Wiegmann SN4 SERIES ENCLOSURES Catalog Page

Page 1
SN4 SERIES ENCLOSURES NEMA 4 FLANGED SINGLE DOOR DISCONNECT
F6
FEATURES-SPECIFICATIONS
Industry Standards
UL 508, Types 4, 12, & 13 CSA Certified, Types 4 & 12 NEMA/EEMAC Types 3, 4, 12, & 13 JIC EL-1-71
UL File E64791
CSA File LL66078
Applications
Designed to house the following:
Allen-Bradley Bulletin 1494V discon-
nect switches with flange-mounted variable depth operating mechanisms and Bulletin 1494V flange-mounted variable depth operating mechanisms for circuit breakers.
Allen-Bradley Bulletin 1494V-R1,
-R2, and -W2 operating handles and Allen-Bradley Bulletin 1494F disconnect devices or Bulletin 1494D circuit breaker operators will not fit these enclosures.
ABB Controls flange-mounted
variable depth operating mechanisms for disconnect switches and circuit breakers
Cutler-Hammer/Westinghouse
Type C361 flange-mounted variable depth operating mechanisms with disconnect switches and Type C371 flange-mounted variable depth oper­ating mechanisms for circuit breakers
General Electric Type STDA flange
handles and variable depth operating mechanisms for disconnect switches and circuit breakers. Also Spectra Flex™ cable operators for circuit breakers
I-T-E Max-Flex™ flange-mounted
variable depth operating handles for circuit breakers.
Square D Class 9422 disconnect
switches with flange-mounted variable depth operating mechanisms or
cable mechanism and Class 9422 flange-mounted variable depth operating mechanisms or cable mechanism for circuit breakers.
Bulletin A19 enclosures will not accept Square D Class 9422 bracket­mounted disconnect devices, 9422TGI, or TG2 devices
Construction
• Bodies and doors fabricated from 14 gauge steel
• Plasma welded seams
• Rolled lip around all sides of enclo­sure opening excludes liquids and contaminants
• All exterior hardware is stainless steel
• Stainless steel door clamps are provided around three sides of doors for a watertight seal, additional door hardware is not required
• Body and door stiffeners provided in larger enclosures for extra rigidity
• Doors easily removed by pulling continuous hinge pin
• Polyurethane poured-in-place gasket
• External mounting feet.
• Collar studs for mounting optional back panel
• Grounding provisions provided
• Bracket welded to door for attaching disconnect interlock door catch
• Holes provided in body for mounting disconnect operating handle and operating mechanism. These
enclosures are designed to operate properly without the use of door hardware
• Print pocket is provided
Finish
• ANSI 61 gray polyester powder inside and out over phosphatized surfaces
Optional back panels are white polyester powder over phosphatized surfaces
Accessories
• Back panels (reference tables)
• See pages J1-J19
• Blank Adapter Plates on pages F57 and J12
IMPORTANT
• Disconnect switch or circuit breakers, operating handle, and operating mechanism are not furnished with the enclosure and must be ordered separately from the disconnect manufacturer
• Operator adapter plates are not required with this enclosure
• Disconnect ordering information is located on page F8
• Review space occupied by discon­nect drawing on page F7 and disconnect tables on pages F9-F15 to determine if the disconnect device you are using will fit the enclosure size you have selected
SN4242108
DATA SUBJECT TO CHANGE WITHOUT NOTICE
®
R
Page 2
SN4 SERIES ENCLOSURES
NEMA 4 FLANGED SINGLE DOOR DISCONNECT
F7
CATALOG BODY/DOOR ENCLOSURE SIZE BACK PANEL BACK PANEL
STIFFENER
NUMBER STEEL GAUGE H X W X D CATALOG NUMBER* SIZE A X B
DOOR BODY
SN4242108 14/14 24.00x21.38x8.13 (610x543x207) NP2420 21.00x17.00 (533x432) No No
SN4242508 14/14 24.00x25.38x8.13 (610x645x207) NP2424 21.00x21.00 (533x533) No No
SN4302508 14/14 30.00x25.38x8.13 (762x645x207) NP3024 27.00x21.00 (686x533) No No
SN4363108 14/14 36.00x31.38x8.13 (914x797x207) NP3630 33.00x27.00 (838x686) No Yes
SN4423112 14/14 42.00x31.38x12.13 (1067x797x308) NP4230 39.00x27.00 (991x686) Yes Yes
SN4423712 14/14 42.00x37.38x12.13 (1067x949x308) NP4236 39.00x33.00 (991x838) Yes Yes
SN4483712** 14/14 48.00x37.38x12.13 (1219x949x308) NP4836 45.00x33.00 (1143x838) Yes Yes
SN4603712** 14/14 60.00x37.38x12.13 (1524x949x308) NP6036 57.00x33.00 (1448x838) Yes Yes
SN4 SERIES WALL-MOUNT DISCONNECTS
*Back panels must be ordered separately. **Enclosures are supplied with closed cell neoprene gasket (not foam-in-place).
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0.63
3.00
Ø0.44
W
3.00
2.00
D
Y
OMIT TWO MIDDLE STUDS IF W = LESS THAN 32.00"
1.50
0.63
3.00 TYP
X
W-3.13
H
H-1.63
1.25
0.44
1.25
DOOR STIFFENER IF H = 42.00" OR MORE
D-0.28
X
Y
0.88
0.88
H-6.00
A
B1.75 2.62
1.50
MOUNTING FEET
PANEL (Order Separately)
STIFFENER SEE TABLE
OMIT TWO MIDDLE STUDS IF H = LESS THAN 31.00"
SECTION Y-Y
CONTINUOUS HINGE
0.63
0.88
1.31
D
1.09
GASKET
3/8 - 16 COLLAR STUD
12 GA.
DOOR STIFFENER
1.25 TYP
PANEL (ORDER SEPARATELY)
2.50
14 GA.
2.75
Notes:
1. Large print pocket (8" x 10") is provided in each enclosure.
2. Panels are made from 12 Ga. steel.
3. Panels have flanges along all sides when either dimension exceeds 17".
4. The number of door clamps is dependent on size of enclosure. Clamps are furnished along three sides of door.
0.19
MOUNTING FEET
SECTION X-X
Space Occupied by Disconnect
E = 8.63 when D = 8.00 E = 11.62 when D = 12.00 WB = Wiring Space
See pages F9-F15 for various brands of disconnects for "F", "G", & "WB" dimensions.
Disconnects will occupy space on panel shown by dimensions "E", "F", & "G". Wiring space "WB" is available when disconnect is installed in the enclosure.
Refer to National Electrical Code 1996 article 430-10(b) for wiring space required for line side conductors to be connected to disconnect. Verify your application to determine if wiring space is adequate.
BODY STIFFENER
0.75
THIS SPACE IS OCCUPIED
BY DISCONNECT SWITCH
AND FUSE CLIP (IF USED)
OR CIRCUIT BREAKER.
1.50
TOP HOLE IN R.H. FLANGE
W
G
E
F
1.59
2.75
Page 3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SN4 SERIES ENCLOSURES NEMA 4 FLANGED SINGLE DOOR DISCONNECT
5.15
Allen-Bradley
When using a Bulletin 1494V discon­nect switch, order:
1.A disconnect switch with operating mechanism (Bulletin 1494V)
2.An operating handle (Bulletin 1494V-W1)
3.A connecting rod [Bulletin 1494V­RA1 for 8.00" (203mm) deep enclo­sures; Bulletin 1494V-RA2 for 12.00" (305mm) deep enclosures]
4.A trailer fuse block kit, if required (Bulletin 1494V)
5.A fuse clip kit, if required
6.Line and load connectors, if required
When using a Bulletin 1494V circuit breaker operating mechanism, order:
1.A circuit breaker (C-H/Westinghouse)
2.A circuit breaker operating mecha­nism (Bulletin 1494V)
3.An operating handle (Bulletin 494V-W11)
4.A connecting rod [Bulletin 1494V­RA1 for 8.00" (203mm) deep enclo­sures; Bulletin 1494V-RA2 for 12.00" (305mm) deep enclosures]
ABB Controls
When using a disconnect switch, order:
1.A flange operated switch (fusible or non-fusible)
2.A shaft [DSFHS-12]
3.A handle (DSFHN-HS4)
When using a circuit breaker, order:
1.A circuit breaker (ABB)
2.An operating mechanism
3.A shaft [FHS-12]
4.A handle (FHN-HS4)
Cutler-Hammer/Westinghouse
When using a Type C361 disconnect switch, order:
1.A disconnect switch with an operating mechanism
2.An operating handle (C361H2 or C361H4)
When using a Type C371 circuit breaker operating mechanism with a C-H/ Westinghouse circuit breaker, order:
1.A circuit breaker
2.An operating mechanism
3.An operating handle (C371H2 or C371H4)
When using a C-H/Westinghouse cir­cuit breaker with a Type 4/4X Flex Shaft™ handle mechanism, order:
1.A circuit breaker
2.A complete Flex Shaft™ handle mechanism
General Electric
When using a disconnect switch, order:
1.A disconnect switch (Type QMR or QMW)
2.A fuse clip kit or no-fuse kit
3.A flange handle (STDA1X)
4.A variable depth operating mecha­nism
When using a circuit breaker, order:
1.A circuit breaker
2.A flange handle (STDA1X)
3.A variable depth operating mecha­nism
When using a circuit breaker with a Spectra Flex™ cable operator, order:
1.A circuit breaker
2.A flange-mounted handle mechanism
3.A breaker-mounted mechanism
4.An operating cable
I-T-E Siemens
When using a disconnect switch, order:
1.A basic switch (right-hand)
2.A fuse or no-fuse kit
3.A flange-mounted handle (FHOHS4)
4.Switch operator
5.Cable, 36.00" When using a circuit breaker, order:
1. A circuit breaker
2.Pressure wire connectors
3.A flange-mounted handle (FH0H4)
4.A circuit breaker operator mecha­nism
5.An operating cable (standard 36.00")
Square D
When using a Class 9422 disconnect switch, order:
1.A disconnect switch with operating mechanism (Class 9422)
2.A handle mechanism (Class 9422 Type A-2 or A-1)
When using a circuit breaker, order:
1. A circuit breaker (Square D)
2.An operating mechanism (Class
9422)
3.A handle mechanism (Class 9422 Type A-2 or A-1)
When using a Class 9422 Type “T” disconnect switch with a cable mecha­nism, order:
1.A disconnect switch with operating mechanism (Class 9422, Type T)
2.A handle mechanism (Class 9422 Type A-1)
3.A cable mechanism (Class 9422 CFT_O) 3-, 5-, or 10-foot
When using a circuit breaker with a cable mechanism, order:
1.A circuit breaker (Square D)
2.A handle mechanism (Class 9422 Type A-1)
3.A cable mechanism (Class 9422 CFT_O) 3-, 5-, or 10-foot
PLEASE NOTE:
1. Operator adapter plates and door hardware are not required with enclosures on page F7.
2. Various other switch accessories and circuit breaker accessories are available from disconnect manufacturers. The above information is subject to change without notice. Please contact Hubbell-Wiegmann or the disconnect manufacturer if there are further questions.
3. The “Space Occupied” tables (pages F9-F15) are based upon information supplied by disconnect manufacturers. Hubbell-Wiegmann does not assume responsibility for the accuracy of these dimensions.
* Items available from disconnect manufacturer as complete kits.
DISCONNECT ORDERING INFORMATION
When ordering wall-mounted disconnects from the various manufacturers, be sure to order all of the necessary items. Each company has a different system, so care is required. Order the following items from the disconnect manufacturer.
F8
Use a Type 4 disconnect operating handle on the enclosure flange to provide corrosion resistance and maintain enclosure rating.
Page 4
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F9
DS30 30A No fuse 3.88 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 30A-250V H, K, R 5.25 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 30A-600V H, K, R 8.00 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 30A-600V J 5.25 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 60A-250V H, K 6.00 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 60A-600V H, K 8.50 6.62 2.88 5.25 9.75 6.75 9.75
DS30 30A 60A-600V J 5.38 6.62 2.88 5.25 9.75 6.75 9.75
DS60 60A No fuse 3.88 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 60A-250V H, K, R 6.00 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 60A-600V H, K, R 8.50 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 60A-600V J 5.38 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 30A-600V H, K, R 8.00 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 100A-250V H, K 8.50 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 100A-600V H, K 10.50 6.62 2.75 5.12 9.62 6.62 9.62
DS60 60A 100A-600V J 7.25 6.62 2.75 5.12 9.62 6.62 9.62
DS100 100A*** No fuse 3.88 6.62 5.12 9.62 6.44 9.62
DS100 100A*** 100A-250V H, K, R 8.12 6.62 5.12 9.62 6.44 9.62
DS100 100A*** 100A-600V H, K, R 10.12 6.62 5.12 9.62 6.44 9.62
DS100 100A*** 100A-600V J 6.88 6.62 5.12 9.62 6.44 9.62
DS100 100A*** 60A-600V H, K, R 10.12 6.62 5.12 9.62 6.44 9.62
DS100 100A*** 60A-600V J 8.88 6.62 5.12 9.62 6.44 9.62
DS200 200A*** No fuse 4.75 7.88 8.12 8.12
DS200 200A*** 200A-250V H, K, R 10.88 7.88 8.12 8.12
DS200 200A*** 200A-600V H, K, R 13.38 7.88 8.12 8.12
DS200 200A*** 200A-600V J 9.50 7.88 8.12 8.12
DS200 200A*** 100A-600V H, K, R 12.00 7.88 8.12 8.12
DS200 200A*** 100A-600V J 8.75 7.88 8.12 8.12
DS400 400A** No fuse 10.75 10.88
DS400 400A** 400A-250V H, K, R 16.12 10.88
DS400 400A** 400A-600V H, K, R 19.12 10.88
DS400 400A** 400A-600V J 14.62 10.88
DS600 600A No fuse 10.75 10.88
DS600 600A**** 600A-250V H, R 10.75 10.88
DS600 600A**** 600A-600V H, R 10.75 10.88
DS600 600A 600A-600V J 17.59 10.88
Westinghouse
M40 15A-150A
Circuit Breakers
5.00 4.50 4.25 6.62 11.12 8.12 11.12
EHD, FD, FDB, FDC, HFD, HMCP
Westinghouse
M50 70A-250A
Circuit Breakers
9.75 4.75 10.62 10.62
JD, JDB, JDC, HJD, HMCP
Westinghouse
M60 100A-400A
Circuit Breakers
9.69 6.12 10.50 10.50
KD, KDB, KDC, HKD, HMCP
TYPE AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER RATING CLIP CLASS
FG*
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
ALLEN-BRADLEY BULLETIN 1494V DISCONNECTS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
* Does not include space for optional auxiliary switch.
** The 400 amp disconnect switch and the 600 amp disconnect switch will only fit catalog number SDN12603812A (see page F2).
Wire bend space of 12.13" is provided above disconnect when installed.
*** Series B
**** ”F” and “G” do not include separately mounted fuse blocks.
Page 5
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F10
OETL-NF30-F 40A No fuse 4.45 3.78 6.41 8.75 13.28 10.28 13.28
OETL-NF60-F 80A No fuse 4.86 3.78 6.22 8.56 13.09 10.09 13.09
OETL-NF100-F 100A No fuse 4.86 4.78 5.66 8.00 12.53 9.53 12.53
OETL-NF175-F 175A No fuse 7.30 6.49 5.75 10.28 7.28 10.28
OETL-NF200-F 200A No fuse 7.36 7.28 5.75 10.28 7.28 10.28
OESA-F30J6-F 30A 30A-600V J 4.28 6.58 4.73 7.07 11.61 8.61 11.61
OESA-F60J6-F 60A 60A-600V J 4.28 6.26 4.73 7.07 11.61 8.61 11.61
OESA-F100J6-F 100A 100A-600V J 6.54 7.65 4.30 6.64 11.17 8.17 11.17
SWITCH AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER RATING CLIP CLASS
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
ABB CONTROLS DISCONNECT SWITCHES WITH FLANGE-MOUNTED OPERATORS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
FHD-M 150A D 6.92 3.94 5.29 7.64 12.17 9.17 12.17
FHF-M 150A-225A E/Q 5.98 4.23 3.84 6.19 10.72 7.72 10.72
FHF-M 225A F 7.44 4.23 3.84 6.19 10.72 7.72 10.72
FHJ-M 400A J 9.71 5.62 8.77 8.77
FHM-M 600A L 8.28 11.26 8.28 8.28
FHM-M 800A M 10.11 11.26 7.87 7.87
AMP FRAME
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM
RATING TYPE
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
ABB CONTROLS CIRCUIT BREAKERS WITH FLANGE-MOUNTED OPERATORS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
C361 NC 30A No fuse 5.75 7.43 3.44 5.75 10.31 7.31 10.31
C361 SC21 30A 30A-250V H, K, R 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 SC61 30A 60A-250V H, K, R 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 SC61 30A 30A-600V H, J, K, R 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 ND 60A No fuse 5.75 7.43 3.44 5.75 10.31 7.31 10.31
C361 SD22 60A 60A-250V H, K, R 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 SD22 60A 30A-600V J 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 SD62 60A 60A-600V H, K, R 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 SD62 60A 60A-600V J 8.38 7.43 3.44 5.75 10.31 7.31 10.31
C361 NE 100A No fuse 5.56 8.95 3.00 5.38 9.91 7.47 9.91
C361 SE263 100A 100A-250V H, K, R 10.31 8.95 3.00 5.38 9.91 7.47 9.91
C361 SE263 100A 100A-600V H, K, R 10.31 8.95 3.00 5.38 9.91 7.47 9.91
C361 SE263 100A 100A-600V J 10.31 8.95 3.00 5.38 9.91 7.47 9.91
C361 NF* 200A No fuse 13.06 10.00 7.94 4.94 7.94
C361 SF264* 200A 200A-250V H, K, R 13.06 10.00 7.94 4.94 7.94
C361 SF264* 200A 200A-600V H, J, K, R 13.06 10.00 7.94 4.94 7.94
SWITCH TYPE AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER NUMBER RATING CLIP CLASS
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
CUTLER-HAMMER C361 CIRCUIT DISCONNECT SWITCHES
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
*200 amp switch should be installed in an enclosure with an "H" dimension of 30.00" (762mm) or more.
Page 6
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F11
C371E 225A F Frame: EHD, FDB, FD, HFD, FDC 6.00 5.50 4.44 6.81 11.44 8.44 11.44
C371E 150A F Frame: HMCP 6.00 5.50 4.44 6.81 11.44 8.44 11.44
C371F 250A J Frame: JDB, JD, HJD, JDC 8.94 8.00 6.75 11.25 11.25
C371F 250A J Frame: HMCP 10.94 8.00 6.75 11.25 11.25
C371F 400A K Frame: DK, KDB, KD, HKD 9.75 8.00 10.75 10.75
C371F 400A K Frame: HMCP 9.75 8.00 10.75 10.75
C371G 600A L Frame: LD, HLD, LDC 8.44 11.88 9.18 9.18
C371G 600A L Frame: HMCP 8.44 11.88 9.18 9.18
TYPE
MAX
FRAME TYPE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER
AMP
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00
RATING WB WB WB WB WB
CUTLER-HAMMER C371 CIRCUIT BREAKER OPERATORS FOR C-H/WESTINGHOUSE CIRCUIT BREAKERS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
COMPLETE OPERATOR AMP FRAME BREAKER BREAKER MECHANISM RATING TYPE HEIGHT WIDTH
F1S03 225A F Frame: EHD, FDB, FD, HFD, FDC 6.00 4.12
F1S03 150A F Frame: HMCP 6.00 4.12
F2S03 250A J Frame: JDB, JD, HJD, JDC 10.00 4.12
F2S03 250A J Frame: HMCP 10.00 4.12
F3S03 400A K Frame: DK, KDB, KD, HKD 10.12 5.50
F3S03 400A K Frame: HMCP 12.45 5.50
F4S04 600A L Frame: LD, HLD, LDC 10.75 8.25
F4S04 600A L Frame: HMCP 12.50 8.25
F7S04 800A M Frame: MD, MDS 16.00 8.25
F5S04 1200A N Frame: ND, HND, NDC 16.00 8.25
F6S04 2500A R Frame: RD, CRD, RDC 16.00 15.50
CUTLER-HAMMER FLEX SHAFT™OPERATOR MECHANISMS FOR C-H/WESTINGHOUSE CIRCUIT BREAKERS
Catalog numbers for complete mechanisms include a flange-mounted handle, flexible shaft and circuit breaker mechanism.The last digit of the catalog number denotes the length of shaft (F1S03 = 3-foot shaft). The F, J, K frame Flex Shafts™ are available in 3-foot to 10-foot lengths. The L, N, R frame Flex Shafts are available in 4-foot to 6-foot lengths.
Space Occupied by Disconnect
• The Flex Shaft™ system allows the circuit breaker to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Choose the length of shaft based on placement of the circuit breaker in the enclosure ensuring a 4-inch min. bending radius for the Flex Shaft™.
• Space occupied by circuit breaker is determined by overall height "X", width "Y", wire bend space "WB" and location "G" as selected from right to left.
Page 7
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F12
TDOM1A 30A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 30A 30A-250V H, R 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 30A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 60A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 60A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 60A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 60A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 60A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 100A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 100A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 100A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 100A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 100A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 200A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 200A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM2 200A No fuse 7.00 9.12 9.50 6.50 9.50
TDOM2 200A 200A-250V H, R 15.38 9.12 9.50 6.50 9.50
TDOM2 200A 200A-600V H, R 15.38 9.12 9.50 6.50 9.50
AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM
RATING CLIP CLASS
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
GENERAL ELECTRIC TYPE STDA OPERATORS FOR DISCONNECTS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
* Disconnect moved down .88" to fit on panel.
** Dimension applies to 8.00" (203mm) deep enclosures and is .88" less in deeper enclosures.
SDOM1A 150A TEB, TED, THED 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
SDOM1A 150A TEC 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1B 150A TB1 12.38** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1B 150A TEC, TECL 12.38** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1C 150A TEL 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1D 150A THLC1 7.75** 5.25 5.12 9.62 6.62 9.62
TDOM3 225A TFJ 10.38 5.75 6.06 10.62 7.62 10.62
TDOM3 225A TFK, THFK, TFL 10.38 5.75 6.06 10.62 7.62 10.62
TDOM4 400A TJJ, TJK4, THJK4, TJL4V 8.25 9.38 5.12 9.69 6.69 9.69
TDOM4 600A TJK6, THJK6, TJ4V, TJL4V 8.25 9.38 5.12 9.69 6.69 9.69
TDOM5 400A TB4, TJH6S 14.25 9.38 5.12 9.69 6.69 9.69
TDOM6 225A TLB2, THLC2 11.75 9.38 9.12 6.12 9.12
TDOM6 400A TLB4, THLC4 11.75 9.38 7.75 4.75 7.75
SDOM1A 150A SPECTRA SE150 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
SDOM3 250A SPECTR SF250 10.38 5.75 6.06 10.62 7.06 10.06
SDOM4 600A SPECTRA SG600 10.00 7.00 7.93 7.93
AMP
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM
RATING
FRAME TYPE
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
GENERAL ELECTRIC TYPE STDA OPERATORS FOR CIRCUIT BREAKERS
OPERATORS FOR CIRCUIT BREAKERS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
* Disconnect moved down .88" to fit on panel.
** Dimension applies to 8.00" (203mm) deep enclosures and is .88" less in deeper enclosures.
Page 8
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F13
FRAME MAXIMUM CIRCUIT BREAKER CIRCUIT BREAKER
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
SIZE AMP RATING HEIGHT X WIDTH Y
E150 150A 6.31 4.12
SE150 150A 6.31 4.12
SF250 250A 10.12 4.12
SG600 600A 10.09 5.50
SK1200 1200A 15.50 8.25
GENERAL ELECTRIC CIRCUIT BREAKERS WITH SPECTRA FLEX™CABLE OPERATORS
For enclosures that accept these devices, see page F2-F5.
For enclosures that accept these devices, see page F6-F8.
FRAME BREAKER FLANGE-MOUNTING OPERATING SIZE MECHANISM HANDLE** CABLE*
E150 SCOM1A SCH1 SC3L
SE150/SF250 SCOM1EF SCH1 SC3L
SG600 SCOM1G SCH1 SC3L
SK1200 SCOM1K SCH2K SC3H
* Operating cables are available in 3-foot to 10-foot lengths. (The number 3 in the catalog number denotes
3-foot cable.)
** Add “X” for NEMA 4 or 4X flange-mounted handle.
Space Occupied by Circuit Breaker
• The General Electric Spectra-Flex™ system allows the circuit breaker to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Choose the operating cable length based on placement of the circuit breaker in the enclosure ensuring a 3" minimum bending radius for the cable.
• Space occupied by circuit breaker is determined by overall circuit breaker size ("X" height and "Y" width) plus "WB" wire bend space and location "G" as selected from right to left.
SWITCH
AMP FUSE FUSE DISCONNECT DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
RATING CLIP CLASS HEIGHT X WIDTH Y
MCS603R 30A No fuse 5.52 6.13
MCS603R 30A 30A-250V H, K, R 8.11 6.13
MCS603R 30A 30A-600V H, K, R 10.11 6.13
MCS603R 30A 30A-600V J 8.48 6.13
MCS606R 60A No fuse 5.52 6.13
MCS606R 60A 60A-250V H, K, R 7.86 6.13
MCS606R 60A 60A-600V H, K, R 10.38 6.13
MCS606R 60A 60A-600V J 8.36 6.13
MCS610R 100A No fuse 7.59 7.38
MCS610R 100A 100A-250V H, K, R 11.85 7.38
MCS610R 100A 100A-600V H, K, R 13.85 7.38
MCS610R 100A 100A-600V J 10.60 7.38
MCS620R 200A No fuse 9.02 9.17
MCS620R 200A 200A-250V H, K, R 14.70 9.17
MCS620R 200A 200A-600V H, K, R 17.20 9.17
MCS620R 200A 200A-600V J 13.32 9.17
I-T-E DISCONNECT SWITCHES FOR MAX-FLEX™OPERATORS
For enclosures that accept these devices, see page F2-F5.
For enclosures that accept these devices, see page F6-F8.
Page 9
SDN12 SERIES & SN4 SERIES ENCLOSURES DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F14
SWITCH
AMP FUSE FUSE DISCONNECT DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
RATING CLIP CLASS HEIGHT X WIDTH Y
TCN-30 30A No fuse 5.90 6.20
TCF-30 30A 30A-250V H, K, R 7.50 6.20
TCF-33 30A 30A-600V H, K, R 10.15 6.20
TCF-33 30A 60A-250V H, K, R 8.15 6.20
TCF-33 30A 30A-600V J 7.50 6.20
TDN-60 60A No fuse 5.90 6.20
TDF-60 60A 30A-600V H, K, R 10.15 6.20
TDF-60 60A 60A-250V H, K, R 8.15 6.20
TDF-63 60A 60A-600V H, K, R 10.65 6.20
TDF-63 60A 60A-600V J 7.50 6.20
TEN-10 100A No fuse 5.90 6.20
TEF-10 100A 100A-250V H, K, R 10.35 6.20
TEF-10 100A 100A-600V H, K, R 10.35 6.20
TEF-10 100A 100A-600V J 10.35 6.20
SQUARE D CLASS 9422 DISCONNECT SWITCHES USED WITH CABLE MECHANISM 9422-CFT30 AND 9422A-1 HANDLE MECHANISM
CABLE TYPE CIRCUIT BREAKER CIRCUIT BREAKER
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS
SWITCH
AMP RATING FRAME TYPE
HEIGHT X WIDTH Y
9422 CGJ30 75A GJL 4.75 3.50
9422 CGJ300 100A GJL 4.75 3.50
9422 CGJ30 100A FAL, FHL 6.00 4.50
9422 CGJ30 250A KAL, KHL 8.00 4.50
9422 CGJ30 400A LAL, LHL, Q4L 11.00 6.00
SQUARE D CLASS 9422 CABLE MECHANISM FOR CIRCUIT BREAKERS
Use switches listed above with appropriate cable mechanism and 9422-A1 handle mechanism.
Use cable mechanism with appropriate circuit breaker and 9422-A1 handle mechanism. Cable operators are available in 3-foot, 5-foot, and 10-foot lengths. Numbers shown (30) are for 3-foot cables.
For enclosures that
accept these devices,
see page F2-F5.
For enclosures that
accept these devices,
see page F6-F8.
For enclosures that
accept these devices,
see page F2-F5.
For enclosures that
accept these devices,
see page F6-F8.
Mechanisms and circuit breakers listed above will fit any SDN12 wall-mounts on pages F2-F5, or SN4 wall-mounts on pages F6-F8 except as noted. The last 3 digits of operator mechanism number indicates cable length in inches. Also 48" cables are available for ED, FD, JD/LD operators,
and 60" cables for MD/ND, PD/RD operators. For Type 4 applications order handle, cable and circuit breaker separately. *This operator mechanism can only be installed in catalog number SDN12603812A (see page F3) which has the appropriate flange cutout.
Space Occupied by Disconnect
• The I-T-E Max-Flex™ cable system allows the disconnect to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Refer to Siemens I-T-E installation instructions for limits on disconnect location when 36-inch or 48-inch Max-Flex™ cables.
• Space occupied by disconnect is determined by overall height "X", width "Y", wire bend space "WB" and location "G" as selected from right to left.
COMPLETE OPERATOR CIRCUIT BREAKER MAXIMUM CIRCUIT BREAKER CIRCUIT BREAKER
CIRCUIT BREAKER TYPE
MECHANISM FRAME AMP RATING HEIGHT X WIDTH Y
FHOE036 ED 125A 6.34 3.00 ED2. ED4. ED6. HED4. HED6
FHOE036 CED 125A 9.58 3.00 CED6
FHOF036 FD 250A 9.50 4.50 FXD6-A, FD6-A, HFD6, FXD6-ETJ, HHFD6, HHFXD6
FHOJ036 CFD 250A 14.25 4.50 CFD6, CFD6-ETI
FHOJ036 JD 400A 11.00 7.50 JXD2, JXD6, JD6, HJD6, HHJD6, HHJXD6, JXD6-ETI
FHOJ036 CJD 400A 17.86 7.50 CJD6, CJD6-ETI
FHOJ036 LD 600A 11.00 7.50 LXD6, LD6, HLD6, HHLD6, HHLDX6, LXD6-ETI
FHOJ036 CLD 600A 17.86 7.50 CLD6, CLD6-ETI
FHOLM036 LMD 800A 16.00 9.00 LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI
FHON048* MD 800A 24.00 9.00 MD2, MXD6, HMD6, HMXD6, CMD6, MXD6-ETI, CMD6-ETI
FHON048* ND 1200A 24.00 9.00 ND6, NXD6, HND6, HNXD6, CND6
I-T-E CIRCUIT BREAKERS FOR MAX-FLEX™OPERATORS
Space Occupied by Disconnect Switch or Circuit Breaker
• Square D cable mechanisms allows disconnect devices to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code®1996 article 430-10(b) for wiring space "WB" required for line side conductors.
• Choose cable mechanism length based on placement of disconnect in enclosure. See Square D Instruction Bulletin for minimum bend radius for cable.
• Space occupied by disconnect is determined by overall height "X", width "Y", wire bend space "WB" and location "G" as selected from right to left.
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Page 10
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SDN12 SERIES & SN4 SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F15
TCN-30 30A No fuse 3.80 6.84 3.69 6.03 10.56 7.56 10.56
TCF-30 30A 30A-250V H, K, R 5.53 6.84 3.69 6.03 10.56 7.56 10.56
TCF-33 30A 30A-600V H, K, R 8.15 6.84 3.69 6.03 10.56 7.56 10.56
TCF-33 30A 60A-250V H, K, R 6.15 6.84 3.69 6.03 10.56 7.56 10.56
TCF-33 30A 30A-600V J 5.53 6.84 3.69 6.03 10.56 7.56 10.56
TDN-60 60A No fuse 3.80 6.84 3.69 6.03 10.56 7.56 10.56
TDF-60 60A 30A-600V H, K, R 8.15 6.84 3.69 6.03 10.56 7.56 10.56
TDF-60 60A 60A-250V H, K, R 6.15 6.84 3.69 6.03 10.56 7.56 10.56
TDF-63 60A 60A-600V H, K, R 8.65 6.84 3.69 6.03 10.56 7.56 10.56
TDF-63 60A 60A-600V J 5.53 6.84 3.69 6.03 10.56 7.56 10.56
TEN-10 100A No fuse 3.80 6.84 5.91 10.44 7.44 10.44
TEF-10 100A 100A-250V H, K, R 8.25 6.84 5.91 10.44 7.44 10.44
TEF-10 100A 100A-600V H, K, R 10.25 6.84 5.91 10.44 7.44 10.44
TEF-10 100A 100A-600V J 7.05 6.84 5.91 10.44 7.44 10.44
TC-1 30A No fuse 5.75 6.00 3.12 5.12 9.62 6.62 9.62
TC-2 30A 30A-250V H, K, R 5.75 6.00 3.12 5.12 9.62 6.62 9.62
TC-3 30A 30A-600V H, K, R 7.75 6.00 3.12 5.12 9.62 6.62 9.62
TC-3 30A 60A-250V H, K, R 5.88 6.00 3.12 5.12 9.62 6.62 9.62
TC-3 30A 30A-600V J 5.75 6.00 3.12 5.12 9.62 6.62 9.62
TD-1 60A No fuse 6.38 6.62 3.62 6.00 10.50 7.50 10.50
TD-2 60A 30A-600V H, K, R 8.50 6.62 3.62 6.00 10.50 7.50 10.50
TD-2 60A 60A-250V H, K, R 6.50 6.62 3.62 6.00 10.50 7.50 10.50
TD-3 60A 60A-600V H, K, R 9.00 6.62 3.62 6.00 10.50 7.50 10.50
TD-3 60A 60A-600V J 6.38 6.62 3.62 6.00 10.50 7.50 10.50
TE-1 100A No fuse 4.75 8.38 5.75 10.25 10.25
TE-2 100A 100A-250V H, K, R 7.50 8.38 5.75 10.25 10.25
TE-2 100A 100A-600V H, K, R 9.50 8.38 5.75 10.25 10.25
TE-2 100A 100A-600V J 6.25 8.38 5.75 10.25 10.25
TE-3 100A 200A-600V J 13.75 8.38 5.75 10.25 10.25
TF-1 200A No fuse 5.50 11.62 8.88 8.88
TF-2 200A 200A-250V H, K, R 11.50 11.62 8.88 8.88
TF-2 200A 200A-600V H, K, R 14.00 11.62 8.88 8.88
TF-2 200A 200A-600V J 10.12 11.62 8.88 8.88
TF-3 200A 400A-600V J 14.50 11.62 8.88 8.88
RG-1 75A GJL Circuit breaker 3.53 3.74 3.59 5.93 10.47 7.47 10.47
RG-1 100A GJL Circuit breaker 3.53 3.74 3.59 5.93 10.47 7.47 10.47
RN-1 100A FAL, FHL Circuit breaker 5.12 5.25 3.75 6.12 10.62 7.62 10.62
RP-1 250A KAL, KHL Circuit breaker 7.12 5.62 4.25* 6.88 11.38 8.38 11.38
RR-1 400A LAL,LHL,Q4L Circuit breaker 7.62 8.75 7.00 7.00
TYPE AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER RATING CLIP CLASS
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00 WB WB WB WB WB
SQUARE D CLASS 9422 DISCONNECTS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
SDN12 WALL-MOUNTS SN4 WALL-MOUNTS (PAGE F2-F5) (PAGE F6-F8)
*Not recommended except with #1 or smaller line conductors.
Page 11
NP SERIES BACK PANELS ACCESSORY PANELS FOR NEMA 1, 3R, 12, 4 & 4X WALL-MOUNTS
I4
FEATURES-SPECIFICATIONS
Description
• Steel and stainless panels are 12 gauge
• Aluminum panels are 5052-H32 aluminum alloy, .080-inch thick
• Panel with any side over 17.00" has 3/4" flange on all sides
• Steel panels are painted white polyester powder
• Panels fit the following enclosures: – NEMA 1, Large (NIC) – NEMA 3R, Hinge Cover (RHC, Large) – NEMA 4, 412, & 4X
Single Door (N12, N4, N412, SSN4)
– NEMA 12
2-Door Wall-Mount, (WAWF), Single Door
Right Flange Disconnect (SDN12, ABN12)
Large JIC (B-CH, Large) Single door N12
CATALOG NUMBER
PAINTED STEEL 316 STAINLESS PANEL SIZE A X B (WHITE) STEEL
ALUMINUM
NP1212 9.00X9.00 (229X229)
NP1224 9.00X21.00 (229X533)
NP1612 NP1612SSA ALNP1612 13.00X9.00 (330X229)
NP1616 NP1616SSA ALNP1616 13.00X13.00 (330X330)
NP1620 17.00X13.00 (432X330)
NP2012 17.00X9.00 (432X229)
NP2016 NP2016SSA ALNP2016 17.00X13.00 (432X330)
NP2024 21.00X17.00 (533X432)
NP2020 NP2020SSA ALNP2020 17.00X17.00 (432X432)
NP2412 21.00X9.00 (533X229)
NP2416 NP2416SSA 21.00X13.00 (533X330)
NP2420 NP2420SSA ALNP2420 21.00X17.00 (533X432)
NP2424 NP2424SSA ALNP2424 21.00X21.00 (533X533)
NP2430 27.00X21.00 (686X533)
NP3016 27.00X13.00 (686X330)
NP3020 NP3020SSA 27.00X17.00 (686X432)
NP3024 NP3024SSA ALNP3024 27.00X21.00 (686X533)
NP3030 NP3030SSA 27.00X27.00 (686X686)
NP3036 33.00X27.00 (838X686)
NP3042 39.00X27.00 (991X686)
NP3624 NP3624SSA ALNP3624 33.00X21.00 (838X533)
NP3630 NP3630SSA ALNP3630 33.00X27.00 (838X686)
NP3636 NP3636SSA 33.00X33.00 (838X838)
NP3642 39.00X33.00 (991X838)
NP4024 37.00X21.00 (940X533)
NP4224 39.00X21.00 (991X533)
NP4230 NP4230SSA 39.00X27.00 (991X686)
NP4236 NP4236SSA 39.00X33.00 (991X838)
NP4824 45.00X21.00 (1143X533)
NP4830 45.00X27.00 (1143X686)
NP4836 NP4836SSA ALNP4836 45.00X33.00 (1143X838)
NP6030 57.00X27.00 (1448X686)
NP6036 NP6036SSA ALNP6036 57.00X33.00 (1448X838)
NP7230 69.00X27.00 (1753X686)
NP7236 69.00X33.00 (1753X838)
BACK PANELS FOR NEMA 1, 3R, 12, 4 & 4X WALL-MOUNT ENCLOSURES
B
A
Ø .563 TYP.
.875 TYP.
.875 TYP.
IF "A" IS LESS THAN 31"
OMIT MIDDLE HOLES
IF "B" IS LESS THAN 31"
OMIT MIDDLE HOLES
(SEE TABLE)
SIDE FLANGES
.75
TOP VIEW
SIDE VIEW
FRONT VIEW
2.0
2.0
Ø .312 TYP. (2PL) GROUND HOLE
DATA SUBJECT TO CHANGE WITHOUT NOTICE
NP1212