SDN12 SERIES & SN4 SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F14
SWITCH
AMP FUSE FUSE DISCONNECT DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
RATING CLIP CLASS HEIGHT X WIDTH Y
TCN-30 30A No fuse — 5.90 6.20
TCF-30 30A 30A-250V H, K, R 7.50 6.20
TCF-33 30A 30A-600V H, K, R 10.15 6.20
TCF-33 30A 60A-250V H, K, R 8.15 6.20
TCF-33 30A 30A-600V J 7.50 6.20
TDN-60 60A No fuse — 5.90 6.20
TDF-60 60A 30A-600V H, K, R 10.15 6.20
TDF-60 60A 60A-250V H, K, R 8.15 6.20
TDF-63 60A 60A-600V H, K, R 10.65 6.20
TDF-63 60A 60A-600V J 7.50 6.20
TEN-10 100A No fuse — 5.90 6.20
TEF-10 100A 100A-250V H, K, R 10.35 6.20
TEF-10 100A 100A-600V H, K, R 10.35 6.20
TEF-10 100A 100A-600V J 10.35 6.20
SQUARE D CLASS 9422 DISCONNECT SWITCHES USED WITH CABLE MECHANISM 9422-CFT30 AND 9422A-1 HANDLE MECHANISM
CABLE TYPE CIRCUIT BREAKER CIRCUIT BREAKER
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
SWITCH
AMP RATING FRAME TYPE
HEIGHT X WIDTH Y
9422 CGJ30 75A GJL 4.75 3.50
9422 CGJ300 100A GJL 4.75 3.50
9422 CGJ30 100A FAL, FHL 6.00 4.50
9422 CGJ30 250A KAL, KHL 8.00 4.50
9422 CGJ30 400A LAL, LHL, Q4L 11.00 6.00
SQUARE D CLASS 9422 CABLE MECHANISM FOR CIRCUIT BREAKERS
Use switches listed above with appropriate cable mechanism and 9422-A1 handle mechanism.
Use cable mechanism with appropriate circuit breaker and 9422-A1 handle mechanism. Cable operators are available in 3-foot, 5-foot, and 10-foot lengths.
Numbers shown (30) are for 3-foot cables.
For enclosures that
accept these devices,
see page F2-F5.
For enclosures that
accept these devices,
see page F6-F8.
For enclosures that
accept these devices,
see page F2-F5.
For enclosures that
accept these devices,
see page F6-F8.
Mechanisms and circuit breakers listed above will fit any SDN12 wall-mounts on pages F2-F5, or SN4 wall-mounts on pages F6-F8 except as noted.
The last 3 digits of operator mechanism number indicates cable length in inches. Also 48" cables are available for ED, FD, JD/LD operators,
and 60" cables for MD/ND, PD/RD operators.
For Type 4 applications order handle, cable and circuit breaker separately.
*This operator mechanism can only be installed in catalog number SDN12603812A (see page F3) which has the appropriate flange cutout.
Space Occupied by Disconnect
• The I-T-E Max-Flex™ cable system allows the disconnect to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Refer to Siemens I-T-E installation instructions for limits on disconnect location when 36-inch or 48-inch Max-Flex™ cables.
• Space occupied by disconnect is determined by overall height "X", width "Y", wire bend space "WB" and location "G" as selected from right to left.
COMPLETE OPERATOR CIRCUIT BREAKER MAXIMUM CIRCUIT BREAKER CIRCUIT BREAKER
CIRCUIT BREAKER TYPE
MECHANISM FRAME AMP RATING HEIGHT X WIDTH Y
FHOE036 ED 125A 6.34 3.00 ED2. ED4. ED6. HED4. HED6
FHOE036 CED 125A 9.58 3.00 CED6
FHOF036 FD 250A 9.50 4.50 FXD6-A, FD6-A, HFD6, FXD6-ETJ, HHFD6, HHFXD6
FHOJ036 CFD 250A 14.25 4.50 CFD6, CFD6-ETI
FHOJ036 JD 400A 11.00 7.50 JXD2, JXD6, JD6, HJD6, HHJD6, HHJXD6, JXD6-ETI
FHOJ036 CJD 400A 17.86 7.50 CJD6, CJD6-ETI
FHOJ036 LD 600A 11.00 7.50 LXD6, LD6, HLD6, HHLD6, HHLDX6, LXD6-ETI
FHOJ036 CLD 600A 17.86 7.50 CLD6, CLD6-ETI
FHOLM036 LMD 800A 16.00 9.00 LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI
FHON048* MD 800A 24.00 9.00 MD2, MXD6, HMD6, HMXD6, CMD6, MXD6-ETI, CMD6-ETI
FHON048* ND 1200A 24.00 9.00 ND6, NXD6, HND6, HNXD6, CND6
I-T-E CIRCUIT BREAKERS FOR MAX-FLEX™OPERATORS
Space Occupied by Disconnect Switch or Circuit Breaker
• Square D cable mechanisms allows disconnect devices to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code®1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Choose cable mechanism length based on placement of disconnect in enclosure.
See Square D Instruction Bulletin for minimum bend radius for cable.
• Space occupied by disconnect is determined by overall height "X", width "Y",
wire bend space "WB" and location "G" as selected from right to left.