WAX-U & WACPX-U SERIES ENCLOSURES NEMA 12 FLOOR-MOUNT DISCONNECT
F30
FEATURES-SPECIFICATIONS
Industry Standards
UL 508, Type 12 CSA Certified, Type 12 NEMA/EEMAC Type 12 JIC EL-1-71
UL File E64791
CSA File LL66078
Applications
Designed to house the following:
Allen-Bradley Bulletin 1494F flange-
mounted disconnect switches and Bulletin 1494D flange-mounted operators for circuit breakers. Allen­Bradley Bulletin 1494V variable depth flange-mounted disconnect switches and circuit breakers mechanisms
ABB Controls flange-mounted
variable depth operating mechanisms for disconnect switches and circuit breakers
Cutler-Hammer/Westinghouse
Type C361 disconnect switches and operating mechanisms, and Type C371 circuit breakers and circuit breakers operating mechanisms. Also Type SM safety handle mechanisms and Flex Shaft™ handle operators for circuit breakers
General Electric Type STDA flange
handles and variable depth operating mechanisms for disconnect switches and circuit breakers. Also Spectra Flex™ cable operators for circuit breakers
I-T-E Max-Flex™ flange-mounted
variable depth operating handles for disconnect switches and circuit breakers
Square D disconnect switches and
circuit breakers used with Class 9422 flange-mounted variable depth operating mechanisms or cable mechanisms
These enclosures will not receive Class 9422 bracket-mounted disconnect devices, 9422TG1, or TG2 devices
Construction
• Bodies and doors fabricated from 10 gauge steel
• Continuously welded seams ground smooth
• Body stiffeners provided for extra rigidity
• Heavy gauge continuous hinges to secure doors
• Heavy duty 3-point padlocking handles on all doors
• Print pocket is provided
• 15-inch floor stands are welded to enclosure
• Doors are supplied with closed cell neoprene gasket
• Heavy duty lifting eyes and provisions for fluorescent lighting are provided
• Panel supports
• Collar studs are provided for mounting optional sub panels
• Grounding provisions provided
• Unless specified, the right door is considered to be the “master” door on the “Right Flange” mount enclosures and the left door is the “master” door on the “Center Post” mount enclosures
• A mechanical interlock is provided and prevents the slave door from opening before opening the master door
• Disconnects come with a universal cutout which provides mounting for most disconnects operators by using operator adapters
• Removable center post permits easy panel installation
• FTC rolled lip around all sides of enclosure opening excludes liquids and contaminants
Finish
• ANSI 61 gray polyester powder inside and out over phosphatized surfaces
Optional back panels are white polyester powder over phosphatized surfaces
Accessories
• Back panels (reference tables)
• See pages J1-J19
• Blank adapter plates on pages F57 and J12
IMPORTANT
• Disconnect switch or circuit breakers, operating handle and operating mechanism are not furnished with the enclosure and must be ordered separately from the disconnect manufacturer
Operator adapter plates are required with this enclosure and must be purchased separately. See pages F57 and K12 to select the proper operator adapter for the brand and type of disconnect being used
• Disconnect ordering information is located on page F33
• Review space occupied by discon­nect drawings on page F32 and disconnect tables on pages F47-F56 to determine if the disconnect device you are using will fit the enclosure size you have selected
WA60X4912U WA60CPX4912U
DATA SUBJECT TO CHANGE WITHOUT NOTICE
®
R
WAX-U & WACPX-U SERIES ENCLOSURES
NEMA 12 FLOOR-MOUNT DISCONNECT
F31
PROVISION CATALOG NUMBER
BODY/DOOR ENCLOSURE SIZE BACK PANEL BACK PANEL
RIGHT FLANGE MNT. CENTER POST MNT.
STEEL GAUGE H X W X D CATALOG NUMBER* SIZE A X B
WA60X4912U WA60CPX4912U6 10/10 60.13x49.75x12.13 (1527x1264x308) NPDD6048 56.00x44.00 (1422x1118)
WA60X4918U 10/10 60.13x49.75x18.13 (1527x1264x460) NPDD6048 56.00x44.00 (1422x1118)
WA60X4924U6 WA60CPX4924U6 10/10 60.13x49.75x24.13 (1527x1264x613) NPDD6048 56.00x44.00 (1422x1118)
WA60X6112U WA60CPX6112U6 10/10 60.13x61.75x12.13 (1527x1568x308) NPDD6060 56.00x56.00 (1422x1422)
WA60X6118U 10/10 60.13x61.75x18.13 (1527x1568x460) NPDD6060 56.00x56.00 (1422x1422)
WA60X6124U6 WA60CPX6124U6 10/10 60.13x61.75x24.13 (1527x1568x613) NPDD6060 56.00x56.00 (1422x1422)
WA72X6112U 10/10 72.13x61.75x12.13 (1832x1568x308) NPDD7260 68.00x56.00 (1727x1422)
WA72X6118U 10/10 72.13x61.75x18.13 (1832x1568x460) NPDD7260 68.00x56.00 (1727x1422)
WA72X7312U WA72CPX7312U6 10/10 72.13x73.75x12.13 (1832x1873x308) NPDD7272 68.00x68.00 (1727x1727)
WA72X7318U WA72CPX7318U6 10/10 72.13x73.75x18.13 (1832x1873x460) NPDD7272 68.00x68.00 (1727x1727)
WA72X7324U 10/10 72.13x73.75x24.13 (1832x1873x613) NPDD7272 68.00x68.00 (1727x1727)
WAX-U AND WACPX-U SERIES FLOOR-MOUNT DISCONNECTS
6 NEW PRODUCT IN 2003
*Back panels must be ordered separately. Panels are made from 10 gauge steel.
SECTION X-X
1.00
0.438
C
L
L
C
SECTION Y-Y
BODY STIFFENER
(NOT PROVIDED IF
H OR W = 56.00"
OR LESS)
2.06
2.06
PANEL
SUPPORT
OPTIONAL
PANEL
LIGHT BRACKET
(UNISTRUT CHANNEL)
0.88
0.88
B
A
3.31
2.44
SIDE VIEW
PADLOCKING
HANDLE
D1.25
D
H/2 + 15.00"
Y
Y
FRONT VIEW
0.81 2.191.75
TYP
1.94 4.81 4.81
CLEAR SPACE AVAILABLE
15.00
H H - 1.38
0.69
0.69
1.94
1.94
3.00
3.50
1.50
H - 3.00
1.50
1.94
3.00
X
X
LIFTING EYE
1.75 W/2 - 4.13
REMOVABLE
CENTER POST
CONTINUOUS HINGE
W
W/2 - 2.38 W/2 - 2.38
W/2 - 4.13
W
W/2 - 1.75 W/2 - 1.75
H - 3.00
1.50
1.50
0.81
1.88 0.81
1.94 4.81 4.81 1.94
CENTER POST
REMOVABLE
AVAILABLE
SPACE
CLEAR
HINGE
CONTINUOUS
3.50
X
X
TYP
3.00
W/2 - 3.50
1.75
FRONT VIEW
15.00
H H - 1.38
0.69
0.69
1.94
1.94
1.75 W/2 - 3.50
SECTION X-X
1.00
0.438
C
L
L
C
SECTION Y-Y
OR LESS)
H OR W = 56.00"
(NOT PROVIDED IF
BODY STIFFENER
2.06
2.06
SUPPORT
PANEL
PANEL
OPTIONAL
LIGHT BRACKET
(UNISTRUT CHANNEL)
0.88
0.88
B
A
3.31
2.44
SIDE VIEW
HANDLE
PADLOCKING
D1.25
D
H/2 + 15.00"
Y
Y
WAX-U
WACPX-U
DATA SUBJECT TO CHANGE WITHOUT NOTICE