conditional ORcombination is valid only if
the result of the Reset
function before was =1
(see pages 46/47).
SA-IN-S1
samos
module
Type
K3 K3A
SA-BM-S1 SA-IN-S1
FUNCTION 3.1 2 7
Function group AB A B
External circuitry category (EN ISO 13849-1)
up to
4
AB A B
4 4
Cross-circuit monitoring X X –
Synchronous time monitoring – – –
Stop category (EN 60204-1) 0
OFF delay
Q4
0 s
Retriggering ON –
AUTO-RESET after POWER ON
MANUAL RESET after POWER ON X
AUTO-RESET
MANUAL RESET X
Comment
Change to
control circuit
configuration
(inputs
settings on
S1, S2, S3
Deliberate
acceptance of
an incorrect
configuration
... during operation
(power not switched
off)
System response System response when
All outputs shut down
immediately
System goes into
“System error”
condition
Red FLT LED on affected
module flashes
Green PWR LED flashes
All other FLT LEDs
continuous red
Message via field bus
coupler module
Outputs of system/
system group shut
down at next cycle
Red FLT LED on affected
module flashes
)
Message via field bus
coupler module
The configurations are
saved internally in nonvolatile form and can be
read out by the
manufacturer if required
The leadable cover SA-COVER is available as an accessory for the safe samos modules. It
prevents the rotary switches from changing their setting after system start-up.
... with power off
power connected
System outputs cannot
be switched on
Red FLT LED on master
module flashes
All other FLT LEDs
continuous red
System/system group
outputs cannot be
switched on
Red FLT LED on master
module flashes
All other FLT LEDs
continuous red
Action required
Return switch to original
position (setting aid if
power remains on:
flashing PWR LED
switches to continuous
green)
Restart system by
switching power off and
on again
Restore old configurations on S1, S2, S3.
Restart system by
switching power off and
on again
User reads out last
(correct) configuration
CRC via bus coupler
module
Cyclical visual check of
configuration
nne
Error Codes of
FLT
Error LED
Blink code Cause of error
Error codes FLT
Static Secondary error on modules that have not discovered the error themselves
2x Error in module configurations on S1, S2, S3, other module configuration
3x Rotary switch altered during operation
4x Module location list comparison when power switched on has detected a
difference (including alteration of rotary switch position before or during
power off)
5x Voltage supply internal and external
6x Self-monitoring, internal error, etc. (e.g. enter button pressed longer than 5 s)
Place device on DIN rail A.
Ensure that earth spring B
is in the correct position.
The earth spring on the
module must make a
secure and electrically
conductive connection
with the DIN rail.
Snap the module onto the
DIN rail by pressing gently
in the direction of the
arrow.
If there are several modules,
push them together one at
a time in the direction of
the arrow until the
connectors at the sides
engage and then install the
end clamps at the left and
right ends.
Removing
Remove the plug-in terminals, wiring and end
clamps.
If there are several modules,
push them apart one at a
time in the direction of the
arrow until the connectors
at the sides disengage.
Push down at the back.
While pressing down,
remove the module from
the DIN rail in the direction
of the arrow.
The modules are equipped with coded pluggable terminal
blocks with 4 screw terminals each.
To avoid mix-ups, all module blocks are coded differently.
Individual modules are not coded differently. Up to 2
stranded wires can be contacted per terminal.
The modules are equipped with coded pluggable terminal
blocks with 4 spring force terminals each.
To avoid mix-ups, all module blocks are coded differently.
Individual modules are not coded differently.
Up to 2 stranded wires can be contacted per terminal.
The spring force terminals are provided with push-in
technology. This means that no tools are required for
installation.
Stranded wires are removed with a screwdriver by pushing
the terminal from the front of the module (vertically to the
inserted stranded wires). The voltage check can also be
carried out vertically to the stranded wires through the
inspection holes provided.
nne
Screw terminals
For technical data of the
terminal see general
technical data.
Spring force
terminals
For technical data of the
terminal see general
technical data.
Switch Cover
The optional switch cover SA-COVER can be snapped onto
the front of the safe module to prevent the switch setting
from changing after start-up. The cover is leadable and can
only be removed with a tool (screwdriver) after the lead has
been removed.
The screwdriver is
inserted at the lower edge
vertically to the cover and
releases the cover from its
locked position using an
upward lever movement.
The SA-COVER accessory can be used with safe modules
as of revision C-01.
Ambient operating temperature T
Storage temperature –25 to +70 °C
Relative humidity 10 to 95%, no condensation
Climatic conditions (EN 61131-2)
Air pressure in operation 860 to 1060 hPa
Sinusoidal vibration (EN 60068-2-6)
Frequency range 5 to 150 Hz
Amplitude 3.5 mm (5 to < 9 Hz)
Acceleration 1 g (9 to 150 Hz)
Number of cycles 10 per axis (on 3 axes)
Broad-band random vibration (EN 60068-2-64)
Frequency range 5 to 500 Hz
Acceleration 4.9 g
Semi-sinusoidal shock (EN 60068-2-27)
Acceleration / Duration 15 g / 11 ms
Protect. type housing / terminals (EN 60529) IP 40 / IP 20
Finger-proof to DIN EN 50274
Clearance/creepage (EN 61131 -2)
Overvoltage category III
Contamination level 2 inside, 3 outside
Test voltage
DC 24 V
AC 300 V
SA-BM-S1-4EKL-A Master module, off delay 0-5 s Cod. 1 Screws R1.180.0010.0
SA-BM-S1-4EKL-A Master module, off delay 0-50 s Cod. 1 Screws R1.180.0020.0
SA-BM-S1-4EKL-A Master module, off delay 0-5 min Cod. 1 Screws R1.180.0030.0
SA-BM-S1-4EKL-C Master module, off delay 0-5 s Cod. 1 Spring force R1.180.0360.0
SA-BM-S1-4EKL-C Master module, off delay 0-50 s Cod. 1 Spring force R1.180.0370.0
SA-BM-S1-4EKL-C Master module, off delay 0-5 min Cod. 1 Spring force R1.180.0380.0
Input module
SA-IN-S1-K-A 2 x 4 inputs, 2 x 10 input functions Cod. 1 Screws R1.180.0070.0
SA-IN-S1-K-C 2 x 4 inputs, 2 x 10 input functions Cod. 1 Spring force R1.180.0420.0
*) Please consider the needed coding and the note More safety via coding on page 7 by
ordering.
Relay output modules
SA-OR-S1-4RK-A 2 x 2 relay outputs Screws R1.180.0080.0
SA-OR-S2-2RK-A 1 x 2 relay outputs Screws R1.180.0320.0
SA-OR-S1-4RK-C 2 x 2 relay outputs Spring force R1.180.0430.0
SA-OR-S2-2RK-C 1 x 2 relay outputs Spring force R1.180.0440.0
Gateways
SA-PROFIBUS-DP-A Profibus-DP field bus Screws R1.180.0090.0
SA-CANopen-A CANopen field bus Screws R1.180.0100.0
SA-DeviceNet-A DeviceNet field bus Screws R1.180.0350.0
SA-EN-MOD-A Modbus/TCP Screws R1.180.0750.0
SA-EN-PN-A Profinet Screws R1.180.0760.0
SA-EN-IP-A EtherNet/IP Screws R1.180.0770.0
Accessories
SA-COVER Cover for samos modules, leadable,PU 10 p. R9.211.0430.0
Relay output module 42
O
Occupational health and safety directive
4
Operating errors 18
Operating voltage 18, 48
Operation
Base module 17, 18
Input module 35
Relay output module 44
OR function 22, 37
OR link 40, 47, 55
OR operation 21, 39
Order numbers 69
OSSD 22, 52
Output dynamization 48
Output function 12, 48
Output switching element 52
Overcurrent limitation 52
Overview of devices 69
P
Parallel-connected module inputs 14, 68
PFD 49
PFH 49
PLC 12, 48
Position monitoring 52
Position switch 52
Press control 23, 52
Probability of failure 49
Product liability 4, 49
Proper use 4
R
RC combination 13
Relay output module 8, 11, 18, 42
Release delay 12, 21, 23, 25, 47, 48, 52
Release time 25
Removing 64
Removing modules 18
Reset 24
Reset after safety event. 47
Reset behavior 21, 24
Reset button 21, 24, 47
Reset condition 18, 47
Reset function 12, 47, 48
Residual risk 9, 49
Response signal 23, 52
Restart 18
Restarting lockout 24, 47
Retriggering 23, 25, 47
Risk assessment 9
Risk minimization 9
S
SA-BM-S1 13
Safe state of inputs 24, 25
Safety bus 11, 12, 21, 32, 48
Safety chain 49
Safety circuits 10
Safety communication 11
Safety devices 10
Safety door monitoring 52
Safety event 24
Safety function 11, 49
Safety integrity level 49
Safety level 23
Safety measures 3
Safety requirements 49
Safety rules 3
Safety sensors 10
Safety shutdown 52
Safety standards 4
Safety structure 49
Safety zones 10, 48
Safety-related information 3
This is a blank samos configuration list (module location list) for copying. We recommend
keeping a record of the configuration with the documentation or in a clearly visible place in
the enclosure.
Diese Übersicht zeigt die Anzahl, Reihenfolge und Konfiguration der aktiven
sicheren samos-Module eines Systems in einem bestimmten, vom Anwender
gewählten Zustand der Maschine. Sie dient der Dokumentationsergänz ung einer
Anlage/Maschine.
Die dargestellt en Informationen sind vo m Anwender mit dem tatsächlichen
Zust and des samo s-Systems zu vergleic hen! Für die Rich tigkeit u nd
D
D
Vollständigkeit der Daten übernimmt die Firma Wieland keine Haftung!
Ausgangsmodule Relais SA-OR sind nicht dargestellt.
This overview shows the number, the order, and the configuration of the active
samos modules of a system designed and constructed by the user's selected
structure of the machine. This overview can be used to supplement the
documentation for the machine configuration.
The indicated information must be compared with the actual conditions of the
samos syst em! Company Wielan d does no t take responsibilit y for the
GB
GB
correctness a nd comp letion of th e dates!
Output modules relays SA-OR are not shown in this overview.
Type:
=
SW-Ver:
=
== = =
== = =
== = =
Type:
=
SW-Ver:
=
Type:
=
SW-Ver:
=
== = =
== = =
== = =
Type:
=
SW-Ver:
=
== = =
== = =
== = =
Reading samos-config
Type:
=
SW-Ver:
=
Type:
=
SW-Ver:
=
Type:
=
SW-Ver:
=
Type:
=
SW-Ver:
=
Type:
=
SW-Ver:
=
max. m odule num ber
Type:
=
SW-Ver:
=
Faults:
Company:Project:
Ref. to drawing No.:
Date:
Comment:
Rev.:
Name:
Sign:
Data transfer betw een samos-module SA-PROFIBUS-DP-A and P C via Mastersimulator BW1131 (company Bihl+Wiedemann)
Download of samosConf igListSetupX.X.zip under www.wieland-electric.com --> Infoservice --> Download Center